Thermostat / temperature controller · Modbus register map

Watlow EZ-ZONE PM PID / limit / integrated controller (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

The EZ-ZONE PM is Watlow's panel-mount PID and limit controller family. With the Modbus RTU option every parameter has a fixed register: floats take two registers and enumerated settings use Watlow's numeric codes (for example 106 = Yes). This map covers the operations values an integrator needs: input process values and errors, loop set points, control mode, PID terms, output power, autotune, event and limit states, alarm 1 set points and status, and the basic communications settings. The full parameter list is in the manual.

This page lists 45 Modbus registers for the Watlow EZ-ZONE PM PID / limit / integrated controller (Modbus RTU) — 26 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Watlow’s own free documentation (linked below) and checked against it.

Manufacturer
Watlow
Model
EZ-ZONE PM PID / limit / integrated controller (Modbus RTU)
Equipment type
Thermostat / temperature controller
Registers
45 (26 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
8N1
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
CDAB low word first (word-swapped)
Also known as
EZ-ZONE PM, EZ-ZONE PM Limit, EZ-ZONE PM Integrated
Source document
EZ-ZONE PM Controller Communications Manual · 0600-0056-0000 Rev. B · rev. 2007-11 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Watlow EZ-ZONE PM PID / limit / integrated controller (Modbus RTU)

Integration in brief

Read the process value as a low-word-first float at 360-361 and the closed-loop set point at 2160-2161; write the set point with function 16. Control mode is at 1880 and output power at 1908.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 360Analog input 1 process valueFLOAT32 CDABAnalog input 1 process valueRead
HR 362Analog input 1 error statusUINT16Input 1 error statusRead
HR 2160Closed loop set pointFLOAT32 CDABClosed loop set pointRead/write
HR 1880Control modeUINT16Control modeRead/write
HR 1908Control loop output powerFLOAT32 CDABOutput powerRead
HR 1928Loop error statusUINT16Loop error statusRead

Enable Modbus control & writes

Set Protocol to Modbus RTU and set the Modbus address, baud rate and parity in the Communications menu of the Setup Page on the front panel.

Byte order & addressing

Network setup

Watch out for

Watlow EZ-ZONE PM PID / limit / integrated controller (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

