Thermostat / room controller (temperature, humidity, CO2, VOC) · Modbus register map
Neptronic AROB series universal room controller (Modbus communication module) Modbus register map
Updated 19 November 2026
The AROB is a wall-mounted universal room controller with temperature and optional humidity, CO2 and VOC sensors, two analog and two binary outputs. Its Modbus RTU module exposes the sensor readings, calibrations, output values and their configuration, cooling, heating, humidity, CO2 and VOC setpoints with limits, PI bands and demands, the system and fan modes, and occupancy / filter / airflow input states, all as holding registers.
This page lists 151 Modbus registers for the Neptronic AROB series universal room controller (Modbus communication module) — 120 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Neptronic’s own free documentation (linked below) and checked against it.
- Manufacturer
- Neptronic
- Model
- AROB series universal room controller (Modbus communication module)
- Registers
- 151 (120 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- AROB, AROB24T, AROB24TH, AROB24TGH, AROB24TGVH, ARO
Integration notes: Neptronic AROB series universal room controller (Modbus communication module)
Read temperature (13), CO2 (11) and VOC (12) and the cooling / heating demands (2074, 2083). Set Main system mode (2116) and Temperature system mode (2117), then write the cooling and heating setpoints (2075, 2084; x10).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 13 | Temperature Level | INT16 | Room temperature | Read |
| HR 11 | CO2 Level | UINT16 | CO2 | Read |
| HR 2116 | Main system mode | UINT16 | Main system on/off | Read/write |
| HR 2117 | Temperature system mode | UINT16 | Temperature mode | Read/write |
| HR 2075 | Cooling Setpoint | UINT16 | Cooling setpoint | Read/write |
| HR 2084 | Heating Setpoint | UINT16 | Heating setpoint | Read/write |
| HR 2074 | Cooling Demand | UINT16 | Cooling demand | Read |
| HR 2083 | Heating Demand | UINT16 | Heating demand | Read |
Enable Modbus control & writes
Fit the Modbus communication module and set the address from the device menu or register 0.
Byte order & addressing
- Printed register numbers start at 40000 for address 0.
- Auto baud detection is the default; supported rates 9600-76800 per the text (the register row lists up to 57600).
Network setup
- RS-485 two-wire, RTU mode.
- Device address 1-246.
Watch out for
- OAT lockouts work only when analog input 1 mode (42000) is set to OAT sensor.
- Unoccupied setpoints need an input (42000/42001) set to occupancy.
Neptronic AROB series universal room controller (Modbus communication module) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 40000 | Address - Neptronic ID and Modbus address of the current device | High byte = product id 18 (read only); low byte = Modbus address 1-246. | UINT16 | Read/write | ||||
| HR | 1doc 40001 | Baud Rate | Baud / 100 (e.g. 384 = 38400); 0 = auto-detect. | UINT16 | × 100 | baud | Read/write | 0 = Auto baud rate detection | |
| HR | 2doc 40002 | Communication port configuration | UINT16 | Read/write | 0 = No parity, 2 stop bits; 1 = Even parity, 1 stop bit; 2 = Odd parity, 1 stop bit | ||||
| HR | 7doc 40007 | Actual firmware version | UINT16 | Read | |||||
| HR | 8doc 40008 | Actual ROM version | UINT16 | Read | |||||
| HR | 11doc 40011 | CO2 Level | Needs CO2 sensor. | UINT16 | ppm | Read | |||
| HR | 12doc 40012 | VOC Level | Needs VOC sensor. | UINT16 | ppb | Read | |||
