Air handler (EC fan) · Modbus register map
ebm-papst EC fans with MODBUS Lite (series 84/112/150/200 Lite) Modbus register map
Updated 17 November 2026
ebm-papst EC fans with MODBUS Lite electronics expose a common Modbus RTU parameter set on RS485. Live values (speed, status and warning bits, DC-link voltage/current, temperatures, power) are input registers from D000; settings such as set-value source, set value, control mode, address and serial format are holding registers. Speed, voltage, current and power are scaled against per-fan reference registers, so read those first.
This page lists 33 Modbus registers for the ebm-papst EC fans with MODBUS Lite (series 84/112/150/200 Lite) — 12 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from ebm-papst’s own free documentation (linked below) and checked against it.
- Manufacturer
- ebm-papst
- Model
- EC fans with MODBUS Lite (series 84/112/150/200 Lite)
- Equipment type
- Air handler (EC fan)
- Registers
- 33 (12 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 19200 baud, 8E1
- Documented addressing
- hexadecimal, 0-based
- Firmware
- MODBUS Lite specification V5.01
- Also known as
- MODBUS Lite V5.01, ebm-papst RadiCal Modbus, ebm-papst RadiPac Modbus, ebm-papst series 84 Lite, ebm-papst series 112 Lite, ebm-papst series 150 Lite, ebm-papst series 200 Lite
Integration notes: ebm-papst EC fans with MODBUS Lite (series 84/112/150/200 Lite)
Read D119 (nMax) and D1A0/D1A1 once, then poll input registers D010-D021 with function 04. To run the fan from Modbus set D101 = 1 and write the set value to holding register D001.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 53264 | Actual speed | UINT16 | Actual speed (scaled by nMax) | Read |
| IR 53265 | Motor status | BITMAP16 | Motor status / error bits | Read |
| IR 53266 | Warning | BITMAP16 | Warning bits | Read |
| IR 53281 | Current power | UINT16 | Current power | Read |
| HR 53249 | Default set value | UINT16 | Set value from Modbus | Read/write |
| HR 53505 | Source set value | UINT16 | Set value source (1 = RS485) | Read/write |
| HR 53529 | Maximum speed (nMax) | UINT16 | Maximum speed reference | Read/write |
Enable Modbus control & writes
Write Source set value D101 = 1 (RS485) so the fan follows Default set value D001 instead of the 0-10 V input.
Communication loss & watchdog
A fail-safe function can apply a separate set value and running direction when the Modbus connection breaks (sections 2.35-2.38 of the source); it is not mapped here.
Byte order & addressing
- Do not enable Save set value (D103) if D001 is written often; the EEPROM allows about 100,000 writes.
- The 4 least significant bits of the set value are ignored.
- New baud/parity settings only apply after 'Adopt parameters' (D000 bit 1), a reset or power cycle.
Network setup
- Recommended/standard serial format: 19200 baud, 8E1. Changing D149/D14A needs at least customer-level password.
- Emergency function: after 10 bad telegrams the fan falls back to 19200 8E1, after 10 more to 2400 8E1, which helps find an unknown setting.
- Fan address is set in D100 (1-247).
Watch out for
- Input and holding registers overlap in address (both from D000); use function 04 for live values and 03 for settings.
- Selecting 8N1 breaks the 11-bit frame rule of the Modbus serial specification; prefer 8E1 or 8N2.
ebm-papst EC fans with MODBUS Lite (series 84/112/150/200 Lite) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 53248doc D000 | Identification | Electronics/protocol type code; see the identification table in the source. | UINT16 | Read | ||||
| IR | 53249doc D001 | Maximum number of bytes | Largest telegram the fan accepts. | UINT16 | Read | ||||
| IR | 53250doc D002 | Software name of bus controller | UINT16 | Read | |||||
| IR | 53251doc D003 | Software version of bus controller | Version in the low byte; high byte is 0. | UINT16 | Read | ||||
| IR | 53264doc D010 | Actual speed | rpm = raw x nMax / 64000, where nMax is Maximum speed (D119). Capped at 0xFFF0. | UINT16 | Read | ||||
| IR | 53265doc D011 | Motor status | Errors currently detected; FB is set with every error. | BITMAP16 | Read | bit 0 = PHA: phase failure / mains undervoltage; bit 2 = TFE: power module overheated; bit 4 = FB: fan bad (general error); bit 5 = TFM: motor overheated; bit 6 = HLL: Hall sensor error; bit 7 = BLK: locked motor; bit 12 = UzLow: DC-link undervoltage | |||
