Air handler humidifier (high-pressure atomizer) · Modbus register map
Neptronic SKH4 high-pressure atomizer humidifier (Modbus communication module) Modbus register map
Updated 19 November 2026
The SKH4 is Neptronic's high-pressure atomizing humidifier with up to six spray stages and six zones. Its Modbus RTU module puts everything in holding registers: input signal voltages, scaled readings (room and supply RH, temperatures, water temperature, pump pressure), set points and PID terms, zone demands, binary inputs and relay states as 0/1 registers, and enumerated profile, source, state and alarm registers.
This page lists 250 Modbus registers for the Neptronic SKH4 high-pressure atomizer humidifier (Modbus communication module) — 177 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Neptronic’s own free documentation (linked below) and checked against it.
- Manufacturer
- Neptronic
- Model
- SKH4 high-pressure atomizer humidifier (Modbus communication module)
- Equipment type
- Air handler humidifier (high-pressure atomizer)
- Registers
- 250 (177 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 8N2
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- SKH4, SKH4 High-Pressure Atomizer, Neptronic SKH4 Modbus
Integration notes: Neptronic SKH4 high-pressure atomizer humidifier (Modbus communication module)
Read State (15017), System Alarm (15018), Room RH (6006), Power Output (6001) and Pressure (6025). For BAS control, set Control Profile (15006) and Control Demand Source (15013) to a network option, then write Control Network Demand (6049) or Room RH Network Reading (6033).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 15017 | State | UINT16 | Operating state | Read |
| HR 15018 | System Alarm | UINT16 | System alarm | Read |
| HR 6006 | Room RH | UINT16 | Room RH | Read |
| HR 6034 | Room RH Setpoint | UINT16 | Room RH set point | Read/write |
| HR 6001 | Power Output | UINT16 | Power output | Read |
| HR 6025 | Pressure | UINT16 | Pump pressure | Read |
| HR 6049 | Control Network Demand | UINT16 | Network demand | Read/write |
| HR 15006 | Control Profile | UINT16 | Control profile | Read/write |
Enable Modbus control & writes
Fit the Modbus communication module, set the address from the device menu or register 0, and pick a network control profile (15006) and sources (15009-15015) when the BAS should supply readings or demand.
Byte order & addressing
- All points, binary ones included, are holding registers (FC03/06/16 only).
- Auto baud detection is the default; after two or more bad frames in one second at a given rate the device moves to the next rate.
Network setup
- RS-485 two-wire, RTU mode, 9600-57600 baud or auto baud detection.
- Device address 1-246 per the requirements text (the register row says 1-247); set in the device menu or register 0.
- Parity / stop bits via register 2 or the Modbus Comport Config menu item (default no parity, 2 stop bits).
Watch out for
- Many timers and counters are split over several registers with no word order given, so they are not in this map.
- Readings switch between metric and imperial with register 15001.
Neptronic SKH4 high-pressure atomizer humidifier (Modbus communication module) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 0 / 400001 | Modbus Address and Product Type | High byte = product type (read only); low byte = Modbus address 1-247 (writable). | UINT16 | Read/write | ||||
| HR | 1doc 1 / 400002 | Device Baud Rate | Baud / 100 (e.g. 384 = 38400); 0 = auto-detect. | UINT16 | × 100 | baud | Read/write | 0 = Auto baud rate detection | |
| HR | 2doc 2 / 400003 | Modbus Slave Communication Port Configuration | UINT16 | Read/write | 0 = No parity, 2 stop bits; 1 = Even parity, 1 stop bit; 2 = Odd parity, 1 stop bit | ||||
| HR | 7doc 7 / 400008 | Product Actual Firmware Version (in Integer x100) | Firmware version x100 (e.g. 100 = 1.00). | UINT16 | × 0.01 | Read | |||
| HR | 8doc 8 / 400009 | Product Actual EEPROM Version (in Integer x100) | EEPROM version x100. | UINT16 | × 0.01 | Read | |||
| HR | 2000doc 2000 / 402001 | Control Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 2001doc 2001 / 402002 | Room RH Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 2002doc 2002 / 402003 | Supply RH Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 2004doc 2004 / 402005 | Pressure Sensor Signal | UINT16 | × 0.001 | V | Read/write | |||
| HR | 2005doc 2005 / 402006 | Board Temperature Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 2006doc 2006 / 402007 | Main Power Supply | UINT16 | × 0.1 | V | Read | |||
| HR | 2007doc 2007 / 402008 | Room Temperature Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 2008doc 2008 / 402009 | Supply Temperature Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 4000doc 4000 / 404001 | Power Output Feedback Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 4001doc 4001 / 404002 | Drive Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 6000doc 6000 / 406001 | Demand | UINT16 | × 0.01 | % | Read/write | |||
