Air handler evaporative cooler (adiabatic cooling / humidification) · Modbus register map

Neptronic SKVF evaporative cooler / humidifier (Modbus communication module) Modbus register map

Updated 19 November 2026

Short answer

The Neptronic SKVF is an evaporative cooler that can run humidification or cooling control profiles. Its Modbus RTU module exposes holding registers only: signal voltages, room and supply RH and temperature readings, demand and output, humidity and cooling set points with PID terms, water supply, drain and drying settings, inputs and relays as 0/1 registers, and state, alarm, request and control-profile codes.

This page lists 143 Modbus registers for the Neptronic SKVF evaporative cooler / humidifier (Modbus communication module) — 95 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Neptronic’s own free documentation (linked below) and checked against it.

Manufacturer
Neptronic
Model
SKVF evaporative cooler / humidifier (Modbus communication module)
Equipment type
Air handler evaporative cooler (adiabatic cooling / humidification)
Registers
143 (95 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
8N2
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
SKVF Evaporative Cooler, SKVF Series, Neptronic SKVF Modbus
Source document
SKVF Evaporative Cooler - Modbus Communication Module User Guide · SKVF-Modbus Guide-211025 · rev. 2021-10-25
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Neptronic SKVF evaporative cooler / humidifier (Modbus communication module)

Integration in brief

Read Room RH (6008), Room Temperature (6012), Power Output (6028), State (15009) and System Alarm (15010). For BAS control choose a network Control Profile (15016) and Control Demand Source (15027 = Network) and write Control Network Demand (6112).

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 6008Room RHUINT16Room RHRead
HR 6012Room TemperatureINT16Room temperatureRead/write
HR 6028Power OutputUINT16Power outputRead
HR 6073Room RH SetpointUINT16Room RH set pointRead/write
HR 15009StateUINT16Unit stateRead
HR 15010System AlarmUINT16System alarmRead
HR 15016Control ProfileUINT16Control profileRead/write
HR 6112Control Network DemandUINT16Network demandRead/write

Enable Modbus control & writes

Fit the Modbus communication module, set the address in the device menu (or register 0) and choose the control profile (15016) and sources (15019-15028) if the BAS supplies readings or demand.

Communication loss & watchdog

A Network Timeout exists but it is printed as a two-register value without word order (6117-6118), so it is not listed; Network Control State (12000) flags a network fault.

Byte order & addressing

Network setup

Watch out for

Neptronic SKVF evaporative cooler / humidifier (Modbus communication module) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