| IR | 53266doc D012 | Warning | Pre-alarm conditions. | BITMAP16 | Read | bit 0 = I_Limit: current limitation; bit 2 = P_Limit: power limitation; bit 3 = TE_high: output stage temperature high; bit 4 = TM_high: motor temperature high; bit 5 = TEI_high: interior electronics temperature high; bit 6 = UzLow: DC-link voltage low; bit 7 = Brake: braking against external drive; bit 9 = n_Low: speed below running-monitor limit; bit 10 = Cable break at analogue set value input; bit 12 = UzHigh: DC-link voltage high; bit 13 = nGrenz: limiting speed exceeded; bit 14 = UeHigh: supply voltage high; bit 15 = LRF: shedding function active | |||
| IR | 53267doc D013 | DC-link voltage | V = raw x reference Uz (D1A0) / 256. | UINT16 | Read | ||||
| IR | 53268doc D014 | DC-link current | A = raw x reference Iz (D1A1) / 256. | UINT16 | Read | ||||
| IR | 53270doc D016 | Motor temperature | INT16 | °C | Read | ||||
| IR | 53271doc D017 | Interior electronics temperature | INT16 | °C | Read | ||||
| IR | 53272doc D018 | Current direction of rotation | UINT16 | Read | 0 = Anti-clockwise; 1 = Clockwise | ||||
| IR | 53273doc D019 | Current modulation level | Percent = raw x 100 / 65536. | UINT16 | × 0.0015258789 | % | Read | ||
| IR | 53274doc D01A | Current set value | Speed control: rpm = raw x nMax / 64000, where nMax is Maximum speed (D119). PWM control: % = raw x 100 / 65536. | UINT16 | Read | ||||
| IR | 53275doc D01B | Sensor actual value | Voltage at the analogue input = raw x 10 / 65536. | UINT16 | × 0.0001525879 | V | Read | ||
| IR | 53277doc D01D | Current parameter set | UINT16 | Read | 0 = Parameter set 1; 1 = Parameter set 2 | ||||
| IR | 53281doc D021 | Current power | W = raw x reference Uz x reference Iz / 65536. | UINT16 | Read | ||||
| HR | 53248doc D000 | Reset | Bits clear themselves once executed. | BITMAP16 | Read/write | bit 0 = User software reset (communication kept); bit 1 = Adopt parameters (EEPROM to RAM); bit 2 = Reset errors; bit 3 = Full software reset (comms drop for seconds) | |||
| HR | 53249doc D001 | Default set value | Set value when source is RS485. Speed: raw = rpm x 64000 / nMax; PWM: raw = % x 65536 / 100. | UINT16 | Read/write | ||||
| HR | 53257doc D009 | Operating hours counter | Stops at 65535. Only ebm-papst level may write it. | UINT16 | h | Read | |||
| HR | 53258doc D00A | Operating minutes counter | Only ebm-papst level may write it. | UINT16 | min | Read | |||
| HR | 53504doc D100 | Fan address | 1-247, low byte. | UINT16 | Read/write | ||||
| HR | 53505doc D101 | Source set value | UINT16 | Read/write | 0 = Analogue input 0-10 V; 1 = RS485 (default set value D001) | ||||
| HR | 53506doc D102 | Preferred running direction | UINT16 | Read/write | 0 = Anti-clockwise; 1 = Clockwise | ||||
| HR | 53507doc D103 | Save set value | 1 also stores D001 in EEPROM (limited to 100,000 writes). | UINT16 | Read/write | 0 = Not stored (fan stopped after reset); 1 = Stored in EEPROM | |||
| HR | 53509doc D105 | Internal parameter set | UINT16 | Read/write | 0 = Parameter set 1; 1 = Parameter set 2 | ||||
| HR | 53510doc D106 | Control mode (parameter set 1) | UINT16 | Read/write | 0 = Closed-loop speed control; 2 = Open-loop PWM control | ||||
| HR | 53511doc D107 | Control mode (parameter set 2) | UINT16 | Read/write | 0 = Closed-loop speed control; 2 = Open-loop PWM control | ||||
| HR | 53529doc D119 | Maximum speed (nMax) | Reference for all speed values (64000 = nMax). | UINT16 | rpm | Read/write | |||
| HR | 53577doc D149 | Transfer rate | Applied after Adopt parameters/Reset or power cycle. | UINT16 | Read/write | 1 = 2400; 2 = 4800; 3 = 9600; 4 = 19200 (recommended); 5 = 38400; 6 = 57600; 7 = 115200 | |||
| HR | 53578doc D14A | Parity configuration | Applied after Adopt parameters/Reset or power cycle. | UINT16 | Read/write | 0 = 8E1 (recommended); 1 = 8O1; 2 = 8N2; 3 = 8N1 | |||
| HR | 53664doc D1A0 | Reference value of DC-link voltage | Raw x 20 mV; used to scale D013 and D021. | UINT16 | × 0.02 | V | Read | ||
| HR | 53665doc D1A1 | Reference value of DC-link current | Raw x 2 mA; used to scale D014 and D021. | UINT16 | × 0.002 | A | Read |
Notes on this map
- Encoding: the document states parameters are big endian (high byte first). All registers listed here are single 16-bit values.
- Speed values use 64000 = Maximum speed (D119); DC-link voltage and current use reference values D1A0 (20 mV steps) and D1A1 (2 mA steps); power uses both. Those registers carry raw values with scale 1 and the formula in the description.
- Bit positions in Motor status (D011), Warning (D012) and Reset (D000) were read from the column layout of the encoding tables (MSB = bits 15-8, LSB = bits 7-0).
