  3. Neptronic
  4. SKH4 high-pressure atomizer humidifier (Modbus communication module)

Air handler humidifier (high-pressure atomizer) · Modbus register map

Neptronic SKH4 high-pressure atomizer humidifier (Modbus communication module) Modbus register map

Updated 19 November 2026

Short answer

The SKH4 is Neptronic's high-pressure atomizing humidifier with up to six spray stages and six zones. Its Modbus RTU module puts everything in holding registers: input signal voltages, scaled readings (room and supply RH, temperatures, water temperature, pump pressure), set points and PID terms, zone demands, binary inputs and relay states as 0/1 registers, and enumerated profile, source, state and alarm registers.

This page lists 250 Modbus registers for the Neptronic SKH4 high-pressure atomizer humidifier (Modbus communication module) — 177 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Neptronic’s own free documentation (linked below) and checked against it.

Manufacturer
Neptronic
Model
SKH4 high-pressure atomizer humidifier (Modbus communication module)
Equipment type
Air handler humidifier (high-pressure atomizer)
Registers
250 (177 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
8N2
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
SKH4, SKH4 High-Pressure Atomizer, Neptronic SKH4 Modbus
Source document
SKH4 High-Pressure Atomizer - Modbus Communication Module User Guide · SKH4-Modbus Guide-240126 (V.1.00) · rev. 2024-01-26
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Neptronic SKH4 high-pressure atomizer humidifier (Modbus communication module)

Integration in brief

Read State (15017), System Alarm (15018), Room RH (6006), Power Output (6001) and Pressure (6025). For BAS control, set Control Profile (15006) and Control Demand Source (15013) to a network option, then write Control Network Demand (6049) or Room RH Network Reading (6033).

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 15017StateUINT16Operating stateRead
HR 15018System AlarmUINT16System alarmRead
HR 6006Room RHUINT16Room RHRead
HR 6034Room RH SetpointUINT16Room RH set pointRead/write
HR 6001Power OutputUINT16Power outputRead
HR 6025PressureUINT16Pump pressureRead
HR 6049Control Network DemandUINT16Network demandRead/write
HR 15006Control ProfileUINT16Control profileRead/write

Enable Modbus control & writes

Fit the Modbus communication module, set the address from the device menu or register 0, and pick a network control profile (15006) and sources (15009-15015) when the BAS should supply readings or demand.

Byte order & addressing

Network setup

Watch out for

Neptronic SKH4 high-pressure atomizer humidifier (Modbus communication module) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

