- CMU compact make-up air unit (Modbus communication module)
Air handler (compact make-up air unit) · Modbus register map
Neptronic CMU compact make-up air unit (Modbus communication module) Modbus register map
Updated 19 November 2026
The Neptronic CMU is a compact make-up air unit with an ECM fan, electric heater, damper, sensor inputs and an exhaust-fan output. Its Modbus RTU module exposes holding registers only: input voltages and temperatures, room temperature, RH, CO2, VOC and light from the TDF room sensor, supply and outdoor air readings, static pressure and airflow, set points and loop tuning, input/output configuration, occupancy and alarm flags.
This page lists 98 Modbus registers for the Neptronic CMU compact make-up air unit (Modbus communication module) — 60 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Neptronic’s own free documentation (linked below) and checked against it.
- Manufacturer
- Neptronic
- Model
- CMU compact make-up air unit (Modbus communication module)
- Equipment type
- Air handler (compact make-up air unit)
- Registers
- 98 (60 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- Compact Make-up Air Unit, Neptronic CMU, CMU Series
Integration notes: Neptronic CMU compact make-up air unit (Modbus communication module)
Read supply air temperature (23), duct static pressure (27), fan speed (30) and alarm status (104). Command occupancy with register 85 and set occupied / unoccupied airflow with 35 / 36.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 23 | Supply air temperature | UINT16 | Supply air temperature | Read |
| HR 27 | Duct static pressure | UINT16 | Duct static pressure | Read |
| HR 30 | CMU ECM fan speed feedback value | UINT16 | Fan speed feedback | Read |
| HR 31 | Heater vernier stage duty cycle | UINT16 | Heater duty cycle | Read |
| HR 85 | CMU occupancy state | UINT16 | Occupancy state | Read/write |
| HR 104 | Alarm status | BITMAP16 | Alarm status | Read |
| HR 35 | Occupied airflow setpoint in percent of maximum capacity | UINT16 | Occupied airflow set point | Read/write |
Enable Modbus control & writes
Fit the Modbus communication module and set the address in the device menu or register 0.
Communication loss & watchdog
Modbus timeout (67, 15-1800 s) and number of synchronisation timeouts (68) are provided; the guide does not describe the fallback action.
Byte order & addressing
- All points are holding registers (FC03/06/16).
- Auto baud detection is the default; 9600-76800 baud supported.
Network setup
- RS-485 two-wire, RTU mode.
Watch out for
- Input and output modes (87-99) change what the analog/binary I/O registers mean.
Neptronic CMU compact make-up air unit (Modbus communication module) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1doc 1 / 40002 | Analog input 1 voltage | UINT16 | × 0.001 | V | Read | |||
| HR | 2doc 2 / 40003 | Analog input 2 voltage | UINT16 | × 0.001 | V | Read | |||
| HR | 3doc 3 / 40004 | Analog input 3 temperature | INT16 | × 0.01 | °C / °F | Read | |||
| HR | 4doc 4 / 40005 | Analog input 4 temperature | INT16 | × 0.01 | °C / °F | Read | |||
| HR | 5doc 5 / 40006 | Room air temperature value measured by TDF | UINT16 | × 0.01 | °C / °F | Read | |||
| HR | 6doc 6 / 40007 | Room air relative humidity value measured by TDF | UINT16 | × 0.1 | %RH | Read | |||
| HR | 7doc 7 / 40008 | Room CO2 concentration value measured by TDF | UINT16 | ppm | Read | ||||
| HR | 8doc 8 / 40009 | Volatile organic compound index measured by TDF | UINT16 | Read | |||||
| HR | 9doc 9 / 40010 | Luminous flux measured by TDF | UINT16 | lx | Read | ||||
