Air handler evaporative cooler (adiabatic cooling / humidification) · Modbus register map
Neptronic SKVF evaporative cooler / humidifier (Modbus communication module) Modbus register map
Updated 19 November 2026
The Neptronic SKVF is an evaporative cooler that can run humidification or cooling control profiles. Its Modbus RTU module exposes holding registers only: signal voltages, room and supply RH and temperature readings, demand and output, humidity and cooling set points with PID terms, water supply, drain and drying settings, inputs and relays as 0/1 registers, and state, alarm, request and control-profile codes.
This page lists 143 Modbus registers for the Neptronic SKVF evaporative cooler / humidifier (Modbus communication module) — 95 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Neptronic’s own free documentation (linked below) and checked against it.
- Manufacturer
- Neptronic
- Model
- SKVF evaporative cooler / humidifier (Modbus communication module)
- Registers
- 143 (95 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 8N2
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- SKVF Evaporative Cooler, SKVF Series, Neptronic SKVF Modbus
Integration notes: Neptronic SKVF evaporative cooler / humidifier (Modbus communication module)
Read Room RH (6008), Room Temperature (6012), Power Output (6028), State (15009) and System Alarm (15010). For BAS control choose a network Control Profile (15016) and Control Demand Source (15027 = Network) and write Control Network Demand (6112).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 6008 | Room RH | UINT16 | Room RH | Read |
| HR 6012 | Room Temperature | INT16 | Room temperature | Read/write |
| HR 6028 | Power Output | UINT16 | Power output | Read |
| HR 6073 | Room RH Setpoint | UINT16 | Room RH set point | Read/write |
| HR 15009 | State | UINT16 | Unit state | Read |
| HR 15010 | System Alarm | UINT16 | System alarm | Read |
| HR 15016 | Control Profile | UINT16 | Control profile | Read/write |
| HR 6112 | Control Network Demand | UINT16 | Network demand | Read/write |
Enable Modbus control & writes
Fit the Modbus communication module, set the address in the device menu (or register 0) and choose the control profile (15016) and sources (15019-15028) if the BAS supplies readings or demand.
Communication loss & watchdog
A Network Timeout exists but it is printed as a two-register value without word order (6117-6118), so it is not listed; Network Control State (12000) flags a network fault.
Byte order & addressing
- All points, binary ones included, are holding registers (FC03/06/16 only).
- Default framing is no parity with 2 stop bits.
Network setup
- RS-485 two-wire, RTU; 9600-57600 baud or auto baud detection.
- Parity/stop bits via register 2 or the Modbus Comport Config menu item.
Watch out for
- Control Profile chooses humidification (Hum) or cooling (Cool) logic; network profiles need the matching network registers written.
Neptronic SKVF evaporative cooler / humidifier (Modbus communication module) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 0 / 400001 | Modbus Address and Product Type | High byte = product type (read only); low byte = Modbus address 1-247 (writable). | UINT16 | Read/write | ||||
| HR | 1doc 1 / 400002 | Device Baud Rate | Baud rate / 100 (e.g. 384 = 38400); 0 = auto-detect. | UINT16 | × 100 | baud | Read/write | 0 = Auto baud rate detection | |
| HR | 2doc 2 / 400003 | Modbus Slave Communication Port Configuration | UINT16 | Read/write | 0 = No parity, 2 stop bits; 1 = Even parity, 1 stop bit; 2 = Odd parity, 1 stop bit | ||||