| HR | 6001doc 6001 / 406002 | Power Output | UINT16 | × 0.01 | % | Read | |||
| HR | 6002doc 6002 / 406003 | Control Input | UINT16 | × 0.01 | % | Read/write | |||
| HR | 6003doc 6003 / 406004 | Control Min | UINT16 | × 0.01 | % | Read/write | |||
| HR | 6004doc 6004 / 406005 | Control Max | UINT16 | × 0.01 | % | Read/write | |||
| HR | 6006doc 6006 / 406007 | Room RH | UINT16 | × 0.01 | %RH | Read | |||
| HR | 6007doc 6007 / 406008 | Room RH Min | UINT16 | × 0.01 | %RH | Read/write | |||
| HR | 6008doc 6008 / 406009 | Room RH Max | UINT16 | × 0.01 | %RH | Read/write | |||
| HR | 6010doc 6010 / 406011 | Supply High Limit RH | UINT16 | × 0.01 | %RH | Read | |||
| HR | 6011doc 6011 / 406012 | Supply High Limit RH Min | UINT16 | × 0.01 | %RH | Read/write | |||
| HR | 6012doc 6012 / 406013 | Supply High Limit RH Max | UINT16 | × 0.01 | %RH | Read/write | |||
| HR | 6024doc 6024 / 406025 | Water Temperature | UINT16 | × 0.1 | °C / °F | Read | |||
| HR | 6025doc 6025 / 406026 | Pressure | UINT16 | psi | Read | ||||
| HR | 6026doc 6026 / 406027 | Service Interval | UINT16 | h | Read/write | ||||
| HR | 6027doc 6027 / 406028 | Board Temperature | UINT16 | × 0.1 | °C / °F | Read/write | |||
| HR | 6028doc 6028 / 406029 | Power Output Feedback Bias | UINT16 | × 0.001 | V | Read/write | |||
| HR | 6029doc 6029 / 406030 | Power Output Feedback Min | UINT16 | × 0.001 | V | Read/write | |||
| HR | 6030doc 6030 / 406031 | Power Output Feedback Max | UINT16 | × 0.001 | V | Read/write | |||
| HR | 6033doc 6033 / 406034 | Room RH Network Reading | UINT16 | × 0.01 | %RH | Read/write | |||
| HR | 6034doc 6034 / 406035 | Room RH Setpoint | UINT16 | × 0.1 | %RH | Read/write | |||
| HR | 6035doc 6035 / 406036 | Room RH Unoccupied Setpoint | UINT16 | × 0.1 | %RH | Read/write | |||
| HR | 6036doc 6036 / 406037 | Room RH Vacant Setpoint | UINT16 | × 0.1 | %RH | Read/write | |||
| HR | 6037doc 6037 / 406038 | Room RH Demand Proportional Gain | UINT16 | × 0.1 | Read/write | ||||
| HR | 6038doc 6038 / 406039 | Room RH Demand Integral Time | UINT16 | × 0.1 | s | Read/write | |||
| HR | 6039doc 6039 / 406040 | Room RH Demand Derivative Time | UINT16 | × 0.1 | s | Read/write | |||
| HR | 6040doc 6040 / 406041 | Room RH Demand | UINT16 | × 0.01 | % | Read | |||
| HR | 6041doc 6041 / 406042 | RH Supply High Limit Network Reading | UINT16 | × 0.01 | %RH | Read/write | |||
| HR | 6042doc 6042 / 406043 | RH Supply High Limit Setpoint | UINT16 | × 0.1 | %RH | Read/write | |||
| HR | 6043doc 6043 / 406044 | RH Supply High Limit Unoccupied Setpoint | UINT16 | × 0.1 | %RH | Read/write | |||
| HR | 6044doc 6044 / 406045 | RH Supply High Limit Vacant Setpoint | UINT16 | × 0.1 | %RH | Read/write | |||
| HR | 6045doc 6045 / 406046 | RH Supply High Limit Proportional Gain | UINT16 | × 0.1 | Read/write | ||||
| HR | 6046doc 6046 / 406047 | RH Supply High Limit Integral Time | UINT16 | × 0.1 | s | Read/write | |||
| HR | 6047doc 6047 / 406048 | RH Supply High Limit Derivative Time | UINT16 | × 0.1 | s | Read/write | |||
| HR | 6048doc 6048 / 406049 | RH Supply High Limit Demand | UINT16 | × 0.01 | % | Read | |||
| HR | 6049doc 6049 / 406050 | Control Network Demand | UINT16 | × 0.01 | % | Read/write | |||
| HR | 6050doc 6050 / 406051 | Control Network High Limit | UINT16 | × 0.01 | % | Read/write | |||
| HR | 6051doc 6051 / 406052 | User Demand | UINT16 | × 0.01 | % | Read | |||
| HR | 6052doc 6052 / 406053 | System Steam Capacity | Printed as steam capacity in kg/h or lb/h. | UINT16 | × 0.1 | kg/h / lb/h | Read | ||
| HR | 6053doc 6053 / 406054 | Room Temperature | INT16 | × 0.01 | °C / °F | Read | |||
| HR | 6054doc 6054 / 406055 | Room Temperature Min | INT16 | × 0.01 | °C / °F | Read/write | |||
| HR | 6055doc 6055 / 406056 | Room Temperature Max | INT16 | × 0.01 | °C / °F | Read/write | |||
| HR | 6056doc 6056 / 406057 | Room Temperature Bias | INT16 | × 0.01 | Δ°C / Δ°F | Read/write | |||
| HR | 6057doc 6057 / 406058 | Room Temperature Network Reading | INT16 | × 0.01 | °C / °F | Read/write | |||
| HR | 6060doc 6060 / 406061 | Room Temperature Unoccupied Setpoint | UINT16 | × 0.1 | °C / °F | Read/write | |||
| HR | 6061doc 6061 / 406062 | Room Temperature Vacant Setpoint | UINT16 | × 0.1 | °C / °F | Read/write | |||
| HR | 6064doc 6064 / 406065 | Room Temperature Demand Integral Time | UINT16 | × 0.1 | s | Read/write | |||
| HR | 6065doc 6065 / 406066 | Room Temperature Demand Derivative Time | UINT16 | × 0.1 | s | Read/write | |||
| HR | 6066doc 6066 / 406067 | Room Temperature Demand | UINT16 | × 0.01 | % | Read | |||
| HR | 6067doc 6067 / 406068 | HRL Temperature | INT16 | × 0.01 | °C / °F | Read | |||
| HR | 6068doc 6068 / 406069 | HRL Humidity | UINT16 | × 0.1 | %RH | Read/write | |||
| HR | 6069doc 6069 / 406070 | Room Temp Demand Proportional Band | UINT16 | × 0.1 | % | Read/write | |||
| HR | 6070doc 6070 / 406071 | Temp Supply High Limit Network Reading | INT16 | × 0.01 | °C / °F | Read/write | |||
