- Entro-V heat recovery unit controller (Basic / Digital controller, Modbus RTU)
Air handler (heat recovery ventilation unit) · Modbus register map
Airflow Developments Entro-V heat recovery unit controller (Basic / Digital controller, Modbus RTU) Modbus register map
Updated 17 November 2026
The Entro-V is a heat recovery ventilation unit whose control board acts as a Modbus RTU slave on RS-485. Only function 03 (read) and 06 (write single) are supported and every point is a single 16-bit register. The map covers on/off, fan speed stages and mode, temperatures and sensor values, output and input states, the set point and the alarm code.
This page lists 34 Modbus registers for the Airflow Developments Entro-V heat recovery unit controller (Basic / Digital controller, Modbus RTU) — 6 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Airflow Developments’s own free documentation (linked below) and checked against it.
- Manufacturer
- Airflow Developments
- Model
- Entro-V heat recovery unit controller (Basic / Digital controller, Modbus RTU)
- Equipment type
- Air handler (heat recovery ventilation unit)
- Registers
- 34 (6 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8N1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- Entro-V Basic Controller, Entro-V Digital Controller, 90001308, 90001299, DuplexVent Entro-V
Integration notes: Airflow Developments Entro-V heat recovery unit controller (Basic / Digital controller, Modbus RTU)
Wire RS-485 to the MODBUS connector on the control board, poll address 1 at 9600 8N1 with FC03, and use FC06 to write. Start/stop with ID 1, set fan stages with IDs 101/102 and the set point with ID 128; watch ID 2 for faults.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 1 | Unit on/off | UINT16 | Unit on/off | Read/write |
| HR 2 | Alarm code | UINT16 | Alarm code | Read |
| HR 101 | Fresh air fan speed stage | UINT16 | Fresh air fan speed stage | Read/write |
| HR 102 | Exhaust air fan speed stage | UINT16 | Exhaust air fan speed stage | Read/write |
| HR 22 | Supply air temperature | INT16 | Supply air temperature | Read |
| HR 20 | Outdoor air temperature | INT16 | Outdoor air temperature | Read |
| HR 21 | Return air temperature | INT16 | Return air temperature | Read |
| HR 128 | Set temperature | UINT16 | Set temperature | Read/write |
Enable Modbus control & writes
Modbus is built into the control board. Slave address (ID 153), link speed (ID 154, 0 = 9600) and frame type (ID 155, 0 = N81 RTU) are service-level parameters in the full list.
Byte order & addressing
- Only FC03 and FC06 are supported: no FC04, no FC16 multi-register writes.
- IDs are 0-based wire addresses.
- Fan speed stage values run 0 = Low, 1 = Mid, 2 = High, 3 = Stop.
Network setup
- Defaults: address 1, 9600 baud, no parity, 8 data bits, 1 stop bit.
- Fit a 120 ohm terminating resistor at each end of a long RS-485 line, as the manual advises.
- Avoid duplicate addresses when several units share the bus.
Watch out for
- The link to the digital controller panel uses its own Modbus address parameters (IDs 235/236), separate from the BMS slave address (ID 153).
Airflow Developments Entro-V heat recovery unit controller (Basic / Digital controller, Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0 | Version of program | Installed program version as MMYY. | UINT16 | Read | ||||
| HR | 1 | Unit on/off | UINT16 | Read/write | 0 = Stop; 1 = Start | ||||
| HR | 2 | Alarm code | Active fault number; 0 when running normally. | UINT16 | Read | 0 = Normal operation; 1 = ERR 1 Fire alarm (FRE input); 2 = ERR 2 Electric heater failure (HTI); 3 = ERR 3 Fresh air fan failure; 4 = ERR 4 Exhaust air fan failure; 5 = ERR 5 Outdoor air temperature sensor failure (T_OA); 6 = ERR 6 Return air temperature sensor failure (T_RA); 7 = ERR 7 Panel temperature sensor failure (T_PA); 8 = ERR 8 Supply air temperature sensor failure (T_SA); 9 = ERR 9 Sensor-1 failure (SE1); 10 = ERR 10 Sensor-2 failure (SE2); 11 = ERR 11 Freon pressure failure (DXH/DXL); 12 = ERR 12 Filter dirty alarm (FIL); 13 = ERR 13 Clock malfunction; 14 = ERR 14 RF communication failure; 15 = ERR 15 Digital controller communication failure; 16 = ERR 16 Constant flow maximum limit failure | |||