143 of 143 shown
Neptronic SKVF evaporative cooler / humidifier (Modbus communication module) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 0 / 400001Modbus Address and Product TypeHigh byte = product type (read only); low byte = Modbus address 1-247 (writable).UINT16Read/write
HR1doc 1 / 400002Device Baud RateBaud rate / 100 (e.g. 384 = 38400); 0 = auto-detect.UINT16× 100baudRead/write0 = Auto baud rate detection
HR2doc 2 / 400003Modbus Slave Communication Port ConfigurationUINT16Read/write0 = No parity, 2 stop bits; 1 = Even parity, 1 stop bit; 2 = Odd parity, 1 stop bit
HR7doc 7 / 400008Product Actual Firmware Version (in Integer x100)Firmware version x100 (e.g. 100 = 1.00).UINT16× 0.01Read
HR8doc 8 / 400009Product Actual EEPROM Version (in Integer x100)EEPROM version x100.UINT16× 0.01Read
HR2000doc 2000 / 402001Control SignalUINT16× 0.001VRead
HR2002doc 2002 / 402003Room RH SignalUINT16× 0.001VRead
HR2003doc 2003 / 402004Room Temperature SignalUINT16× 0.001VRead
HR2004doc 2004 / 402005Supply RH SignalUINT16× 0.001VRead
HR2005doc 2005 / 402006Supply Temperature SignalUINT16× 0.001VRead
HR2006doc 2006 / 402007ECM Fan FeedbackUINT16HzRead
HR2007doc 2007 / 402008ECM Fan Feedback 2UINT16HzRead
HR2008doc 2008 / 402009Float Switch SignalUINT16× 0.001VRead
HR2009doc 2009 / 402010Board Temperature SignalUINT16× 0.001VRead
HR2010doc 2010 / 402011Main Power SupplyUINT16× 0.1VRead
HR4000doc 4000 / 404001Power Output Feedback SignalUINT16× 0.001VRead
HR6000doc 6000 / 406001Control InputUINT16× 0.01%Read/write
HR6001doc 6001 / 406002Control MinUINT16× 0.01%Read/write
HR6002doc 6002 / 406003Control MaxUINT16× 0.01%Read/write
HR6003doc 6003 / 406004Control BiasINT16× 0.01%Read/write
HR6008doc 6008 / 406009Room RHUINT16× 0.01%RHRead
HR6009doc 6009 / 406010Room RH MinUINT16× 0.01%RHRead/write
HR6010doc 6010 / 406011Room RH MaxUINT16× 0.01%RHRead/write
HR6012doc 6012 / 406013Room TemperatureRoom temperature reading; printed as writable.INT16× 0.01°C / °FRead/write
HR6013doc 6013 / 406014Room Temperature MinINT16× 0.01°C / °FRead/write
HR6014doc 6014 / 406015Room Temperature MaxINT16× 0.01°C / °FRead/write
HR6015doc 6015 / 406016Room Temperature BiasINT16× 0.01°C / °FRead/write
HR6016doc 6016 / 406017Supply High Limit RHUINT16× 0.01%RHRead
HR6017doc 6017 / 406018Supply High Limit RH MinUINT16× 0.01%RHRead/write
HR6018doc 6018 / 406019Supply High Limit RH MaxUINT16× 0.01%RHRead/write
HR6019doc 6019 / 406020Supply High Limit RH BiasINT16× 0.01%Read/write
HR6020doc 6020 / 406021Supply High Limit TemperatureINT16× 0.01°C / °FRead/write
HR6021doc 6021 / 406022Supply High Limit Temperature MinINT16× 0.01°C / °FRead/write
HR6022doc 6022 / 406023Supply High Limit Temperature MaxINT16× 0.01°C / °FRead/write
HR6023doc 6023 / 406024Supply High Limit Temperature BiasINT16× 0.01°C / °FRead/write
HR6028doc 6028 / 406029Power OutputUINT16× 0.01%Read
HR6045doc 6045 / 406046Dead BandUINT16%Read/write
HR6046doc 6046 / 406047Minimum Production OutputUINT16%Read/write
HR6047doc 6047 / 406048Maximum Production OutputUINT16%Read/write
HR6048doc 6048 / 406049Fan On DelayUINT16minRead/write
HR6049doc 6049 / 406050Dry Fan SpeedUINT16%Read/write
HR6050doc 6050 / 406051Service IntervalUINT16hRead/write
HR6051doc 6051 / 406052Dilution RatioUINT16%Read/write
HR6052doc 6052 / 406053Drain IntervalUINT16hRead/write
HR6053doc 6053 / 406054Fixed Drain TimeUINT16hRead/write
HR6054doc 6054 / 406055Line Rinse TimeUINT16sRead/write
HR6061doc 6061 / 406062Completely Dry DelayUINT16hRead/write
HR6062doc 6062 / 406063Hour of Day Drying CycleUINT16hRead/write
HR6065doc 6065 / 406066HRL TemperatureINT16× 0.01°C / °FRead
HR6066doc 6066 / 406067HRL HumidityUINT16× 0.01%RHRead
HR6067doc 6067 / 406068Board TemperatureUINT16× 0.01°C / °FRead
HR6068doc 6068 / 406069Power Output Feedback BiasUINT16× 0.001VRead/write
HR6069doc 6069 / 406070Power Output Feedback MinUINT16× 0.001VRead/write
HR6070doc 6070 / 406071Power Output Feedback MaxUINT16× 0.001VRead/write
HR6071doc 6071 / 406072Power Output FeedbackUINT16× 0.01%Read