| HR | 6071doc 6071 / 40672 | Temp Supply High Limit Setpoint | UINT16 | × 0.01 | °C / °F | Read/write | |||
| HR | 6072doc 6072 / 406073 | Temp Supply High Limit Unoccupied Setpoint | UINT16 | × 0.01 | °C / °F | Read/write | |||
| HR | 6073doc 6073 / 406074 | Temp Supply High Limit Vacant Setpoint | UINT16 | × 0.01 | °C / °F | Read/write | |||
| HR | 6074doc 6074 / 406075 | Temp Supply High Limit Proportional Gain | UINT16 | × 0.1 | Read/write | ||||
| HR | 6075doc 6075 / 406076 | Temp Supply High Limit Integral Time | UINT16 | × 0.1 | s | Read/write | |||
| HR | 6078doc 6078 / 406079 | Temp Supply High Limit Derivative Time | UINT16 | × 0.1 | s | Read/write | |||
| HR | 6079doc 6079 / 406080 | Temp Supply High Limit Demand | UINT16 | × 0.01 | % | Read | |||
| HR | 6080doc 6080 / 406081 | Temp Supply High Limit Proportional Band | UINT16 | % | Read | ||||
| HR | 6081doc 6081 / 406082 | Supply High Limit Temperature | INT16 | × 0.01 | °C / °F | Read | |||
| HR | 6082doc 6082 / 406083 | Supply High Limit Temperature Min | INT16 | × 0.01 | °C / °F | Read/write | |||
| HR | 6083doc 6083 / 406084 | Supply High Limit Temperature Max | INT16 | × 0.01 | °C / °F | Read/write | |||
| HR | 6084doc 6084 / 406085 | Supply High Limit Temperature Bias | INT16 | × 0.01 | Δ°C / Δ°F | Read/write | |||
| HR | 6093doc 6093 / 406094 | Water Temperature Bias | INT16 | × 0.01 | Δ°C / Δ°F | Read | |||
| HR | 6094doc 6094 / 406095 | Control Timer | UINT16 | s | Read/write | ||||
| HR | 6095doc 6095 / 406096 | Zone A Demand | UINT16 | × 0.01 | % | Read/write | |||
| HR | 6096doc 6096 / 406097 | Zone A Temperature | INT16 | × 0.01 | °C / °F | Read/write | |||
| HR | 6097doc 6097 / 406098 | Zone A Humidity | UINT16 | × 0.01 | %RH | Read/write | |||
| HR | 6098doc 6098 / 406099 | Zone B Demand | UINT16 | × 0.01 | % | Read/write | |||
| HR | 6099doc 6099 / 406100 | Zone B Temperature | INT16 | × 0.01 | °C / °F | Read/write | |||
| HR | 6100doc 6100 / 406101 | Zone B Humidity | UINT16 | × 0.01 | %RH | Read/write | |||
| HR | 6101doc 6101 / 406102 | Zone C Demand | UINT16 | × 0.01 | % | Read/write | |||
| HR | 6102doc 6102 / 406103 | Zone C Temperature | INT16 | × 0.01 | °C / °F | Read/write | |||
| HR | 6103doc 6103 / 406104 | Zone C Humidity | UINT16 | × 0.01 | %RH | Read/write | |||
| HR | 6104doc 6104 / 406105 | Zone D Demand | UINT16 | × 0.01 | % | Read/write | |||
| HR | 6105doc 6105 / 406106 | Zone D Temperature | INT16 | × 0.01 | °C / °F | Read/write | |||
| HR | 6108doc 6108 / 406109 | Zone E Demand | UINT16 | × 0.01 | % | Read/write | |||
| HR | 6109doc 6109 / 406110 | Zone E Temperature | INT16 | × 0.01 | °C / °F | Read/write | |||
| HR | 6110doc 6110 / 406111 | Zone E Humidity | UINT16 | × 0.01 | %RH | Read/write | |||
| HR | 6111doc 6111 / 406112 | Zone F Demand | UINT16 | × 0.01 | % | Read/write | |||
| HR | 6112doc 6112 / 406113 | Zone F Temperature | INT16 | × 0.01 | °C / °F | Read/write | |||
| HR | 6115doc 6115 / 406116 | Stage 1 Capacity | UINT16 | l/h | Read/write | ||||
| HR | 6118doc 6118 / 406119 | Stage 2 Capacity | UINT16 | l/h | Read/write | ||||
| HR | 6121doc 6121 / 406122 | Stage 3 Capacity | UINT16 | l/h | Read/write | ||||
| HR | 6124doc 6124 / 406125 | Stage 4 Capacity | UINT16 | l/h | Read/write | ||||
| HR | 6127doc 6127 / 406128 | Stage 5 Capacity | UINT16 | l/h | Read/write | ||||
| HR | 6130doc 6130 / 406131 | Stage 6 Capacity | UINT16 | l/h | Read/write | ||||
| HR | 6133doc 6133 / 406134 | Stage 1 Drain Time | UINT16 | s | Read/write | ||||
| HR | 6134doc 6134 / 406135 | Stage 2 Drain Time | UINT16 | s | Read/write | ||||
| HR | 6135doc 6135 / 406136 | Stage 3 Drain Time | UINT16 | s | Read/write | ||||
| HR | 6136doc 6136 / 406137 | Stage 4 Drain Time | UINT16 | s | Read/write | ||||
| HR | 6137doc 6137 / 406138 | Stage 5 Drain Time | UINT16 | s | Read/write | ||||
| HR | 6138doc 6138 / 406139 | Stage 6 Drain Time | UINT16 | s | Read/write | ||||
| HR | 6175doc 6175 / 406176 | Cool Drain Timer | UINT16 | min | Read/write | ||||
| HR | 6188doc 6188 / 406189 | Stage 1 Max On Time | UINT16 | s | Read/write | ||||
| HR | 6189doc 6189 / 406190 | Stage 2 Max On Time | UINT16 | s | Read/write | ||||
| HR | 6190doc 6190 / 406191 | Stage 3 Max On Time | UINT16 | s | Read/write | ||||
| HR | 6191doc 6191 / 406192 | Stage 4 Max On Time | UINT16 | s | Read/write | ||||
| HR | 6192doc 6192 / 406193 | Stage 5 Max On Time | UINT16 | s | Read/write | ||||
| HR | 6193doc 6193 / 406194 | Stage 6 Max On Time | UINT16 | s | Read/write | ||||
| HR | 6194doc 6194 / 406195 | Stage 1 Pause Time | UINT16 | s | Read/write | ||||
| HR | 6195doc 6195 / 406196 | Stage 2 Pause Time | UINT16 | s | Read/write | ||||
| HR | 6196doc 6196 / 406197 | Stage 3 Pause Time | UINT16 | s | Read/write | ||||
| HR | 6197doc 6197 / 406198 | Stage 4 Pause Time | UINT16 | s | Read/write | ||||
| HR | 6198doc 6198 / 406199 | Stage 5 Pause Time | UINT16 | s | Read/write | ||||
