Air handler humidifier (hybrid / spray) · Modbus register map

Condair DL II hybrid humidifier (Integrated Controller, Modbus RTU/TCP) Modbus register map

Updated 17 November 2026

Short answer

The Condair DL is a hybrid spray-and-evaporation humidifier for air handling units. Its Integrated Controller is a Modbus RTU slave on RS-485 or a Modbus TCP server. This map covers status, valve and safety-loop states, capacity, humidity, pressures, water quality and Ag-ion values, and the writable setpoint, control and remote-enable registers.

This page lists 40 Modbus registers for the Condair DL II hybrid humidifier (Integrated Controller, Modbus RTU/TCP) — 8 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Condair’s own free documentation (linked below) and checked against it.

Manufacturer
Condair
Model
DL II hybrid humidifier (Integrated Controller, Modbus RTU/TCP)
Equipment type
Air handler humidifier (hybrid / spray)
Registers
40 (8 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
10
Default serial
19200 baud, 8E1
TCP port
502
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
Condair DL, Condair DL II, DL
Source document
Modbus addendum manual for DL II, ME II, RS II, RO-E and Vita (Integrated Controller) · 2603326-G EN 2607
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Condair DL II hybrid humidifier (Integrated Controller, Modbus RTU/TCP)

Integration in brief

Read input registers 2000-2019 (UInt16 states) and 2025-2050 (floats). To control over Modbus, write the demand or humidity value to holding 3004 at least once per signal timeout and enable via 3005.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 2001Device StatusUINT16Device statusRead
IR 2002Maintenance and Error StatusUINT16Maintenance and error statusRead
IR 2003Error or Warning CodeUINT16Error/warning codeRead
IR 2027Actual Humidification CapacityFLOAT32 ABCDActual capacityRead
IR 2029Actual Humidity or DemandFLOAT32 ABCDActual humidity or demandRead
HR 3004Actual Humidity or Demand via ModbusUINT16Demand/humidity via ModbusRead/write
HR 3005Remote EnableUINT16Remote enableRead/write

Enable Modbus control & writes

Controls > Signal Settings: set Source = Modbus (and Remote Enable = Modbus to use register 43006). The demand register 43005 only works when Source is not Analog.

Communication loss & watchdog

When the demand or humidity signal comes from Modbus, it must be rewritten within 'Signal Timeout' (1-300 s, default 300 s); otherwise warning W35 is raised and the unit stops humidifying.

Byte order & addressing

Network setup

Watch out for

Condair DL II hybrid humidifier (Integrated Controller, Modbus RTU/TCP) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

