Air handler (compact make-up air unit) · Modbus register map

Neptronic CMU compact make-up air unit (Modbus communication module) Modbus register map

Updated 19 November 2026

Short answer

The Neptronic CMU is a compact make-up air unit with an ECM fan, electric heater, damper, sensor inputs and an exhaust-fan output. Its Modbus RTU module exposes holding registers only: input voltages and temperatures, room temperature, RH, CO2, VOC and light from the TDF room sensor, supply and outdoor air readings, static pressure and airflow, set points and loop tuning, input/output configuration, occupancy and alarm flags.

This page lists 98 Modbus registers for the Neptronic CMU compact make-up air unit (Modbus communication module) — 60 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Neptronic’s own free documentation (linked below) and checked against it.

Manufacturer
Neptronic
Model
CMU compact make-up air unit (Modbus communication module)
Equipment type
Air handler (compact make-up air unit)
Registers
98 (60 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
Compact Make-up Air Unit, Neptronic CMU, CMU Series
Source document
Compact Make-up Air Unit - Modbus Communication Module User Guide · CMU-Modbus Guide-211125 · rev. 2021-11-25
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Neptronic CMU compact make-up air unit (Modbus communication module)

Integration in brief

Read supply air temperature (23), duct static pressure (27), fan speed (30) and alarm status (104). Command occupancy with register 85 and set occupied / unoccupied airflow with 35 / 36.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 23Supply air temperatureUINT16Supply air temperatureRead
HR 27Duct static pressureUINT16Duct static pressureRead
HR 30CMU ECM fan speed feedback valueUINT16Fan speed feedbackRead
HR 31Heater vernier stage duty cycleUINT16Heater duty cycleRead
HR 85CMU occupancy stateUINT16Occupancy stateRead/write
HR 104Alarm statusBITMAP16Alarm statusRead
HR 35Occupied airflow setpoint in percent of maximum capacityUINT16Occupied airflow set pointRead/write

Enable Modbus control & writes

Fit the Modbus communication module and set the address in the device menu or register 0.

Communication loss & watchdog

Modbus timeout (67, 15-1800 s) and number of synchronisation timeouts (68) are provided; the guide does not describe the fallback action.

Byte order & addressing

Network setup

Watch out for

Neptronic CMU compact make-up air unit (Modbus communication module) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