| HR | 6199doc 6199 / 406200 | Stage 6 Pause Time | UINT16 | s | Read/write | ||||
| HR | 6200doc 6200 / 406201 | Zone A Stage Opening Delay | UINT16 | s | Read/write | ||||
| HR | 6201doc 6201 / 406202 | Zone B Stage Opening Delay | UINT16 | s | Read/write | ||||
| HR | 6202doc 6202 / 406203 | Zone C Stage Opening Delay | UINT16 | s | Read/write | ||||
| HR | 6203doc 6203 / 406204 | Zone D Stage Opening Delay | UINT16 | s | Read/write | ||||
| HR | 6204doc 6204 / 406205 | Zone E Stage Opening Delay | UINT16 | s | Read/write | ||||
| HR | 6205doc 6205 / 406206 | Zone F Stage Opening Delay | UINT16 | s | Read/write | ||||
| HR | 6230doc 6230 / 406231 | Diagnostic Period | UINT16 | min | Read/write | ||||
| HR | 6231doc 6231 / 406232 | Zone A MAC | UINT16 | Read/write | |||||
| HR | 6232doc 6232 / 406233 | Zone B MAC | UINT16 | Read/write | |||||
| HR | 6233doc 6233 / 406234 | Zone C MAC | UINT16 | Read/write | |||||
| HR | 6234doc 6234 / 406235 | Zone D MAC | UINT16 | Read/write | |||||
| HR | 6235doc 6235 / 406236 | Zone E MAC | UINT16 | Read/write | |||||
| HR | 6236doc 6236 / 406237 | Zone F MAC | UINT16 | Read/write | |||||
| HR | 6237doc 6237 / 406238 | Control Input | Second 'Control Input' row, printed in temperature units. | INT16 | × 0.01 | °C / °F | Read/write | ||
| HR | 6238doc 6238 / 406239 | Control Min | INT16 | × 0.01 | °C / °F | Read/write | |||
| HR | 6239doc 6239 / 406240 | Control Max | INT16 | × 0.01 | °C / °F | Read/write | |||
| HR | 6240doc 6240 / 406241 | Control Bias | INT16 | × 0.01 | Δ°C / Δ°F | Read/write | |||
| HR | 6241doc 6241 / 406242 | Zone Communication Timeout Delay | UINT16 | s | Read/write | ||||
| HR | 10000doc 10000 / 410001 | Air Flow | UINT16 | Read | 0 = Closed; 1 = Open | ||||
| HR | 10001doc 10001 / 410002 | Supply High Limit | UINT16 | Read | 0 = Closed; 1 = Open | ||||
| HR | 10002doc 10002 / 410003 | Interlock | UINT16 | Read | 0 = Closed; 1 = Open | ||||
| HR | 10003doc 10003 / 410004 | Binary External Demand | UINT16 | Read | 0 = 0%; 1 = 100% | ||||
| HR | 10004doc 10004 / 410005 | Water Leak Detection | UINT16 | Read | 0 = Ok; 1 = Leak | ||||
| HR | 10005doc 10005 / 410006 | Drive Status | UINT16 | Read | 0 = Ok; 1 = Fault | ||||
| HR | 10006doc 10006 / 410007 | Inlet Pressure Switch | UINT16 | Read | 0 = Low; 1 = Ok | ||||
| HR | 10007doc 10007 / 410008 | RS485 Interface | UINT16 | Read | 0 = No; 1 = Yes | ||||
| HR | 10008doc 10008 / 410009 | Ethernet Interface | UINT16 | Read | 0 = No; 1 = Yes | ||||
| HR | 10009doc 10009 / 410010 | Relay Fuse | UINT16 | Read | 0 = Normal; 1 = Open Fuse | ||||
| HR | 10010doc 10010 / 410011 | Control PCB Fuse | UINT16 | Read | 0 = Normal; 1 = Open Fuse | ||||
| HR | 11000doc 11000 / 411001 | Alarm Warning Relay | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11001doc 11001 / 411002 | Service Warning Relay | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11002doc 11002 / 411003 | Valve 1 | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11003doc 11003 / 411004 | Valve 2 | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11004doc 11004 / 411005 | Valve 3 | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11005doc 11005 / 411006 | Valve 4 | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11006doc 11006 / 411007 | Valve 5 | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11007doc 11007 / 411008 | Valve 6 | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11008doc 11008 / 411009 | Valve 7 | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11009doc 11009 / 411010 | Valve 8 | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11010doc 11010 / 411011 | Valve 9 | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11011doc 11011 / 411012 | Valve 10 | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11012doc 11012 / 411013 | Valve 11 | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11013doc 11013 / 411014 | Valve 12 | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11014doc 11014 / 411015 | Alarm LED | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11015doc 11015 / 411016 | Power LED | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11016doc 11016 / 411017 | Buzzer | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11017doc 11017 / 411018 | Contactor Pump | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11018doc 11018 / 411019 | Drive Enable | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12000doc 12000 / 412001 | Service Due | UINT16 | Read | 0 = No; 1 = Yes | ||||
| HR | 12001doc 12001 / 412002 | Startup Line Rinse | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 12002doc 12002 / 412003 | Run While Service Alarm | UINT16 | Read/write | 0 = NotAllowed; 1 = Allowed | ||||
| HR | 12003doc 12003 / 412004 | HRL Lock Setpoint | UINT16 | Read/write | 0 = Unlock; 1 = Lock | ||||
| HR | 12004doc 12004 / 412005 | Network Control State | UINT16 | Read/write | 0 = Normal; 1 = Fault | ||||