250 of 250 shown
Neptronic SKH4 high-pressure atomizer humidifier (Modbus communication module) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 0 / 400001Modbus Address and Product TypeHigh byte = product type (read only); low byte = Modbus address 1-247 (writable).UINT16Read/write
HR1doc 1 / 400002Device Baud RateBaud / 100 (e.g. 384 = 38400); 0 = auto-detect.UINT16× 100baudRead/write0 = Auto baud rate detection
HR2doc 2 / 400003Modbus Slave Communication Port ConfigurationUINT16Read/write0 = No parity, 2 stop bits; 1 = Even parity, 1 stop bit; 2 = Odd parity, 1 stop bit
HR7doc 7 / 400008Product Actual Firmware Version (in Integer x100)Firmware version x100 (e.g. 100 = 1.00).UINT16× 0.01Read
HR8doc 8 / 400009Product Actual EEPROM Version (in Integer x100)EEPROM version x100.UINT16× 0.01Read
HR2000doc 2000 / 402001Control SignalUINT16× 0.001VRead
HR2001doc 2001 / 402002Room RH SignalUINT16× 0.001VRead
HR2002doc 2002 / 402003Supply RH SignalUINT16× 0.001VRead
HR2004doc 2004 / 402005Pressure Sensor SignalUINT16× 0.001VRead/write
HR2005doc 2005 / 402006Board Temperature SignalUINT16× 0.001VRead
HR2006doc 2006 / 402007Main Power SupplyUINT16× 0.1VRead
HR2007doc 2007 / 402008Room Temperature SignalUINT16× 0.001VRead
HR2008doc 2008 / 402009Supply Temperature SignalUINT16× 0.001VRead
HR4000doc 4000 / 404001Power Output Feedback SignalUINT16× 0.001VRead
HR4001doc 4001 / 404002Drive SignalUINT16× 0.001VRead
HR6000doc 6000 / 406001DemandUINT16× 0.01%Read/write
HR6001doc 6001 / 406002Power OutputUINT16× 0.01%Read
HR6002doc 6002 / 406003Control InputUINT16× 0.01%Read/write
HR6003doc 6003 / 406004Control MinUINT16× 0.01%Read/write
HR6004doc 6004 / 406005Control MaxUINT16× 0.01%Read/write
HR6006doc 6006 / 406007Room RHUINT16× 0.01%RHRead
HR6007doc 6007 / 406008Room RH MinUINT16× 0.01%RHRead/write
HR6008doc 6008 / 406009Room RH MaxUINT16× 0.01%RHRead/write
HR6010doc 6010 / 406011Supply High Limit RHUINT16× 0.01%RHRead
HR6011doc 6011 / 406012Supply High Limit RH MinUINT16× 0.01%RHRead/write
HR6012doc 6012 / 406013Supply High Limit RH MaxUINT16× 0.01%RHRead/write
HR6024doc 6024 / 406025Water TemperatureUINT16× 0.1°C / °FRead
HR6025doc 6025 / 406026PressureUINT16psiRead
HR6026doc 6026 / 406027Service IntervalUINT16hRead/write
HR6027doc 6027 / 406028Board TemperatureUINT16× 0.1°C / °FRead/write
HR6028doc 6028 / 406029Power Output Feedback BiasUINT16× 0.001VRead/write
HR6029doc 6029 / 406030Power Output Feedback MinUINT16× 0.001VRead/write
HR6030doc 6030 / 406031Power Output Feedback MaxUINT16× 0.001VRead/write
HR6033doc 6033 / 406034Room RH Network ReadingUINT16× 0.01%RHRead/write
HR6034doc 6034 / 406035Room RH SetpointUINT16× 0.1%RHRead/write
HR6035doc 6035 / 406036Room RH Unoccupied SetpointUINT16× 0.1%RHRead/write
HR6036doc 6036 / 406037Room RH Vacant SetpointUINT16× 0.1%RHRead/write
HR6037doc 6037 / 406038Room RH Demand Proportional GainUINT16× 0.1Read/write
HR6038doc 6038 / 406039Room RH Demand Integral TimeUINT16× 0.1sRead/write
HR6039doc 6039 / 406040Room RH Demand Derivative TimeUINT16× 0.1sRead/write
HR6040doc 6040 / 406041Room RH DemandUINT16× 0.01%Read
HR6041doc 6041 / 406042RH Supply High Limit Network ReadingUINT16× 0.01%RHRead/write
HR6042doc 6042 / 406043RH Supply High Limit SetpointUINT16× 0.1%RHRead/write
HR6043doc 6043 / 406044RH Supply High Limit Unoccupied SetpointUINT16× 0.1%RHRead/write
