- EZ-ZONE PM PID / limit / integrated controller (Modbus RTU)
Thermostat / temperature controller · Modbus register map
Watlow EZ-ZONE PM PID / limit / integrated controller (Modbus RTU) Modbus register map
Updated 17 November 2026
The EZ-ZONE PM is Watlow's panel-mount PID and limit controller family. With the Modbus RTU option every parameter has a fixed register: floats take two registers and enumerated settings use Watlow's numeric codes (for example 106 = Yes). This map covers the operations values an integrator needs: input process values and errors, loop set points, control mode, PID terms, output power, autotune, event and limit states, alarm 1 set points and status, and the basic communications settings. The full parameter list is in the manual.
This page lists 45 Modbus registers for the Watlow EZ-ZONE PM PID / limit / integrated controller (Modbus RTU) — 26 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Watlow’s own free documentation (linked below) and checked against it.
- Manufacturer
- Watlow
- Model
- EZ-ZONE PM PID / limit / integrated controller (Modbus RTU)
- Equipment type
- Thermostat / temperature controller
- Registers
- 45 (26 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 8N1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- CDAB low word first (word-swapped)
- Also known as
- EZ-ZONE PM, EZ-ZONE PM Limit, EZ-ZONE PM Integrated
Integration notes: Watlow EZ-ZONE PM PID / limit / integrated controller (Modbus RTU)
Read the process value as a low-word-first float at 360-361 and the closed-loop set point at 2160-2161; write the set point with function 16. Control mode is at 1880 and output power at 1908.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 360 | Analog input 1 process value | FLOAT32 CDAB | Analog input 1 process value | Read |
| HR 362 | Analog input 1 error status | UINT16 | Input 1 error status | Read |
| HR 2160 | Closed loop set point | FLOAT32 CDAB | Closed loop set point | Read/write |
| HR 1880 | Control mode | UINT16 | Control mode | Read/write |
| HR 1908 | Control loop output power | FLOAT32 CDAB | Output power | Read |
| HR 1928 | Loop error status | UINT16 | Loop error status | Read |
Enable Modbus control & writes
Set Protocol to Modbus RTU and set the Modbus address, baud rate and parity in the Communications menu of the Setup Page on the front panel.
Byte order & addressing
- Floats are low word first by default (CDAB).
- Watlow uses numeric codes for enumerations (106 = Yes, 59 = No).
- Temperature unit for the comms channel is set separately (2490).
Network setup
- Defaults per the manual footnote: 8 data bits, no parity, 1 stop bit; Modbus address 1 (range 1-247).
Watch out for
- Settings written over the network are not saved to EEPROM by default; the Nonvolatile Memory Save parameter changes this. The EEPROM is rated for about 1,000,000 writes, so avoid continuous writes in a loop.
- Some parameters exist only on some model configurations (PID, limit, integrated).
Watlow EZ-ZONE PM PID / limit / integrated controller (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 360 | Analog input 1 process value | In the display units set for this channel (°F default). | FLOAT32 | CDAB | Read | |||
| HR | 362 | Analog input 1 error status | UINT16 | Read | 9 = Ambient error; 61 = None; 65 = Open; 127 = Shorted; 139 = Bad calibration data; 140 = Measurement error; 141 = RTD lead resistance error | ||||
| HR | 382 | Analog input 1 calibration offset | FLOAT32 | CDAB | Read/write | ||||
| HR | 440 | Analog input 2 process value | Marked for integrated (Int.) models only. | FLOAT32 | CDAB | Read | |||
| HR | 442 | Analog input 2 error status | Marked for integrated (Int.) models only. | UINT16 | Read | 9 = Ambient error; 61 = None; 65 = Open; 127 = Shorted; 139 = Bad calibration data; 140 = Measurement error; 141 = RTD lead resistance error | |||
| HR | 446 | Ambient temperature, input 2 | FLOAT32 | CDAB | Read | ||||
| HR | 462 | Analog input 2 calibration offset | Marked for integrated (Int.) models only. | FLOAT32 | CDAB | Read/write | |||
