Air handler (EC fan) · Modbus register map

ebm-papst EC fans with MODBUS Lite (series 84/112/150/200 Lite) Modbus register map

Updated 17 November 2026

Short answer

ebm-papst EC fans with MODBUS Lite electronics expose a common Modbus RTU parameter set on RS485. Live values (speed, status and warning bits, DC-link voltage/current, temperatures, power) are input registers from D000; settings such as set-value source, set value, control mode, address and serial format are holding registers. Speed, voltage, current and power are scaled against per-fan reference registers, so read those first.

This page lists 33 Modbus registers for the ebm-papst EC fans with MODBUS Lite (series 84/112/150/200 Lite) — 12 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from ebm-papst’s own free documentation (linked below) and checked against it.

Manufacturer
ebm-papst
Model
EC fans with MODBUS Lite (series 84/112/150/200 Lite)
Equipment type
Air handler (EC fan)
Registers
33 (12 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
19200 baud, 8E1
Documented addressing
hexadecimal, 0-based
Firmware
MODBUS Lite specification V5.01
Also known as
MODBUS Lite V5.01, ebm-papst RadiCal Modbus, ebm-papst RadiPac Modbus, ebm-papst series 84 Lite, ebm-papst series 112 Lite, ebm-papst series 150 Lite, ebm-papst series 200 Lite
Source document
MODBUS parameters ebm-papst series 84 / 112 / 150 / 200 Lite (MODBUS Lite Basic Functionality V5.01) · V5.01
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: ebm-papst EC fans with MODBUS Lite (series 84/112/150/200 Lite)

Integration in brief

Read D119 (nMax) and D1A0/D1A1 once, then poll input registers D010-D021 with function 04. To run the fan from Modbus set D101 = 1 and write the set value to holding register D001.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 53264Actual speedUINT16Actual speed (scaled by nMax)Read
IR 53265Motor statusBITMAP16Motor status / error bitsRead
IR 53266WarningBITMAP16Warning bitsRead
IR 53281Current powerUINT16Current powerRead
HR 53249Default set valueUINT16Set value from ModbusRead/write
HR 53505Source set valueUINT16Set value source (1 = RS485)Read/write
HR 53529Maximum speed (nMax)UINT16Maximum speed referenceRead/write

Enable Modbus control & writes

Write Source set value D101 = 1 (RS485) so the fan follows Default set value D001 instead of the 0-10 V input.

Communication loss & watchdog

A fail-safe function can apply a separate set value and running direction when the Modbus connection breaks (sections 2.35-2.38 of the source); it is not mapped here.

Byte order & addressing

Network setup

Watch out for

ebm-papst EC fans with MODBUS Lite (series 84/112/150/200 Lite) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