| HR | 7doc 7 / 400008 | Product Actual Firmware Version (in Integer x100) | Firmware version x100 (e.g. 100 = 1.00). | UINT16 | × 0.01 | Read | |||
| HR | 8doc 8 / 400009 | Product Actual EEPROM Version (in Integer x100) | EEPROM version x100. | UINT16 | × 0.01 | Read | |||
| HR | 2000doc 2000 / 402001 | Control Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 2002doc 2002 / 402003 | Room RH Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 2003doc 2003 / 402004 | Room Temperature Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 2004doc 2004 / 402005 | Supply RH Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 2005doc 2005 / 402006 | Supply Temperature Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 2006doc 2006 / 402007 | ECM Fan Feedback | UINT16 | Hz | Read | ||||
| HR | 2007doc 2007 / 402008 | ECM Fan Feedback 2 | UINT16 | Hz | Read | ||||
| HR | 2008doc 2008 / 402009 | Float Switch Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 2009doc 2009 / 402010 | Board Temperature Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 2010doc 2010 / 402011 | Main Power Supply | UINT16 | × 0.1 | V | Read | |||
| HR | 4000doc 4000 / 404001 | Power Output Feedback Signal | UINT16 | × 0.001 | V | Read | |||
| HR | 6000doc 6000 / 406001 | Control Input | UINT16 | × 0.01 | % | Read/write | |||
| HR | 6001doc 6001 / 406002 | Control Min | UINT16 | × 0.01 | % | Read/write | |||
| HR | 6002doc 6002 / 406003 | Control Max | UINT16 | × 0.01 | % | Read/write | |||
| HR | 6003doc 6003 / 406004 | Control Bias | INT16 | × 0.01 | % | Read/write | |||
| HR | 6008doc 6008 / 406009 | Room RH | UINT16 | × 0.01 | %RH | Read | |||
| HR | 6009doc 6009 / 406010 | Room RH Min | UINT16 | × 0.01 | %RH | Read/write | |||
| HR | 6010doc 6010 / 406011 | Room RH Max | UINT16 | × 0.01 | %RH | Read/write | |||
| HR | 6012doc 6012 / 406013 | Room Temperature | Room temperature reading; printed as writable. | INT16 | × 0.01 | °C / °F | Read/write | ||
| HR | 6013doc 6013 / 406014 | Room Temperature Min | INT16 | × 0.01 | °C / °F | Read/write | |||
| HR | 6014doc 6014 / 406015 | Room Temperature Max | INT16 | × 0.01 | °C / °F | Read/write | |||
| HR | 6015doc 6015 / 406016 | Room Temperature Bias | INT16 | × 0.01 | °C / °F | Read/write | |||
| HR | 6016doc 6016 / 406017 | Supply High Limit RH | UINT16 | × 0.01 | %RH | Read | |||
| HR | 6017doc 6017 / 406018 | Supply High Limit RH Min | UINT16 | × 0.01 | %RH | Read/write | |||
| HR | 6018doc 6018 / 406019 | Supply High Limit RH Max | UINT16 | × 0.01 | %RH | Read/write | |||
| HR | 6019doc 6019 / 406020 | Supply High Limit RH Bias | INT16 | × 0.01 | % | Read/write | |||
| HR | 6020doc 6020 / 406021 | Supply High Limit Temperature | INT16 | × 0.01 | °C / °F | Read/write | |||
| HR | 6021doc 6021 / 406022 | Supply High Limit Temperature Min | INT16 | × 0.01 | °C / °F | Read/write | |||
| HR | 6022doc 6022 / 406023 | Supply High Limit Temperature Max | INT16 | × 0.01 | °C / °F | Read/write | |||
| HR | 6023doc 6023 / 406024 | Supply High Limit Temperature Bias | INT16 | × 0.01 | °C / °F | Read/write | |||
| HR | 6028doc 6028 / 406029 | Power Output | UINT16 | × 0.01 | % | Read | |||
| HR | 6045doc 6045 / 406046 | Dead Band | UINT16 | % | Read/write | ||||
| HR | 6046doc 6046 / 406047 | Minimum Production Output | UINT16 | % | Read/write | ||||
| HR | 6047doc 6047 / 406048 | Maximum Production Output | UINT16 | % | Read/write | ||||
| HR | 6048doc 6048 / 406049 | Fan On Delay | UINT16 | min | Read/write | ||||
| HR | 6049doc 6049 / 406050 | Dry Fan Speed | UINT16 | % | Read/write | ||||