| HR | 10doc 10 / 40011 | CMU on-board potentiometer temperature setpoint | UINT16 | × 0.01 | °C / °F | Read | |||
| HR | 11doc 11 / 40012 | CMU intake temperature | INT16 | × 0.01 | °C / °F | Read | |||
| HR | 12doc 12 / 40013 | CMU outtake temperature | INT16 | × 0.01 | °C / °F | Read | |||
| HR | 13doc 13 / 40014 | CMU board temperature | INT16 | × 0.01 | °C / °F | Read | |||
| HR | 14doc 14 / 40015 | CMU SSR temperature | INT16 | × 0.01 | °C / °F | Read | |||
| HR | 15doc 15 / 40016 | AI3/BI3 multi-mode input state | UINT16 | Read | 0 = Open; 1 = Closed | ||||
| HR | 16doc 16 / 40017 | AI4/BI4 multi-mode input state | UINT16 | Read | 0 = Open; 1 = Closed | ||||
| HR | 17doc 17 / 40018 | Room movement detection occupancy sensor | UINT16 | Read | 0 = No; 1 = Yes | ||||
| HR | 18doc 18 / 40019 | CMU On/Off contact input state | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 19doc 19 / 40020 | Analog output 1 voltage | UINT16 | × 0.01 | V | Read | |||
| HR | 20doc 20 / 40021 | Analog output 2 voltage | UINT16 | × 0.01 | V | Read | |||
| HR | 21doc 21 / 40022 | Binary output 1 state | UINT16 | Read | 0 = Open; 1 = Closed | ||||
| HR | 22doc 22 / 40023 | Binary output 1 state | UINT16 | Read | 0 = Open; 1 = Closed | ||||
| HR | 23doc 23 / 40024 | Supply air temperature | UINT16 | × 0.01 | °C / °F | Read | |||
| HR | 24doc 24 / 40025 | Supply air relative humidity | UINT16 | × 0.01 | %RH | Read | |||
| HR | 25doc 25 / 40026 | Outside air temperature | INT16 | × 0.01 | °C / °F | Read | |||
| HR | 26doc 26 / 40027 | Outside air relative humidity | UINT16 | × 0.01 | %RH | Read | |||
| HR | 27doc 27 / 40028 | Duct static pressure | UINT16 | × 0.1 | Pa | Read | |||
| HR | 28doc 28 / 40029 | Damper position feedback | UINT16 | % | Read | ||||
| HR | 29doc 29 / 40030 | Current airflow setpoint in percent of maximum capacity | UINT16 | % | Read | ||||
| HR | 30doc 30 / 40031 | CMU ECM fan speed feedback value | UINT16 | rpm | Read | ||||
| HR | 31doc 31 / 40032 | Heater vernier stage duty cycle | UINT16 | × 0.1 | % | Read | |||
| HR | 35doc 35 / 40036 | Occupied airflow setpoint in percent of maximum capacity | UINT16 | % | Read/write | ||||
| HR | 36doc 36 / 40037 | Unoccupied airflow setpoint in percent of maximum capacity | UINT16 | % | Read/write | ||||
| HR | 37doc 37 / 40038 | Binary input 3 stage weight | UINT16 | % | Read/write | ||||
| HR | 38doc 38 / 40039 | Binary input 4 stage weight | UINT16 | % | Read/write | ||||
| HR | 39doc 39 / 40040 | Exhaust fan start delay | UINT16 | s | Read/write | ||||
| HR | 40doc 40 / 40041 | Exhaust fan control signal minimum value | UINT16 | × 0.01 | V | Read/write | |||
| HR | 41doc 41 / 40042 | Exhaust fan control signal maximum value | UINT16 | × 0.01 | V | Read/write | |||
| HR | 42doc 42 / 40043 | Damper stroke time | UINT16 | s | Read/write | ||||
| HR | 43doc 43 / 40044 | Occupancy inputs minimum time | UINT16 | min | Read/write | ||||
| HR | 46doc 46 / 40047 | Dry mode relative humidity setpoint | UINT16 | %RH | Read/write | ||||
| HR | 47doc 47 / 40048 | Dry mode relative humidity setpoint dead band | UINT16 | %RH | Read/write | ||||
| HR | 48doc 48 / 40049 | Occupied static pressure control loop setpoint | UINT16 | × 0.1 | Pa | Read/write | |||
| HR | 49doc 49 / 40050 | Unoccupied static pressure control loop setpoint | UINT16 | × 0.1 | Pa | Read/write | |||
| HR | 50doc 50 / 40051 | CO2 concentration setpoint | UINT16 | ppm | Read/write | ||||
| HR | 51doc 51 / 40052 | CO2 concentration setpoint dead band | UINT16 | ppm | Read/write | ||||
| HR | 52doc 52 / 40053 | Supply air temperature offset | INT16 | × 0.01 | °C / °F | Read/write | |||
