  4. Entro-V heat recovery unit controller (Basic / Digital controller, Modbus RTU)

Air handler (heat recovery ventilation unit) · Modbus register map

Airflow Developments Entro-V heat recovery unit controller (Basic / Digital controller, Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

The Entro-V is a heat recovery ventilation unit whose control board acts as a Modbus RTU slave on RS-485. Only function 03 (read) and 06 (write single) are supported and every point is a single 16-bit register. The map covers on/off, fan speed stages and mode, temperatures and sensor values, output and input states, the set point and the alarm code.

This page lists 34 Modbus registers for the Airflow Developments Entro-V heat recovery unit controller (Basic / Digital controller, Modbus RTU) — 6 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Airflow Developments’s own free documentation (linked below) and checked against it.

Manufacturer
Airflow Developments
Model
Entro-V heat recovery unit controller (Basic / Digital controller, Modbus RTU)
Equipment type
Air handler (heat recovery ventilation unit)
Registers
34 (6 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8N1
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
Entro-V Basic Controller, Entro-V Digital Controller, 90001308, 90001299, DuplexVent Entro-V
Source document
Entro-V Controls - Basic Controller, Digital Controller and Other Control Options - User Manual · 80001022 Issue 1 · rev. 2020-08 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Airflow Developments Entro-V heat recovery unit controller (Basic / Digital controller, Modbus RTU)

Integration in brief

Wire RS-485 to the MODBUS connector on the control board, poll address 1 at 9600 8N1 with FC03, and use FC06 to write. Start/stop with ID 1, set fan stages with IDs 101/102 and the set point with ID 128; watch ID 2 for faults.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 1Unit on/offUINT16Unit on/offRead/write
HR 2Alarm codeUINT16Alarm codeRead
HR 101Fresh air fan speed stageUINT16Fresh air fan speed stageRead/write
HR 102Exhaust air fan speed stageUINT16Exhaust air fan speed stageRead/write
HR 22Supply air temperatureINT16Supply air temperatureRead
HR 20Outdoor air temperatureINT16Outdoor air temperatureRead
HR 21Return air temperatureINT16Return air temperatureRead
HR 128Set temperatureUINT16Set temperatureRead/write

Enable Modbus control & writes

Modbus is built into the control board. Slave address (ID 153), link speed (ID 154, 0 = 9600) and frame type (ID 155, 0 = N81 RTU) are service-level parameters in the full list.

Byte order & addressing

Network setup

Watch out for

Airflow Developments Entro-V heat recovery unit controller (Basic / Digital controller, Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