| HR | 6050doc 6050 / 406051 | Service Interval | UINT16 | h | Read/write | ||||
| HR | 6051doc 6051 / 406052 | Dilution Ratio | UINT16 | % | Read/write | ||||
| HR | 6052doc 6052 / 406053 | Drain Interval | UINT16 | h | Read/write | ||||
| HR | 6053doc 6053 / 406054 | Fixed Drain Time | UINT16 | h | Read/write | ||||
| HR | 6054doc 6054 / 406055 | Line Rinse Time | UINT16 | s | Read/write | ||||
| HR | 6061doc 6061 / 406062 | Completely Dry Delay | UINT16 | h | Read/write | ||||
| HR | 6062doc 6062 / 406063 | Hour of Day Drying Cycle | UINT16 | h | Read/write | ||||
| HR | 6065doc 6065 / 406066 | HRL Temperature | INT16 | × 0.01 | °C / °F | Read | |||
| HR | 6066doc 6066 / 406067 | HRL Humidity | UINT16 | × 0.01 | %RH | Read | |||
| HR | 6067doc 6067 / 406068 | Board Temperature | UINT16 | × 0.01 | °C / °F | Read | |||
| HR | 6068doc 6068 / 406069 | Power Output Feedback Bias | UINT16 | × 0.001 | V | Read/write | |||
| HR | 6069doc 6069 / 406070 | Power Output Feedback Min | UINT16 | × 0.001 | V | Read/write | |||
| HR | 6070doc 6070 / 406071 | Power Output Feedback Max | UINT16 | × 0.001 | V | Read/write | |||
| HR | 6071doc 6071 / 406072 | Power Output Feedback | UINT16 | × 0.01 | % | Read | |||
| HR | 6072doc 6072 / 406073 | Room RH Network Reading | Room RH written by the BAS when Room RH Source = Network. | UINT16 | × 0.01 | %RH | Read/write | ||
| HR | 6073doc 6073 / 406074 | Room RH Setpoint | UINT16 | × 0.01 | %RH | Read/write | |||
| HR | 6074doc 6074 / 406075 | Room RH Unoccupied Setpoint | UINT16 | × 0.01 | %RH | Read/write | |||
| HR | 6075doc 6075 / 406076 | Room RH Vacant Setpoint | UINT16 | × 0.01 | %RH | Read/write | |||
| HR | 6076doc 6076 / 406077 | Room RH Demand Proportional Gain | UINT16 | × 0.1 | Read/write | ||||
| HR | 6077doc 6077 / 406078 | Room RH Demand Integral Time | UINT16 | × 0.1 | s | Read/write | |||
| HR | 6078doc 6078 / 406079 | Room RH Demand Derivative Time | UINT16 | × 0.1 | s | Read/write | |||
| HR | 6079doc 6079 / 406080 | Room RH Demand | UINT16 | × 0.01 | %RH | Read | |||
| HR | 6085doc 6085 / 406086 | Room Temperature Unoccupied Setpoint | UINT16 | × 0.01 | °C / °F | Read/write | |||
| HR | 6086doc 6086 / 406087 | Room Temperature Vacant Setpoint | UINT16 | × 0.01 | °C / °F | Read/write | |||
| HR | 6089doc 6089 / 406090 | Room Temperature Demand Integral Time | UINT16 | × 0.1 | s | Read/write | |||
| HR | 6090doc 6090 / 406091 | Room Temperature Demand Derivative Time | UINT16 | × 0.1 | s | Read/write | |||
| HR | 6091doc 6091 / 406092 | Room Temperature Demand | UINT16 | × 0.01 | % | Read | |||
| HR | 6092doc 6092 / 406093 | Room Temp Demand Proportional Band | UINT16 | × 0.1 | % | Read/write | |||
| HR | 6093doc 6093 / 406094 | RH Supply High Limit Network Reading | UINT16 | × 0.01 | %RH | Read/write | |||
| HR | 6094doc 6094 / 406095 | RH Supply High Limit Setpoint | UINT16 | × 0.01 | %RH | Read/write | |||
| HR | 6095doc 6095 / 406096 | RH Supply High Limit Unoccupied Setpoint | UINT16 | × 0.01 | %RH | Read/write | |||
| HR | 6096doc 6096 / 406097 | RH Supply High Limit Vacant Setpoint | UINT16 | × 0.01 | %RH | Read/write | |||
| HR | 6097doc 6097 / 406098 | RH Supply High Limit Proportional Gain | UINT16 | × 0.1 | Read/write | ||||
| HR | 6098doc 6098 / 406099 | RH Supply High Limit Integral Time | UINT16 | × 0.1 | s | Read/write | |||
| HR | 6099doc 6099 / 406100 | RH Supply High Limit Derivative Time | UINT16 | × 0.1 | s | Read/write | |||
| HR | 6100doc 6100 / 406101 | RH Supply High Limit Demand | UINT16 | × 0.01 | %RH | Read | |||