| HR | 53doc 53 / 40054 | Supply air temperature humidity offset | INT16 | × 0.01 | %RH | Read/write | |||
| HR | 54doc 54 / 40055 | Outside air temperature offset | INT16 | × 0.01 | °C / °F | Read/write | |||
| HR | 55doc 55 / 40056 | Outside air temperature humidity offset | INT16 | × 0.01 | %RH | Read/write | |||
| HR | 56doc 56 / 40057 | Room air temperature offset | INT16 | × 0.01 | °C / °F | Read/write | |||
| HR | 57doc 57 / 40058 | Room air relative humidity offset | INT16 | × 0.01 | %RH | Read/write | |||
| HR | 59doc 59 / 40060 | Minimum fan speed | UINT16 | % | Read/write | ||||
| HR | 60doc 60 / 40061 | Temperature control proportional band | UINT16 | × 0.01 | °C / °F | Read/write | |||
| HR | 61doc 61 / 40062 | Temperature control integral time | UINT16 | s | Read/write | ||||
| HR | 62doc 62 / 40063 | Temperature control derivate time | UINT16 | s | Read/write | ||||
| HR | 63doc 63 / 40064 | Static pressure control proportional band | UINT16 | Pa | Read/write | ||||
| HR | 64doc 64 / 40065 | Static pressure control integral time | UINT16 | s | Read/write | ||||
| HR | 65doc 65 / 40066 | Static pressure control derivate time | UINT16 | s | Read/write | ||||
| HR | 66doc 66 / 40067 | Control band | UINT16 | × 0.01 | °C / °F | Read/write | |||
| HR | 67doc 67 / 40068 | Modbus timeout | UINT16 | s | Read/write | ||||
| HR | 68doc 68 / 40069 | Number of synchronization timeouts | UINT16 | Read/write | |||||
| HR | 69doc 69 / 40070 | No heat detection deadband | UINT16 | × 0.01 | °C / °F | Read/write | |||
| HR | 70doc 70 / 40071 | No heat detection delay | UINT16 | s | Read/write | ||||
| HR | 71doc 71 / 40072 | Exhaust fan state | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 72doc 72 / 40073 | On/Off damper state | UINT16 | Read | 0 = Closed; 1 = Open | ||||
| HR | 73doc 73 / 40074 | On/Off damper feedback | UINT16 | Read | 0 = Closed; 1 = Open | ||||
| HR | 74doc 74 / 40075 | CMU fan enable | UINT16 | Read | 0 = No; 1 = Yes | ||||
| HR | 75doc 75 / 40076 | CMU heater stage 2 state | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 76doc 76 / 40077 | Binary input 3 contact type | UINT16 | Read/write | 0 = NO; 1 = NC | ||||
| HR | 77doc 77 / 40078 | Binary input 4 contact type | UINT16 | Read/write | 0 = NO; 1 = NC | ||||
| HR | 78doc 78 / 40079 | Binary output 1 contact type | UINT16 | Read/write | 0 = NO; 1 = NC | ||||
| HR | 79doc 79 / 40080 | Binary output 2 contact type | UINT16 | Read/write | 0 = NO; 1 = NC | ||||
| HR | 80doc 80 / 40081 | Enable occupancy inputs | UINT16 | Read/write | 0 = No; 1 = Yes | ||||
| HR | 81doc 81 / 40082 | Dry mode | UINT16 | Read/write | 0 = Disable; 1 = Enable | ||||
| HR | 82doc 82 / 40083 | CO2 extract | UINT16 | Read/write | 0 = Disable; 1 = Enable | ||||
| HR | 83doc 83 / 40084 | Static pressure loop | UINT16 | Read/write | 0 = Disable; 1 = Enable | ||||
| HR | 84doc 84 / 40085 | Occupancy inactive mode | UINT16 | Read/write | 0 = Unoccupied; 1 = Off | ||||
| HR | 85doc 85 / 40086 | CMU occupancy state | UINT16 | Read/write | 1 = Occupied; 2 = Unoccupied; 3 = Off | ||||
| HR | 86doc 86 / 40087 | Temperature setpoint source | UINT16 | Read/write | 1 = On Board; 2 = TSTAT; 3 = Network | ||||
| HR | 87doc 87 / 40088 | AI1 input mode | UINT16 | Read/write | 1 = Off; 2 = SAT; 3 = SARH; 4 = OAT; 5 = OARH; 6 = Static Pressure; 7 = Fan Setpoint; 8 = Damper Feedback | ||||
| HR | 88doc 88 / 40089 | AI2 input mode | UINT16 | Read/write | 1 = Off; 2 = SAT; 3 = SARH; 4 = OAT; 5 = OARH; 6 = Static Pressure; 7 = Fan Setpoint; 8 = Damper Feedback | ||||
| HR | 89doc 89 / 40090 | AI3/BI3 input mode | UINT16 | Read/write | 1 = Off; 2 = SAT; 3 = OAT; 4 = Damper Feedback; 5 = Occupancy; 6 = Fan Speed Stage | ||||