| HR | 12005doc 12005 / 412006 | Notify Alarm | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 12006doc 12006 / 412007 | Notify Warning | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 12007doc 12007 / 412008 | Notify App Msg | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 12008doc 12008 / 412009 | Drive State | UINT16 | Read | 0 = Ok; 1 = Fault | ||||
| HR | 12009doc 12009 / 412010 | Stage 1 Diagnostic Enable | UINT16 | Read/write | 0 = No; 1 = Yes | ||||
| HR | 12010doc 12010 / 412011 | Stage 2 Diagnostic Enable | UINT16 | Read/write | 0 = No; 1 = Yes | ||||
| HR | 12011doc 12011 / 412012 | Stage 3 Diagnostic Enable | UINT16 | Read/write | 0 = No; 1 = Yes | ||||
| HR | 12012doc 12012 / 412013 | Stage 4 Diagnostic Enable | UINT16 | Read/write | 0 = No; 1 = Yes | ||||
| HR | 12013doc 12013 / 412014 | Stage 5 Diagnostic Enable | UINT16 | Read/write | 0 = No; 1 = Yes | ||||
| HR | 12014doc 12014 / 412015 | Stage 6 Diagnostic Enable | UINT16 | Read/write | 0 = No; 1 = Yes | ||||
| HR | 12015doc 12015 / 412016 | Zone A Communication Timeout | UINT16 | Read | 0 = Ok; 1 = Timeout | ||||
| HR | 12016doc 12016 / 412017 | Zone B Communication Timeout | UINT16 | Read | 0 = Ok; 1 = Timeout | ||||
| HR | 12017doc 12017 / 412018 | Zone C Communication Timeout | UINT16 | Read | 0 = Ok; 1 = Timeout | ||||
| HR | 12018doc 12018 / 412019 | Zone D Communication Timeout | UINT16 | Read | 0 = Ok; 1 = Timeout | ||||
| HR | 12019doc 12019 / 412020 | Zone E Communication Timeout | UINT16 | Read | 0 = Ok; 1 = Timeout | ||||
| HR | 12020doc 12020 / 412021 | Zone F Communication Timeout | UINT16 | Read | 0 = Ok; 1 = Timeout | ||||
| HR | 12021doc 12021 / 412022 | Configuation Status | UINT16 | Read | 0 = Ok; 1 = Fail | ||||
| HR | 12022doc 12022 / 412023 | Low Water Temperature Warning | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 15000doc 15000 / 415001 | System Log Verbose Level | UINT16 | Read/write | 0 = None; 1 = Emergency; 2 = Alert; 3 = Critical; 4 = Error; 5 = Warning; 6 = Notice; 7 = Info; 8 = Debug | ||||
| HR | 15001doc 15001 / 415002 | Modbus Server Units | UINT16 | Read/write | 0 = Metric; 1 = Imperial | ||||
| HR | 15002doc 15002 / 415003 | Control Signal Type | UINT16 | Read/write | 0 = 0-10Vdc; 1 = 2-10Vdc; 2 = 4-20mA; 3 = 0-20mA | ||||
| HR | 15003doc 15003 / 415004 | Room RH Signal Type | UINT16 | Read/write | 0 = 0-10Vdc; 1 = 2-10Vdc; 2 = 4-20mA; 3 = 0-20mA | ||||
| HR | 15004doc 15004 / 415005 | Supply RH Signal Type | UINT16 | Read/write | 0 = 0-10Vdc; 1 = 2-10Vdc; 2 = 4-20mA; 3 = 0-20mA | ||||
| HR | 15005doc 15005 / 415006 | Request | UINT16 | Read/write | 0 = None; 1 = ResetAlarms; 2 = Drain; 3 = ResetServCnt | ||||
| HR | 15006doc 15006 / 415007 | Control Profile | UINT16 | Read/write | 0 = ExternAnalog; 1 = ExternNetwork; 2 = InternHumAnalog; 3 = InternHumNetwork; 4 = InternCoolAnalog; 5 = InternCoolNetwork; 6 = HRL Hum; 7 = HRL Cool | ||||
| HR | 15007doc 15007 / 415008 | Modulating High Limit Profile | UINT16 | Read/write | 0 = Disabled; 1 = ExternAnalog; 2 = ExternNetwork; 3 = InternHumAnalog; 4 = InternHumNetwork; 5 = InternCoolAnalog; 6 = InternCoolNetwork; 7 = Custom | ||||
| HR | 15008doc 15008 / 415009 | Occupancy State | UINT16 | Read | 0 = Occupied; 1 = Unoccupied; 2 = Vacant; 3 = Off | ||||
| HR | 15009doc 15009 / 415010 | Room RH Source | UINT16 | Read/write | 0 = None; 1 = RoomRH; 2 = Network; 3 = HRL | ||||
| HR | 15010doc 15010 / 415011 | Room RH Setpoint Source | UINT16 | Read/write | 0 = None; 1 = Internal; 2 = ControlInput | ||||
| HR | 15011doc 15011 / 415012 | RH Supply High Limit Reading Source | UINT16 | Read/write | 0 = None; 1 = SupplyHLRH; 2 = Network | ||||
| HR | 15012doc 15012 / 415013 | RH Supply High Limit Setpoint Source | UINT16 | Read/write | 0 = None; 1 = Internal; 2 = ControlInput | ||||
| HR | 15013doc 15013 / 415014 | Control Demand Source | UINT16 | Read/write | 0 = None; 1 = ControlInput; 2 = HumRoomDemand; 3 = Network; 4 = TempRoomDemand | ||||
| HR | 15014doc 15014 / 415015 | Control High Limit Source | UINT16 | Read/write | 0 = None; 1 = ControlInput; 2 = RHSupplyHLDemand; 3 = Network; 4 = TempSupplyHLDemand | ||||
| HR | 15015doc 15015 / 415016 | Control Binary Demand Source | UINT16 | Read/write | 0 = None; 1 = BinaryExtDemand | ||||
| HR | 15016doc 15016 / 415017 | Control Cutout State | UINT16 | Read | 0 = Off; 1 = Normal; 2 = LowLimit; 3 = HighLimit; 4 = NoAirFlow; 5 = Interlock | ||||
| HR | 15017doc 15017 / 415018 | State | UINT16 | Read | 0 = Off; 1 = Idle; 2 = Spraying; 3 = Draining; 4 = Alarm | ||||
| HR | 15018doc 15018 / 415019 | System Alarm | UINT16 | Read | 0 = Normal; 1 = WatHiTemp; 2 = WatLoTemp; 3 = OutHiPress; 4 = OutLoPress; 5 = InLowPress; 6 = WaterLeak; 7 = Service; 8 = Config | ||||
| HR | 15019doc 15019 / 415020 | Room Temperature Setpoint Source | UINT16 | Read/write | 0 = None; 1 = Internal; 2 = ControlInput | ||||
| HR | 15020doc 15020 / 415021 | Temp Supply High Limit Reading Source | UINT16 | Read/write | 0 = None; 1 = SupplyHLTemp; 2 = Network | ||||