34 of 34 shown
Airflow Developments Entro-V heat recovery unit controller (Basic / Digital controller, Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0Version of programInstalled program version as MMYY.UINT16Read
HR1Unit on/offUINT16Read/write0 = Stop; 1 = Start
HR2Alarm codeActive fault number; 0 when running normally.UINT16Read0 = Normal operation; 1 = ERR 1 Fire alarm (FRE input); 2 = ERR 2 Electric heater failure (HTI); 3 = ERR 3 Fresh air fan failure; 4 = ERR 4 Exhaust air fan failure; 5 = ERR 5 Outdoor air temperature sensor failure (T_OA); 6 = ERR 6 Return air temperature sensor failure (T_RA); 7 = ERR 7 Panel temperature sensor failure (T_PA); 8 = ERR 8 Supply air temperature sensor failure (T_SA); 9 = ERR 9 Sensor-1 failure (SE1); 10 = ERR 10 Sensor-2 failure (SE2); 11 = ERR 11 Freon pressure failure (DXH/DXL); 12 = ERR 12 Filter dirty alarm (FIL); 13 = ERR 13 Clock malfunction; 14 = ERR 14 RF communication failure; 15 = ERR 15 Digital controller communication failure; 16 = ERR 16 Constant flow maximum limit failure
HR3Fresh air fan speedMeasured fan speed.UINT16rpmRead
HR4Exhaust air fan speedMeasured fan speed.UINT16rpmRead
HR5PWM value of fresh air fan0-100 %.UINT16%Read
HR6PWM value of exhaust air fan0-100 %.UINT16%Read
HR20Outdoor air temperatureSensor T_OA, -40 to 80 °C.INT16× 0.1°CRead
HR21Return air temperatureSensor T_RA, -40 to 80 °C.INT16× 0.1°CRead
HR22Supply air temperatureSensor T_SA, -40 to 80 °C.INT16× 0.1°CRead
HR23Panel temperatureController panel sensor T_PA, -40 to 80 °C; listed read/write.INT16× 0.1°CRead/write
HR24Sensor 1 valueInput voltage on SE1.UINT16× 0.01VRead
HR25Sensor 2 valueInput voltage on SE2.UINT16× 0.01VRead
HR26RF sensor 1 valueVoltage value of wireless sensor SR1.UINT16× 0.01VRead
HR27RF sensor 2 valueVoltage value of the second wireless sensor (table labels it SR1).UINT16× 0.01VRead
HR29Relative humidityProcessed humidity sensor reading.UINT16× 0.1%Read
HR30CO2 valueProcessed CO2 sensor reading; multiplier 0.1 as printed.UINT16× 0.1ppmRead
HR31Pressure valueProcessed pressure sensor reading.UINT16× 0.1hPaRead
HR60DO1 output [RUN]Run indication relay.UINT16Read0 = Closed; 1 = Run
HR61DO2 output [FLT]Fault indication relay.UINT16Read0 = Closed; 1 = Run
HR62LP0 output [BYP]Bypass output.UINT16Read0 = Closed; 1 = Run
HR63LP1 output [HT1]Electric heater stage 1.UINT16Read0 = Closed; 1 = Run
HR64LP2 output [HT2]Electric heater stage 2.UINT16Read0 = Closed; 1 = Run
HR65LP3 output [PH1]Electric preheater stage 1.UINT16Read0 = Closed; 1 = Run
HR66LP4 output [PH2]Electric preheater stage 2.UINT16Read0 = Closed; 1 = Run
HR80DI1 input [BST]Boost input.UINT16Read0 = Closed; 1 = Run
HR81DI2 input [BMS]External BMS on/off input.UINT16Read0 = Closed; 1 = Run
HR82DI3 input [FRE]Fire input.UINT16Read0 = Closed; 1 = Run
HR83DI4 input [HTI]Heater failure input.UINT16Read0 = Closed; 1 = Run
HR84DI5 input [FIL]Filter alarm input.UINT16Read0 = Closed; 1 = Run
HR100Mode selectionUINT16Read/write0 = Standard fan speed; 1 = VOD
HR101Fresh air fan speed stageUINT16Read/write0 = Low; 1 = Mid; 2 = High; 3 = Stop
HR102Exhaust air fan speed stageUINT16Read/write0 = Low; 1 = Mid; 2 = High; 3 = Stop
HR128Set temperatureTemperature set point, 18-28 °C, default 22.UINT16°CRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Airflow Developments Entro-V heat recovery unit controller (Basic / Digital controller, Modbus RTU)

What Modbus registers does the Airflow Developments Entro-V heat recovery unit controller (Basic / Digital controller, Modbus RTU) have?

This map lists 34 registers: 34 holding registers. 6 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Airflow Developments Entro-V heat recovery unit controller (Basic / Digital controller, Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The register list's ID column is the wire address. The manual's example frame reads the '2nd register' with register ID bytes 0x00 0x02, and the list starts at ID 0 (program version), so use the ID unchanged in the request.

What are the minimum Modbus registers to integrate the Airflow Developments Entro-V heat recovery unit controller (Basic / Digital controller, Modbus RTU)?

Start with HR 1 Unit on/off (Unit on/off); HR 2 Alarm code (Alarm code); HR 101 Fresh air fan speed stage (Fresh air fan speed stage); HR 102 Exhaust air fan speed stage (Exhaust air fan speed stage); HR 22 Supply air temperature (Supply air temperature); HR 20 Outdoor air temperature (Outdoor air temperature); HR 21 Return air temperature (Return air temperature); HR 128 Set temperature (Set temperature).

How do I enable Modbus control of the Airflow Developments Entro-V heat recovery unit controller (Basic / Digital controller, Modbus RTU)?

Modbus is built into the control board. Slave address (ID 153), link speed (ID 154, 0 = 9600) and frame type (ID 155, 0 = N81 RTU) are service-level parameters in the full list.

Where is the official Airflow Developments Entro-V heat recovery unit controller (Basic / Digital controller, Modbus RTU) Modbus documentation?

The source is Entro-V Controls - Basic Controller, Digital Controller and Other Control Options - User Manual (80001022 Issue 1), revision 2020-08. Airflow Developments doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.specifiedby.com/airflow/entro-v-basic-controller/airflow_entro-v-basic-controller_operations_1_entro-v20controls20user20manual.pdf. It may be an older revision, so check it against the live unit.

Other hvac equipment register maps

All hvac equipment Modbus register maps →

Source: Entro-V Controls - Basic Controller, Digital Controller and Other Control Options - User Manual · 80001022 Issue 1 · rev. 2020-08 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.