| HR | 6103doc 6103 / 406104 | Temp Supply High Limit Network Reading | INT16 | × 0.01 | °C / °F | Read/write | |||
| HR | 6104doc 6104 / 406105 | Temp Supply High Limit Setpoint | UINT16 | × 0.01 | °C / °F | Read/write | |||
| HR | 6105doc 6105 / 406106 | Temp Supply High Limit Unoccupied Setpoint | UINT16 | × 0.01 | °C / °F | Read/write | |||
| HR | 6106doc 6106 / 406107 | Temp Supply High Limit Vacant Setpoint | UINT16 | × 0.01 | °C / °F | Read/write | |||
| HR | 6107doc 6107 / 406108 | Temp Supply High Limit Proportional Gain | UINT16 | × 0.1 | Read/write | ||||
| HR | 6108doc 6108 / 406109 | Temp Supply High Limit Integral Time | UINT16 | × 0.1 | s | Read/write | |||
| HR | 6109doc 6109 / 406110 | Temp Supply High Limit Derivative Time | UINT16 | × 0.1 | s | Read/write | |||
| HR | 6110doc 6110 / 406111 | Temp Supply High Limit Demand | UINT16 | × 0.01 | % | Read | |||
| HR | 6112doc 6112 / 406113 | Control Network Demand | Demand written by the BAS when Control Demand Source = Network. | UINT16 | × 0.01 | % | Read/write | ||
| HR | 6113doc 6113 / 406114 | Control Network High Limit | UINT16 | × 0.01 | % | Read/write | |||
| HR | 6114doc 6114 / 406115 | User Demand | UINT16 | × 0.01 | % | Read | |||
| HR | 6119doc 6119 / 406120 | System Steam Capacity | UINT16 | × 0.1 | kg/h / lb/h | Read | |||
| HR | 10000doc 10000 / 410001 | Air Flow | UINT16 | Read | 0 = Closed; 1 = Open | ||||
| HR | 10001doc 10001 / 410002 | Supply High Limit | UINT16 | Read | 0 = Closed; 1 = Open | ||||
| HR | 10002doc 10002 / 410003 | Interlock | UINT16 | Read | 0 = Closed; 1 = Open | ||||
| HR | 10003doc 10003 / 410004 | Binary External Demand | UINT16 | Read | 0 = 0 %; 1 = 100 % | ||||
| HR | 10004doc 10004 / 410005 | Water Leak Detection | UINT16 | Read | 0 = Ok; 1 = Leak | ||||
| HR | 10005doc 10005 / 410006 | RS485 Interface | UINT16 | Read | 0 = No; 1 = Yes | ||||
| HR | 10006doc 10006 / 410007 | Ethernet Interface | UINT16 | Read | 0 = No; 1 = Yes | ||||
| HR | 10007doc 10007 / 410008 | Relay Fuse | UINT16 | Read | 0 = Normal; 1 = Blown Fuse | ||||
| HR | 10008doc 10008 / 410009 | Control PCB Fuse | UINT16 | Read | 0 = Normal; 1 = Open Fuse | ||||
| HR | 11000doc 11000 / 411001 | Alarm Warning Relay | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11001doc 11001 / 411002 | Service Warning Relay | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11002doc 11002 / 411003 | Water Supply Valve | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11003doc 11003 / 411004 | Drain Valve | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11004doc 11004 / 411005 | Circulation Pump | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 11007doc 11007 / 411008 | Buzzer | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 12000doc 12000 / 412001 | Network Control State | UINT16 | Read/write | 0 = Normal; 1 = Fault | ||||
| HR | 12001doc 12001 / 412002 | Float Switch | UINT16 | Read | 0 = Inactive; 1 = Active | ||||
| HR | 12002doc 12002 / 412003 | Water Treatment Service Due | UINT16 | Read | 0 = No; 1 = Yes | ||||
| HR | 12003doc 12003 / 412004 | Service Due | UINT16 | Read/write | 0 = Not Allowed; 1 = Allowed | ||||
| HR | 12004doc 12004 / 412005 | Run While Water Service Alarm | UINT16 | Read/write | 0 = Not Allowed; 1 = Allowed | ||||
| HR | 12005doc 12005 / 412006 | Startup Line Rinse | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 12006doc 12006 / 412007 | Run While Service Alarm | UINT16 | Read/write | 0 = Not Allowed; 1 = Allowed | ||||
| HR | 12007doc 12007 / 412008 | HRL Lock Setpoint | UINT16 | Read/write | 0 = Unlock; 1 = Lock | ||||