33 of 33 shown
ebm-papst EC fans with MODBUS Lite (series 84/112/150/200 Lite) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR53248doc D000IdentificationElectronics/protocol type code; see the identification table in the source.UINT16Read
IR53249doc D001Maximum number of bytesLargest telegram the fan accepts.UINT16Read
IR53250doc D002Software name of bus controllerUINT16Read
IR53251doc D003Software version of bus controllerVersion in the low byte; high byte is 0.UINT16Read
IR53264doc D010Actual speedrpm = raw x nMax / 64000, where nMax is Maximum speed (D119). Capped at 0xFFF0.UINT16Read
IR53265doc D011Motor statusErrors currently detected; FB is set with every error.BITMAP16Readbit 0 = PHA: phase failure / mains undervoltage; bit 2 = TFE: power module overheated; bit 4 = FB: fan bad (general error); bit 5 = TFM: motor overheated; bit 6 = HLL: Hall sensor error; bit 7 = BLK: locked motor; bit 12 = UzLow: DC-link undervoltage
IR53266doc D012WarningPre-alarm conditions.BITMAP16Readbit 0 = I_Limit: current limitation; bit 2 = P_Limit: power limitation; bit 3 = TE_high: output stage temperature high; bit 4 = TM_high: motor temperature high; bit 5 = TEI_high: interior electronics temperature high; bit 6 = UzLow: DC-link voltage low; bit 7 = Brake: braking against external drive; bit 9 = n_Low: speed below running-monitor limit; bit 10 = Cable break at analogue set value input; bit 12 = UzHigh: DC-link voltage high; bit 13 = nGrenz: limiting speed exceeded; bit 14 = UeHigh: supply voltage high; bit 15 = LRF: shedding function active
IR53267doc D013DC-link voltageV = raw x reference Uz (D1A0) / 256.UINT16Read
IR53268doc D014DC-link currentA = raw x reference Iz (D1A1) / 256.UINT16Read
IR53270doc D016Motor temperatureINT16°CRead
IR53271doc D017Interior electronics temperatureINT16°CRead
IR53272doc D018Current direction of rotationUINT16Read0 = Anti-clockwise; 1 = Clockwise
IR53273doc D019Current modulation levelPercent = raw x 100 / 65536.UINT16× 0.0015258789%Read
IR53274doc D01ACurrent set valueSpeed control: rpm = raw x nMax / 64000, where nMax is Maximum speed (D119). PWM control: % = raw x 100 / 65536.UINT16Read
IR53275doc D01BSensor actual valueVoltage at the analogue input = raw x 10 / 65536.UINT16× 0.0001525879VRead
IR53277doc D01DCurrent parameter setUINT16Read0 = Parameter set 1; 1 = Parameter set 2
IR53281doc D021Current powerW = raw x reference Uz x reference Iz / 65536.UINT16Read
HR53248doc D000ResetBits clear themselves once executed.BITMAP16Read/writebit 0 = User software reset (communication kept); bit 1 = Adopt parameters (EEPROM to RAM); bit 2 = Reset errors; bit 3 = Full software reset (comms drop for seconds)
HR53249doc D001Default set valueSet value when source is RS485. Speed: raw = rpm x 64000 / nMax; PWM: raw = % x 65536 / 100.UINT16Read/write
HR53257doc D009Operating hours counterStops at 65535. Only ebm-papst level may write it.UINT16hRead
HR53258doc D00AOperating minutes counterOnly ebm-papst level may write it.UINT16minRead
HR53504doc D100Fan address1-247, low byte.UINT16Read/write
HR53505doc D101Source set valueUINT16Read/write0 = Analogue input 0-10 V; 1 = RS485 (default set value D001)
HR53506doc D102Preferred running directionUINT16Read/write0 = Anti-clockwise; 1 = Clockwise
HR53507doc D103Save set value1 also stores D001 in EEPROM (limited to 100,000 writes).UINT16Read/write0 = Not stored (fan stopped after reset); 1 = Stored in EEPROM
HR53509doc D105Internal parameter setUINT16Read/write0 = Parameter set 1; 1 = Parameter set 2
HR53510doc D106Control mode (parameter set 1)UINT16Read/write0 = Closed-loop speed control; 2 = Open-loop PWM control
HR53511doc D107Control mode (parameter set 2)UINT16Read/write0 = Closed-loop speed control; 2 = Open-loop PWM control
HR53529doc D119Maximum speed (nMax)Reference for all speed values (64000 = nMax).UINT16rpmRead/write
HR53577doc D149Transfer rateApplied after Adopt parameters/Reset or power cycle.UINT16Read/write1 = 2400; 2 = 4800; 3 = 9600; 4 = 19200 (recommended); 5 = 38400; 6 = 57600; 7 = 115200
HR53578doc D14AParity configurationApplied after Adopt parameters/Reset or power cycle.UINT16Read/write0 = 8E1 (recommended); 1 = 8O1; 2 = 8N2; 3 = 8N1
HR53664doc D1A0Reference value of DC-link voltageRaw x 20 mV; used to scale D013 and D021.UINT16× 0.02VRead
HR53665doc D1A1Reference value of DC-link currentRaw x 2 mA; used to scale D014 and D021.UINT16× 0.002ARead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the ebm-papst EC fans with MODBUS Lite (series 84/112/150/200 Lite)

What Modbus registers does the ebm-papst EC fans with MODBUS Lite (series 84/112/150/200 Lite) have?

This map lists 33 registers: 17 input registers, 16 holding registers. 12 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the ebm-papst EC fans with MODBUS Lite (series 84/112/150/200 Lite) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are printed in hex and are the register address sent in the frame; the manual's own example telegrams write D149 as bytes D1 49 and trigger Adopt parameters with 06 D0 00. Input and holding registers both start at D000 but are separate tables.

What are the minimum Modbus registers to integrate the ebm-papst EC fans with MODBUS Lite (series 84/112/150/200 Lite)?

Start with IR 53264 Actual speed (Actual speed (scaled by nMax)); IR 53265 Motor status (Motor status / error bits); IR 53266 Warning (Warning bits); IR 53281 Current power (Current power); HR 53249 Default set value (Set value from Modbus); HR 53505 Source set value (Set value source (1 = RS485)); HR 53529 Maximum speed (nMax) (Maximum speed reference).

How do I enable Modbus control of the ebm-papst EC fans with MODBUS Lite (series 84/112/150/200 Lite)?

Write Source set value D101 = 1 (RS485) so the fan follows Default set value D001 instead of the 0-10 V input.

What happens when the ebm-papst EC fans with MODBUS Lite (series 84/112/150/200 Lite) loses Modbus communication?

A fail-safe function can apply a separate set value and running direction when the Modbus connection breaks (sections 2.35-2.38 of the source); it is not mapped here.

Where is the official ebm-papst EC fans with MODBUS Lite (series 84/112/150/200 Lite) Modbus documentation?

The source is MODBUS parameters ebm-papst series 84 / 112 / 150 / 200 Lite (MODBUS Lite Basic Functionality V5.01) (V5.01), published free by ebm-papst at https://www.ebmpapst.com/content/dam/ebm-papst/loc/europe/gb/modbus-parameter-specifications/MODBUS%20Lite%20Basic%20Functionality%20V5_01.pdf.

Other hvac equipment register maps

All hvac equipment Modbus register maps →

Source: MODBUS parameters ebm-papst series 84 / 112 / 150 / 200 Lite (MODBUS Lite Basic Functionality V5.01) · V5.01. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.