HR6044doc 6044 / 406045RH Supply High Limit Vacant SetpointUINT16× 0.1%RHRead/write
HR6045doc 6045 / 406046RH Supply High Limit Proportional GainUINT16× 0.1Read/write
HR6046doc 6046 / 406047RH Supply High Limit Integral TimeUINT16× 0.1sRead/write
HR6047doc 6047 / 406048RH Supply High Limit Derivative TimeUINT16× 0.1sRead/write
HR6048doc 6048 / 406049RH Supply High Limit DemandUINT16× 0.01%Read
HR6049doc 6049 / 406050Control Network DemandUINT16× 0.01%Read/write
HR6050doc 6050 / 406051Control Network High LimitUINT16× 0.01%Read/write
HR6051doc 6051 / 406052User DemandUINT16× 0.01%Read
HR6052doc 6052 / 406053System Steam CapacityPrinted as steam capacity in kg/h or lb/h.UINT16× 0.1kg/h / lb/hRead
HR6053doc 6053 / 406054Room TemperatureINT16× 0.01°C / °FRead
HR6054doc 6054 / 406055Room Temperature MinINT16× 0.01°C / °FRead/write
HR6055doc 6055 / 406056Room Temperature MaxINT16× 0.01°C / °FRead/write
HR6056doc 6056 / 406057Room Temperature BiasINT16× 0.01Δ°C / Δ°FRead/write
HR6057doc 6057 / 406058Room Temperature Network ReadingINT16× 0.01°C / °FRead/write
HR6060doc 6060 / 406061Room Temperature Unoccupied SetpointUINT16× 0.1°C / °FRead/write
HR6061doc 6061 / 406062Room Temperature Vacant SetpointUINT16× 0.1°C / °FRead/write
HR6064doc 6064 / 406065Room Temperature Demand Integral TimeUINT16× 0.1sRead/write
HR6065doc 6065 / 406066Room Temperature Demand Derivative TimeUINT16× 0.1sRead/write
HR6066doc 6066 / 406067Room Temperature DemandUINT16× 0.01%Read
HR6067doc 6067 / 406068HRL TemperatureINT16× 0.01°C / °FRead
HR6068doc 6068 / 406069HRL HumidityUINT16× 0.1%RHRead/write
HR6069doc 6069 / 406070Room Temp Demand Proportional BandUINT16× 0.1%Read/write
HR6070doc 6070 / 406071Temp Supply High Limit Network ReadingINT16× 0.01°C / °FRead/write
HR6071doc 6071 / 40672Temp Supply High Limit SetpointUINT16× 0.01°C / °FRead/write
HR6072doc 6072 / 406073Temp Supply High Limit Unoccupied SetpointUINT16× 0.01°C / °FRead/write
HR6073doc 6073 / 406074Temp Supply High Limit Vacant SetpointUINT16× 0.01°C / °FRead/write
HR6074doc 6074 / 406075Temp Supply High Limit Proportional GainUINT16× 0.1Read/write
HR6075doc 6075 / 406076Temp Supply High Limit Integral TimeUINT16× 0.1sRead/write
HR6078doc 6078 / 406079Temp Supply High Limit Derivative TimeUINT16× 0.1sRead/write
HR6079doc 6079 / 406080Temp Supply High Limit DemandUINT16× 0.01%Read
HR6080doc 6080 / 406081Temp Supply High Limit Proportional BandUINT16%Read
HR6081doc 6081 / 406082Supply High Limit TemperatureINT16× 0.01°C / °FRead
HR6082doc 6082 / 406083Supply High Limit Temperature MinINT16× 0.01°C / °FRead/write
HR6083doc 6083 / 406084Supply High Limit Temperature MaxINT16× 0.01°C / °FRead/write
HR6084doc 6084 / 406085Supply High Limit Temperature BiasINT16× 0.01Δ°C / Δ°FRead/write
HR6093doc 6093 / 406094Water Temperature BiasINT16× 0.01Δ°C / Δ°FRead
HR6094doc 6094 / 406095Control TimerUINT16sRead/write
HR6095doc 6095 / 406096Zone A DemandUINT16× 0.01%Read/write
HR6096doc 6096 / 406097Zone A TemperatureINT16× 0.01°C / °FRead/write
HR6097doc 6097 / 406098Zone A HumidityUINT16× 0.01%RHRead/write
HR6098doc 6098 / 406099Zone B DemandUINT16× 0.01%Read/write
HR6099doc 6099 / 406100Zone B TemperatureINT16× 0.01°C / °FRead/write
HR6100doc 6100 / 406101Zone B HumidityUINT16× 0.01%RHRead/write
HR6101doc 6101 / 406102Zone C DemandUINT16× 0.01%Read/write
HR6102doc 6102 / 406103Zone C TemperatureINT16× 0.01°C / °FRead/write