| HR | 13doc 40013 | Temperature Level | INT16 | × 0.1 | °C / °F | Read | |||
| HR | 14doc 40014 | Humidity Level | Needs the humidity sensor fitted. | UINT16 | × 0.1 | %RH | Read | ||
| HR | 17doc 40017 | Dew Point | Needs humidity sensor. | INT16 | × 0.1 | °C / °F | Read | ||
| HR | 18doc 40018 | External Temperature Level | INT16 | × 0.1 | °C / °F | Read | |||
| HR | 20doc 40020 | Binary Input 1 Reading | UINT16 | Read | 0 = Opened; 1 = Closed | ||||
| HR | 21doc 40021 | CO2 sensor calibration | Needs CO2 sensor. | INT16 | ppm | Read/write | |||
| HR | 22doc 40022 | VOC sensor calibration | Needs VOC sensor. | INT16 | ppb | Read/write | |||
| HR | 23doc 40023 | Temperature sensor calibration | INT16 | × 0.01 | °C / °F | Read/write | |||
| HR | 24doc 40024 | Humidity sensor calibration | Needs humidity sensor. | INT16 | × 0.01 | %RH | Read/write | ||
| HR | 26doc 40026 | External temperature sensor calibration | INT16 | × 0.01 | °C / °F | Read/write | |||
| HR | 27doc 40027 | Analog Output 1 value | UINT16 | × 0.1 | % | Read/write | |||
| HR | 28doc 40028 | Analog Output 2 value | UINT16 | × 0.1 | % | Read/write | |||
| HR | 29doc 40029 | Binary Output 1 value | UINT16 | Read/write | 0 = Opened; 1 = Closed | ||||
| HR | 30doc 40030 | Binary Output 1 value | Printed with the same name as 40029. | UINT16 | Read/write | 0 = Opened; 1 = Closed | |||
| HR | 31doc 40031 | Display options | Other bits reserved. | BITMAP16 | Read/write | bit 0 = Display CO2; bit 1 = Display VOC; bit 2 = Display temperature; bit 3 = Display humidity; bit 7 = Enable backlight; bit 8 = Enable autoscroll | |||
| HR | 33doc 40033 | Local units of display on the device | UINT16 | Read/write | 0 = Metric; 1 = Imperial | ||||
| HR | 34doc 40034 | Units of display over the network | UINT16 | Read/write | 0 = Metric; 1 = Imperial | ||||
| HR | 35doc 40035 | Lock options | Other bits reserved. | BITMAP16 | Read/write | bit 4 = Keypad upper-left lock; bit 5 = Keypad bottom-left lock; bit 6 = Keypad arrows lock; bit 7 = Program mode lock | |||
| HR | 2000doc 42000 | Analog Input 1 Mode | UINT16 | Read/write | 0 = Off; 1 = OAT Sensor; 2 = Occupancy; 3 = Night Setback; 4 = Dirty Filter; 5 = Air Flow Switch; 6 = Air Flow Lockout | ||||
| HR | 2001doc 42001 | Binary Input 1 Mode | UINT16 | Read/write | 0 = Off; 1 = Occupancy; 2 = Night Setback; 3 = Dirty Filter; 4 = Air Flow Switch; 5 = Air Flow Lockout | ||||
| HR | 2002doc 42002 | Analog Output 1 Demand | UINT16 | × 0.1 | % | Read | |||
| HR | 2003doc 42003 | Analog Output 1 Value in Millivolts | UINT16 | mV | Read | ||||
| HR | 2005doc 42005 | Analog Output 1 Minimum Voltage | UINT16 | × 0.01 | V | Read/write | |||
| HR | 2006doc 42006 | Analog Output 1 Maximum Voltage | UINT16 | × 0.01 | V | Read/write | |||
| HR | 2007doc 42007 | Analog Output 1 Control Mode | UINT16 | Read/write | 0 = Highest; 1 = Average | ||||
| HR | 2008doc 42008 | Analog Output 1 direction | UINT16 | Read/write | 0 = Direct Mode; 1 = Reverse Mode | ||||
| HR | 2009doc 42009 | Analog Output 1 cooling | UINT16 | Read/write | 0 = No; 1 = Yes | ||||
| HR | 2010doc 42010 | Analog Output 1 heating | UINT16 | Read/write | 0 = No; 1 = Yes | ||||
| HR | 2011doc 42011 | Analog Output 1 Dehumidification | Needs humidity sensor. | UINT16 | Read/write | 0 = No; 1 = Yes | |||
| HR | 2012doc 42012 | Analog Output 1 Humidification | Needs humidity sensor. | UINT16 | Read/write | 0 = No; 1 = Yes | |||