98 of 98 shown
Neptronic CMU compact make-up air unit (Modbus communication module) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR1doc 1 / 40002Analog input 1 voltageUINT16× 0.001VRead
HR2doc 2 / 40003Analog input 2 voltageUINT16× 0.001VRead
HR3doc 3 / 40004Analog input 3 temperatureINT16× 0.01°C / °FRead
HR4doc 4 / 40005Analog input 4 temperatureINT16× 0.01°C / °FRead
HR5doc 5 / 40006Room air temperature value measured by TDFUINT16× 0.01°C / °FRead
HR6doc 6 / 40007Room air relative humidity value measured by TDFUINT16× 0.1%RHRead
HR7doc 7 / 40008Room CO2 concentration value measured by TDFUINT16ppmRead
HR8doc 8 / 40009Volatile organic compound index measured by TDFUINT16Read
HR9doc 9 / 40010Luminous flux measured by TDFUINT16lxRead
HR10doc 10 / 40011CMU on-board potentiometer temperature setpointUINT16× 0.01°C / °FRead
HR11doc 11 / 40012CMU intake temperatureINT16× 0.01°C / °FRead
HR12doc 12 / 40013CMU outtake temperatureINT16× 0.01°C / °FRead
HR13doc 13 / 40014CMU board temperatureINT16× 0.01°C / °FRead
HR14doc 14 / 40015CMU SSR temperatureINT16× 0.01°C / °FRead
HR15doc 15 / 40016AI3/BI3 multi-mode input stateUINT16Read0 = Open; 1 = Closed
HR16doc 16 / 40017AI4/BI4 multi-mode input stateUINT16Read0 = Open; 1 = Closed
HR17doc 17 / 40018Room movement detection occupancy sensorUINT16Read0 = No; 1 = Yes
HR18doc 18 / 40019CMU On/Off contact input stateUINT16Read0 = Off; 1 = On
HR19doc 19 / 40020Analog output 1 voltageUINT16× 0.01VRead
HR20doc 20 / 40021Analog output 2 voltageUINT16× 0.01VRead
HR21doc 21 / 40022Binary output 1 stateUINT16Read0 = Open; 1 = Closed
HR22doc 22 / 40023Binary output 1 stateUINT16Read0 = Open; 1 = Closed
HR23doc 23 / 40024Supply air temperatureUINT16× 0.01°C / °FRead
HR24doc 24 / 40025Supply air relative humidityUINT16× 0.01%RHRead
HR25doc 25 / 40026Outside air temperatureINT16× 0.01°C / °FRead
HR26doc 26 / 40027Outside air relative humidityUINT16× 0.01%RHRead
HR27doc 27 / 40028Duct static pressureUINT16× 0.1PaRead
HR28doc 28 / 40029Damper position feedbackUINT16%Read
HR29doc 29 / 40030Current airflow setpoint in percent of maximum capacityUINT16%Read
HR30doc 30 / 40031CMU ECM fan speed feedback valueUINT16rpmRead
HR31doc 31 / 40032Heater vernier stage duty cycleUINT16× 0.1%Read
HR35doc 35 / 40036Occupied airflow setpoint in percent of maximum capacityUINT16%Read/write
HR36doc 36 / 40037Unoccupied airflow setpoint in percent of maximum capacityUINT16%Read/write
HR37doc 37 / 40038Binary input 3 stage weightUINT16%Read/write
HR38doc 38 / 40039Binary input 4 stage weightUINT16%Read/write
HR39doc 39 / 40040Exhaust fan start delayUINT16sRead/write
HR40doc 40 / 40041Exhaust fan control signal minimum valueUINT16× 0.01VRead/write
HR41doc 41 / 40042Exhaust fan control signal maximum valueUINT16× 0.01VRead/write
HR42doc 42 / 40043Damper stroke timeUINT16sRead/write
HR43doc 43 / 40044Occupancy inputs minimum timeUINT16minRead/write
HR46doc 46 / 40047Dry mode relative humidity setpointUINT16%RHRead/write
HR47doc 47 / 40048Dry mode relative humidity setpoint dead bandUINT16%RHRead/write
HR48doc 48 / 40049Occupied static pressure control loop setpointUINT16× 0.1PaRead/write
HR49doc 49 / 40050Unoccupied static pressure control loop setpointUINT16× 0.1PaRead/write
HR50doc 50 / 40051CO2 concentration setpointUINT16ppmRead/write
HR51doc 51 / 40052CO2 concentration setpoint dead bandUINT16ppmRead/write
HR52doc 52 / 40053Supply air temperature offsetINT16× 0.01°C / °FRead/write
HR53doc 53 / 40054Supply air temperature humidity offsetINT16× 0.01%RHRead/write
HR54doc 54 / 40055Outside air temperature offsetINT16× 0.01°C / °FRead/write
HR55doc 55 / 40056Outside air temperature humidity offsetINT16× 0.01%RHRead/write
HR56doc 56 / 40057Room air temperature offsetINT16× 0.01°C / °FRead/write
HR57doc 57 / 40058Room air relative humidity offsetINT16× 0.01%RHRead/write
HR59doc 59 / 40060Minimum fan speedUINT16%Read/write
HR60doc 60 / 40061Temperature control proportional bandUINT16× 0.01°C / °FRead/write
HR61doc 61 / 40062Temperature control integral timeUINT16sRead/write
HR62doc 62 / 40063Temperature control derivate timeUINT16sRead/write
HR63doc 63 / 40064Static pressure control proportional bandUINT16PaRead/write
HR64doc 64 / 40065Static pressure control integral timeUINT16sRead/write
HR65doc 65 / 40066Static pressure control derivate timeUINT16sRead/write
HR66doc 66 / 40067Control bandUINT16× 0.01°C / °FRead/write
HR67doc 67 / 40068Modbus timeoutUINT16sRead/write
HR68doc 68 / 40069Number of synchronization timeoutsUINT16Read/write
HR69doc 69 / 40070No heat detection deadbandUINT16× 0.01°C / °FRead/write
HR70doc 70 / 40071No heat detection delayUINT16sRead/write
HR71doc 71 / 40072Exhaust fan stateUINT16Read0 = Off; 1 = On