| HR | 12008doc 12008 / 412009 | Notify Alarm | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 12009doc 12009 / 412010 | Notify Warning | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 12010doc 12010 / 412011 | Notify App Msg | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 15000doc 15000 / 415001 | System Power State | Cooler on/off state (printed read-only). | UINT16 | Read | 0 = Off; 1 = On | |||
| HR | 15001doc 15001 / 415002 | System Log Verbose Level | UINT16 | Read/write | 0 = None; 1 = Emergency; 2 = Alert; 3 = Critical; 4 = Error; 5 = Warning; 6 = Notice; 7 = Info; 8 = Debug | ||||
| HR | 15002doc 15002 / 415003 | Modbus Server Units | UINT16 | Read/write | 0 = Metric; 1 = Imperial | ||||
| HR | 15005doc 15005 / 415006 | Room RH Signal Type | UINT16 | Read/write | 0 = 0-10Vdc; 1 = 2-10Vdc; 2 = 4-20mA; 3 = 0-20mA | ||||
| HR | 15006doc 15006 / 415007 | Room Temperature Signal Type | UINT16 | Read/write | 0 = 0-10Vdc; 1 = 2-10Vdc; 2 = 4-20mA; 3 = 0-20mA | ||||
| HR | 15007doc 15007 / 415008 | Supply RH Signal Type | UINT16 | Read/write | 0 = 0-10Vdc; 1 = 2-10Vdc; 2 = 4-20mA; 3 = 0-20mA | ||||
| HR | 15008doc 15008 / 415009 | Supply Temperature Signal Type | UINT16 | Read/write | 0 = 0-10Vdc; 1 = 2-10Vdc; 2 = 4-20mA; 3 = 0-20mA | ||||
| HR | 15009doc 15009 / 415010 | State | UINT16 | Read | 0 = Off; 1 = Idle; 2 = LineRinse; 3 = Filling; 4 = Draining; 5 = Running; 6 = Alarm; 7 = Drying | ||||
| HR | 15010doc 15010 / 415011 | System Alarm | UINT16 | Read | 0 = Normal; 1 = DrainTimeout; 2 = FillTimeout; 3 = WaterLeak; 4 = FanDefect | ||||
| HR | 15011doc 15011 / 415012 | Recirculation Request | UINT16 | Read/write | 0 = None; 1 = ResetAlarms; 2 = Drain; 3 = ResetServCnt; 4 = ResetWtrServCnt; 5 = Filling | ||||
| HR | 15012doc 15012 / 415013 | DirectFeed Request | UINT16 | Read/write | 0 = None; 1 = ResetAlarms; 3 = ResetServCnt; 4 = ResetWtrServCnt | ||||
| HR | 15013doc 15013 / 415014 | Fan Request | UINT16 | Read/write | 0 = Off; 1 = Default; 2 = On | ||||
| HR | 15014doc 15014 / 415015 | Pump Request | UINT16 | Read/write | 0 = Off; 1 = Default; 2 = On | ||||
| HR | 15015doc 15015 / 415016 | Water Supply Request | UINT16 | Read/write | 0 = Off; 1 = Default; 2 = On | ||||
| HR | 15016doc 15016 / 415017 | Control Profile | UINT16 | Read/write | 0 = ExternAnalog; 1 = ExternNetwork; 2 = InternHumAnalog; 3 = InternHumNetwork; 4 = InternCoolAnalog; 5 = InternCoolNetwork; 6 = HRLHum; 7 = HRLCool; 8 = Custom | ||||
| HR | 15017doc 15017 / 415018 | Modulating High Limit Profile | UINT16 | Read/write | 0 = Disabled; 1 = ExternAnalog; 2 = ExternNetwork; 3 = InternHumAnalog; 4 = InternHumNetwork; 5 = InternCoolAnalog; 6 = InternCoolNetwork; 7 = Custom | ||||
| HR | 15018doc 15018 / 415019 | Occupancy State | UINT16 | Read | 0 = Occupied; 1 = Unoccupied; 2 = Vacant; 3 = Off | ||||
| HR | 15019doc 15019 / 415020 | Room RH Source | UINT16 | Read/write | 0 = None; 1 = RoomRH; 2 = Network; 3 = HRL | ||||
| HR | 15020doc 15020 / 415021 | Room RH Setpoint Source | UINT16 | Read/write | 0 = None; 1 = Internal; 2 = ControlInput | ||||
| HR | 15021doc 15021 / 415022 | Room Temperature Source | UINT16 | Read/write | 0 = None; 1 = RoomTemp; 2 = Network; 3 = HRL | ||||
| HR | 15022doc 15022 / 415023 | Room Temperature Setpoint Source | UINT16 | Read/write | 0 = None; 1 = Internal; 2 = ControlInput | ||||
| HR | 15023doc 15023 / 415024 | RH Supply High Limit Reading Source | UINT16 | Read/write | 0 = None; 1 = SuppyHLRH; 2 = Network | ||||