| HR | 2013doc 42013 | Analog Output 1 VOC | Needs VOC sensor. | UINT16 | Read/write | 0 = No; 1 = Yes | |||
| HR | 2014doc 42014 | Analog Output 1 CO2 | Needs CO2 sensor. | UINT16 | Read/write | 0 = No; 1 = Yes | |||
| HR | 2015doc 42015 | Analog Output 1 Fan | UINT16 | Read/write | 0 = No; 1 = Yes | ||||
| HR | 2016doc 42016 | Analog Output 2 Demand | App Profile only. | UINT16 | × 0.1 | % | Read | ||
| HR | 2017doc 42017 | Analog Output 2 Value in Millivolts | App Profile only. | UINT16 | mV | Read | |||
| HR | 2019doc 42019 | Analog Output 2 Minimum Voltage | App Profile only. | UINT16 | × 0.01 | V | Read/write | ||
| HR | 2020doc 42020 | Analog Output 2 Maximum Voltage | App Profile only. | UINT16 | × 0.01 | V | Read/write | ||
| HR | 2021doc 42021 | Analog Output 2 Control Mode | App Profile only. | UINT16 | Read/write | 0 = Highest; 1 = Average | |||
| HR | 2022doc 42022 | Analog Output 2 direction | App Profile only. | UINT16 | Read/write | 0 = Direct Mode; 1 = Reverse Mode | |||
| HR | 2023doc 42023 | Analog Output 2 cooling | App Profile only. | UINT16 | Read/write | 0 = No; 1 = Yes | |||
| HR | 2024doc 42024 | Analog Output 2 heating | App Profile only. | UINT16 | Read/write | 0 = No; 1 = Yes | |||
| HR | 2025doc 42025 | Analog Output 2 Dehumidification | App Profile only. Needs humidity sensor. | UINT16 | Read/write | 0 = No; 1 = Yes | |||
| HR | 2026doc 42026 | Analog Output 2 Humidification | App Profile only. Needs humidity sensor. | UINT16 | Read/write | 0 = No; 1 = Yes | |||
| HR | 2027doc 42027 | Analog Output 2 VOC | App Profile only. Needs VOC sensor. | UINT16 | Read/write | 0 = No; 1 = Yes | |||
| HR | 2028doc 42028 | Analog Output 2 CO2 | App Profile only. Needs CO2 sensor. | UINT16 | Read/write | 0 = No; 1 = Yes | |||
| HR | 2029doc 42029 | Analog Output 2 Fan | App Profile only. | UINT16 | Read/write | 0 = No; 1 = Yes | |||
| HR | 2030doc 42030 | Binary Output 1 Demand | UINT16 | × 0.1 | % | Read | |||
| HR | 2031doc 42031 | Binary Output 1 (Relay State) | UINT16 | Read | 0 = Off; 1 = Set; 2 = Reset | ||||
| HR | 2032doc 42032 | Binary Output 1 Control Mode | UINT16 | Read/write | 0 = Highest; 1 = Average | ||||
| HR | 2033doc 42033 | Binary Output 1 Type | UINT16 | Read/write | 0 = Normally Closed; 1 = Normally Open | ||||
| HR | 2034doc 42034 | Binary Output 1 Signal | UINT16 | Read/write | 0 = Time Proportional Modulation (TPM); 1 = Hysteresis Mode | ||||
| HR | 2035doc 42035 | Binary Output 1 CPH (Cycles per hour) | UINT16 | Read/write | 0 = 8 CPH (1 cycle = 7.5 minutes); 1 = 4 CPH (1 cycle = 15 minutes); 2 = 3 CPH (1 cycle = 20 minutes) | ||||
| HR | 2036doc 42036 | Binary Output 1 Anti-cycle delay in seconds | UINT16 | s | Read/write | ||||
| HR | 2037doc 42037 | Binary Output 1 Hysteresis Low percent | UINT16 | × 0.1 | % | Read/write | |||
| HR | 2038doc 42038 | Binary Output 1 Hysteresis High percent | UINT16 | × 0.1 | % | Read/write | |||
| HR | 2039doc 42039 | Binary Output 1 Cooling | UINT16 | Read/write | 0 = No; 1 = Yes | ||||
| HR | 2040doc 42040 | Binary Output 1 heating | UINT16 | Read/write | 0 = No; 1 = Yes | ||||
| HR | 2041doc 42041 | Binary Output 1 Dehumidification | Needs humidity sensor. | UINT16 | Read/write | 0 = No; 1 = Yes | |||
| HR | 2042doc 42042 | Binary Output 1 Humidification | Needs humidity sensor. | UINT16 | Read/write | 0 = No; 1 = Yes | |||
| HR | 2043doc 42043 | Binary Output 1 VOC | Needs VOC sensor. | UINT16 | Read/write | 0 = No; 1 = Yes | |||