| HR | 90doc 90 / 40091 | AI4/BI4 input mode | UINT16 | Read/write | 1 = Off; 2 = SAT; 3 = OAT; 4 = Damper Feedback; 5 = Occupancy; 6 = Fan Speed Stage | ||||
| HR | 91doc 91 / 40092 | AO1 output mode | UINT16 | Read/write | 1 = Off; 2 = Exhaust Fan; 3 = Damper | ||||
| HR | 92doc 92 / 40093 | AO2 output mode | UINT16 | Read/write | 1 = Off; 2 = Exhaust Fan; 3 = Damper | ||||
| HR | 93doc 93 / 40094 | BO1 output mode | UINT16 | Read/write | 1 = Off; 2 = Exhaust Fan; 3 = Damper | ||||
| HR | 94doc 94 / 40095 | BO2 output mode | UINT16 | Read/write | 1 = Off; 2 = Exhaust Fan; 3 = Damper | ||||
| HR | 95doc 95 / 40096 | Static pressure sensor range | UINT16 | Read/write | 1 = 250 Pa; 2 = 500 Pa; 3 = 1250 Pa | ||||
| HR | 96doc 96 / 40097 | Analog input 1 signal range | UINT16 | Read/write | 1 = 2-10Vdc; 2 = 0-10Vdc | ||||
| HR | 97doc 97 / 40098 | Analog input 2 signal range | UINT16 | Read/write | 1 = 2-10Vdc; 2 = 0-10Vdc | ||||
| HR | 98doc 98 / 40099 | Analog output 1 signal range | UINT16 | Read/write | 1 = 2-10Vdc; 2 = 0-10Vdc | ||||
| HR | 99doc 99 / 40100 | Analog output 2 signal range | UINT16 | Read/write | 1 = 2-10Vdc; 2 = 0-10Vdc | ||||
| HR | 100doc 100 / 40101 | Control temperature source | UINT16 | Read/write | 1 = SAT; 2 = RAT | ||||
| HR | 101doc 101 / 40102 | LCD screen top line value | UINT16 | Read/write | 1 = None; 2 = Time; 3 = CO2; 4 = SARH; 5 = RARH | ||||
| HR | 102doc 102 / 40103 | LCD screen displayed temperature | UINT16 | Read/write | 1 = Default; 2 = Alternate; 3 = SAT; 4 = TSTAT | ||||
| HR | 103doc 103 / 40104 | LCD screen last reset reason | UINT16 | Read | 1 = No reason; 2 = Independent Watchdog; 3 = Window Watchdog; 4 = Software Reset; 5 = Power Down | ||||
| HR | 104doc 104 / 40105 | Alarm status | Alarm flags (bits 0-7 used). | BITMAP16 | Read | bit 0 = Unblocking damper required; bit 1 = SSOR1 sensor not detected; bit 2 = SSOR2 sensor not required; bit 3 = SAT not detected; bit 4 = RAT not detected; bit 5 = Communication timeout; bit 6 = AI1 reading error; bit 7 = AI2 reading error |
Notes on this map
- Only function codes 03, 06 and 16 are supported; every point is a 16-bit holding register.
- 'Scale N' with 'Value x N' means raw = engineering value x N; this map stores the multiplier 1/N. Units follow the °C/°F setting.
- Left out: register 0 (product type / address; the byte description is garbled); network / TDF / anti-freeze temperature set points 32-34 and set point min/max 44-45 (Scale 100 but 'Value x 1'); static pressure offset 58 (Scale 10 but example 2 Pa = 200); System alarm host 105 (bits up to B31 printed for a 16-bit register).
- Alarm status (104) is printed with 'B8 to B31 = Reserved'; only bits 0-7 carry meanings and are listed.
- Both 22 and 23 rows read 'Binary output 1 state' in the guide; 23 is presumably binary output 2 but is copied as printed.
- Serial framing defaults are not given; the guide lists 9600-76800 baud with auto-baud detection as the default.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Neptronic CMU compact make-up air unit (Modbus communication module)
What Modbus registers does the Neptronic CMU compact make-up air unit (Modbus communication module) have?
This map lists 98 registers: 98 holding registers. 60 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Neptronic CMU compact make-up air unit (Modbus communication module) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide prints the protocol-base (0-based) address and the holding register (base 40001) side by side, e.g. 23 / 40024. The protocol-base number is the wire address.
