- DL II hybrid humidifier (Integrated Controller, Modbus RTU/TCP)
Air handler humidifier (hybrid / spray) · Modbus register map
Condair DL II hybrid humidifier (Integrated Controller, Modbus RTU/TCP) Modbus register map
Updated 17 November 2026
The Condair DL is a hybrid spray-and-evaporation humidifier for air handling units. Its Integrated Controller is a Modbus RTU slave on RS-485 or a Modbus TCP server. This map covers status, valve and safety-loop states, capacity, humidity, pressures, water quality and Ag-ion values, and the writable setpoint, control and remote-enable registers.
This page lists 40 Modbus registers for the Condair DL II hybrid humidifier (Integrated Controller, Modbus RTU/TCP) — 8 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Condair’s own free documentation (linked below) and checked against it.
- Manufacturer
- Condair
- Model
- DL II hybrid humidifier (Integrated Controller, Modbus RTU/TCP)
- Equipment type
- Air handler humidifier (hybrid / spray)
- Registers
- 40 (8 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- 10
- Default serial
- 19200 baud, 8E1
- TCP port
- 502
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- Condair DL, Condair DL II, DL
Integration notes: Condair DL II hybrid humidifier (Integrated Controller, Modbus RTU/TCP)
Read input registers 2000-2019 (UInt16 states) and 2025-2050 (floats). To control over Modbus, write the demand or humidity value to holding 3004 at least once per signal timeout and enable via 3005.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 2001 | Device Status | UINT16 | Device status | Read |
| IR 2002 | Maintenance and Error Status | UINT16 | Maintenance and error status | Read |
| IR 2003 | Error or Warning Code | UINT16 | Error/warning code | Read |
| IR 2027 | Actual Humidification Capacity | FLOAT32 ABCD | Actual capacity | Read |
| IR 2029 | Actual Humidity or Demand | FLOAT32 ABCD | Actual humidity or demand | Read |
| HR 3004 | Actual Humidity or Demand via Modbus | UINT16 | Demand/humidity via Modbus | Read/write |
| HR 3005 | Remote Enable | UINT16 | Remote enable | Read/write |
Enable Modbus control & writes
Controls > Signal Settings: set Source = Modbus (and Remote Enable = Modbus to use register 43006). The demand register 43005 only works when Source is not Analog.
Communication loss & watchdog
When the demand or humidity signal comes from Modbus, it must be rewritten within 'Signal Timeout' (1-300 s, default 300 s); otherwise warning W35 is raised and the unit stops humidifying.
Byte order & addressing
- The address column is the wire address; 32001 is address 2000.
- Floats are two registers, MSR first by default.
Network setup
- Menu > password 8808 > Network > Modbus Settings: set protocol (Modbus/RTU or Modbus/TCP), address, parity, baud rate and register sequence; the controller restarts after a protocol change.
- For Modbus TCP set the IP parameters under Network > IP Settings (factory setting DHCP).
Watch out for
- With Modbus as signal source, do not also wire a hard demand signal to the driver board.
- Remote enable via 43006 needs software 1.4.0 or later.