40 of 40 shown
Condair DL II hybrid humidifier (Integrated Controller, Modbus RTU/TCP) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR2000doc 32001DL TypeUINT16Read0 = Humidifier; 1 = Humidifier + FC; 2 = Humidifier + FC - Off
IR2001doc 32002Device StatusUINT16Read0 = Initializing; 1 = Diagnostic; 2 = Stopped; 3 = Flushing; 4 = Standby; 5 = Humidifying; 6 = Ready; 7 = Air Cleaning; 8 = Filling; 9 = Conductivity Flush; 10 = Switched Off; 11 = Remote Off; 12 = Temperature Flush; 13 = Ceramic Wash Over
IR2002doc 32003Maintenance and Error StatusUINT16Read0 = No Info; 1 = Warning; 2 = Activation Code; 3 = Out of Commissioning; 4 = Refill Disinfection; 5 = Maintenance; 6 = Error; 7 = Replace Ag Cartridge; 8 = Disinfection
IR2003doc 32004Error or Warning Code0 = no error; other codes are listed in the device operation manual.UINT16Read
IR2004doc 32005Safety LoopRange 0 = Open 1 = Closed (=ok).UINT16Read
IR2005doc 32006Y1 Inlet ValveUINT16Read0 = Closed; 1 = Open
IR2007doc 32008Y3 Valve Air CleaningUINT16Read0 = Closed; 1 = Open
IR2008doc 32009Y4 Valve External Pipe FlushUINT16Read0 = Closed; 1 = Open
IR2009doc 32010Y5 Spray ValveUINT16Read0 = Closed; 1 = Open
IR2010doc 32011Y6 Spray ValveUINT16Read0 = Closed; 1 = Open
IR2011doc 32012Y7 Spray ValveUINT16Read0 = Closed; 1 = Open
IR2012doc 32013Y8 Spray ValveUINT16Read0 = Closed; 1 = Open
IR2013doc 32014Y9 Spray ValveUINT16Read0 = Closed; 1 = Open
IR2014doc 32015Y10 Drain Valve (NO)UINT16Read0 = Open; 1 = Closed
IR2015doc 32016Y11 Auxiliary Outlet ValveUINT16Read0 = Open; 1 = Closed
IR2016doc 32017Frequency Converter EnableUINT16Read0 = Disable; 1 = Enable
IR2017doc 32018Frequency Converter StatusUINT16Read0 = Off; 1 = Power On
IR2018doc 32019FanUINT16Read0 = On; 1 = Off
IR2019doc 32020Disinfection Pump (Relay Dosing Pump)UINT16Read0 = Off; 1 = On
IR2025doc 32026Max. Humidification CapacityRange 2 - 1000 kg/h 4 - 2573 lb/hr. Metric or imperial per controller setting.FLOAT32ABCDkg/hRead
IR2027doc 32028Actual Humidification CapacityRange 0 - 1000 kg/h 0 - 2573 lb/hr. Metric or imperial per controller setting.FLOAT32ABCDkg/hRead
IR2029doc 32030Actual Humidity or DemandRange 0 - 100 %.FLOAT32ABCD%Read
IR2031doc 32032Operating HoursRange 0 - 1200000 h.FLOAT32ABCDhRead
IR2033doc 32034Next MaintenanceRange 0 - 10000 h.FLOAT32ABCDhRead
IR2035doc 32036Remaining Ag-Ion CapacityRange 0 - 58.4 Ah.FLOAT32ABCDAhRead
IR2037doc 32038Target Ag-Ion CurrentRange 0 - 29.2 mA.FLOAT32ABCDmARead
IR2039doc 32040PS4 Inlet PressureRange 0 - 10.0 bar 0 - 145.0 psi. Metric or imperial per controller setting.FLOAT32ABCDbarRead
IR2041doc 32042PS5 Nozzle PressureRange 0 - 10.0 bar 0 - 145.0 psi. Metric or imperial per controller setting.FLOAT32ABCDbarRead
IR2043doc 32044Water TemperatureRange °C or °F. Metric or imperial per controller setting.FLOAT32ABCD°CRead
IR2045doc 32046Water ConductivityRange 0 - x μS/cm.FLOAT32ABCDuS/cmRead
IR2047doc 32048Pump CurrentRange 0 - 6.0 A.FLOAT32ABCDARead
IR2049doc 32050Ag-Ion CurrentRange 0 - x mA.FLOAT32ABCDmARead
HR3000doc 43001SetpointRange 0 - 95 %.UINT16%Read/write
HR3001doc 43002P-BandRange 6 - 65 %.UINT16%Read/write
HR3002doc 43003I-TimeRange 1 - 60 min.UINT16minRead/write
HR3003doc 43004Capacity LimitationRange 20 - 100 %.UINT16%Read/write
HR3004doc 43005Actual Humidity or Demand via ModbusRange 0 - 100 %.UINT16%Read/write
HR3005doc 43006Remote EnableUINT16Read/write0 = Off; 1 = On
HR5001doc 45002Remote FlushingRead 100 = off or 0-99 = progress %; write 1 = start, 0 = stop.UINT16%Read/write
HR5002doc 45003Remote Ceramic Wash OverRead 100 = off or 0-99 = progress %; write 1 = start, 0 = stop.UINT16%Read/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Condair DL II hybrid humidifier (Integrated Controller, Modbus RTU/TCP)

What Modbus registers does the Condair DL II hybrid humidifier (Integrated Controller, Modbus RTU/TCP) have?

This map lists 40 registers: 32 input registers, 8 holding registers. 8 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Condair DL II hybrid humidifier (Integrated Controller, Modbus RTU/TCP) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Tables print the 5-digit register (32001 = input register, 43001 = holding register) and the 0-based address beside it (2000 / 3000). The address column is what goes on the wire; the manual's own example: register 43004 = address 3003.

What byte order does the Condair DL II hybrid humidifier (Integrated Controller, Modbus RTU/TCP) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Condair DL II hybrid humidifier (Integrated Controller, Modbus RTU/TCP)?

Start with IR 2001 Device Status (Device status); IR 2002 Maintenance and Error Status (Maintenance and error status); IR 2003 Error or Warning Code (Error/warning code); IR 2027 Actual Humidification Capacity (Actual capacity); IR 2029 Actual Humidity or Demand (Actual humidity or demand); HR 3004 Actual Humidity or Demand via Modbus (Demand/humidity via Modbus); HR 3005 Remote Enable (Remote enable).

How do I enable Modbus control of the Condair DL II hybrid humidifier (Integrated Controller, Modbus RTU/TCP)?

Controls > Signal Settings: set Source = Modbus (and Remote Enable = Modbus to use register 43006). The demand register 43005 only works when Source is not Analog.

What happens when the Condair DL II hybrid humidifier (Integrated Controller, Modbus RTU/TCP) loses Modbus communication?

When the demand or humidity signal comes from Modbus, it must be rewritten within 'Signal Timeout' (1-300 s, default 300 s); otherwise warning W35 is raised and the unit stops humidifying.

Where is the official Condair DL II hybrid humidifier (Integrated Controller, Modbus RTU/TCP) Modbus documentation?

The source is Modbus addendum manual for DL II, ME II, RS II, RO-E and Vita (Integrated Controller) (2603326-G EN 2607), published free by Condair at https://www.condair.com/m/0/2603326-e-modbus-for-dl-series-addendum.pdf.

More Condair Modbus register maps

Other hvac equipment register maps

All hvac equipment Modbus register maps →

Source: Modbus addendum manual for DL II, ME II, RS II, RO-E and Vita (Integrated Controller) · 2603326-G EN 2607. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.