HR6103doc 6103 / 406104Zone C HumidityUINT16× 0.01%RHRead/write
HR6104doc 6104 / 406105Zone D DemandUINT16× 0.01%Read/write
HR6105doc 6105 / 406106Zone D TemperatureINT16× 0.01°C / °FRead/write
HR6108doc 6108 / 406109Zone E DemandUINT16× 0.01%Read/write
HR6109doc 6109 / 406110Zone E TemperatureINT16× 0.01°C / °FRead/write
HR6110doc 6110 / 406111Zone E HumidityUINT16× 0.01%RHRead/write
HR6111doc 6111 / 406112Zone F DemandUINT16× 0.01%Read/write
HR6112doc 6112 / 406113Zone F TemperatureINT16× 0.01°C / °FRead/write
HR6115doc 6115 / 406116Stage 1 CapacityUINT16l/hRead/write
HR6118doc 6118 / 406119Stage 2 CapacityUINT16l/hRead/write
HR6121doc 6121 / 406122Stage 3 CapacityUINT16l/hRead/write
HR6124doc 6124 / 406125Stage 4 CapacityUINT16l/hRead/write
HR6127doc 6127 / 406128Stage 5 CapacityUINT16l/hRead/write
HR6130doc 6130 / 406131Stage 6 CapacityUINT16l/hRead/write
HR6133doc 6133 / 406134Stage 1 Drain TimeUINT16sRead/write
HR6134doc 6134 / 406135Stage 2 Drain TimeUINT16sRead/write
HR6135doc 6135 / 406136Stage 3 Drain TimeUINT16sRead/write
HR6136doc 6136 / 406137Stage 4 Drain TimeUINT16sRead/write
HR6137doc 6137 / 406138Stage 5 Drain TimeUINT16sRead/write
HR6138doc 6138 / 406139Stage 6 Drain TimeUINT16sRead/write
HR6175doc 6175 / 406176Cool Drain TimerUINT16minRead/write
HR6188doc 6188 / 406189Stage 1 Max On TimeUINT16sRead/write
HR6189doc 6189 / 406190Stage 2 Max On TimeUINT16sRead/write
HR6190doc 6190 / 406191Stage 3 Max On TimeUINT16sRead/write
HR6191doc 6191 / 406192Stage 4 Max On TimeUINT16sRead/write
HR6192doc 6192 / 406193Stage 5 Max On TimeUINT16sRead/write
HR6193doc 6193 / 406194Stage 6 Max On TimeUINT16sRead/write
HR6194doc 6194 / 406195Stage 1 Pause TimeUINT16sRead/write
HR6195doc 6195 / 406196Stage 2 Pause TimeUINT16sRead/write
HR6196doc 6196 / 406197Stage 3 Pause TimeUINT16sRead/write
HR6197doc 6197 / 406198Stage 4 Pause TimeUINT16sRead/write
HR6198doc 6198 / 406199Stage 5 Pause TimeUINT16sRead/write
HR6199doc 6199 / 406200Stage 6 Pause TimeUINT16sRead/write
HR6200doc 6200 / 406201Zone A Stage Opening DelayUINT16sRead/write
HR6201doc 6201 / 406202Zone B Stage Opening DelayUINT16sRead/write
HR6202doc 6202 / 406203Zone C Stage Opening DelayUINT16sRead/write
HR6203doc 6203 / 406204Zone D Stage Opening DelayUINT16sRead/write
HR6204doc 6204 / 406205Zone E Stage Opening DelayUINT16sRead/write
HR6205doc 6205 / 406206Zone F Stage Opening DelayUINT16sRead/write
HR6230doc 6230 / 406231Diagnostic PeriodUINT16minRead/write
HR6231doc 6231 / 406232Zone A MACUINT16Read/write
HR6232doc 6232 / 406233Zone B MACUINT16Read/write
HR6233doc 6233 / 406234Zone C MACUINT16Read/write
HR6234doc 6234 / 406235Zone D MACUINT16Read/write
HR6235doc 6235 / 406236Zone E MACUINT16Read/write
HR6236doc 6236 / 406237Zone F MACUINT16Read/write
HR6237doc 6237 / 406238Control InputSecond 'Control Input' row, printed in temperature units.INT16× 0.01°C / °FRead/write
HR6238doc 6238 / 406239Control MinINT16× 0.01°C / °FRead/write
HR6239doc 6239 / 406240Control MaxINT16× 0.01°C / °FRead/write
HR6240doc 6240 / 406241Control BiasINT16× 0.01Δ°C / Δ°FRead/write
HR6241doc 6241 / 406242Zone Communication Timeout DelayUINT16sRead/write
HR10000doc 10000 / 410001Air FlowUINT16Read0 = Closed; 1 = Open
HR10001doc 10001 / 410002Supply High LimitUINT16Read0 = Closed; 1 = Open
HR10002doc 10002 / 410003InterlockUINT16Read0 = Closed; 1 = Open
HR10003doc 10003 / 410004Binary External DemandUINT16Read0 = 0%; 1 = 100%