What are the minimum Modbus registers to integrate the Neptronic CMU compact make-up air unit (Modbus communication module)?
Start with HR 23 Supply air temperature (Supply air temperature); HR 27 Duct static pressure (Duct static pressure); HR 30 CMU ECM fan speed feedback value (Fan speed feedback); HR 31 Heater vernier stage duty cycle (Heater duty cycle); HR 85 CMU occupancy state (Occupancy state); HR 104 Alarm status (Alarm status); HR 35 Occupied airflow setpoint in percent of maximum capacity (Occupied airflow set point).
How do I enable Modbus control of the Neptronic CMU compact make-up air unit (Modbus communication module)?
Fit the Modbus communication module and set the address in the device menu or register 0.
What happens when the Neptronic CMU compact make-up air unit (Modbus communication module) loses Modbus communication?
Modbus timeout (67, 15-1800 s) and number of synchronisation timeouts (68) are provided; the guide does not describe the fallback action.
Where is the official Neptronic CMU compact make-up air unit (Modbus communication module) Modbus documentation?
The source is Compact Make-up Air Unit - Modbus Communication Module User Guide (CMU-Modbus Guide-211125), revision 2021-11-25, published free by Neptronic at https://www.neptronic.com/Heaters/pdf/20211206/CMU-Modbus%20Guide-211125.pdf.
More Neptronic Modbus register maps
- Thermostat / room controller (temperature, humidity, CO2, VOC)
Neptronic AROB series universal room controller (Modbus communication module)
Neptronic AROB24T / AROB24TH / AROB24TGH / AROB24TGVH universal room controllers with the Modbus module, ARO Modbus Guide_170824.
Also known as: AROB, AROB24T, AROB24TH, AROB24TGH, AROB24TGVH, ARO - Thermostat / fan coil controller
Neptronic EFCB Series networkable fan coil controller (Modbus RTU)
Neptronic EFCB Series fan coil controllers (24, 120 and 240 Vac; 2 or 4 relays) with the Modbus communication module, guide EFCB-Modbus Guide-260626.
Also known as: EFCB10TU2, EFCB10TU4, EFCB11TU2, EFCB11TU4, EFCB12TU2, EFCB12TU4, EFCB fan coil controller - Thermostat / fan coil controller
Neptronic EFCB-OE1 Series networkable fan coil controller (Modbus RTU)
Neptronic EFCB-OE1 Series fan coil controllers (24 or 240 Vac; 0, 2 or 4 relays), guide EFCB1x-OE1-Modbus Guide (V2.16)-260626.
Also known as: EFCB10T-OE1, EFCB12T-OE1, EFCB10TU2-OE1, EFCB10TU4-OE1, EFCB12TU2-OE1, EFCB12TU4-OE1, EFCB1x-OE1 - Air handler terminal (dual-duct VAV controller)
Neptronic EVCBM dual-duct VAV controller (Modbus communication module)
Neptronic EVCBM dual-duct VAV controllers (master + slave airflow) with the Modbus module, guide EVCBM Dual Duct-V500-Modbus Guide-180927-ESA.
Also known as: EVCBM Dual Duct, EVCB, Neptronic EVCBM Modbus - Air handler humidifier (electric steam)
Neptronic SKE4 electric steam humidifier (Modbus communication module)
Neptronic SKE4 series electric steam humidifiers with the Modbus communication module, guide SKE4-Modbus Guide-240531 (V2.07).
Also known as: SKE4-E, SKE4-N, SKE4 Steam Humidifier, Neptronic SKE4 Modbus - Air handler humidifier (gas-fired steam)
Neptronic SKG4 gas-fired steam humidifier (Modbus communication module)
Neptronic SKG4 series gas-fired steam humidifiers (one to four burner modules) with the Modbus communication module, guide SKG4-Modbus Guide-221114 (V2.04).
Also known as: SKG4-E, SKG4-N, SKG4 Gas Fired Humidifier, Neptronic SKG4 Modbus - Air handler humidifier (high-pressure atomizer)
Neptronic SKH4 high-pressure atomizer humidifier (Modbus communication module)
Neptronic SKH4 high-pressure atomizers with the Modbus communication module, guide SKH4-Modbus Guide-240126 (V.1.00).
Also known as: SKH4, SKH4 High-Pressure Atomizer, Neptronic SKH4 Modbus - Pump / water treatment unit (reverse osmosis for humidifiers)
Neptronic SKRO reverse osmosis water treatment unit (Modbus communication module)
Neptronic SKRO reverse osmosis water treatment units with the Modbus communication module, guide SKRO-Modbus Guide-250913 (V1.0).