| HR | 3 | Fresh air fan speed | Measured fan speed. | UINT16 | rpm | Read | |||
| HR | 4 | Exhaust air fan speed | Measured fan speed. | UINT16 | rpm | Read | |||
| HR | 5 | PWM value of fresh air fan | 0-100 %. | UINT16 | % | Read | |||
| HR | 6 | PWM value of exhaust air fan | 0-100 %. | UINT16 | % | Read | |||
| HR | 20 | Outdoor air temperature | Sensor T_OA, -40 to 80 °C. | INT16 | × 0.1 | °C | Read | ||
| HR | 21 | Return air temperature | Sensor T_RA, -40 to 80 °C. | INT16 | × 0.1 | °C | Read | ||
| HR | 22 | Supply air temperature | Sensor T_SA, -40 to 80 °C. | INT16 | × 0.1 | °C | Read | ||
| HR | 23 | Panel temperature | Controller panel sensor T_PA, -40 to 80 °C; listed read/write. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 24 | Sensor 1 value | Input voltage on SE1. | UINT16 | × 0.01 | V | Read | ||
| HR | 25 | Sensor 2 value | Input voltage on SE2. | UINT16 | × 0.01 | V | Read | ||
| HR | 26 | RF sensor 1 value | Voltage value of wireless sensor SR1. | UINT16 | × 0.01 | V | Read | ||
| HR | 27 | RF sensor 2 value | Voltage value of the second wireless sensor (table labels it SR1). | UINT16 | × 0.01 | V | Read | ||
| HR | 29 | Relative humidity | Processed humidity sensor reading. | UINT16 | × 0.1 | % | Read | ||
| HR | 30 | CO2 value | Processed CO2 sensor reading; multiplier 0.1 as printed. | UINT16 | × 0.1 | ppm | Read | ||
| HR | 31 | Pressure value | Processed pressure sensor reading. | UINT16 | × 0.1 | hPa | Read | ||
| HR | 60 | DO1 output [RUN] | Run indication relay. | UINT16 | Read | 0 = Closed; 1 = Run | |||
| HR | 61 | DO2 output [FLT] | Fault indication relay. | UINT16 | Read | 0 = Closed; 1 = Run | |||
| HR | 62 | LP0 output [BYP] | Bypass output. | UINT16 | Read | 0 = Closed; 1 = Run | |||
| HR | 63 | LP1 output [HT1] | Electric heater stage 1. | UINT16 | Read | 0 = Closed; 1 = Run | |||
| HR | 64 | LP2 output [HT2] | Electric heater stage 2. | UINT16 | Read | 0 = Closed; 1 = Run | |||
| HR | 65 | LP3 output [PH1] | Electric preheater stage 1. | UINT16 | Read | 0 = Closed; 1 = Run | |||
| HR | 66 | LP4 output [PH2] | Electric preheater stage 2. | UINT16 | Read | 0 = Closed; 1 = Run | |||
| HR | 80 | DI1 input [BST] | Boost input. | UINT16 | Read | 0 = Closed; 1 = Run | |||
| HR | 81 | DI2 input [BMS] | External BMS on/off input. | UINT16 | Read | 0 = Closed; 1 = Run | |||
| HR | 82 | DI3 input [FRE] | Fire input. | UINT16 | Read | 0 = Closed; 1 = Run | |||
| HR | 83 | DI4 input [HTI] | Heater failure input. | UINT16 | Read | 0 = Closed; 1 = Run | |||
| HR | 84 | DI5 input [FIL] | Filter alarm input. | UINT16 | Read | 0 = Closed; 1 = Run | |||
| HR | 100 | Mode selection | UINT16 | Read/write | 0 = Standard fan speed; 1 = VOD | ||||
| HR | 101 | Fresh air fan speed stage | UINT16 | Read/write | 0 = Low; 1 = Mid; 2 = High; 3 = Stop | ||||
| HR | 102 | Exhaust air fan speed stage | UINT16 | Read/write | 0 = Low; 1 = Mid; 2 = High; 3 = Stop | ||||
| HR | 128 | Set temperature | Temperature set point, 18-28 °C, default 22. | UINT16 | °C | Read/write |
Notes on this map
- Airflow does not host this manual as a direct PDF on airflow.com that we could find; this copy sits in Airflow's product listing on the SpecifiedBy library and is the unaltered Airflow document (Airflow Developments Ltd footer).
- Registers listed here are those in section 9.4 'Modbus Register List' (the IDs flagged for Modbus in the full parameter list). The full list on pp. 28-32 has more IDs (service settings, I/O assignment, timers); they are not flagged as Modbus points and are left out.
- Temperatures have a -40 to 80 °C range with multiplier 0.1, so they are treated as signed 16-bit; the manual does not spell out the signed encoding.
- The CO2 register (30) is printed with multiplier 0.1 and unit ppm; check against a known reading before relying on it.
- Alarm code values come from the fault code list (Part III, p. 25).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Airflow Developments Entro-V heat recovery unit controller (Basic / Digital controller, Modbus RTU)
What Modbus registers does the Airflow Developments Entro-V heat recovery unit controller (Basic / Digital controller, Modbus RTU) have?