- Left out: module temperature (D015) because the document gives no signed/unsigned format for it, unlike the motor and electronics temperatures; P/I factors, modulation limits, potentiometer curve, fail-safe, derating, error history, password, sensor scaling and production data.
- Many holding registers need a password at a given authorisation level (write it to D002-D004); this map lists the customer-level settings an integrator normally touches.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the ebm-papst EC fans with MODBUS Lite (series 84/112/150/200 Lite)
What Modbus registers does the ebm-papst EC fans with MODBUS Lite (series 84/112/150/200 Lite) have?
This map lists 33 registers: 17 input registers, 16 holding registers. 12 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the ebm-papst EC fans with MODBUS Lite (series 84/112/150/200 Lite) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are printed in hex and are the register address sent in the frame; the manual's own example telegrams write D149 as bytes D1 49 and trigger Adopt parameters with 06 D0 00. Input and holding registers both start at D000 but are separate tables.
What are the minimum Modbus registers to integrate the ebm-papst EC fans with MODBUS Lite (series 84/112/150/200 Lite)?
Start with IR 53264 Actual speed (Actual speed (scaled by nMax)); IR 53265 Motor status (Motor status / error bits); IR 53266 Warning (Warning bits); IR 53281 Current power (Current power); HR 53249 Default set value (Set value from Modbus); HR 53505 Source set value (Set value source (1 = RS485)); HR 53529 Maximum speed (nMax) (Maximum speed reference).
How do I enable Modbus control of the ebm-papst EC fans with MODBUS Lite (series 84/112/150/200 Lite)?
Write Source set value D101 = 1 (RS485) so the fan follows Default set value D001 instead of the 0-10 V input.
What happens when the ebm-papst EC fans with MODBUS Lite (series 84/112/150/200 Lite) loses Modbus communication?
A fail-safe function can apply a separate set value and running direction when the Modbus connection breaks (sections 2.35-2.38 of the source); it is not mapped here.
Where is the official ebm-papst EC fans with MODBUS Lite (series 84/112/150/200 Lite) Modbus documentation?
The source is MODBUS parameters ebm-papst series 84 / 112 / 150 / 200 Lite (MODBUS Lite Basic Functionality V5.01) (V5.01), published free by ebm-papst at https://www.ebmpapst.com/content/dam/ebm-papst/loc/europe/gb/modbus-parameter-specifications/MODBUS%20Lite%20Basic%20Functionality%20V5_01.pdf.
Other hvac equipment register maps
- Thermostat
Johnson Controls PENN TC3223 refrigeration temperature controller (Modbus RTU)
PENN TC3223 electronic refrigeration controller with built-in Modbus RTU, per the TC3 Modbus Protocol Reference Guide LIT-12013523 (2020-04-28).
Also known as: TC3223, TC3, PENN TC3, LIT-12013523 - Air handler (computer room air conditioner)
Mitsubishi Electric s-MEXT-G00 computer room air conditioner (ME28 relC)
Mitsubishi Electric (Hydronics & IT Cooling) s-MEXT-G00 006-044 close-control units with ME28-relC software and the Modbus serial board.
Also known as: s-MEXT, s-MEXT-G00 006-044, s-MEXT G00, ME28 relC - Air handler humidifier (gas-fired steam)
Neptronic SKG4 gas-fired steam humidifier (Modbus communication module)
Neptronic SKG4 series gas-fired steam humidifiers (one to four burner modules) with the Modbus communication module, guide SKG4-Modbus Guide-221114 (V2.04).
Also known as: SKG4-E, SKG4-N, SKG4 Gas Fired Humidifier, Neptronic SKG4 Modbus - Air handler controller
Regin Corrigo ventilation controller (ventilation application 3.6)
Regin Corrigo controllers running the pre-programmed ventilation (air handling unit) application, version 3.6 or later; not the heating or Exigo applications.
Also known as: Corrigo E, Corrigo ventilation, Corrigo E ventilation, Corrigo AHU controller - Air handler (heat recovery unit controller)
Swegon TAC5 DG/DM/DT controller (Global HRglobal, HRup, HRflat, HRtotal, HRmural)
Swegon (Global) TAC5 DG, DM and DT regulation boards with the SAT MODBUS (RTU) or SAT WIFI/ETHERNET (TCP) satellite; TAC5 + MODBUS TABLE Cid 050338 (2021-09-20). The TAC5 SC/F single-flow boards use other registers and are not covered.
Also known as: TAC5 DG, TAC5 DM, TAC5 DT, Global HRglobal, Global HRup, Global HRflat, Global HRtotal, Global HRmural, SAT MODBUS - Thermostat / temperature controller
Watlow EZ-ZONE PM PID / limit / integrated controller (Modbus RTU)
Watlow EZ-ZONE PM panel-mount controllers (PID, limit and integrated models) with Modbus RTU, per communications manual 0600-0056-0000 Rev. B (Nov 2007).
Also known as: EZ-ZONE PM, EZ-ZONE PM Limit, EZ-ZONE PM Integrated
All hvac equipment Modbus register maps →
Source: MODBUS parameters ebm-papst series 84 / 112 / 150 / 200 Lite (MODBUS Lite Basic Functionality V5.01) · V5.01. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.