| HR | 2044doc 42044 | Binary Output 1 CO2 | Needs CO2 sensor. | UINT16 | Read/write | 0 = No; 1 = Yes | |||
| HR | 2045doc 42045 | Binary Output 1 Fan | UINT16 | Read/write | 0 = No; 1 = Yes | ||||
| HR | 2046doc 42046 | Binary Output 2 Demand | App Profile only. | UINT16 | × 0.1 | % | Read | ||
| HR | 2047doc 42047 | Binary Output 2 (Relay State) | App Profile only. | UINT16 | Read | 0 = Off; 1 = Set; 2 = Reset | |||
| HR | 2048doc 42048 | Binary Output 2 Control Mode | App Profile only. | UINT16 | Read/write | 0 = Highest; 1 = Average | |||
| HR | 2049doc 42049 | Binary Output 2 Type | App Profile only. | UINT16 | Read/write | 0 = Normally Closed; 1 = Normally Open | |||
| HR | 2050doc 42050 | Binary Output 2 Signal | App Profile only. | UINT16 | Read/write | 0 = Time Proportional Modulation (TPM); 1 = Hysteresis Mode | |||
| HR | 2051doc 42051 | Binary Output 2 CPH (Cycles per hour) | App Profile only. | UINT16 | Read/write | 0 = 8 CPH (1 cycle = 7.5 minutes); 1 = 4 CPH (1 cycle = 15 minutes); 2 = 3 CPH (1 cycle = 20 minutes) | |||
| HR | 2052doc 42052 | Binary Output 2 Anti-cycle delay in seconds | App Profile only. | UINT16 | s | Read/write | |||
| HR | 2053doc 42053 | Binary Output 2 Hysteresis Low percent | App Profile only. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 2054doc 42054 | Binary Output 2 Hysteresis High percent | App Profile only. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 2055doc 42055 | Binary Output 2 Cooling | App Profile only. | UINT16 | Read/write | 0 = No; 1 = Yes | |||
| HR | 2056doc 42056 | Binary Output 2 heating | App Profile only. | UINT16 | Read/write | 0 = No; 1 = Yes | |||
| HR | 2057doc 42057 | Binary Output 2 Dehumidification | Needs humidity sensor. | UINT16 | Read/write | 0 = No; 1 = Yes | |||
| HR | 2058doc 42058 | Binary Output 2 Humidification | App Profile only. Needs humidity sensor. | UINT16 | Read/write | 0 = No; 1 = Yes | |||
| HR | 2059doc 42059 | Binary Output 2 VOC | App Profile only. Needs VOC sensor. | UINT16 | Read/write | 0 = No; 1 = Yes | |||
| HR | 2060doc 42060 | Binary Output 2 CO2 | App Profile only. Needs CO2 sensor. | UINT16 | Read/write | 0 = No; 1 = Yes | |||
| HR | 2061doc 42061 | Binary Output 2 Fan | App Profile only. | UINT16 | Read/write | 0 = No; 1 = Yes | |||
| HR | 2062doc 42062 | AO1 OAT (Outside Air Temperature) High lockout | INT16 | × 0.1 | °C / °F | Read/write | |||
| HR | 2063doc 42063 | AO1 OAT (Outside Air Temperature) Low lockout | INT16 | × 0.1 | °C / °F | Read/write | |||
| HR | 2064doc 42064 | AO1 OAT (Outside Air Temperature) Lock | UINT16 | Read | 0 = No; 1 = Yes | ||||
| HR | 2065doc 42065 | AO2 OAT (Outside Air Temperature) High lockout | App Profile only. | INT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 2066doc 42066 | AO2 OAT (Outside Air Temperature) Low lockout | App Profile only. | INT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 2067doc 42067 | AO2 OAT (Outside Air Temperature) Lock | App Profile only. | UINT16 | Read | 0 = No; 1 = Yes | |||
| HR | 2068doc 42068 | BO1 OAT (Outside Air Temperature) High lockout | INT16 | × 0.1 | °C / °F | Read/write | |||
| HR | 2069doc 42069 | BO1 OAT (Outside Air Temperature) Low lockout | INT16 | × 0.1 | °C / °F | Read/write | |||
| HR | 2070doc 42070 | BO1 OAT (Outside Air Temperature) Lock | UINT16 | Read | 0 = No; 1 = Yes | ||||
