Thermostat / room controller (temperature, humidity, CO2, VOC) · Modbus register map

Neptronic AROB series universal room controller (Modbus communication module) Modbus register map

Updated 19 November 2026

Short answer

The AROB is a wall-mounted universal room controller with temperature and optional humidity, CO2 and VOC sensors, two analog and two binary outputs. Its Modbus RTU module exposes the sensor readings, calibrations, output values and their configuration, cooling, heating, humidity, CO2 and VOC setpoints with limits, PI bands and demands, the system and fan modes, and occupancy / filter / airflow input states, all as holding registers.

This page lists 151 Modbus registers for the Neptronic AROB series universal room controller (Modbus communication module) — 120 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Neptronic’s own free documentation (linked below) and checked against it.

Manufacturer
Neptronic
Model
AROB series universal room controller (Modbus communication module)
Equipment type
Thermostat / room controller (temperature, humidity, CO2, VOC)
Registers
151 (120 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
AROB, AROB24T, AROB24TH, AROB24TGH, AROB24TGVH, ARO
Source document
AROB Series Universal Room Controller - Modbus Communication Module User Guide · ARO Modbus Guide_170824 · rev. 2017-08-24
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Neptronic AROB series universal room controller (Modbus communication module)

Integration in brief

Read temperature (13), CO2 (11) and VOC (12) and the cooling / heating demands (2074, 2083). Set Main system mode (2116) and Temperature system mode (2117), then write the cooling and heating setpoints (2075, 2084; x10).

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 13Temperature LevelINT16Room temperatureRead
HR 11CO2 LevelUINT16CO2Read
HR 2116Main system modeUINT16Main system on/offRead/write
HR 2117Temperature system modeUINT16Temperature modeRead/write
HR 2075Cooling SetpointUINT16Cooling setpointRead/write
HR 2084Heating SetpointUINT16Heating setpointRead/write
HR 2074Cooling DemandUINT16Cooling demandRead
HR 2083Heating DemandUINT16Heating demandRead

Enable Modbus control & writes

Fit the Modbus communication module and set the address from the device menu or register 0.

Byte order & addressing

Network setup

Watch out for

Neptronic AROB series universal room controller (Modbus communication module) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