| HR | 15024doc 15024 / 415025 | RH Supply High Limit Setpoint Source | UINT16 | Read/write | 0 = None; 1 = Internal; 2 = ControlInput | ||||
| HR | 15025doc 15025 / 415026 | Temp Supply High Limit Reading Source | UINT16 | Read/write | 0 = None; 1 = SuppyHLTemp; 2 = Network | ||||
| HR | 15026doc 15026 / 415027 | Temp Supply High Limit Setpoint Source | UINT16 | Read/write | 0 = None; 1 = Internal; 2 = ControlInput | ||||
| HR | 15027doc 15027 / 415028 | Control Demand Source | UINT16 | Read/write | 0 = None; 1 = ControlInput; 2 = RoomDemand; 3 = Network | ||||
| HR | 15028doc 15028 / 415029 | Control High Limit Source | UINT16 | Read/write | 0 = None; 1 = ControlInput; 2 = RHSupplyHLDemand; 3 = Network; 4 = TempSupplyHLDemand | ||||
| HR | 15029doc 15029 / 415030 | Control Cutout State | UINT16 | Read | 0 = Off; 1 = Normal; 2 = LowLimit; 3 = HighLimit; 4 = NoAirFlow; 5 = Interlock |
Notes on this map
- Only function codes 03, 06 and 16 are supported, so binary points (inputs, relays, flags) are 16-bit holding registers holding 0 or 1.
- 'Scale N' with 'Value x N' means the raw value is the engineering value times N; this map stores the multiplier 1/N.
- Temperature and capacity units follow Modbus Server Units (415001): 0 metric, 1 imperial.
- The guide text calls automatic baud detection the default, while register 1 lists 19200 as its default value; the baud default is left blank here.
- Default unit address is not stated; it is set from the device menu or register 0.
- Left out: product name ASCII registers 3-6; 2001 (a second 'Control Signal' row) and 15003/15004 (two rows both named 'Control Signal Type'), where it is unclear which is which; ECM Fan Signal 4001, RH and temperature Supply High Limit Proportional Band 6101/6111 (scale and example disagree); the temperature-control block 6004-6007 (names repeat Control Input/Min/Max/Bias and the example is in %); Room RH Bias 6011 and Room Temperature Network Reading 6082 (typed unsigned with negative ranges); Alarm LED / Power LED 11005/11006 (holding numbers 411004/411005 clash with the protocol column).
- Several values are printed as two- or four-register entries marked (0)...(3) - Demand, run/on/service time counters, Room Temperature Setpoint, Room RH and Room Temperature Demand Proportional Band/Gain, Water Supply Duty Cycle/Period, Water Treatment Service Interval, Keep Alive, Demand Low Dead Band and Network Timeout. No word order is given, so they are left out.
- System Power State (15000) is printed read-only in this guide.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Neptronic SKVF evaporative cooler / humidifier (Modbus communication module)
What Modbus registers does the Neptronic SKVF evaporative cooler / humidifier (Modbus communication module) have?
This map lists 143 registers: 143 holding registers. 95 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Neptronic SKVF evaporative cooler / humidifier (Modbus communication module) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide prints a protocol-base (0-based) address and a six-digit holding register (base 400001) side by side, e.g. 6005 / 406006. The protocol-base number is the wire address.
What are the minimum Modbus registers to integrate the Neptronic SKVF evaporative cooler / humidifier (Modbus communication module)?
Start with HR 6008 Room RH (Room RH); HR 6012 Room Temperature (Room temperature); HR 6028 Power Output (Power output); HR 6073 Room RH Setpoint (Room RH set point); HR 15009 State (Unit state); HR 15010 System Alarm (System alarm); HR 15016 Control Profile (Control profile); HR 6112 Control Network Demand (Network demand).