HR6072doc 6072 / 406073Room RH Network ReadingRoom RH written by the BAS when Room RH Source = Network.UINT16× 0.01%RHRead/write
HR6073doc 6073 / 406074Room RH SetpointUINT16× 0.01%RHRead/write
HR6074doc 6074 / 406075Room RH Unoccupied SetpointUINT16× 0.01%RHRead/write
HR6075doc 6075 / 406076Room RH Vacant SetpointUINT16× 0.01%RHRead/write
HR6076doc 6076 / 406077Room RH Demand Proportional GainUINT16× 0.1Read/write
HR6077doc 6077 / 406078Room RH Demand Integral TimeUINT16× 0.1sRead/write
HR6078doc 6078 / 406079Room RH Demand Derivative TimeUINT16× 0.1sRead/write
HR6079doc 6079 / 406080Room RH DemandUINT16× 0.01%RHRead
HR6085doc 6085 / 406086Room Temperature Unoccupied SetpointUINT16× 0.01°C / °FRead/write
HR6086doc 6086 / 406087Room Temperature Vacant SetpointUINT16× 0.01°C / °FRead/write
HR6089doc 6089 / 406090Room Temperature Demand Integral TimeUINT16× 0.1sRead/write
HR6090doc 6090 / 406091Room Temperature Demand Derivative TimeUINT16× 0.1sRead/write
HR6091doc 6091 / 406092Room Temperature DemandUINT16× 0.01%Read
HR6092doc 6092 / 406093Room Temp Demand Proportional BandUINT16× 0.1%Read/write
HR6093doc 6093 / 406094RH Supply High Limit Network ReadingUINT16× 0.01%RHRead/write
HR6094doc 6094 / 406095RH Supply High Limit SetpointUINT16× 0.01%RHRead/write
HR6095doc 6095 / 406096RH Supply High Limit Unoccupied SetpointUINT16× 0.01%RHRead/write
HR6096doc 6096 / 406097RH Supply High Limit Vacant SetpointUINT16× 0.01%RHRead/write
HR6097doc 6097 / 406098RH Supply High Limit Proportional GainUINT16× 0.1Read/write
HR6098doc 6098 / 406099RH Supply High Limit Integral TimeUINT16× 0.1sRead/write
HR6099doc 6099 / 406100RH Supply High Limit Derivative TimeUINT16× 0.1sRead/write
HR6100doc 6100 / 406101RH Supply High Limit DemandUINT16× 0.01%RHRead
HR6103doc 6103 / 406104Temp Supply High Limit Network ReadingINT16× 0.01°C / °FRead/write
HR6104doc 6104 / 406105Temp Supply High Limit SetpointUINT16× 0.01°C / °FRead/write
HR6105doc 6105 / 406106Temp Supply High Limit Unoccupied SetpointUINT16× 0.01°C / °FRead/write
HR6106doc 6106 / 406107Temp Supply High Limit Vacant SetpointUINT16× 0.01°C / °FRead/write
HR6107doc 6107 / 406108Temp Supply High Limit Proportional GainUINT16× 0.1Read/write
HR6108doc 6108 / 406109Temp Supply High Limit Integral TimeUINT16× 0.1sRead/write
HR6109doc 6109 / 406110Temp Supply High Limit Derivative TimeUINT16× 0.1sRead/write
HR6110doc 6110 / 406111Temp Supply High Limit DemandUINT16× 0.01%Read
HR6112doc 6112 / 406113Control Network DemandDemand written by the BAS when Control Demand Source = Network.UINT16× 0.01%Read/write
HR6113doc 6113 / 406114Control Network High LimitUINT16× 0.01%Read/write
HR6114doc 6114 / 406115User DemandUINT16× 0.01%Read
HR6119doc 6119 / 406120System Steam CapacityUINT16× 0.1kg/h / lb/hRead
HR10000doc 10000 / 410001Air FlowUINT16Read0 = Closed; 1 = Open
HR10001doc 10001 / 410002Supply High LimitUINT16Read0 = Closed; 1 = Open
HR10002doc 10002 / 410003InterlockUINT16Read0 = Closed; 1 = Open
HR10003doc 10003 / 410004Binary External DemandUINT16Read0 = 0 %; 1 = 100 %
HR10004doc 10004 / 410005Water Leak DetectionUINT16Read0 = Ok; 1 = Leak
HR10005doc 10005 / 410006RS485 InterfaceUINT16Read0 = No; 1 = Yes
HR10006doc 10006 / 410007Ethernet InterfaceUINT16Read0 = No; 1 = Yes
HR10007doc 10007 / 410008Relay FuseUINT16Read0 = Normal; 1 = Blown Fuse
HR10008doc 10008 / 410009Control PCB FuseUINT16Read0 = Normal; 1 = Open Fuse
HR11000doc 11000 / 411001Alarm Warning RelayUINT16Read0 = Off; 1 = On
HR11001doc 11001 / 411002Service Warning RelayUINT16Read0 = Off; 1 = On
HR11002doc 11002 / 411003Water Supply ValveUINT16Read0 = Off; 1 = On
HR11003doc 11003 / 411004Drain ValveUINT16Read0 = Off; 1 = On
HR11004doc 11004 / 411005Circulation PumpUINT16Read0 = Off; 1 = On
HR11007doc 11007 / 411008BuzzerUINT16Read0 = Off; 1 = On
HR12000doc 12000 / 412001Network Control StateUINT16Read/write0 = Normal; 1 = Fault
HR12001doc 12001 / 412002Float SwitchUINT16Read0 = Inactive; 1 = Active
HR12002doc 12002 / 412003Water Treatment Service DueUINT16Read0 = No; 1 = Yes