151 of 151 shown
Neptronic AROB series universal room controller (Modbus communication module) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 40000Address - Neptronic ID and Modbus address of the current deviceHigh byte = product id 18 (read only); low byte = Modbus address 1-246.UINT16Read/write
HR1doc 40001Baud RateBaud / 100 (e.g. 384 = 38400); 0 = auto-detect.UINT16× 100baudRead/write0 = Auto baud rate detection
HR2doc 40002Communication port configurationUINT16Read/write0 = No parity, 2 stop bits; 1 = Even parity, 1 stop bit; 2 = Odd parity, 1 stop bit
HR7doc 40007Actual firmware versionUINT16Read
HR8doc 40008Actual ROM versionUINT16Read
HR11doc 40011CO2 LevelNeeds CO2 sensor.UINT16ppmRead
HR12doc 40012VOC LevelNeeds VOC sensor.UINT16ppbRead
HR13doc 40013Temperature LevelINT16× 0.1°C / °FRead
HR14doc 40014Humidity LevelNeeds the humidity sensor fitted.UINT16× 0.1%RHRead
HR17doc 40017Dew PointNeeds humidity sensor.INT16× 0.1°C / °FRead
HR18doc 40018External Temperature LevelINT16× 0.1°C / °FRead
HR20doc 40020Binary Input 1 ReadingUINT16Read0 = Opened; 1 = Closed
HR21doc 40021CO2 sensor calibrationNeeds CO2 sensor.INT16ppmRead/write
HR22doc 40022VOC sensor calibrationNeeds VOC sensor.INT16ppbRead/write
HR23doc 40023Temperature sensor calibrationINT16× 0.01°C / °FRead/write
HR24doc 40024Humidity sensor calibrationNeeds humidity sensor.INT16× 0.01%RHRead/write
HR26doc 40026External temperature sensor calibrationINT16× 0.01°C / °FRead/write
HR27doc 40027Analog Output 1 valueUINT16× 0.1%Read/write
HR28doc 40028Analog Output 2 valueUINT16× 0.1%Read/write
HR29doc 40029Binary Output 1 valueUINT16Read/write0 = Opened; 1 = Closed
HR30doc 40030Binary Output 1 valuePrinted with the same name as 40029.UINT16Read/write0 = Opened; 1 = Closed
HR31doc 40031Display optionsOther bits reserved.BITMAP16Read/writebit 0 = Display CO2; bit 1 = Display VOC; bit 2 = Display temperature; bit 3 = Display humidity; bit 7 = Enable backlight; bit 8 = Enable autoscroll
HR33doc 40033Local units of display on the deviceUINT16Read/write0 = Metric; 1 = Imperial
HR34doc 40034Units of display over the networkUINT16Read/write0 = Metric; 1 = Imperial
HR35doc 40035Lock optionsOther bits reserved.BITMAP16Read/writebit 4 = Keypad upper-left lock; bit 5 = Keypad bottom-left lock; bit 6 = Keypad arrows lock; bit 7 = Program mode lock
HR2000doc 42000Analog Input 1 ModeUINT16Read/write0 = Off; 1 = OAT Sensor; 2 = Occupancy; 3 = Night Setback; 4 = Dirty Filter; 5 = Air Flow Switch; 6 = Air Flow Lockout
HR2001doc 42001Binary Input 1 ModeUINT16Read/write0 = Off; 1 = Occupancy; 2 = Night Setback; 3 = Dirty Filter; 4 = Air Flow Switch; 5 = Air Flow Lockout
HR2002doc 42002Analog Output 1 DemandUINT16× 0.1%Read
HR2003doc 42003Analog Output 1 Value in MillivoltsUINT16mVRead
HR2005doc 42005Analog Output 1 Minimum VoltageUINT16× 0.01VRead/write
HR2006doc 42006Analog Output 1 Maximum VoltageUINT16× 0.01VRead/write
HR2007doc 42007Analog Output 1 Control ModeUINT16Read/write0 = Highest; 1 = Average
HR2008doc 42008Analog Output 1 directionUINT16Read/write0 = Direct Mode; 1 = Reverse Mode
HR2009doc 42009Analog Output 1 coolingUINT16Read/write0 = No; 1 = Yes
HR2010doc 42010Analog Output 1 heatingUINT16Read/write0 = No; 1 = Yes
HR2011doc 42011Analog Output 1 DehumidificationNeeds humidity sensor.UINT16Read/write0 = No; 1 = Yes
HR2012doc 42012Analog Output 1 HumidificationNeeds humidity sensor.UINT16Read/write0 = No; 1 = Yes
HR2013doc 42013Analog Output 1 VOCNeeds VOC sensor.UINT16Read/write0 = No; 1 = Yes
HR2014doc 42014Analog Output 1 CO2Needs CO2 sensor.UINT16Read/write0 = No; 1 = Yes
HR2015doc 42015Analog Output 1 FanUINT16Read/write0 = No; 1 = Yes
HR2016doc 42016Analog Output 2 DemandApp Profile only.UINT16× 0.1%Read
HR2017doc 42017Analog Output 2 Value in MillivoltsApp Profile only.UINT16mVRead
HR2019doc 42019Analog Output 2 Minimum VoltageApp Profile only.UINT16× 0.01VRead/write
HR2020doc 42020Analog Output 2 Maximum VoltageApp Profile only.UINT16× 0.01VRead/write
HR2021doc 42021Analog Output 2 Control ModeApp Profile only.UINT16Read/write0 = Highest; 1 = Average
HR2022doc 42022Analog Output 2 directionApp Profile only.UINT16Read/write0 = Direct Mode; 1 = Reverse Mode
HR2023doc 42023Analog Output 2 coolingApp Profile only.UINT16Read/write0 = No; 1 = Yes
HR2024doc 42024Analog Output 2 heatingApp Profile only.UINT16Read/write0 = No; 1 = Yes