How do I enable Modbus control of the Neptronic SKVF evaporative cooler / humidifier (Modbus communication module)?
Fit the Modbus communication module, set the address in the device menu (or register 0) and choose the control profile (15016) and sources (15019-15028) if the BAS supplies readings or demand.
What happens when the Neptronic SKVF evaporative cooler / humidifier (Modbus communication module) loses Modbus communication?
A Network Timeout exists but it is printed as a two-register value without word order (6117-6118), so it is not listed; Network Control State (12000) flags a network fault.
Where is the official Neptronic SKVF evaporative cooler / humidifier (Modbus communication module) Modbus documentation?
The source is SKVF Evaporative Cooler - Modbus Communication Module User Guide (SKVF-Modbus Guide-211025), revision 2021-10-25, published free by Neptronic at https://www.neptronic.com/humidifiers/pdf/SKVF/20211208/SKVF-Modbus%20Guide-211025.pdf.
More Neptronic Modbus register maps
- Thermostat / room controller (temperature, humidity, CO2, VOC)
Neptronic AROB series universal room controller (Modbus communication module)
Neptronic AROB24T / AROB24TH / AROB24TGH / AROB24TGVH universal room controllers with the Modbus module, ARO Modbus Guide_170824.
Also known as: AROB, AROB24T, AROB24TH, AROB24TGH, AROB24TGVH, ARO - Air handler (compact make-up air unit)
Neptronic CMU compact make-up air unit (Modbus communication module)
Neptronic CMU compact make-up air units with the Modbus communication module, guide CMU-Modbus Guide-211125.
Also known as: Compact Make-up Air Unit, Neptronic CMU, CMU Series - Thermostat / fan coil controller
Neptronic EFCB Series networkable fan coil controller (Modbus RTU)
Neptronic EFCB Series fan coil controllers (24, 120 and 240 Vac; 2 or 4 relays) with the Modbus communication module, guide EFCB-Modbus Guide-260626.
Also known as: EFCB10TU2, EFCB10TU4, EFCB11TU2, EFCB11TU4, EFCB12TU2, EFCB12TU4, EFCB fan coil controller - Thermostat / fan coil controller
Neptronic EFCB-OE1 Series networkable fan coil controller (Modbus RTU)
Neptronic EFCB-OE1 Series fan coil controllers (24 or 240 Vac; 0, 2 or 4 relays), guide EFCB1x-OE1-Modbus Guide (V2.16)-260626.
Also known as: EFCB10T-OE1, EFCB12T-OE1, EFCB10TU2-OE1, EFCB10TU4-OE1, EFCB12TU2-OE1, EFCB12TU4-OE1, EFCB1x-OE1 - Air handler terminal (dual-duct VAV controller)
Neptronic EVCBM dual-duct VAV controller (Modbus communication module)
Neptronic EVCBM dual-duct VAV controllers (master + slave airflow) with the Modbus module, guide EVCBM Dual Duct-V500-Modbus Guide-180927-ESA.
Also known as: EVCBM Dual Duct, EVCB, Neptronic EVCBM Modbus - Air handler humidifier (electric steam)
Neptronic SKE4 electric steam humidifier (Modbus communication module)
Neptronic SKE4 series electric steam humidifiers with the Modbus communication module, guide SKE4-Modbus Guide-240531 (V2.07).
Also known as: SKE4-E, SKE4-N, SKE4 Steam Humidifier, Neptronic SKE4 Modbus - Air handler humidifier (gas-fired steam)
Neptronic SKG4 gas-fired steam humidifier (Modbus communication module)
Neptronic SKG4 series gas-fired steam humidifiers (one to four burner modules) with the Modbus communication module, guide SKG4-Modbus Guide-221114 (V2.04).
Also known as: SKG4-E, SKG4-N, SKG4 Gas Fired Humidifier, Neptronic SKG4 Modbus - Air handler humidifier (high-pressure atomizer)
Neptronic SKH4 high-pressure atomizer humidifier (Modbus communication module)
Neptronic SKH4 high-pressure atomizers with the Modbus communication module, guide SKH4-Modbus Guide-240126 (V.1.00).