This map lists 34 registers: 34 holding registers. 6 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Airflow Developments Entro-V heat recovery unit controller (Basic / Digital controller, Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The register list's ID column is the wire address. The manual's example frame reads the '2nd register' with register ID bytes 0x00 0x02, and the list starts at ID 0 (program version), so use the ID unchanged in the request.
What are the minimum Modbus registers to integrate the Airflow Developments Entro-V heat recovery unit controller (Basic / Digital controller, Modbus RTU)?
Start with HR 1 Unit on/off (Unit on/off); HR 2 Alarm code (Alarm code); HR 101 Fresh air fan speed stage (Fresh air fan speed stage); HR 102 Exhaust air fan speed stage (Exhaust air fan speed stage); HR 22 Supply air temperature (Supply air temperature); HR 20 Outdoor air temperature (Outdoor air temperature); HR 21 Return air temperature (Return air temperature); HR 128 Set temperature (Set temperature).
How do I enable Modbus control of the Airflow Developments Entro-V heat recovery unit controller (Basic / Digital controller, Modbus RTU)?
Modbus is built into the control board. Slave address (ID 153), link speed (ID 154, 0 = 9600) and frame type (ID 155, 0 = N81 RTU) are service-level parameters in the full list.
Where is the official Airflow Developments Entro-V heat recovery unit controller (Basic / Digital controller, Modbus RTU) Modbus documentation?
The source is Entro-V Controls - Basic Controller, Digital Controller and Other Control Options - User Manual (80001022 Issue 1), revision 2020-08. Airflow Developments doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.specifiedby.com/airflow/entro-v-basic-controller/airflow_entro-v-basic-controller_operations_1_entro-v20controls20user20manual.pdf. It may be an older revision, so check it against the live unit.
Other hvac equipment register maps
- Air handler humidifier (evaporative)
Condair ME II evaporative humidifier / cooler (Integrated Controller, Modbus RTU/TCP)
Condair ME with the Integrated Controller, per addendum 2603326-G.
Also known as: Condair ME, Condair ME II, ME - Air handler (demand-controlled ventilation unit)
Duco DucoBox ventilation units / IQ unit (Modbus RTU, master node)
DucoBox Silent Connect, Focus, Energy (all variants) and ECO with the Communication Print option, and the Duco IQ unit (Modbus standard), per information sheet L8000009-B.
Also known as: DucoBox Silent Connect, DucoBox Focus, DucoBox Energy, DucoBox Energy Premium, DucoBox ECO, Duco IQ unit, L8000009 - Thermostat
Johnson Controls PENN TC3222 refrigeration temperature controller (Modbus RTU)
PENN TC3222 electronic refrigeration controller with built-in Modbus RTU, per the TC3 Modbus Protocol Reference Guide LIT-12013523 (2020-04-28).
Also known as: TC3222, TC3, PENN TC3, LIT-12013523 - Air handler (heat recovery ventilation unit)
Mitsubishi Electric MelcoBEMS MINI (A1M+ / A1M) gateway for Lossnay heat recovery ventilators (LGH and VL series)
Procon MelcoBEMS MINI A1M+ (manual v1.0.3, firmware 4.1.1) on Lossnay LGH-15..200RVX-E1, LGH-150..250RVXT-E1 and VL-250..500CZPVU-R/L-E; the older A1M (manual v1.1.11) prints the identical Lossnay table.
Also known as: A1M+ Lossnay, MelcoBEMS MINI Lossnay, Procon A1M+, Procon A1M, A1M, Lossnay LGH-RVX Modbus, LGH-15RVX-E1, LGH-200RVX-E1, LGH-150RVXT-E1, LGH-250RVXT-E1, VL-250CZPVU-R-E, VL-500CZPVU-L-E, Lossnay VL Vertical - Air handler humidifier (electric steam)
Neptronic SKE4 electric steam humidifier (Modbus communication module)
Neptronic SKE4 series electric steam humidifiers with the Modbus communication module, guide SKE4-Modbus Guide-240531 (V2.07).
Also known as: SKE4-E, SKE4-N, SKE4 Steam Humidifier, Neptronic SKE4 Modbus - Thermostat / temperature and process PID controller
Red Lion PAX2C temperature/process PID controller (Modbus RTU/ASCII)
PAX2C version 2.0 register table (LP0905F, 2017-02-27); the FlexCard (PX2FCA0/PX2FCA1) blocks of the same table are not included.
Also known as: PAX2CHZVR, PAX2C00000, PX2FCA0, PX2FCA1
All hvac equipment Modbus register maps →
Source: Entro-V Controls - Basic Controller, Digital Controller and Other Control Options - User Manual · 80001022 Issue 1 · rev. 2020-08 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.