HR2025doc 42025Analog Output 2 DehumidificationApp Profile only. Needs humidity sensor.UINT16Read/write0 = No; 1 = Yes
HR2026doc 42026Analog Output 2 HumidificationApp Profile only. Needs humidity sensor.UINT16Read/write0 = No; 1 = Yes
HR2027doc 42027Analog Output 2 VOCApp Profile only. Needs VOC sensor.UINT16Read/write0 = No; 1 = Yes
HR2028doc 42028Analog Output 2 CO2App Profile only. Needs CO2 sensor.UINT16Read/write0 = No; 1 = Yes
HR2029doc 42029Analog Output 2 FanApp Profile only.UINT16Read/write0 = No; 1 = Yes
HR2030doc 42030Binary Output 1 DemandUINT16× 0.1%Read
HR2031doc 42031Binary Output 1 (Relay State)UINT16Read0 = Off; 1 = Set; 2 = Reset
HR2032doc 42032Binary Output 1 Control ModeUINT16Read/write0 = Highest; 1 = Average
HR2033doc 42033Binary Output 1 TypeUINT16Read/write0 = Normally Closed; 1 = Normally Open
HR2034doc 42034Binary Output 1 SignalUINT16Read/write0 = Time Proportional Modulation (TPM); 1 = Hysteresis Mode
HR2035doc 42035Binary Output 1 CPH (Cycles per hour)UINT16Read/write0 = 8 CPH (1 cycle = 7.5 minutes); 1 = 4 CPH (1 cycle = 15 minutes); 2 = 3 CPH (1 cycle = 20 minutes)
HR2036doc 42036Binary Output 1 Anti-cycle delay in secondsUINT16sRead/write
HR2037doc 42037Binary Output 1 Hysteresis Low percentUINT16× 0.1%Read/write
HR2038doc 42038Binary Output 1 Hysteresis High percentUINT16× 0.1%Read/write
HR2039doc 42039Binary Output 1 CoolingUINT16Read/write0 = No; 1 = Yes
HR2040doc 42040Binary Output 1 heatingUINT16Read/write0 = No; 1 = Yes
HR2041doc 42041Binary Output 1 DehumidificationNeeds humidity sensor.UINT16Read/write0 = No; 1 = Yes
HR2042doc 42042Binary Output 1 HumidificationNeeds humidity sensor.UINT16Read/write0 = No; 1 = Yes
HR2043doc 42043Binary Output 1 VOCNeeds VOC sensor.UINT16Read/write0 = No; 1 = Yes
HR2044doc 42044Binary Output 1 CO2Needs CO2 sensor.UINT16Read/write0 = No; 1 = Yes
HR2045doc 42045Binary Output 1 FanUINT16Read/write0 = No; 1 = Yes
HR2046doc 42046Binary Output 2 DemandApp Profile only.UINT16× 0.1%Read
HR2047doc 42047Binary Output 2 (Relay State)App Profile only.UINT16Read0 = Off; 1 = Set; 2 = Reset
HR2048doc 42048Binary Output 2 Control ModeApp Profile only.UINT16Read/write0 = Highest; 1 = Average
HR2049doc 42049Binary Output 2 TypeApp Profile only.UINT16Read/write0 = Normally Closed; 1 = Normally Open
HR2050doc 42050Binary Output 2 SignalApp Profile only.UINT16Read/write0 = Time Proportional Modulation (TPM); 1 = Hysteresis Mode
HR2051doc 42051Binary Output 2 CPH (Cycles per hour)App Profile only.UINT16Read/write0 = 8 CPH (1 cycle = 7.5 minutes); 1 = 4 CPH (1 cycle = 15 minutes); 2 = 3 CPH (1 cycle = 20 minutes)
HR2052doc 42052Binary Output 2 Anti-cycle delay in secondsApp Profile only.UINT16sRead/write
HR2053doc 42053Binary Output 2 Hysteresis Low percentApp Profile only.UINT16× 0.1%Read/write
HR2054doc 42054Binary Output 2 Hysteresis High percentApp Profile only.UINT16× 0.1%Read/write
HR2055doc 42055Binary Output 2 CoolingApp Profile only.UINT16Read/write0 = No; 1 = Yes
HR2056doc 42056Binary Output 2 heatingApp Profile only.UINT16Read/write0 = No; 1 = Yes
HR2057doc 42057Binary Output 2 DehumidificationNeeds humidity sensor.UINT16Read/write0 = No; 1 = Yes
HR2058doc 42058Binary Output 2 HumidificationApp Profile only. Needs humidity sensor.UINT16Read/write0 = No; 1 = Yes
HR2059doc 42059Binary Output 2 VOCApp Profile only. Needs VOC sensor.UINT16Read/write0 = No; 1 = Yes
HR2060doc 42060Binary Output 2 CO2App Profile only. Needs CO2 sensor.UINT16Read/write0 = No; 1 = Yes
HR2061doc 42061Binary Output 2 FanApp Profile only.UINT16Read/write0 = No; 1 = Yes
HR2062doc 42062AO1 OAT (Outside Air Temperature) High lockoutINT16× 0.1°C / °FRead/write
HR2063doc 42063AO1 OAT (Outside Air Temperature) Low lockoutINT16× 0.1°C / °FRead/write
HR2064doc 42064AO1 OAT (Outside Air Temperature) LockUINT16Read0 = No; 1 = Yes
HR2065doc 42065AO2 OAT (Outside Air Temperature) High lockoutApp Profile only.INT16× 0.1°C / °FRead/write
HR2066doc 42066AO2 OAT (Outside Air Temperature) Low lockoutApp Profile only.INT16× 0.1°C / °FRead/write
HR2067doc 42067AO2 OAT (Outside Air Temperature) LockApp Profile only.UINT16Read0 = No; 1 = Yes
HR2068doc 42068BO1 OAT (Outside Air Temperature) High lockoutINT16× 0.1°C / °FRead/write
HR2069doc 42069BO1 OAT (Outside Air Temperature) Low lockoutINT16× 0.1°C / °FRead/write
HR2070doc 42070BO1 OAT (Outside Air Temperature) LockUINT16Read0 = No; 1 = Yes