HR10004doc 10004 / 410005Water Leak DetectionUINT16Read0 = Ok; 1 = Leak
HR10005doc 10005 / 410006Drive StatusUINT16Read0 = Ok; 1 = Fault
HR10006doc 10006 / 410007Inlet Pressure SwitchUINT16Read0 = Low; 1 = Ok
HR10007doc 10007 / 410008RS485 InterfaceUINT16Read0 = No; 1 = Yes
HR10008doc 10008 / 410009Ethernet InterfaceUINT16Read0 = No; 1 = Yes
HR10009doc 10009 / 410010Relay FuseUINT16Read0 = Normal; 1 = Open Fuse
HR10010doc 10010 / 410011Control PCB FuseUINT16Read0 = Normal; 1 = Open Fuse
HR11000doc 11000 / 411001Alarm Warning RelayUINT16Read0 = Off; 1 = On
HR11001doc 11001 / 411002Service Warning RelayUINT16Read0 = Off; 1 = On
HR11002doc 11002 / 411003Valve 1UINT16Read0 = Off; 1 = On
HR11003doc 11003 / 411004Valve 2UINT16Read0 = Off; 1 = On
HR11004doc 11004 / 411005Valve 3UINT16Read0 = Off; 1 = On
HR11005doc 11005 / 411006Valve 4UINT16Read0 = Off; 1 = On
HR11006doc 11006 / 411007Valve 5UINT16Read0 = Off; 1 = On
HR11007doc 11007 / 411008Valve 6UINT16Read0 = Off; 1 = On
HR11008doc 11008 / 411009Valve 7UINT16Read0 = Off; 1 = On
HR11009doc 11009 / 411010Valve 8UINT16Read0 = Off; 1 = On
HR11010doc 11010 / 411011Valve 9UINT16Read0 = Off; 1 = On
HR11011doc 11011 / 411012Valve 10UINT16Read0 = Off; 1 = On
HR11012doc 11012 / 411013Valve 11UINT16Read0 = Off; 1 = On
HR11013doc 11013 / 411014Valve 12UINT16Read0 = Off; 1 = On
HR11014doc 11014 / 411015Alarm LEDUINT16Read0 = Off; 1 = On
HR11015doc 11015 / 411016Power LEDUINT16Read0 = Off; 1 = On
HR11016doc 11016 / 411017BuzzerUINT16Read0 = Off; 1 = On
HR11017doc 11017 / 411018Contactor PumpUINT16Read0 = Off; 1 = On
HR11018doc 11018 / 411019Drive EnableUINT16Read0 = Off; 1 = On
HR12000doc 12000 / 412001Service DueUINT16Read0 = No; 1 = Yes
HR12001doc 12001 / 412002Startup Line RinseUINT16Read/write0 = Off; 1 = On
HR12002doc 12002 / 412003Run While Service AlarmUINT16Read/write0 = NotAllowed; 1 = Allowed
HR12003doc 12003 / 412004HRL Lock SetpointUINT16Read/write0 = Unlock; 1 = Lock
HR12004doc 12004 / 412005Network Control StateUINT16Read/write0 = Normal; 1 = Fault
HR12005doc 12005 / 412006Notify AlarmUINT16Read/write0 = Off; 1 = On
HR12006doc 12006 / 412007Notify WarningUINT16Read/write0 = Off; 1 = On
HR12007doc 12007 / 412008Notify App MsgUINT16Read/write0 = Off; 1 = On
HR12008doc 12008 / 412009Drive StateUINT16Read0 = Ok; 1 = Fault
HR12009doc 12009 / 412010Stage 1 Diagnostic EnableUINT16Read/write0 = No; 1 = Yes
HR12010doc 12010 / 412011Stage 2 Diagnostic EnableUINT16Read/write0 = No; 1 = Yes
HR12011doc 12011 / 412012Stage 3 Diagnostic EnableUINT16Read/write0 = No; 1 = Yes
HR12012doc 12012 / 412013Stage 4 Diagnostic EnableUINT16Read/write0 = No; 1 = Yes
HR12013doc 12013 / 412014Stage 5 Diagnostic EnableUINT16Read/write0 = No; 1 = Yes
HR12014doc 12014 / 412015Stage 6 Diagnostic EnableUINT16Read/write0 = No; 1 = Yes
HR12015doc 12015 / 412016Zone A Communication TimeoutUINT16Read0 = Ok; 1 = Timeout
HR12016doc 12016 / 412017Zone B Communication TimeoutUINT16Read0 = Ok; 1 = Timeout
HR12017doc 12017 / 412018Zone C Communication TimeoutUINT16Read0 = Ok; 1 = Timeout
HR12018doc 12018 / 412019Zone D Communication TimeoutUINT16Read0 = Ok; 1 = Timeout
HR12019doc 12019 / 412020Zone E Communication TimeoutUINT16Read0 = Ok; 1 = Timeout
HR12020doc 12020 / 412021Zone F Communication TimeoutUINT16Read0 = Ok; 1 = Timeout
HR12021doc 12021 / 412022Configuation StatusUINT16Read0 = Ok; 1 = Fail