| HR | 2071doc 42071 | BO2 OAT (Outside Air Temperature) High level lockout | App Profile only. | INT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 2072doc 42072 | BO2 OAT (Outside Air Temperature) Low level lockout | App Profile only. | INT16 | × 0.1 | °C / °F | Read/write | ||
| HR | 2073doc 42073 | BO2 OAT (Outside Air Temperature) Lock | App Profile only. | UINT16 | Read | 0 = No; 1 = Yes | |||
| HR | 2074doc 42074 | Cooling Demand | UINT16 | × 0.1 | % | Read | |||
| HR | 2075doc 42075 | Cooling Setpoint | UINT16 | × 0.1 | °C / °F | Read/write | |||
| HR | 2076doc 42076 | Minimum Cooling Setpoint | UINT16 | × 0.1 | °C / °F | Read/write | |||
| HR | 2077doc 42077 | Maximum Cooling Setpoint | UINT16 | × 0.1 | °C / °F | Read/write | |||
| HR | 2078doc 42078 | Cooling Proportional Band | UINT16 | × 0.1 | °C / °F | Read/write | |||
| HR | 2079doc 42079 | Cooling Integral Time in seconds | UINT16 | s | Read/write | ||||
| HR | 2080doc 42080 | Cooling Unoccupied Setpoint | UINT16 | × 0.1 | °C / °F | Read/write | |||
| HR | 2081doc 42081 | Minimum Cooling Unoccupied Setpoint | UINT16 | × 0.1 | °C / °F | Read/write | |||
| HR | 2082doc 42082 | Maximum Cooling Unoccupied Setpoint | UINT16 | × 0.1 | °C / °F | Read/write | |||
| HR | 2083doc 42083 | Heating Demand | UINT16 | × 0.1 | % | Read | |||
| HR | 2084doc 42084 | Heating Setpoint | UINT16 | × 0.1 | °C / °F | Read/write | |||
| HR | 2085doc 42085 | Minimum Heating Setpoint | UINT16 | × 0.1 | °C / °F | Read/write | |||
| HR | 2086doc 42086 | Maximum Heating Setpoint | UINT16 | × 0.1 | °C / °F | Read/write | |||
| HR | 2087doc 42087 | Heating Proportional Band | UINT16 | × 0.1 | °C / °F | Read/write | |||
| HR | 2088doc 42088 | Heating Integral Time in seconds | UINT16 | s | Read/write | ||||
| HR | 2089doc 42089 | Heating Unoccupied Setpoint | UINT16 | × 0.1 | °C / °F | Read/write | |||
| HR | 2090doc 42090 | Minimum Heating Unoccupied Setpoint | UINT16 | × 0.1 | °C / °F | Read/write | |||
| HR | 2091doc 42091 | Maximum Heating Unoccupied Setpoint | UINT16 | × 0.1 | °C / °F | Read/write | |||
| HR | 2092doc 42092 | Dehumidification Demand | Needs humidity sensor. | UINT16 | × 0.1 | % | Read | ||
| HR | 2093doc 42093 | Dehumidification Setpoint | Needs humidity sensor. | UINT16 | × 0.1 | %RH | Read/write | ||
| HR | 2094doc 42094 | Minimum Dehumidification Setpoint | Needs humidity sensor. | UINT16 | × 0.1 | %RH | Read/write | ||
| HR | 2095doc 42095 | Maximum Dehumidification Setpoint | Needs humidity sensor. | UINT16 | × 0.1 | %RH | Read/write | ||
| HR | 2096doc 42096 | Humidity Proportional Band | Needs humidity sensor. | UINT16 | × 0.1 | %RH | Read/write | ||
| HR | 2097doc 42097 | Humidity Integral Time in seconds | Needs humidity sensor. | UINT16 | s | Read/write | |||
| HR | 2098doc 42098 | Humidification Demand | Needs humidity sensor. | UINT16 | × 0.1 | % | Read | ||
| HR | 2099doc 42099 | Humidification Setpoint | Needs humidity sensor. | UINT16 | × 0.1 | %RH | Read/write | ||
| HR | 2100doc 42100 | Minimum Humidification Setpoint | Needs humidity sensor. | UINT16 | × 0.1 | %RH | Read/write | ||
| HR | 2101doc 42101 | Maximum Humidification Setpoint | Needs humidity sensor. | UINT16 | × 0.1 | %RH | Read/write | ||
| HR | 2102doc 42102 | CO2 Demand | Needs CO2 sensor. | UINT16 | × 0.1 | % | Read | ||
| HR | 2103doc 42103 | CO2 Setpoint | Needs CO2 sensor. | UINT16 | ppm | Read/write | |||
| HR | 2104doc 42104 | Minimum CO2 Setpoint | Needs CO2 sensor. | UINT16 | ppm | Read/write | |||