HR12003doc 12003 / 412004Service DueUINT16Read/write0 = Not Allowed; 1 = Allowed
HR12004doc 12004 / 412005Run While Water Service AlarmUINT16Read/write0 = Not Allowed; 1 = Allowed
HR12005doc 12005 / 412006Startup Line RinseUINT16Read/write0 = Off; 1 = On
HR12006doc 12006 / 412007Run While Service AlarmUINT16Read/write0 = Not Allowed; 1 = Allowed
HR12007doc 12007 / 412008HRL Lock SetpointUINT16Read/write0 = Unlock; 1 = Lock
HR12008doc 12008 / 412009Notify AlarmUINT16Read/write0 = Off; 1 = On
HR12009doc 12009 / 412010Notify WarningUINT16Read/write0 = Off; 1 = On
HR12010doc 12010 / 412011Notify App MsgUINT16Read/write0 = Off; 1 = On
HR15000doc 15000 / 415001System Power StateCooler on/off state (printed read-only).UINT16Read0 = Off; 1 = On
HR15001doc 15001 / 415002System Log Verbose LevelUINT16Read/write0 = None; 1 = Emergency; 2 = Alert; 3 = Critical; 4 = Error; 5 = Warning; 6 = Notice; 7 = Info; 8 = Debug
HR15002doc 15002 / 415003Modbus Server UnitsUINT16Read/write0 = Metric; 1 = Imperial
HR15005doc 15005 / 415006Room RH Signal TypeUINT16Read/write0 = 0-10Vdc; 1 = 2-10Vdc; 2 = 4-20mA; 3 = 0-20mA
HR15006doc 15006 / 415007Room Temperature Signal TypeUINT16Read/write0 = 0-10Vdc; 1 = 2-10Vdc; 2 = 4-20mA; 3 = 0-20mA
HR15007doc 15007 / 415008Supply RH Signal TypeUINT16Read/write0 = 0-10Vdc; 1 = 2-10Vdc; 2 = 4-20mA; 3 = 0-20mA
HR15008doc 15008 / 415009Supply Temperature Signal TypeUINT16Read/write0 = 0-10Vdc; 1 = 2-10Vdc; 2 = 4-20mA; 3 = 0-20mA
HR15009doc 15009 / 415010StateUINT16Read0 = Off; 1 = Idle; 2 = LineRinse; 3 = Filling; 4 = Draining; 5 = Running; 6 = Alarm; 7 = Drying
HR15010doc 15010 / 415011System AlarmUINT16Read0 = Normal; 1 = DrainTimeout; 2 = FillTimeout; 3 = WaterLeak; 4 = FanDefect
HR15011doc 15011 / 415012Recirculation RequestUINT16Read/write0 = None; 1 = ResetAlarms; 2 = Drain; 3 = ResetServCnt; 4 = ResetWtrServCnt; 5 = Filling
HR15012doc 15012 / 415013DirectFeed RequestUINT16Read/write0 = None; 1 = ResetAlarms; 3 = ResetServCnt; 4 = ResetWtrServCnt
HR15013doc 15013 / 415014Fan RequestUINT16Read/write0 = Off; 1 = Default; 2 = On
HR15014doc 15014 / 415015Pump RequestUINT16Read/write0 = Off; 1 = Default; 2 = On
HR15015doc 15015 / 415016Water Supply RequestUINT16Read/write0 = Off; 1 = Default; 2 = On
HR15016doc 15016 / 415017Control ProfileUINT16Read/write0 = ExternAnalog; 1 = ExternNetwork; 2 = InternHumAnalog; 3 = InternHumNetwork; 4 = InternCoolAnalog; 5 = InternCoolNetwork; 6 = HRLHum; 7 = HRLCool; 8 = Custom
HR15017doc 15017 / 415018Modulating High Limit ProfileUINT16Read/write0 = Disabled; 1 = ExternAnalog; 2 = ExternNetwork; 3 = InternHumAnalog; 4 = InternHumNetwork; 5 = InternCoolAnalog; 6 = InternCoolNetwork; 7 = Custom
HR15018doc 15018 / 415019Occupancy StateUINT16Read0 = Occupied; 1 = Unoccupied; 2 = Vacant; 3 = Off
HR15019doc 15019 / 415020Room RH SourceUINT16Read/write0 = None; 1 = RoomRH; 2 = Network; 3 = HRL
HR15020doc 15020 / 415021Room RH Setpoint SourceUINT16Read/write0 = None; 1 = Internal; 2 = ControlInput
HR15021doc 15021 / 415022Room Temperature SourceUINT16Read/write0 = None; 1 = RoomTemp; 2 = Network; 3 = HRL
HR15022doc 15022 / 415023Room Temperature Setpoint SourceUINT16Read/write0 = None; 1 = Internal; 2 = ControlInput
HR15023doc 15023 / 415024RH Supply High Limit Reading SourceUINT16Read/write0 = None; 1 = SuppyHLRH; 2 = Network
HR15024doc 15024 / 415025RH Supply High Limit Setpoint SourceUINT16Read/write0 = None; 1 = Internal; 2 = ControlInput
HR15025doc 15025 / 415026Temp Supply High Limit Reading SourceUINT16Read/write0 = None; 1 = SuppyHLTemp; 2 = Network
HR15026doc 15026 / 415027Temp Supply High Limit Setpoint SourceUINT16Read/write0 = None; 1 = Internal; 2 = ControlInput
HR15027doc 15027 / 415028Control Demand SourceUINT16Read/write0 = None; 1 = ControlInput; 2 = RoomDemand; 3 = Network
HR15028doc 15028 / 415029Control High Limit SourceUINT16Read/write0 = None; 1 = ControlInput; 2 = RHSupplyHLDemand; 3 = Network; 4 = TempSupplyHLDemand
HR15029doc 15029 / 415030Control Cutout StateUINT16Read0 = Off; 1 = Normal; 2 = LowLimit; 3 = HighLimit; 4 = NoAirFlow; 5 = Interlock