Condair DL II hybrid humidifier (Integrated Controller, Modbus RTU/TCP) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 2000doc 32001 | DL Type | UINT16 | Read | 0 = Humidifier; 1 = Humidifier + FC; 2 = Humidifier + FC - Off | ||||
| IR | 2001doc 32002 | Device Status | UINT16 | Read | 0 = Initializing; 1 = Diagnostic; 2 = Stopped; 3 = Flushing; 4 = Standby; 5 = Humidifying; 6 = Ready; 7 = Air Cleaning; 8 = Filling; 9 = Conductivity Flush; 10 = Switched Off; 11 = Remote Off; 12 = Temperature Flush; 13 = Ceramic Wash Over | ||||
| IR | 2002doc 32003 | Maintenance and Error Status | UINT16 | Read | 0 = No Info; 1 = Warning; 2 = Activation Code; 3 = Out of Commissioning; 4 = Refill Disinfection; 5 = Maintenance; 6 = Error; 7 = Replace Ag Cartridge; 8 = Disinfection | ||||
| IR | 2003doc 32004 | Error or Warning Code | 0 = no error; other codes are listed in the device operation manual. | UINT16 | Read | ||||
| IR | 2004doc 32005 | Safety Loop | Range 0 = Open 1 = Closed (=ok). | UINT16 | Read | ||||
| IR | 2005doc 32006 | Y1 Inlet Valve | UINT16 | Read | 0 = Closed; 1 = Open | ||||
| IR | 2007doc 32008 | Y3 Valve Air Cleaning | UINT16 | Read | 0 = Closed; 1 = Open | ||||
| IR | 2008doc 32009 | Y4 Valve External Pipe Flush | UINT16 | Read | 0 = Closed; 1 = Open | ||||
| IR | 2009doc 32010 | Y5 Spray Valve | UINT16 | Read | 0 = Closed; 1 = Open | ||||
| IR | 2010doc 32011 | Y6 Spray Valve | UINT16 | Read | 0 = Closed; 1 = Open | ||||
| IR | 2011doc 32012 | Y7 Spray Valve | UINT16 | Read | 0 = Closed; 1 = Open | ||||
| IR | 2012doc 32013 | Y8 Spray Valve | UINT16 | Read | 0 = Closed; 1 = Open | ||||
| IR | 2013doc 32014 | Y9 Spray Valve | UINT16 | Read | 0 = Closed; 1 = Open | ||||
| IR | 2014doc 32015 | Y10 Drain Valve (NO) | UINT16 | Read | 0 = Open; 1 = Closed | ||||
| IR | 2015doc 32016 | Y11 Auxiliary Outlet Valve | UINT16 | Read | 0 = Open; 1 = Closed | ||||
| IR | 2016doc 32017 | Frequency Converter Enable | UINT16 | Read | 0 = Disable; 1 = Enable | ||||
| IR | 2017doc 32018 | Frequency Converter Status | UINT16 | Read | 0 = Off; 1 = Power On | ||||
| IR | 2018doc 32019 | Fan | UINT16 | Read | 0 = On; 1 = Off | ||||
| IR | 2019doc 32020 | Disinfection Pump (Relay Dosing Pump) | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 2025doc 32026 | Max. Humidification Capacity | Range 2 - 1000 kg/h 4 - 2573 lb/hr. Metric or imperial per controller setting. | FLOAT32 | ABCD | kg/h | Read | ||
| IR | 2027doc 32028 | Actual Humidification Capacity | Range 0 - 1000 kg/h 0 - 2573 lb/hr. Metric or imperial per controller setting. | FLOAT32 | ABCD | kg/h | Read | ||
| IR | 2029doc 32030 | Actual Humidity or Demand | Range 0 - 100 %. | FLOAT32 | ABCD | % | Read | ||
| IR | 2031doc 32032 | Operating Hours | Range 0 - 1200000 h. | FLOAT32 | ABCD | h | Read | ||
| IR | 2033doc 32034 | Next Maintenance | Range 0 - 10000 h. | FLOAT32 | ABCD | h | Read | ||
| IR | 2035doc 32036 | Remaining Ag-Ion Capacity | Range 0 - 58.4 Ah. | FLOAT32 | ABCD | Ah | Read | ||
| IR | 2037doc 32038 | Target Ag-Ion Current | Range 0 - 29.2 mA. | FLOAT32 | ABCD | mA | Read | ||
| IR | 2039doc 32040 | PS4 Inlet Pressure | Range 0 - 10.0 bar 0 - 145.0 psi. Metric or imperial per controller setting. | FLOAT32 | ABCD | bar | Read | ||
| IR | 2041doc 32042 | PS5 Nozzle Pressure | Range 0 - 10.0 bar 0 - 145.0 psi. Metric or imperial per controller setting. | FLOAT32 | ABCD | bar | Read | ||
| IR | 2043doc 32044 | Water Temperature | Range °C or °F. Metric or imperial per controller setting. | FLOAT32 | ABCD | °C | Read | ||
| IR | 2045doc 32046 | Water Conductivity | Range 0 - x μS/cm. | FLOAT32 | ABCD | uS/cm | Read | ||