| HR | 2105doc 42105 | Maximum CO2 Setpoint | Needs CO2 sensor. | UINT16 | ppm | Read/write | |||
| HR | 2106doc 42106 | CO2 Proportional Band | Needs CO2 sensor. | UINT16 | ppm | Read/write | |||
| HR | 2107doc 42107 | CO2 Integral Time in seconds | Needs CO2 sensor. | UINT16 | s | Read/write | |||
| HR | 2108doc 42108 | VOC Demand | Needs VOC sensor. | UINT16 | × 0.1 | % | Read | ||
| HR | 2109doc 42109 | VOC Setpoint | Needs VOC sensor. | UINT16 | ppb | Read/write | |||
| HR | 2110doc 42110 | Minimum VOC Setpoint | Needs VOC sensor. | UINT16 | ppb | Read/write | |||
| HR | 2111doc 42111 | Maximum VOC Setpoint | Needs VOC sensor. | UINT16 | ppb | Read/write | |||
| HR | 2112doc 42112 | VOC Proportional Band | Needs VOC sensor. | UINT16 | ppb | Read/write | |||
| HR | 2113doc 42113 | VOC Integral Time in seconds | Needs VOC sensor. | UINT16 | s | Read/write | |||
| HR | 2114doc 42114 | Temperature Setpoint Deadband | UINT16 | × 0.1 | °C / °F | Read/write | |||
| HR | 2115doc 42115 | Humidity Setpoint Deadband | Needs humidity sensor. | UINT16 | × 0.1 | %RH | Read/write | ||
| HR | 2116doc 42116 | Main system mode | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 2117doc 42117 | Temperature system mode | UINT16 | Read/write | 0 = Off; 1 = Cool; 2 = Auto; 3 = Heat | ||||
| HR | 2118doc 42118 | Humidity system mode | Needs humidity sensor. | UINT16 | Read/write | 0 = Off; 1 = Dehumidification; 2 = Auto; 3 = Humidification | |||
| HR | 2119doc 42119 | CO2 system mode | Needs CO2 sensor. | UINT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 2120doc 42120 | VOC system mode | Needs VOC sensor. | UINT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 2121doc 42121 | Fan system mode | UINT16 | Read/write | 0 = Off; 1 = Auto; 2 = On | ||||
| HR | 2122doc 42122 | Fan ON Speed | UINT16 | × 0.1 | % | Read/write | |||
| HR | 2123doc 42123 | App Profile | Option 2 needs humidity and CO2 sensors. | UINT16 | Read/write | 0 = No Profile; 1 = Temp Only; 2 = Temp, RH, and CO2 | |||
| HR | 3000doc 43000 | Occupancy status | UINT16 | Read | 0 = No; 1 = Yes | ||||
| HR | 3001doc 43001 | Dirty Filter status | App Profile only. | UINT16 | Read | 0 = No; 1 = Yes | |||
| HR | 3002doc 43002 | Airflow Switch status | App Profile only. | UINT16 | Read | 0 = No; 1 = Yes | |||
| HR | 3003doc 43003 | Airflow Lockout Protection status | App Profile only. | UINT16 | Read | 0 = No; 1 = Yes |
Notes on this map
- Only function codes 03, 06 and 16 are supported; everything is a holding register.
- 'Scale N' with 'Value x N' means raw = engineering value x N; the multiplier here is 1/N.
- Temperatures and enthalpy follow the network units register (40034): 0 metric, 1 imperial.
- Left out: product name ASCII registers 40003-40006; alarm status 40009/40010 (all bits reserved); enthalpy 40016 (its example value lies outside its printed range).
- 40029 and 40030 are both printed 'Binary Output 1 value'; both are listed as printed.
- Several output and lockout registers apply only when an App Profile (42123) is selected, or need the matching sensor; this is noted per register.
- The display and lock option bit tables (40031, 40035) are printed in two interleaved columns; only the bit names are given here (1 = yes / on).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Neptronic AROB series universal room controller (Modbus communication module)
What Modbus registers does the Neptronic AROB series universal room controller (Modbus communication module) have?