HR2071doc 42071BO2 OAT (Outside Air Temperature) High level lockoutApp Profile only.INT16× 0.1°C / °FRead/write
HR2072doc 42072BO2 OAT (Outside Air Temperature) Low level lockoutApp Profile only.INT16× 0.1°C / °FRead/write
HR2073doc 42073BO2 OAT (Outside Air Temperature) LockApp Profile only.UINT16Read0 = No; 1 = Yes
HR2074doc 42074Cooling DemandUINT16× 0.1%Read
HR2075doc 42075Cooling SetpointUINT16× 0.1°C / °FRead/write
HR2076doc 42076Minimum Cooling SetpointUINT16× 0.1°C / °FRead/write
HR2077doc 42077Maximum Cooling SetpointUINT16× 0.1°C / °FRead/write
HR2078doc 42078Cooling Proportional BandUINT16× 0.1°C / °FRead/write
HR2079doc 42079Cooling Integral Time in secondsUINT16sRead/write
HR2080doc 42080Cooling Unoccupied SetpointUINT16× 0.1°C / °FRead/write
HR2081doc 42081Minimum Cooling Unoccupied SetpointUINT16× 0.1°C / °FRead/write
HR2082doc 42082Maximum Cooling Unoccupied SetpointUINT16× 0.1°C / °FRead/write
HR2083doc 42083Heating DemandUINT16× 0.1%Read
HR2084doc 42084Heating SetpointUINT16× 0.1°C / °FRead/write
HR2085doc 42085Minimum Heating SetpointUINT16× 0.1°C / °FRead/write
HR2086doc 42086Maximum Heating SetpointUINT16× 0.1°C / °FRead/write
HR2087doc 42087Heating Proportional BandUINT16× 0.1°C / °FRead/write
HR2088doc 42088Heating Integral Time in secondsUINT16sRead/write
HR2089doc 42089Heating Unoccupied SetpointUINT16× 0.1°C / °FRead/write
HR2090doc 42090Minimum Heating Unoccupied SetpointUINT16× 0.1°C / °FRead/write
HR2091doc 42091Maximum Heating Unoccupied SetpointUINT16× 0.1°C / °FRead/write
HR2092doc 42092Dehumidification DemandNeeds humidity sensor.UINT16× 0.1%Read
HR2093doc 42093Dehumidification SetpointNeeds humidity sensor.UINT16× 0.1%RHRead/write
HR2094doc 42094Minimum Dehumidification SetpointNeeds humidity sensor.UINT16× 0.1%RHRead/write
HR2095doc 42095Maximum Dehumidification SetpointNeeds humidity sensor.UINT16× 0.1%RHRead/write
HR2096doc 42096Humidity Proportional BandNeeds humidity sensor.UINT16× 0.1%RHRead/write
HR2097doc 42097Humidity Integral Time in secondsNeeds humidity sensor.UINT16sRead/write
HR2098doc 42098Humidification DemandNeeds humidity sensor.UINT16× 0.1%Read
HR2099doc 42099Humidification SetpointNeeds humidity sensor.UINT16× 0.1%RHRead/write
HR2100doc 42100Minimum Humidification SetpointNeeds humidity sensor.UINT16× 0.1%RHRead/write
HR2101doc 42101Maximum Humidification SetpointNeeds humidity sensor.UINT16× 0.1%RHRead/write
HR2102doc 42102CO2 DemandNeeds CO2 sensor.UINT16× 0.1%Read
HR2103doc 42103CO2 SetpointNeeds CO2 sensor.UINT16ppmRead/write
HR2104doc 42104Minimum CO2 SetpointNeeds CO2 sensor.UINT16ppmRead/write
HR2105doc 42105Maximum CO2 SetpointNeeds CO2 sensor.UINT16ppmRead/write
HR2106doc 42106CO2 Proportional BandNeeds CO2 sensor.UINT16ppmRead/write
HR2107doc 42107CO2 Integral Time in secondsNeeds CO2 sensor.UINT16sRead/write
HR2108doc 42108VOC DemandNeeds VOC sensor.UINT16× 0.1%Read
HR2109doc 42109VOC SetpointNeeds VOC sensor.UINT16ppbRead/write
HR2110doc 42110Minimum VOC SetpointNeeds VOC sensor.UINT16ppbRead/write
HR2111doc 42111Maximum VOC SetpointNeeds VOC sensor.UINT16ppbRead/write
HR2112doc 42112VOC Proportional BandNeeds VOC sensor.UINT16ppbRead/write
HR2113doc 42113VOC Integral Time in secondsNeeds VOC sensor.UINT16sRead/write
HR2114doc 42114Temperature Setpoint DeadbandUINT16× 0.1°C / °FRead/write
HR2115doc 42115Humidity Setpoint DeadbandNeeds humidity sensor.UINT16× 0.1%RHRead/write
HR2116doc 42116Main system modeUINT16Read/write0 = Off; 1 = On
HR2117doc 42117Temperature system modeUINT16Read/write0 = Off; 1 = Cool; 2 = Auto; 3 = Heat
HR2118doc 42118Humidity system modeNeeds humidity sensor.UINT16Read/write0 = Off; 1 = Dehumidification; 2 = Auto; 3 = Humidification
HR2119doc 42119CO2 system modeNeeds CO2 sensor.UINT16Read/write0 = Off; 1 = On
HR2120doc 42120VOC system modeNeeds VOC sensor.UINT16Read/write0 = Off; 1 = On
HR2121doc 42121Fan system modeUINT16Read/write0 = Off; 1 = Auto; 2 = On
HR2122doc 42122Fan ON SpeedUINT16× 0.1%Read/write
HR2123doc 42123App ProfileOption 2 needs humidity and CO2 sensors.UINT16Read/write0 = No Profile; 1 = Temp Only; 2 = Temp, RH, and CO2
HR3000doc 43000Occupancy statusUINT16Read0 = No; 1 = Yes
HR3001doc 43001Dirty Filter statusApp Profile only.UINT16Read0 = No; 1 = Yes
HR3002doc 43002Airflow Switch statusApp Profile only.UINT16Read0 = No; 1 = Yes
HR3003doc 43003Airflow Lockout Protection statusApp Profile only.UINT16Read0 = No; 1 = Yes