45 of 45 shown
Watlow EZ-ZONE PM PID / limit / integrated controller (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR360Analog input 1 process valueIn the display units set for this channel (°F default).FLOAT32CDABRead
HR362Analog input 1 error statusUINT16Read9 = Ambient error; 61 = None; 65 = Open; 127 = Shorted; 139 = Bad calibration data; 140 = Measurement error; 141 = RTD lead resistance error
HR382Analog input 1 calibration offsetFLOAT32CDABRead/write
HR440Analog input 2 process valueMarked for integrated (Int.) models only.FLOAT32CDABRead
HR442Analog input 2 error statusMarked for integrated (Int.) models only.UINT16Read9 = Ambient error; 61 = None; 65 = Open; 127 = Shorted; 139 = Bad calibration data; 140 = Measurement error; 141 = RTD lead resistance error
HR446Ambient temperature, input 2FLOAT32CDABRead
HR462Analog input 2 calibration offsetMarked for integrated (Int.) models only.FLOAT32CDABRead/write
HR690Limit stateLimit models.UINT16Read28 = Error; 51 = Limit high; 52 = Limit low; 61 = None; 62 = Off
HR1328Event 1 statusUINT16Read5 = Active; 41 = Inactive
HR1348Event 2 statusUINT16Read5 = Active; 41 = Inactive
HR1368EZ key statusThe manual describes it as the status of event 3.UINT16Read5 = Active; 41 = Inactive
HR1480Alarm 1 high set pointProcess value or deviation, per alarm type.FLOAT32CDABRead/write
HR1482Alarm 1 low set pointProcess value or deviation, per alarm type.FLOAT32CDABRead/write
HR1498Alarm 1 latched statusUINT16Read59 = No; 106 = Yes
HR1500Alarm 1 silenced statusUINT16Read59 = No; 106 = Yes
HR1502Alarm 1 clearable statusUINT16Read59 = No; 106 = Yes
HR1504Alarm 1 clear requestWrite 0 to clear the alarm state.UINT16Write
HR1506Alarm 1 silence requestWrite 0 to this request register.UINT16Write
HR1516Alarm 1 working process valueFLOAT32CDABRead
HR1518Alarm 1 working set pointFLOAT32CDABRead
HR1880Control modeUINT16Read/write10 = Auto (closed loop); 54 = Manual (open loop); 62 = Off
HR1890Heat proportional bandFLOAT32CDABRead/write
HR1892Cool proportional bandFLOAT32CDABRead/write
HR1894Time integral0-9999 s per repeat.FLOAT32CDABsRead/write
HR1896Time derivative0-9999 s.FLOAT32CDABsRead/write
HR1898Dead band-1000 to 1000.FLOAT32CDABRead/write
HR1900Heat hysteresisFLOAT32CDABRead/write
HR1902Cool hysteresisFLOAT32CDABRead/write
HR1908Control loop output power-100 to 100 %.FLOAT32CDAB%Read
HR1918Autotune set point50-200 % of the current set point.FLOAT32CDAB%Read/write
HR1920Autotune requestUINT16Read/write59 = No; 106 = Yes
HR1928Loop error statusUINT16Read61 = None; 1274 = Open loop; 1278 = Reversed loop
HR1930Loop error clearUINT16Read/write129 = Clear; 204 = Ignore
HR2160Closed loop set pointDefault 75.0.FLOAT32CDABRead/write
HR2162Open loop set pointFixed output power in manual mode.FLOAT32CDAB%Read/write
HR2176Idle set pointFLOAT32CDABRead/write
HR2178Bumpless set pointSet point that applies if a bumpless transfer occurs.FLOAT32CDABRead
HR2190Ramp active set pointFLOAT32CDABRead
HR2198Ramp target set pointFLOAT32CDABRead
HR2200Remote enableUINT16Read/write59 = No; 106 = Yes
HR2202Remote set point typeUINT16Read/write10 = Auto (closed loop); 54 = Manual (open loop)
HR2482Comms 1 Modbus address1-247, default 1.UINT16Read/write
HR2486Comms 1 Modbus parityUINT16Read/write61 = None; 191 = Even; 192 = Odd
HR2490Comms 1 temperature unitsUINT16Read/write15 = °C; 30 = °F
HR2592Comms 1 protocolUINT16Read/write1057 = Modbus RTU; 1286 = Standard Bus

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Watlow EZ-ZONE PM PID / limit / integrated controller (Modbus RTU)

What Modbus registers does the Watlow EZ-ZONE PM PID / limit / integrated controller (Modbus RTU) have?

This map lists 45 registers: 45 holding registers. 26 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Watlow EZ-ZONE PM PID / limit / integrated controller (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual lists 'relative' Modbus registers (less the 40,001 offset) and sends them unchanged: the worked read of analog input 1 sends 360 as hex 01 68. In a Modicon-style tool, 360 is 40361.

What byte order does the Watlow EZ-ZONE PM PID / limit / integrated controller (Modbus RTU) use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Watlow EZ-ZONE PM PID / limit / integrated controller (Modbus RTU)?

Start with HR 360 Analog input 1 process value (Analog input 1 process value); HR 362 Analog input 1 error status (Input 1 error status); HR 2160 Closed loop set point (Closed loop set point); HR 1880 Control mode (Control mode); HR 1908 Control loop output power (Output power); HR 1928 Loop error status (Loop error status).

How do I enable Modbus control of the Watlow EZ-ZONE PM PID / limit / integrated controller (Modbus RTU)?

Set Protocol to Modbus RTU and set the Modbus address, baud rate and parity in the Communications menu of the Setup Page on the front panel.

Where is the official Watlow EZ-ZONE PM PID / limit / integrated controller (Modbus RTU) Modbus documentation?

The source is EZ-ZONE PM Controller Communications Manual (0600-0056-0000 Rev. B), revision 2007-11. Watlow doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.instrumart.com/assets/ezzone-pm_communicationsmanual.pdf. It may be an older revision, so check it against the live unit.

Other hvac equipment register maps

All hvac equipment Modbus register maps →

Source: EZ-ZONE PM Controller Communications Manual · 0600-0056-0000 Rev. B · rev. 2007-11 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.