This map lists 151 registers: 151 holding registers. 120 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Neptronic AROB series universal room controller (Modbus communication module) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are printed from 40000. The intro puts the device address at holding register index 0, auto baud at index 1 and the port settings at index 2, which are the rows printed 40000-40002, so the wire address is the printed number minus 40000 (42075 cooling setpoint = address 2075). Same layout as Neptronic's TUXB guide.
What are the minimum Modbus registers to integrate the Neptronic AROB series universal room controller (Modbus communication module)?
Start with HR 13 Temperature Level (Room temperature); HR 11 CO2 Level (CO2); HR 2116 Main system mode (Main system on/off); HR 2117 Temperature system mode (Temperature mode); HR 2075 Cooling Setpoint (Cooling setpoint); HR 2084 Heating Setpoint (Heating setpoint); HR 2074 Cooling Demand (Cooling demand); HR 2083 Heating Demand (Heating demand).
How do I enable Modbus control of the Neptronic AROB series universal room controller (Modbus communication module)?
Fit the Modbus communication module and set the address from the device menu or register 0.
Where is the official Neptronic AROB series universal room controller (Modbus communication module) Modbus documentation?
The source is AROB Series Universal Room Controller - Modbus Communication Module User Guide (ARO Modbus Guide_170824), revision 2017-08-24, published free by Neptronic at https://www.neptronic.com/Controls/IAQController/PDF/ARO%20Modbus%20Guide_170824.pdf.
More Neptronic Modbus register maps
- Air handler (compact make-up air unit)
Neptronic CMU compact make-up air unit (Modbus communication module)
Neptronic CMU compact make-up air units with the Modbus communication module, guide CMU-Modbus Guide-211125.
Also known as: Compact Make-up Air Unit, Neptronic CMU, CMU Series - Thermostat / fan coil controller
Neptronic EFCB Series networkable fan coil controller (Modbus RTU)
Neptronic EFCB Series fan coil controllers (24, 120 and 240 Vac; 2 or 4 relays) with the Modbus communication module, guide EFCB-Modbus Guide-260626.
Also known as: EFCB10TU2, EFCB10TU4, EFCB11TU2, EFCB11TU4, EFCB12TU2, EFCB12TU4, EFCB fan coil controller - Thermostat / fan coil controller
Neptronic EFCB-OE1 Series networkable fan coil controller (Modbus RTU)
Neptronic EFCB-OE1 Series fan coil controllers (24 or 240 Vac; 0, 2 or 4 relays), guide EFCB1x-OE1-Modbus Guide (V2.16)-260626.
Also known as: EFCB10T-OE1, EFCB12T-OE1, EFCB10TU2-OE1, EFCB10TU4-OE1, EFCB12TU2-OE1, EFCB12TU4-OE1, EFCB1x-OE1 - Air handler terminal (dual-duct VAV controller)
Neptronic EVCBM dual-duct VAV controller (Modbus communication module)
Neptronic EVCBM dual-duct VAV controllers (master + slave airflow) with the Modbus module, guide EVCBM Dual Duct-V500-Modbus Guide-180927-ESA.
Also known as: EVCBM Dual Duct, EVCB, Neptronic EVCBM Modbus - Air handler humidifier (electric steam)
Neptronic SKE4 electric steam humidifier (Modbus communication module)
Neptronic SKE4 series electric steam humidifiers with the Modbus communication module, guide SKE4-Modbus Guide-240531 (V2.07).
Also known as: SKE4-E, SKE4-N, SKE4 Steam Humidifier, Neptronic SKE4 Modbus - Air handler humidifier (gas-fired steam)
Neptronic SKG4 gas-fired steam humidifier (Modbus communication module)
Neptronic SKG4 series gas-fired steam humidifiers (one to four burner modules) with the Modbus communication module, guide SKG4-Modbus Guide-221114 (V2.04).
Also known as: SKG4-E, SKG4-N, SKG4 Gas Fired Humidifier, Neptronic SKG4 Modbus - Air handler humidifier (high-pressure atomizer)
Neptronic SKH4 high-pressure atomizer humidifier (Modbus communication module)
Neptronic SKH4 high-pressure atomizers with the Modbus communication module, guide SKH4-Modbus Guide-240126 (V.1.00).
Also known as: SKH4, SKH4 High-Pressure Atomizer, Neptronic SKH4 Modbus - Pump / water treatment unit (reverse osmosis for humidifiers)
Neptronic SKRO reverse osmosis water treatment unit (Modbus communication module)
Neptronic SKRO reverse osmosis water treatment units with the Modbus communication module, guide SKRO-Modbus Guide-250913 (V1.0).