HR12022doc 12022 / 412023Low Water Temperature WarningUINT16Read0 = Off; 1 = On
HR15000doc 15000 / 415001System Log Verbose LevelUINT16Read/write0 = None; 1 = Emergency; 2 = Alert; 3 = Critical; 4 = Error; 5 = Warning; 6 = Notice; 7 = Info; 8 = Debug
HR15001doc 15001 / 415002Modbus Server UnitsUINT16Read/write0 = Metric; 1 = Imperial
HR15002doc 15002 / 415003Control Signal TypeUINT16Read/write0 = 0-10Vdc; 1 = 2-10Vdc; 2 = 4-20mA; 3 = 0-20mA
HR15003doc 15003 / 415004Room RH Signal TypeUINT16Read/write0 = 0-10Vdc; 1 = 2-10Vdc; 2 = 4-20mA; 3 = 0-20mA
HR15004doc 15004 / 415005Supply RH Signal TypeUINT16Read/write0 = 0-10Vdc; 1 = 2-10Vdc; 2 = 4-20mA; 3 = 0-20mA
HR15005doc 15005 / 415006RequestUINT16Read/write0 = None; 1 = ResetAlarms; 2 = Drain; 3 = ResetServCnt
HR15006doc 15006 / 415007Control ProfileUINT16Read/write0 = ExternAnalog; 1 = ExternNetwork; 2 = InternHumAnalog; 3 = InternHumNetwork; 4 = InternCoolAnalog; 5 = InternCoolNetwork; 6 = HRL Hum; 7 = HRL Cool
HR15007doc 15007 / 415008Modulating High Limit ProfileUINT16Read/write0 = Disabled; 1 = ExternAnalog; 2 = ExternNetwork; 3 = InternHumAnalog; 4 = InternHumNetwork; 5 = InternCoolAnalog; 6 = InternCoolNetwork; 7 = Custom
HR15008doc 15008 / 415009Occupancy StateUINT16Read0 = Occupied; 1 = Unoccupied; 2 = Vacant; 3 = Off
HR15009doc 15009 / 415010Room RH SourceUINT16Read/write0 = None; 1 = RoomRH; 2 = Network; 3 = HRL
HR15010doc 15010 / 415011Room RH Setpoint SourceUINT16Read/write0 = None; 1 = Internal; 2 = ControlInput
HR15011doc 15011 / 415012RH Supply High Limit Reading SourceUINT16Read/write0 = None; 1 = SupplyHLRH; 2 = Network
HR15012doc 15012 / 415013RH Supply High Limit Setpoint SourceUINT16Read/write0 = None; 1 = Internal; 2 = ControlInput
HR15013doc 15013 / 415014Control Demand SourceUINT16Read/write0 = None; 1 = ControlInput; 2 = HumRoomDemand; 3 = Network; 4 = TempRoomDemand
HR15014doc 15014 / 415015Control High Limit SourceUINT16Read/write0 = None; 1 = ControlInput; 2 = RHSupplyHLDemand; 3 = Network; 4 = TempSupplyHLDemand
HR15015doc 15015 / 415016Control Binary Demand SourceUINT16Read/write0 = None; 1 = BinaryExtDemand
HR15016doc 15016 / 415017Control Cutout StateUINT16Read0 = Off; 1 = Normal; 2 = LowLimit; 3 = HighLimit; 4 = NoAirFlow; 5 = Interlock
HR15017doc 15017 / 415018StateUINT16Read0 = Off; 1 = Idle; 2 = Spraying; 3 = Draining; 4 = Alarm
HR15018doc 15018 / 415019System AlarmUINT16Read0 = Normal; 1 = WatHiTemp; 2 = WatLoTemp; 3 = OutHiPress; 4 = OutLoPress; 5 = InLowPress; 6 = WaterLeak; 7 = Service; 8 = Config
HR15019doc 15019 / 415020Room Temperature Setpoint SourceUINT16Read/write0 = None; 1 = Internal; 2 = ControlInput
HR15020doc 15020 / 415021Temp Supply High Limit Reading SourceUINT16Read/write0 = None; 1 = SupplyHLTemp; 2 = Network
HR15021doc 15021 / 415022Temp Supply High Limit Setpoint SourceUINT16Read/write0 = None; 1 = Internal; 2 = ControlInput
HR15022doc 15022 / 415023Room Temperature SourceUINT16Read/write0 = None; 1 = RoomTemp; 2 = Network; 3 = HRL
HR15023doc 15023 / 415024Room Temperature Signal TypeUINT16Read/write0 = 0-10Vdc; 1 = 2-10Vdc; 2 = 4-20mA; 3 = 0-20mA
HR15024doc 15024 / 415025Supply Temperature Signal TypeUINT16Read/write0 = 0-10Vdc; 1 = 2-10Vdc; 2 = 4-20mA; 3 = 0-20mA
HR15025doc 15025 / 415026System Power StateUINT16Read0 = Off; 1 = On
HR15026doc 15026 / 415027Zone A ControlUINT16Read/write0 = Off; 1 = Normal; 2 = Airflow; 3 = SupplyHighLimit; 4 = Interlock