| IR | 2047doc 32048 | Pump Current | Range 0 - 6.0 A. | FLOAT32 | ABCD | A | Read | ||
| IR | 2049doc 32050 | Ag-Ion Current | Range 0 - x mA. | FLOAT32 | ABCD | mA | Read | ||
| HR | 3000doc 43001 | Setpoint | Range 0 - 95 %. | UINT16 | % | Read/write | |||
| HR | 3001doc 43002 | P-Band | Range 6 - 65 %. | UINT16 | % | Read/write | |||
| HR | 3002doc 43003 | I-Time | Range 1 - 60 min. | UINT16 | min | Read/write | |||
| HR | 3003doc 43004 | Capacity Limitation | Range 20 - 100 %. | UINT16 | % | Read/write | |||
| HR | 3004doc 43005 | Actual Humidity or Demand via Modbus | Range 0 - 100 %. | UINT16 | % | Read/write | |||
| HR | 3005doc 43006 | Remote Enable | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 5001doc 45002 | Remote Flushing | Read 100 = off or 0-99 = progress %; write 1 = start, 0 = stop. | UINT16 | % | Read/write | |||
| HR | 5002doc 45003 | Remote Ceramic Wash Over | Read 100 = off or 0-99 = progress %; write 1 = start, 0 = stop. | UINT16 | % | Read/write |
Notes on this map
- Input registers are read with function 04; holding registers with 03 and written with 06 or 16.
- Floats use 'Register Sequence': MSR first (high register first, ABCD) is the factory setting; LSR first (CDAB) is the option. The map assumes the factory setting.
- Factory serial settings: Modbus RTU, address 10, 19200 baud, even parity, 8 data bits, 1 stop bit. Modbus TCP uses port 502 and unit ID 255 (per the TCP technical data).
- Units marked metric/imperial follow the controller's Metric/Imperial setting; the listed unit is the metric one.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Condair DL II hybrid humidifier (Integrated Controller, Modbus RTU/TCP)
What Modbus registers does the Condair DL II hybrid humidifier (Integrated Controller, Modbus RTU/TCP) have?
This map lists 40 registers: 32 input registers, 8 holding registers. 8 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Condair DL II hybrid humidifier (Integrated Controller, Modbus RTU/TCP) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Tables print the 5-digit register (32001 = input register, 43001 = holding register) and the 0-based address beside it (2000 / 3000). The address column is what goes on the wire; the manual's own example: register 43004 = address 3003.
What byte order does the Condair DL II hybrid humidifier (Integrated Controller, Modbus RTU/TCP) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Condair DL II hybrid humidifier (Integrated Controller, Modbus RTU/TCP)?
Start with IR 2001 Device Status (Device status); IR 2002 Maintenance and Error Status (Maintenance and error status); IR 2003 Error or Warning Code (Error/warning code); IR 2027 Actual Humidification Capacity (Actual capacity); IR 2029 Actual Humidity or Demand (Actual humidity or demand); HR 3004 Actual Humidity or Demand via Modbus (Demand/humidity via Modbus); HR 3005 Remote Enable (Remote enable).
How do I enable Modbus control of the Condair DL II hybrid humidifier (Integrated Controller, Modbus RTU/TCP)?
Controls > Signal Settings: set Source = Modbus (and Remote Enable = Modbus to use register 43006). The demand register 43005 only works when Source is not Analog.
What happens when the Condair DL II hybrid humidifier (Integrated Controller, Modbus RTU/TCP) loses Modbus communication?
When the demand or humidity signal comes from Modbus, it must be rewritten within 'Signal Timeout' (1-300 s, default 300 s); otherwise warning W35 is raised and the unit stops humidifying.
Where is the official Condair DL II hybrid humidifier (Integrated Controller, Modbus RTU/TCP) Modbus documentation?