| HR | 15021doc 15021 / 415022 | Temp Supply High Limit Setpoint Source | UINT16 | Read/write | 0 = None; 1 = Internal; 2 = ControlInput | ||||
| HR | 15022doc 15022 / 415023 | Room Temperature Source | UINT16 | Read/write | 0 = None; 1 = RoomTemp; 2 = Network; 3 = HRL | ||||
| HR | 15023doc 15023 / 415024 | Room Temperature Signal Type | UINT16 | Read/write | 0 = 0-10Vdc; 1 = 2-10Vdc; 2 = 4-20mA; 3 = 0-20mA | ||||
| HR | 15024doc 15024 / 415025 | Supply Temperature Signal Type | UINT16 | Read/write | 0 = 0-10Vdc; 1 = 2-10Vdc; 2 = 4-20mA; 3 = 0-20mA | ||||
| HR | 15025doc 15025 / 415026 | System Power State | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 15026doc 15026 / 415027 | Zone A Control | UINT16 | Read/write | 0 = Off; 1 = Normal; 2 = Airflow; 3 = SupplyHighLimit; 4 = Interlock | ||||
| HR | 15027doc 15027 / 415028 | Zone A Occupancy | UINT16 | Read/write | 0 = Occupied; 1 = Unoccupied; 2 = Off | ||||
| HR | 15028doc 15028 / 415029 | Zone B Control | UINT16 | Read/write | 0 = Off; 1 = Normal; 2 = Airflow; 3 = SupplyHighLimit; 4 = Interlock | ||||
| HR | 15029doc 15029 / 415030 | Zone B Occupancy | UINT16 | Read/write | 0 = Occupied; 1 = Unoccupied; 2 = Off | ||||
| HR | 15030doc 15030 / 415031 | Zone C Control | UINT16 | Read/write | 0 = Off; 1 = Normal; 2 = Airflow; 3 = SupplyHighLimit; 4 = Interlock | ||||
| HR | 15031doc 15031 / 415032 | Zone C Occupancy | UINT16 | Read/write | 0 = Occupied; 1 = Unoccupied; 2 = Off | ||||
| HR | 15032doc 15032 / 415033 | Zone D Control | UINT16 | Read/write | 0 = Off; 1 = Normal; 2 = Airflow; 3 = SupplyHighLimit; 4 = Interlock | ||||
| HR | 15033doc 15033 / 415034 | Zone D Occupancy | UINT16 | Read/write | 0 = Occupied; 1 = Unoccupied; 2 = Off | ||||
| HR | 15034doc 15034 / 415035 | Zone E Control | UINT16 | Read/write | 0 = Off; 1 = Normal; 2 = Airflow; 3 = SupplyHighLimit; 4 = Interlock | ||||
| HR | 15035doc 15035 / 415036 | Zone E Occupancy | UINT16 | Read/write | 0 = Occupied; 1 = Unoccupied; 2 = Off | ||||
| HR | 15036doc 15036 / 415037 | Zone F Control | UINT16 | Read/write | 0 = Off; 1 = Normal; 2 = Airflow; 3 = SupplyHighLimit; 4 = Interlock | ||||
| HR | 15037doc 15037 / 415038 | Zone F Occupancy | UINT16 | Read/write | 0 = Occupied; 1 = Unoccupied; 2 = Off | ||||
| HR | 15038doc 15038 / 415039 | Stage 1 Zone | UINT16 | Read/write | 0 = ZoneA; 1 = ZoneB; 2 = ZoneC; 3 = ZoneD; 4 = ZoneE; 5 = ZoneF | ||||
| HR | 15039doc 15039 / 415040 | Stage1 Drain | UINT16 | Read/write | 0 = Drain7; 1 = Drain8; 2 = Drain9; 3 = Drain10; 4 = Drain11; 5 = Drain12 | ||||
| HR | 15040doc 15040 / 415041 | Stage 2 Zone | UINT16 | Read/write | 0 = ZoneA; 1 = ZoneB; 2 = ZoneC; 3 = ZoneD; 4 = ZoneE; 5 = ZoneF | ||||
| HR | 15041doc 15041 / 415042 | Stage 2 Drain | UINT16 | Read/write | 0 = Drain7; 1 = Drain8; 2 = Drain9; 3 = Drain10; 4 = Drain11; 5 = Drain12 | ||||
| HR | 15042doc 15042 / 415043 | Stage 3 Zone | UINT16 | Read/write | 0 = ZoneA; 1 = ZoneB; 2 = ZoneC; 3 = ZoneD; 4 = ZoneE; 5 = ZoneF | ||||
| HR | 15043doc 15043 / 415044 | Stage 3 Drain | UINT16 | Read/write | 0 = Drain7; 1 = Drain8; 2 = Drain9; 3 = Drain10; 4 = Drain11; 5 = Drain12 | ||||
| HR | 15044doc 15044 / 415045 | Stage 4 Zone | UINT16 | Read/write | 0 = ZoneA; 1 = ZoneB; 2 = ZoneC; 3 = ZoneD; 4 = ZoneE; 5 = ZoneF | ||||
| HR | 15045doc 15045 / 415046 | Stage 4 Drain | UINT16 | Read/write | 0 = Drain7; 1 = Drain8; 2 = Drain9; 3 = Drain10; 4 = Drain11; 5 = Drain12 | ||||
| HR | 15046doc 15046 / 415047 | Stage 5 Zone | UINT16 | Read/write | 0 = ZoneA; 1 = ZoneB; 2 = ZoneC; 3 = ZoneD; 4 = ZoneE; 5 = ZoneF | ||||
| HR | 15047doc 15047 / 415048 | Stage 5 Drain | UINT16 | Read/write | 0 = Drain7; 1 = Drain8; 2 = Drain9; 3 = Drain10; 4 = Drain11; 5 = Drain12 | ||||
| HR | 15048doc 15048 / 415049 | Stage 6 Zone | UINT16 | Read/write | 0 = ZoneA; 1 = ZoneB; 2 = ZoneC; 3 = ZoneD; 4 = ZoneE; 5 = ZoneF | ||||
| HR | 15049doc 15049 / 415050 | Stage 6 Drain | UINT16 | Read/write | 0 = Drain7; 1 = Drain8; 2 = Drain9; 3 = Drain10; 4 = Drain11; 5 = Drain12 | ||||
| HR | 15050doc 15050 / 415051 | Cooling Drain Control Mode | UINT16 | Read/write | 0 = Off; 1 = TimeLatch | ||||
| HR | 15051doc 15051 / 415052 | Low Water Temperature Alarm | UINT16 | Read/write | 0 = Alarm; 1 = Warning | ||||
| HR | 15052doc 15052 / 415053 | Power Up Drain | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 15053doc 15053 / 415054 | Diagnostic State | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 15054doc 15054 / 415055 | Diagnostic Command | UINT16 | Read/write | 0 = Spray; 1 = Drain | ||||
| HR | 15055doc 15055 / 415056 | Control Signal Type | Printed a second time in the guide (same name as 15002). | UINT16 | Read/write | 0 = 0-10Vdc; 1 = 2-10Vdc; 2 = 4-20mA; 3 = 0-20mA | |||
| HR | 15056doc 15056 / 415057 | Update Process Status | UINT16 | Read | 0 = Ok; 1 = CRC; 2 = Device; 3 = Failed |
Notes on this map
- Only function codes 03, 06 and 16 are supported, so binary points (inputs, relays, flags) are 16-bit holding registers holding 0 or 1.