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Neptronic AROB series universal room controller (Modbus communication module)

What Modbus registers does the Neptronic AROB series universal room controller (Modbus communication module) have?

This map lists 151 registers: 151 holding registers. 120 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Neptronic AROB series universal room controller (Modbus communication module) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are printed from 40000. The intro puts the device address at holding register index 0, auto baud at index 1 and the port settings at index 2, which are the rows printed 40000-40002, so the wire address is the printed number minus 40000 (42075 cooling setpoint = address 2075). Same layout as Neptronic's TUXB guide.

What are the minimum Modbus registers to integrate the Neptronic AROB series universal room controller (Modbus communication module)?

Start with HR 13 Temperature Level (Room temperature); HR 11 CO2 Level (CO2); HR 2116 Main system mode (Main system on/off); HR 2117 Temperature system mode (Temperature mode); HR 2075 Cooling Setpoint (Cooling setpoint); HR 2084 Heating Setpoint (Heating setpoint); HR 2074 Cooling Demand (Cooling demand); HR 2083 Heating Demand (Heating demand).

How do I enable Modbus control of the Neptronic AROB series universal room controller (Modbus communication module)?

Fit the Modbus communication module and set the address from the device menu or register 0.

Where is the official Neptronic AROB series universal room controller (Modbus communication module) Modbus documentation?

The source is AROB Series Universal Room Controller - Modbus Communication Module User Guide (ARO Modbus Guide_170824), revision 2017-08-24, published free by Neptronic at https://www.neptronic.com/Controls/IAQController/PDF/ARO%20Modbus%20Guide_170824.pdf.

More Neptronic Modbus register maps

Other hvac equipment register maps

All hvac equipment Modbus register maps →

Source: AROB Series Universal Room Controller - Modbus Communication Module User Guide · ARO Modbus Guide_170824 · rev. 2017-08-24. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.