HR15027doc 15027 / 415028Zone A OccupancyUINT16Read/write0 = Occupied; 1 = Unoccupied; 2 = Off
HR15028doc 15028 / 415029Zone B ControlUINT16Read/write0 = Off; 1 = Normal; 2 = Airflow; 3 = SupplyHighLimit; 4 = Interlock
HR15029doc 15029 / 415030Zone B OccupancyUINT16Read/write0 = Occupied; 1 = Unoccupied; 2 = Off
HR15030doc 15030 / 415031Zone C ControlUINT16Read/write0 = Off; 1 = Normal; 2 = Airflow; 3 = SupplyHighLimit; 4 = Interlock
HR15031doc 15031 / 415032Zone C OccupancyUINT16Read/write0 = Occupied; 1 = Unoccupied; 2 = Off
HR15032doc 15032 / 415033Zone D ControlUINT16Read/write0 = Off; 1 = Normal; 2 = Airflow; 3 = SupplyHighLimit; 4 = Interlock
HR15033doc 15033 / 415034Zone D OccupancyUINT16Read/write0 = Occupied; 1 = Unoccupied; 2 = Off
HR15034doc 15034 / 415035Zone E ControlUINT16Read/write0 = Off; 1 = Normal; 2 = Airflow; 3 = SupplyHighLimit; 4 = Interlock
HR15035doc 15035 / 415036Zone E OccupancyUINT16Read/write0 = Occupied; 1 = Unoccupied; 2 = Off
HR15036doc 15036 / 415037Zone F ControlUINT16Read/write0 = Off; 1 = Normal; 2 = Airflow; 3 = SupplyHighLimit; 4 = Interlock
HR15037doc 15037 / 415038Zone F OccupancyUINT16Read/write0 = Occupied; 1 = Unoccupied; 2 = Off
HR15038doc 15038 / 415039Stage 1 ZoneUINT16Read/write0 = ZoneA; 1 = ZoneB; 2 = ZoneC; 3 = ZoneD; 4 = ZoneE; 5 = ZoneF
HR15039doc 15039 / 415040Stage1 DrainUINT16Read/write0 = Drain7; 1 = Drain8; 2 = Drain9; 3 = Drain10; 4 = Drain11; 5 = Drain12
HR15040doc 15040 / 415041Stage 2 ZoneUINT16Read/write0 = ZoneA; 1 = ZoneB; 2 = ZoneC; 3 = ZoneD; 4 = ZoneE; 5 = ZoneF
HR15041doc 15041 / 415042Stage 2 DrainUINT16Read/write0 = Drain7; 1 = Drain8; 2 = Drain9; 3 = Drain10; 4 = Drain11; 5 = Drain12
HR15042doc 15042 / 415043Stage 3 ZoneUINT16Read/write0 = ZoneA; 1 = ZoneB; 2 = ZoneC; 3 = ZoneD; 4 = ZoneE; 5 = ZoneF
HR15043doc 15043 / 415044Stage 3 DrainUINT16Read/write0 = Drain7; 1 = Drain8; 2 = Drain9; 3 = Drain10; 4 = Drain11; 5 = Drain12
HR15044doc 15044 / 415045Stage 4 ZoneUINT16Read/write0 = ZoneA; 1 = ZoneB; 2 = ZoneC; 3 = ZoneD; 4 = ZoneE; 5 = ZoneF
HR15045doc 15045 / 415046Stage 4 DrainUINT16Read/write0 = Drain7; 1 = Drain8; 2 = Drain9; 3 = Drain10; 4 = Drain11; 5 = Drain12
HR15046doc 15046 / 415047Stage 5 ZoneUINT16Read/write0 = ZoneA; 1 = ZoneB; 2 = ZoneC; 3 = ZoneD; 4 = ZoneE; 5 = ZoneF
HR15047doc 15047 / 415048Stage 5 DrainUINT16Read/write0 = Drain7; 1 = Drain8; 2 = Drain9; 3 = Drain10; 4 = Drain11; 5 = Drain12
HR15048doc 15048 / 415049Stage 6 ZoneUINT16Read/write0 = ZoneA; 1 = ZoneB; 2 = ZoneC; 3 = ZoneD; 4 = ZoneE; 5 = ZoneF
HR15049doc 15049 / 415050Stage 6 DrainUINT16Read/write0 = Drain7; 1 = Drain8; 2 = Drain9; 3 = Drain10; 4 = Drain11; 5 = Drain12
HR15050doc 15050 / 415051Cooling Drain Control ModeUINT16Read/write0 = Off; 1 = TimeLatch
HR15051doc 15051 / 415052Low Water Temperature AlarmUINT16Read/write0 = Alarm; 1 = Warning
HR15052doc 15052 / 415053Power Up DrainUINT16Read/write0 = Off; 1 = On
HR15053doc 15053 / 415054Diagnostic StateUINT16Read/write0 = Off; 1 = On
HR15054doc 15054 / 415055Diagnostic CommandUINT16Read/write0 = Spray; 1 = Drain
HR15055doc 15055 / 415056Control Signal TypePrinted a second time in the guide (same name as 15002).UINT16Read/write0 = 0-10Vdc; 1 = 2-10Vdc; 2 = 4-20mA; 3 = 0-20mA
HR15056doc 15056 / 415057Update Process StatusUINT16Read0 = Ok; 1 = CRC; 2 = Device; 3 = Failed