| HR | 690 | Limit state | Limit models. | UINT16 | Read | 28 = Error; 51 = Limit high; 52 = Limit low; 61 = None; 62 = Off | |||
| HR | 1328 | Event 1 status | UINT16 | Read | 5 = Active; 41 = Inactive | ||||
| HR | 1348 | Event 2 status | UINT16 | Read | 5 = Active; 41 = Inactive | ||||
| HR | 1368 | EZ key status | The manual describes it as the status of event 3. | UINT16 | Read | 5 = Active; 41 = Inactive | |||
| HR | 1480 | Alarm 1 high set point | Process value or deviation, per alarm type. | FLOAT32 | CDAB | Read/write | |||
| HR | 1482 | Alarm 1 low set point | Process value or deviation, per alarm type. | FLOAT32 | CDAB | Read/write | |||
| HR | 1498 | Alarm 1 latched status | UINT16 | Read | 59 = No; 106 = Yes | ||||
| HR | 1500 | Alarm 1 silenced status | UINT16 | Read | 59 = No; 106 = Yes | ||||
| HR | 1502 | Alarm 1 clearable status | UINT16 | Read | 59 = No; 106 = Yes | ||||
| HR | 1504 | Alarm 1 clear request | Write 0 to clear the alarm state. | UINT16 | Write | ||||
| HR | 1506 | Alarm 1 silence request | Write 0 to this request register. | UINT16 | Write | ||||
| HR | 1516 | Alarm 1 working process value | FLOAT32 | CDAB | Read | ||||
| HR | 1518 | Alarm 1 working set point | FLOAT32 | CDAB | Read | ||||
| HR | 1880 | Control mode | UINT16 | Read/write | 10 = Auto (closed loop); 54 = Manual (open loop); 62 = Off | ||||
| HR | 1890 | Heat proportional band | FLOAT32 | CDAB | Read/write | ||||
| HR | 1892 | Cool proportional band | FLOAT32 | CDAB | Read/write | ||||
| HR | 1894 | Time integral | 0-9999 s per repeat. | FLOAT32 | CDAB | s | Read/write | ||
| HR | 1896 | Time derivative | 0-9999 s. | FLOAT32 | CDAB | s | Read/write | ||
| HR | 1898 | Dead band | -1000 to 1000. | FLOAT32 | CDAB | Read/write | |||
| HR | 1900 | Heat hysteresis | FLOAT32 | CDAB | Read/write | ||||
| HR | 1902 | Cool hysteresis | FLOAT32 | CDAB | Read/write | ||||
| HR | 1908 | Control loop output power | -100 to 100 %. | FLOAT32 | CDAB | % | Read | ||
| HR | 1918 | Autotune set point | 50-200 % of the current set point. | FLOAT32 | CDAB | % | Read/write | ||
| HR | 1920 | Autotune request | UINT16 | Read/write | 59 = No; 106 = Yes | ||||
| HR | 1928 | Loop error status | UINT16 | Read | 61 = None; 1274 = Open loop; 1278 = Reversed loop | ||||
| HR | 1930 | Loop error clear | UINT16 | Read/write | 129 = Clear; 204 = Ignore | ||||
| HR | 2160 | Closed loop set point | Default 75.0. | FLOAT32 | CDAB | Read/write | |||
| HR | 2162 | Open loop set point | Fixed output power in manual mode. | FLOAT32 | CDAB | % | Read/write | ||
| HR | 2176 | Idle set point | FLOAT32 | CDAB | Read/write | ||||
| HR | 2178 | Bumpless set point | Set point that applies if a bumpless transfer occurs. | FLOAT32 | CDAB | Read | |||
| HR | 2190 | Ramp active set point | FLOAT32 | CDAB | Read | ||||
| HR | 2198 | Ramp target set point | FLOAT32 | CDAB | Read | ||||
| HR | 2200 | Remote enable | UINT16 | Read/write | 59 = No; 106 = Yes | ||||
| HR | 2202 | Remote set point type | UINT16 | Read/write | 10 = Auto (closed loop); 54 = Manual (open loop) | ||||
| HR | 2482 | Comms 1 Modbus address | 1-247, default 1. | UINT16 | Read/write | ||||
| HR | 2486 | Comms 1 Modbus parity | UINT16 | Read/write | 61 = None; 191 = Even; 192 = Odd | ||||
| HR | 2490 | Comms 1 temperature units | UINT16 | Read/write | 15 = °C; 30 = °F | ||||
| HR | 2592 | Comms 1 protocol | UINT16 | Read/write | 1057 = Modbus RTU; 1286 = Standard Bus |
Notes on this map
- Watlow does not appear to host this communications manual publicly; the copy linked is a distributor (Instrumart) copy of the unaltered Watlow manual, Rev. B from 2007.
- Floats are IEEE 754 in two registers with the low word first by default (CDAB): register 360 holds the low word and 361 the high word, as the manual's example shows. The order can be changed to high-low in the Communications menu; this map assumes the default.
- Integers are unsigned 16-bit. Enumerated parameters use Watlow codes, e.g. 59 = No, 106 = Yes, 62 = Off.
- Temperatures follow the display units chosen for the communications port (°F by default).