- A 'Scale N' data type with 'Value x N' means raw = engineering value x N; this map stores the multiplier 1/N.
- Temperature and capacity units follow Modbus Server Units (15001): 0 metric, 1 imperial.
- Left out because the guide contradicts itself: 2003 Water Temperature Signal (Scale 1 vs Value x 1000); 6005, 6009 and 6013 bias registers (unsigned with a negative range, Scale 10 vs example x100); 6031 Power Output Feedback and 6032 Motor Speed (Scale 100 vs Value x 10); 6176-6187 depress times and drain flows (Scale 10 vs Value x 1).
- Left out because they span two or four registers with no stated word order: every row printed with a (0)/(1)/(2)/(3) suffix, including run, on, idle and service times, cycle counts, drain volumes, Room Temperature Setpoint 6058, Room Temperature Demand Proportional Gain 6062, Modbus TCP keep-alive 6076, Demand Low Dead Band 6085, Network Timeout 6087, the RH proportional bands 6089/6091, Zone D/F humidity 6106/6113 and Control Signal 2009.
- Product name ASCII registers 3-6 are left out.
- The guide prints holding register 40672 next to protocol address 6071 (a typo for 406072); the protocol-base column is used.
- Water Temperature Bias (6093) is marked read-only and Pressure Sensor Signal (2004) writable, as printed.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Neptronic SKH4 high-pressure atomizer humidifier (Modbus communication module)
What Modbus registers does the Neptronic SKH4 high-pressure atomizer humidifier (Modbus communication module) have?
This map lists 250 registers: 250 holding registers. 177 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Neptronic SKH4 high-pressure atomizer humidifier (Modbus communication module) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide says register addresses follow the protocol base (base 0, add 1 for a PLC) and also prints the six-digit holding register (base 400001) beside each one, e.g. 6006 / 406007. The protocol-base number is the wire address.
What are the minimum Modbus registers to integrate the Neptronic SKH4 high-pressure atomizer humidifier (Modbus communication module)?
Start with HR 15017 State (Operating state); HR 15018 System Alarm (System alarm); HR 6006 Room RH (Room RH); HR 6034 Room RH Setpoint (Room RH set point); HR 6001 Power Output (Power output); HR 6025 Pressure (Pump pressure); HR 6049 Control Network Demand (Network demand); HR 15006 Control Profile (Control profile).
How do I enable Modbus control of the Neptronic SKH4 high-pressure atomizer humidifier (Modbus communication module)?
Fit the Modbus communication module, set the address from the device menu or register 0, and pick a network control profile (15006) and sources (15009-15015) when the BAS should supply readings or demand.
Where is the official Neptronic SKH4 high-pressure atomizer humidifier (Modbus communication module) Modbus documentation?
The source is SKH4 High-Pressure Atomizer - Modbus Communication Module User Guide (SKH4-Modbus Guide-240126 (V.1.00)), revision 2024-01-26, published free by Neptronic at https://www.neptronic.com/Humidifiers/pdf/2024/SKH4-Modbus%20Guide-240126%20(V.1.00).pdf.
More Neptronic Modbus register maps
- Thermostat / room controller (temperature, humidity, CO2, VOC)
Neptronic AROB series universal room controller (Modbus communication module)
Neptronic AROB24T / AROB24TH / AROB24TGH / AROB24TGVH universal room controllers with the Modbus module, ARO Modbus Guide_170824.
Also known as: AROB, AROB24T, AROB24TH, AROB24TGH, AROB24TGVH, ARO - Air handler (compact make-up air unit)
Neptronic CMU compact make-up air unit (Modbus communication module)
Neptronic CMU compact make-up air units with the Modbus communication module, guide CMU-Modbus Guide-211125.
Also known as: Compact Make-up Air Unit, Neptronic CMU, CMU Series - Thermostat / fan coil controller
Neptronic EFCB Series networkable fan coil controller (Modbus RTU)
Neptronic EFCB Series fan coil controllers (24, 120 and 240 Vac; 2 or 4 relays) with the Modbus communication module, guide EFCB-Modbus Guide-260626.
Also known as: EFCB10TU2, EFCB10TU4, EFCB11TU2, EFCB11TU4, EFCB12TU2, EFCB12TU4, EFCB fan coil controller - Thermostat / fan coil controller
Neptronic EFCB-OE1 Series networkable fan coil controller (Modbus RTU)
Neptronic EFCB-OE1 Series fan coil controllers (24 or 240 Vac; 0, 2 or 4 relays), guide EFCB1x-OE1-Modbus Guide (V2.16)-260626.