The source is Modbus addendum manual for DL II, ME II, RS II, RO-E and Vita (Integrated Controller) (2603326-G EN 2607), published free by Condair at https://www.condair.com/m/0/2603326-e-modbus-for-dl-series-addendum.pdf.
More Condair Modbus register maps
- Air handler humidifier (evaporative)
Condair ME II evaporative humidifier / cooler (Integrated Controller, Modbus RTU/TCP)
Condair ME with the Integrated Controller, per addendum 2603326-G.
Also known as: Condair ME, Condair ME II, ME - Pump (reverse osmosis water treatment unit)
Condair RO-E reverse osmosis water treatment (Integrated Controller, Modbus RTU/TCP)
Condair RO-E / RO-E+ with the Integrated Controller, per addendum 2603326-G.
Also known as: Condair RO-E, RO-E+, Condair RO-E+ - Air handler humidifier (resistive steam)
Condair RS II resistive steam humidifier (Integrated Controller, Modbus RTU/TCP)
Condair RS with the Integrated Controller (cylinders A and B), per addendum 2603326-G.
Also known as: Condair RS, Condair RS II, RS - Air handler humidifier (high-pressure room system)
Condair Vita high-pressure humidification system (Integrated Controller, Modbus RTU/TCP)
Condair Vita system with the Integrated Controller, per addendum 2603326-G.
Also known as: Condair Vita, Vita System Master
Other hvac equipment register maps
- Air handler humidifier (steam humidifier controller)
DriSteem Vapor-logic 6 humidifier controller (Modbus RTU)
DriSteem humidifiers and humidification systems controlled by Vapor-logic firmware 6.X.X, per IOM form VL6-IOM-EN-REVH-0225.
Also known as: Vapor-logic, Vapor-logic version 6, VL6, DriSteem GTS, DriSteem XT, DriSteem STS, DriSteem LTS, Vaporstream - Thermostat
Johnson Controls PENN TC3221 refrigeration temperature controller (Modbus RTU)
PENN TC3221 electronic refrigeration controller with built-in Modbus RTU, per the TC3 Modbus Protocol Reference Guide LIT-12013523 (2020-04-28).
Also known as: TC3221, TC3, PENN TC3, LIT-12013523 - Rooftop unit / packaged wall-mount air conditioner
Marvair MAH / MGH wall-mount air conditioner control board (Modbus RTU)
Marvair MAH1018A-1060A, MGH1072A, MAH2024A-2060A and MGH2072A wall-mount air conditioners with the electronic control board (I&O manual rev. 7).
Also known as: MAH1018A, MAH1024A, MAH1030A, MAH1036A, MAH1042A, MAH1048A, MAH1060A, MGH1072A, MAH2024A, MAH2030A, MAH2036A, MAH2042A, MAH2048A, MAH2060A, MGH2072A, Marvair MAH, Marvair MGH - Air handler terminal (dual-duct VAV controller)
Neptronic EVCBM dual-duct VAV controller (Modbus communication module)
Neptronic EVCBM dual-duct VAV controllers (master + slave airflow) with the Modbus module, guide EVCBM Dual Duct-V500-Modbus Guide-180927-ESA.
Also known as: EVCBM Dual Duct, EVCB, Neptronic EVCBM Modbus - Thermostat / temperature and process PID controller
Omega CN2200 / CN2400 series temperature and process controllers (Modbus RTU)
Omega CN2200 and CN2400 series controllers with the Modbus comms option (CN2400 software 1.03-3.05, CN2200 1.00-2.10 per the handbook).
Also known as: CN2204, CN2208, CN2408 - Thermostat / room controller (chilled beam with measured airflow and CO2)
Swegon CONDUCTOR W4 room controller (airflow and water, Modbus RTU)
Swegon CONDUCTOR W4 room controller, software 1.12 (technical manual updated 2014-11-21).
Also known as: CONDUCTOR RE W4, CONDUCTOR RE W4 1, Conductor W4
All hvac equipment Modbus register maps →
Source: Modbus addendum manual for DL II, ME II, RS II, RO-E and Vita (Integrated Controller) · 2603326-G EN 2607. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.