- Only a subset is listed (operations-page values, alarm 1 and comms basics); alarms 2-4 follow the same pattern at other registers given in the manual, as do setup and profile parameters.
- Left out: the word-order and non-volatile-save registers, which the manual prints with the same address (2494); the baud-rate register, whose value codes are not printed. The manual gives the default serial format as 9,600 baud in its footnotes but lists 38,400 as the baud-rate default, so the default baud is left blank.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Watlow EZ-ZONE PM PID / limit / integrated controller (Modbus RTU)
What Modbus registers does the Watlow EZ-ZONE PM PID / limit / integrated controller (Modbus RTU) have?
This map lists 45 registers: 45 holding registers. 26 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Watlow EZ-ZONE PM PID / limit / integrated controller (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual lists 'relative' Modbus registers (less the 40,001 offset) and sends them unchanged: the worked read of analog input 1 sends 360 as hex 01 68. In a Modicon-style tool, 360 is 40361.
What byte order does the Watlow EZ-ZONE PM PID / limit / integrated controller (Modbus RTU) use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Watlow EZ-ZONE PM PID / limit / integrated controller (Modbus RTU)?
Start with HR 360 Analog input 1 process value (Analog input 1 process value); HR 362 Analog input 1 error status (Input 1 error status); HR 2160 Closed loop set point (Closed loop set point); HR 1880 Control mode (Control mode); HR 1908 Control loop output power (Output power); HR 1928 Loop error status (Loop error status).
How do I enable Modbus control of the Watlow EZ-ZONE PM PID / limit / integrated controller (Modbus RTU)?
Set Protocol to Modbus RTU and set the Modbus address, baud rate and parity in the Communications menu of the Setup Page on the front panel.
Where is the official Watlow EZ-ZONE PM PID / limit / integrated controller (Modbus RTU) Modbus documentation?
The source is EZ-ZONE PM Controller Communications Manual (0600-0056-0000 Rev. B), revision 2007-11. Watlow doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.instrumart.com/assets/ezzone-pm_communicationsmanual.pdf. It may be an older revision, so check it against the live unit.
Other hvac equipment register maps
- Air handler humidifier (hybrid / spray)
Condair DL II hybrid humidifier (Integrated Controller, Modbus RTU/TCP)
Condair DL with the Integrated Controller, per addendum 2603326-G.
Also known as: Condair DL, Condair DL II, DL - Air handler humidifier (steam humidifier controller)
DriSteem Vapor-logic 6 humidifier controller (Modbus RTU)
DriSteem humidifiers and humidification systems controlled by Vapor-logic firmware 6.X.X, per IOM form VL6-IOM-EN-REVH-0225.
Also known as: Vapor-logic, Vapor-logic version 6, VL6, DriSteem GTS, DriSteem XT, DriSteem STS, DriSteem LTS, Vaporstream - Thermostat
Johnson Controls PENN TC3221 refrigeration temperature controller (Modbus RTU)
PENN TC3221 electronic refrigeration controller with built-in Modbus RTU, per the TC3 Modbus Protocol Reference Guide LIT-12013523 (2020-04-28).
Also known as: TC3221, TC3, PENN TC3, LIT-12013523 - Rooftop unit / packaged wall-mount air conditioner
Marvair MAH / MGH wall-mount air conditioner control board (Modbus RTU)
Marvair MAH1018A-1060A, MGH1072A, MAH2024A-2060A and MGH2072A wall-mount air conditioners with the electronic control board (I&O manual rev. 7).
Also known as: MAH1018A, MAH1024A, MAH1030A, MAH1036A, MAH1042A, MAH1048A, MAH1060A, MGH1072A, MAH2024A, MAH2030A, MAH2036A, MAH2042A, MAH2048A, MAH2060A, MGH2072A, Marvair MAH, Marvair MGH - Air handler terminal (dual-duct VAV controller)
Neptronic EVCBM dual-duct VAV controller (Modbus communication module)
Neptronic EVCBM dual-duct VAV controllers (master + slave airflow) with the Modbus module, guide EVCBM Dual Duct-V500-Modbus Guide-180927-ESA.
Also known as: EVCBM Dual Duct, EVCB, Neptronic EVCBM Modbus - Thermostat / temperature and process PID controller
Omega CN2200 / CN2400 series temperature and process controllers (Modbus RTU)
Omega CN2200 and CN2400 series controllers with the Modbus comms option (CN2400 software 1.03-3.05, CN2200 1.00-2.10 per the handbook).
Also known as: CN2204, CN2208, CN2408
All hvac equipment Modbus register maps →
Source: EZ-ZONE PM Controller Communications Manual · 0600-0056-0000 Rev. B · rev. 2007-11 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.