Also known as: SKRO, SKRO Water Treatment Unit, Neptronic SKRO Modbus - Air handler humidifier (steam-to-steam)
Neptronic SKS4 steam-to-steam humidifier (Modbus communication module)
Neptronic SKS4 series steam-to-steam humidifiers with the Modbus communication module, guide SKS4-Modbus Guide-220509 (V2.03).
Also known as: SKS4-E, SKS4-N, SKS4 Steam to Steam Humidifier, Neptronic SKS4 Modbus - Air handler evaporative cooler (adiabatic cooling / humidification)
Neptronic SKVF evaporative cooler / humidifier (Modbus communication module)
Neptronic SKVF series evaporative coolers with the Modbus communication module, guide SKVF-Modbus Guide-211025.
Also known as: SKVF Evaporative Cooler, SKVF Series, Neptronic SKVF Modbus - Thermostat / fan coil and unitary controller
Neptronic TSUB Series universal wall-mount controller (Modbus RTU)
Neptronic TSUB Series universal wall-mount controllers with Modbus, guide TSUB-Modbus Guide-250829 (V1.13).
Also known as: TSUB Series, TSUB universal wall-mount controller - Thermostat / heat pump and unitary controller
Neptronic TUCB / TUHB Series universal wall-mount controller (Modbus RTU)
Neptronic TUCB24C6X2 (temperature) and TUHB24C6X2 (temperature and humidity) universal wall-mount controllers with 6 binary and 2 analog outputs, guide TUXB-Modbus Guide-190515.
Also known as: TUCB24C6X2, TUHB24C6X2, TUCB, TUHB, TUXB - Thermostat / heat pump and unitary controller
Neptronic TUUB Series universal wall-mount controller (Modbus RTU)
Neptronic TUUB Series universal wall-mount controllers with Modbus, guide TUUB-Modbus Guide-250829 (V1.13).
Also known as: TUUB Series, TUUB universal wall-mount controller
Other hvac equipment register maps
- Thermostat
Smart Temp SMT-770 thermostat with EC-02 module (Modbus RTU)
SMT-770 thermostat (with or without a paired EC-02 module), communications addendum v4.6 for firmware 2.31.
Also known as: SMT-770 Chameleon, EC-02, SMT770 - Sensor (HVAC humidity, temperature and CO2 transmitter)
Vaisala Origo10 transmitters for HVAC (Origo10A, Modbus RTU)
Origo10A duct and wall transmitters ordered with the Modbus RTU output (user guide M213293EN-B). Origo10L has no Modbus.
Also known as: Origo10, Origo10A, Origo 10, Vaisala Origo10 duct transmitter, Vaisala Origo10 wall transmitter - Air handler (in-row chilled-water cooling unit)
APC (Schneider Electric) InRow ACRC30x chilled-water cooling unit (300 mm)
APC by Schneider Electric InRow ACRC30x (300 mm chilled water) units, per register map part number 990-4742B.
Also known as: ACRC30x, ACRC300, ACRC301, InRow RC 300 mm - Air handler humidifier (resistive steam)
Condair RS II resistive steam humidifier (Integrated Controller, Modbus RTU/TCP)
Condair RS with the Integrated Controller (cylinders A and B), per addendum 2603326-G.
Also known as: Condair RS, Condair RS II, RS - Air handler (EC fan)
ebm-papst EC fans with MODBUS Lite (series 84/112/150/200 Lite)
ebm-papst EC fans and motors whose electronics report the MODBUS Lite parameter set (series 84 / 112 / 150 / 200 Lite), specification V5.01.
Also known as: MODBUS Lite V5.01, ebm-papst RadiCal Modbus, ebm-papst RadiPac Modbus, ebm-papst series 84 Lite, ebm-papst series 112 Lite, ebm-papst series 150 Lite, ebm-papst series 200 Lite - Thermostat
Johnson Controls PENN TC3223 refrigeration temperature controller (Modbus RTU)
PENN TC3223 electronic refrigeration controller with built-in Modbus RTU, per the TC3 Modbus Protocol Reference Guide LIT-12013523 (2020-04-28).
Also known as: TC3223, TC3, PENN TC3, LIT-12013523
All hvac equipment Modbus register maps →
Source: Compact Make-up Air Unit - Modbus Communication Module User Guide · CMU-Modbus Guide-211125 · rev. 2021-11-25. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.