Also known as: SKH4, SKH4 High-Pressure Atomizer, Neptronic SKH4 Modbus - Pump / water treatment unit (reverse osmosis for humidifiers)
Neptronic SKRO reverse osmosis water treatment unit (Modbus communication module)
Neptronic SKRO reverse osmosis water treatment units with the Modbus communication module, guide SKRO-Modbus Guide-250913 (V1.0).
Also known as: SKRO, SKRO Water Treatment Unit, Neptronic SKRO Modbus - Air handler humidifier (steam-to-steam)
Neptronic SKS4 steam-to-steam humidifier (Modbus communication module)
Neptronic SKS4 series steam-to-steam humidifiers with the Modbus communication module, guide SKS4-Modbus Guide-220509 (V2.03).
Also known as: SKS4-E, SKS4-N, SKS4 Steam to Steam Humidifier, Neptronic SKS4 Modbus - Thermostat / fan coil and unitary controller
Neptronic TSUB Series universal wall-mount controller (Modbus RTU)
Neptronic TSUB Series universal wall-mount controllers with Modbus, guide TSUB-Modbus Guide-250829 (V1.13).
Also known as: TSUB Series, TSUB universal wall-mount controller - Thermostat / heat pump and unitary controller
Neptronic TUCB / TUHB Series universal wall-mount controller (Modbus RTU)
Neptronic TUCB24C6X2 (temperature) and TUHB24C6X2 (temperature and humidity) universal wall-mount controllers with 6 binary and 2 analog outputs, guide TUXB-Modbus Guide-190515.
Also known as: TUCB24C6X2, TUHB24C6X2, TUCB, TUHB, TUXB - Thermostat / heat pump and unitary controller
Neptronic TUUB Series universal wall-mount controller (Modbus RTU)
Neptronic TUUB Series universal wall-mount controllers with Modbus, guide TUUB-Modbus Guide-250829 (V1.13).
Also known as: TUUB Series, TUUB universal wall-mount controller
Other hvac equipment register maps
- Thermostat / room controller (chilled beam, fan coil water circuits)
Swegon CONDUCTOR W1 room controller (waterborne cooling/heating, Modbus RTU)
Swegon CONDUCTOR W1 room controller, software 1.38 and later (technical manual updated 2015-06-15).
Also known as: CONDUCTOR RE W1, Conductor W1, 942334001 - Air handler (residential heat recovery ventilation)
Vasco SAB RVU ventilation unit controller (D150 Compact, Energy Plus)
Vasco SAB RVU controller boards (models 0x52xx residential and 0x53xx Energy Plus) with protocol release 0x0006, manual 90.01.06.53.
Also known as: D150 Compact, Energy Plus ENY-P1, ENY-P2, ENY-P3, ENY-P4, ESP170V, ESP270, ESP360, ESP460 - Air handler (in-row data-centre cooling unit)
APC (Schneider Electric) InRow ACRD60x / ACRC60x cooling units (Modbus register map 990-5786)
APC / Schneider Electric InRow ACRD60x and ACRC60x in-row cooling units, register map part number 990-5786A.
Also known as: ACRD60x, ACRC60x, InRow ACRD60x, InRow ACRC60x, 990-5786 - Air handler humidifier (high-pressure room system)
Condair Vita high-pressure humidification system (Integrated Controller, Modbus RTU/TCP)
Condair Vita system with the Integrated Controller, per addendum 2603326-G.
Also known as: Condair Vita, Vita System Master - Rooftop unit / packaged wall-mount air conditioner
Eubank EAH / EGH wall-mount air conditioner control board (Modbus RTU)
Eubank EAH1020A-1060A, EGH1072A, EAH2024A-2060A and EGH2072A wall-mount air conditioners with the electronic control board (I&O manual rev. 7).
Also known as: EAH1020A, EAH1024A, EAH1030A, EAH1036A, EAH1042A, EAH1048A, EAH1060A, EGH1072A, EAH2024A, EAH2030A, EAH2036A, EAH2042A, EAH2048A, EAH2060A, EGH2072A, Eubank EAH, Eubank EGH - Thermostat
Johnson Controls PENN TC3224N9V refrigeration temperature controller (Modbus RTU)
PENN TC3224N9V electronic refrigeration controller with built-in Modbus RTU, per the TC3 Modbus Protocol Reference Guide LIT-12013523 (2020-04-28).
Also known as: TC3224N9V, TC3, PENN TC3, LIT-12013523, TC3224N9R, TC3224
All hvac equipment Modbus register maps →