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Neptronic SKVF evaporative cooler / humidifier (Modbus communication module)

What Modbus registers does the Neptronic SKVF evaporative cooler / humidifier (Modbus communication module) have?

This map lists 143 registers: 143 holding registers. 95 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Neptronic SKVF evaporative cooler / humidifier (Modbus communication module) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide prints a protocol-base (0-based) address and a six-digit holding register (base 400001) side by side, e.g. 6005 / 406006. The protocol-base number is the wire address.

What are the minimum Modbus registers to integrate the Neptronic SKVF evaporative cooler / humidifier (Modbus communication module)?

Start with HR 6008 Room RH (Room RH); HR 6012 Room Temperature (Room temperature); HR 6028 Power Output (Power output); HR 6073 Room RH Setpoint (Room RH set point); HR 15009 State (Unit state); HR 15010 System Alarm (System alarm); HR 15016 Control Profile (Control profile); HR 6112 Control Network Demand (Network demand).

How do I enable Modbus control of the Neptronic SKVF evaporative cooler / humidifier (Modbus communication module)?

Fit the Modbus communication module, set the address in the device menu (or register 0) and choose the control profile (15016) and sources (15019-15028) if the BAS supplies readings or demand.

What happens when the Neptronic SKVF evaporative cooler / humidifier (Modbus communication module) loses Modbus communication?

A Network Timeout exists but it is printed as a two-register value without word order (6117-6118), so it is not listed; Network Control State (12000) flags a network fault.

Where is the official Neptronic SKVF evaporative cooler / humidifier (Modbus communication module) Modbus documentation?

The source is SKVF Evaporative Cooler - Modbus Communication Module User Guide (SKVF-Modbus Guide-211025), revision 2021-10-25, published free by Neptronic at https://www.neptronic.com/humidifiers/pdf/SKVF/20211208/SKVF-Modbus%20Guide-211025.pdf.

More Neptronic Modbus register maps

Other hvac equipment register maps

All hvac equipment Modbus register maps →

Source: SKVF Evaporative Cooler - Modbus Communication Module User Guide · SKVF-Modbus Guide-211025 · rev. 2021-10-25. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.