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Neptronic SKH4 high-pressure atomizer humidifier (Modbus communication module)

What Modbus registers does the Neptronic SKH4 high-pressure atomizer humidifier (Modbus communication module) have?

This map lists 250 registers: 250 holding registers. 177 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Neptronic SKH4 high-pressure atomizer humidifier (Modbus communication module) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide says register addresses follow the protocol base (base 0, add 1 for a PLC) and also prints the six-digit holding register (base 400001) beside each one, e.g. 6006 / 406007. The protocol-base number is the wire address.

What are the minimum Modbus registers to integrate the Neptronic SKH4 high-pressure atomizer humidifier (Modbus communication module)?

Start with HR 15017 State (Operating state); HR 15018 System Alarm (System alarm); HR 6006 Room RH (Room RH); HR 6034 Room RH Setpoint (Room RH set point); HR 6001 Power Output (Power output); HR 6025 Pressure (Pump pressure); HR 6049 Control Network Demand (Network demand); HR 15006 Control Profile (Control profile).

How do I enable Modbus control of the Neptronic SKH4 high-pressure atomizer humidifier (Modbus communication module)?

Fit the Modbus communication module, set the address from the device menu or register 0, and pick a network control profile (15006) and sources (15009-15015) when the BAS should supply readings or demand.

Where is the official Neptronic SKH4 high-pressure atomizer humidifier (Modbus communication module) Modbus documentation?

The source is SKH4 High-Pressure Atomizer - Modbus Communication Module User Guide (SKH4-Modbus Guide-240126 (V.1.00)), revision 2024-01-26, published free by Neptronic at https://www.neptronic.com/Humidifiers/pdf/2024/SKH4-Modbus%20Guide-240126%20(V.1.00).pdf.

More Neptronic Modbus register maps

Other hvac equipment register maps

All hvac equipment Modbus register maps →

Source: SKH4 High-Pressure Atomizer - Modbus Communication Module User Guide · SKH4-Modbus Guide-240126 (V.1.00) · rev. 2024-01-26. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.