Also known as: SKRO, SKRO Water Treatment Unit, Neptronic SKRO Modbus - Air handler humidifier (steam-to-steam)
Neptronic SKS4 steam-to-steam humidifier (Modbus communication module)
Neptronic SKS4 series steam-to-steam humidifiers with the Modbus communication module, guide SKS4-Modbus Guide-220509 (V2.03).
Also known as: SKS4-E, SKS4-N, SKS4 Steam to Steam Humidifier, Neptronic SKS4 Modbus - Air handler evaporative cooler (adiabatic cooling / humidification)
Neptronic SKVF evaporative cooler / humidifier (Modbus communication module)
Neptronic SKVF series evaporative coolers with the Modbus communication module, guide SKVF-Modbus Guide-211025.
Also known as: SKVF Evaporative Cooler, SKVF Series, Neptronic SKVF Modbus - Thermostat / fan coil and unitary controller
Neptronic TSUB Series universal wall-mount controller (Modbus RTU)
Neptronic TSUB Series universal wall-mount controllers with Modbus, guide TSUB-Modbus Guide-250829 (V1.13).
Also known as: TSUB Series, TSUB universal wall-mount controller - Thermostat / heat pump and unitary controller
Neptronic TUCB / TUHB Series universal wall-mount controller (Modbus RTU)
Neptronic TUCB24C6X2 (temperature) and TUHB24C6X2 (temperature and humidity) universal wall-mount controllers with 6 binary and 2 analog outputs, guide TUXB-Modbus Guide-190515.
Also known as: TUCB24C6X2, TUHB24C6X2, TUCB, TUHB, TUXB - Thermostat / heat pump and unitary controller
Neptronic TUUB Series universal wall-mount controller (Modbus RTU)
Neptronic TUUB Series universal wall-mount controllers with Modbus, guide TUUB-Modbus Guide-250829 (V1.13).
Also known as: TUUB Series, TUUB universal wall-mount controller
Other hvac equipment register maps
- Air handler (enclosure air conditioner)
Seifert Systems Enclosure air conditioners (standard Modbus table)
Seifert Systems enclosure cooling units with Carel, Variable Speed or Seifert Standard controllers, per technical guide RDTG2001 rev 0.2 (09.02.2021).
Also known as: RDTG2001, Seifert enclosure cooling unit Modbus - Air handler (heat recovery unit controller)
Swegon TAC6 controller (Global units)
Swegon (Global) units with the TAC6 regulation board and a Modbus satellite; TAC6 + MODBUS TABLE Cid 050360 (2021-05-20).
Also known as: Global TAC6, SAT WIFI-ETHERNET (TAC6) - Air handler (heat recovery ventilation unit)
Airflow Developments Entro-V heat recovery unit controller (Basic / Digital controller, Modbus RTU)
Airflow Entro-V MVHR units with the Entro-V control board (Basic controller 90001308 / Digital controller 90001299), per controls manual 80001022 Issue 1 (08/20).
Also known as: Entro-V Basic Controller, Entro-V Digital Controller, 90001308, 90001299, DuplexVent Entro-V - Air handler humidifier (evaporative)
Condair ME II evaporative humidifier / cooler (Integrated Controller, Modbus RTU/TCP)
Condair ME with the Integrated Controller, per addendum 2603326-G.
Also known as: Condair ME, Condair ME II, ME - Air handler (demand-controlled ventilation unit)
Duco DucoBox ventilation units / IQ unit (Modbus RTU, master node)
DucoBox Silent Connect, Focus, Energy (all variants) and ECO with the Communication Print option, and the Duco IQ unit (Modbus standard), per information sheet L8000009-B.
Also known as: DucoBox Silent Connect, DucoBox Focus, DucoBox Energy, DucoBox Energy Premium, DucoBox ECO, Duco IQ unit, L8000009 - Thermostat
Johnson Controls PENN TC3222 refrigeration temperature controller (Modbus RTU)
PENN TC3222 electronic refrigeration controller with built-in Modbus RTU, per the TC3 Modbus Protocol Reference Guide LIT-12013523 (2020-04-28).
Also known as: TC3222, TC3, PENN TC3, LIT-12013523
All hvac equipment Modbus register maps →
Source: AROB Series Universal Room Controller - Modbus Communication Module User Guide · ARO Modbus Guide_170824 · rev. 2017-08-24. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.