Also known as: EFCB10T-OE1, EFCB12T-OE1, EFCB10TU2-OE1, EFCB10TU4-OE1, EFCB12TU2-OE1, EFCB12TU4-OE1, EFCB1x-OE1 - Air handler terminal (dual-duct VAV controller)
Neptronic EVCBM dual-duct VAV controller (Modbus communication module)
Neptronic EVCBM dual-duct VAV controllers (master + slave airflow) with the Modbus module, guide EVCBM Dual Duct-V500-Modbus Guide-180927-ESA.
Also known as: EVCBM Dual Duct, EVCB, Neptronic EVCBM Modbus - Air handler humidifier (electric steam)
Neptronic SKE4 electric steam humidifier (Modbus communication module)
Neptronic SKE4 series electric steam humidifiers with the Modbus communication module, guide SKE4-Modbus Guide-240531 (V2.07).
Also known as: SKE4-E, SKE4-N, SKE4 Steam Humidifier, Neptronic SKE4 Modbus - Air handler humidifier (gas-fired steam)
Neptronic SKG4 gas-fired steam humidifier (Modbus communication module)
Neptronic SKG4 series gas-fired steam humidifiers (one to four burner modules) with the Modbus communication module, guide SKG4-Modbus Guide-221114 (V2.04).
Also known as: SKG4-E, SKG4-N, SKG4 Gas Fired Humidifier, Neptronic SKG4 Modbus - Pump / water treatment unit (reverse osmosis for humidifiers)
Neptronic SKRO reverse osmosis water treatment unit (Modbus communication module)
Neptronic SKRO reverse osmosis water treatment units with the Modbus communication module, guide SKRO-Modbus Guide-250913 (V1.0).
Also known as: SKRO, SKRO Water Treatment Unit, Neptronic SKRO Modbus - Air handler humidifier (steam-to-steam)
Neptronic SKS4 steam-to-steam humidifier (Modbus communication module)
Neptronic SKS4 series steam-to-steam humidifiers with the Modbus communication module, guide SKS4-Modbus Guide-220509 (V2.03).
Also known as: SKS4-E, SKS4-N, SKS4 Steam to Steam Humidifier, Neptronic SKS4 Modbus - Air handler evaporative cooler (adiabatic cooling / humidification)
Neptronic SKVF evaporative cooler / humidifier (Modbus communication module)
Neptronic SKVF series evaporative coolers with the Modbus communication module, guide SKVF-Modbus Guide-211025.
Also known as: SKVF Evaporative Cooler, SKVF Series, Neptronic SKVF Modbus - Thermostat / fan coil and unitary controller
Neptronic TSUB Series universal wall-mount controller (Modbus RTU)
Neptronic TSUB Series universal wall-mount controllers with Modbus, guide TSUB-Modbus Guide-250829 (V1.13).
Also known as: TSUB Series, TSUB universal wall-mount controller - Thermostat / heat pump and unitary controller
Neptronic TUCB / TUHB Series universal wall-mount controller (Modbus RTU)
Neptronic TUCB24C6X2 (temperature) and TUHB24C6X2 (temperature and humidity) universal wall-mount controllers with 6 binary and 2 analog outputs, guide TUXB-Modbus Guide-190515.
Also known as: TUCB24C6X2, TUHB24C6X2, TUCB, TUHB, TUXB - Thermostat / heat pump and unitary controller
Neptronic TUUB Series universal wall-mount controller (Modbus RTU)
Neptronic TUUB Series universal wall-mount controllers with Modbus, guide TUUB-Modbus Guide-250829 (V1.13).
Also known as: TUUB Series, TUUB universal wall-mount controller
Other hvac equipment register maps
- Air handler (enclosure air conditioner)
Seifert Systems Enclosure air conditioners (standard Modbus table)
Seifert Systems enclosure cooling units with Carel, Variable Speed or Seifert Standard controllers, per technical guide RDTG2001 rev 0.2 (09.02.2021).
Also known as: RDTG2001, Seifert enclosure cooling unit Modbus - Air handler (heat recovery unit controller)
Swegon TAC6 controller (Global units)
Swegon (Global) units with the TAC6 regulation board and a Modbus satellite; TAC6 + MODBUS TABLE Cid 050360 (2021-05-20).
Also known as: Global TAC6, SAT WIFI-ETHERNET (TAC6) - Air handler (heat recovery ventilation unit)
Airflow Developments Entro-V heat recovery unit controller (Basic / Digital controller, Modbus RTU)
Airflow Entro-V MVHR units with the Entro-V control board (Basic controller 90001308 / Digital controller 90001299), per controls manual 80001022 Issue 1 (08/20).
Also known as: Entro-V Basic Controller, Entro-V Digital Controller, 90001308, 90001299, DuplexVent Entro-V - Air handler humidifier (evaporative)
Condair ME II evaporative humidifier / cooler (Integrated Controller, Modbus RTU/TCP)
Condair ME with the Integrated Controller, per addendum 2603326-G.
Also known as: Condair ME, Condair ME II, ME - Air handler (demand-controlled ventilation unit)
Duco DucoBox ventilation units / IQ unit (Modbus RTU, master node)
DucoBox Silent Connect, Focus, Energy (all variants) and ECO with the Communication Print option, and the Duco IQ unit (Modbus standard), per information sheet L8000009-B.
Also known as: DucoBox Silent Connect, DucoBox Focus, DucoBox Energy, DucoBox Energy Premium, DucoBox ECO, Duco IQ unit, L8000009 - Thermostat
Johnson Controls PENN TC3222 refrigeration temperature controller (Modbus RTU)
PENN TC3222 electronic refrigeration controller with built-in Modbus RTU, per the TC3 Modbus Protocol Reference Guide LIT-12013523 (2020-04-28).
Also known as: TC3222, TC3, PENN TC3, LIT-12013523
All hvac equipment Modbus register maps →
Source: SKH4 High-Pressure Atomizer - Modbus Communication Module User Guide · SKH4-Modbus Guide-240126 (V.1.00) · rev. 2024-01-26. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.