HR72doc 72 / 40073On/Off damper stateUINT16Read0 = Closed; 1 = Open
HR73doc 73 / 40074On/Off damper feedbackUINT16Read0 = Closed; 1 = Open
HR74doc 74 / 40075CMU fan enableUINT16Read0 = No; 1 = Yes
HR75doc 75 / 40076CMU heater stage 2 stateUINT16Read0 = Off; 1 = On
HR76doc 76 / 40077Binary input 3 contact typeUINT16Read/write0 = NO; 1 = NC
HR77doc 77 / 40078Binary input 4 contact typeUINT16Read/write0 = NO; 1 = NC
HR78doc 78 / 40079Binary output 1 contact typeUINT16Read/write0 = NO; 1 = NC
HR79doc 79 / 40080Binary output 2 contact typeUINT16Read/write0 = NO; 1 = NC
HR80doc 80 / 40081Enable occupancy inputsUINT16Read/write0 = No; 1 = Yes
HR81doc 81 / 40082Dry modeUINT16Read/write0 = Disable; 1 = Enable
HR82doc 82 / 40083CO2 extractUINT16Read/write0 = Disable; 1 = Enable
HR83doc 83 / 40084Static pressure loopUINT16Read/write0 = Disable; 1 = Enable
HR84doc 84 / 40085Occupancy inactive modeUINT16Read/write0 = Unoccupied; 1 = Off
HR85doc 85 / 40086CMU occupancy stateUINT16Read/write1 = Occupied; 2 = Unoccupied; 3 = Off
HR86doc 86 / 40087Temperature setpoint sourceUINT16Read/write1 = On Board; 2 = TSTAT; 3 = Network
HR87doc 87 / 40088AI1 input modeUINT16Read/write1 = Off; 2 = SAT; 3 = SARH; 4 = OAT; 5 = OARH; 6 = Static Pressure; 7 = Fan Setpoint; 8 = Damper Feedback
HR88doc 88 / 40089AI2 input modeUINT16Read/write1 = Off; 2 = SAT; 3 = SARH; 4 = OAT; 5 = OARH; 6 = Static Pressure; 7 = Fan Setpoint; 8 = Damper Feedback
HR89doc 89 / 40090AI3/BI3 input modeUINT16Read/write1 = Off; 2 = SAT; 3 = OAT; 4 = Damper Feedback; 5 = Occupancy; 6 = Fan Speed Stage
HR90doc 90 / 40091AI4/BI4 input modeUINT16Read/write1 = Off; 2 = SAT; 3 = OAT; 4 = Damper Feedback; 5 = Occupancy; 6 = Fan Speed Stage
HR91doc 91 / 40092AO1 output modeUINT16Read/write1 = Off; 2 = Exhaust Fan; 3 = Damper
HR92doc 92 / 40093AO2 output modeUINT16Read/write1 = Off; 2 = Exhaust Fan; 3 = Damper
HR93doc 93 / 40094BO1 output modeUINT16Read/write1 = Off; 2 = Exhaust Fan; 3 = Damper
HR94doc 94 / 40095BO2 output modeUINT16Read/write1 = Off; 2 = Exhaust Fan; 3 = Damper
HR95doc 95 / 40096Static pressure sensor rangeUINT16Read/write1 = 250 Pa; 2 = 500 Pa; 3 = 1250 Pa
HR96doc 96 / 40097Analog input 1 signal rangeUINT16Read/write1 = 2-10Vdc; 2 = 0-10Vdc
HR97doc 97 / 40098Analog input 2 signal rangeUINT16Read/write1 = 2-10Vdc; 2 = 0-10Vdc
HR98doc 98 / 40099Analog output 1 signal rangeUINT16Read/write1 = 2-10Vdc; 2 = 0-10Vdc
HR99doc 99 / 40100Analog output 2 signal rangeUINT16Read/write1 = 2-10Vdc; 2 = 0-10Vdc
HR100doc 100 / 40101Control temperature sourceUINT16Read/write1 = SAT; 2 = RAT
HR101doc 101 / 40102LCD screen top line valueUINT16Read/write1 = None; 2 = Time; 3 = CO2; 4 = SARH; 5 = RARH
HR102doc 102 / 40103LCD screen displayed temperatureUINT16Read/write1 = Default; 2 = Alternate; 3 = SAT; 4 = TSTAT
HR103doc 103 / 40104LCD screen last reset reasonUINT16Read1 = No reason; 2 = Independent Watchdog; 3 = Window Watchdog; 4 = Software Reset; 5 = Power Down
HR104doc 104 / 40105Alarm statusAlarm flags (bits 0-7 used).BITMAP16Readbit 0 = Unblocking damper required; bit 1 = SSOR1 sensor not detected; bit 2 = SSOR2 sensor not required; bit 3 = SAT not detected; bit 4 = RAT not detected; bit 5 = Communication timeout; bit 6 = AI1 reading error; bit 7 = AI2 reading error

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Neptronic CMU compact make-up air unit (Modbus communication module)

What Modbus registers does the Neptronic CMU compact make-up air unit (Modbus communication module) have?

This map lists 98 registers: 98 holding registers. 60 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Neptronic CMU compact make-up air unit (Modbus communication module) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide prints the protocol-base (0-based) address and the holding register (base 40001) side by side, e.g. 23 / 40024. The protocol-base number is the wire address.

What are the minimum Modbus registers to integrate the Neptronic CMU compact make-up air unit (Modbus communication module)?

Start with HR 23 Supply air temperature (Supply air temperature); HR 27 Duct static pressure (Duct static pressure); HR 30 CMU ECM fan speed feedback value (Fan speed feedback); HR 31 Heater vernier stage duty cycle (Heater duty cycle); HR 85 CMU occupancy state (Occupancy state); HR 104 Alarm status (Alarm status); HR 35 Occupied airflow setpoint in percent of maximum capacity (Occupied airflow set point).

How do I enable Modbus control of the Neptronic CMU compact make-up air unit (Modbus communication module)?

Fit the Modbus communication module and set the address in the device menu or register 0.

What happens when the Neptronic CMU compact make-up air unit (Modbus communication module) loses Modbus communication?

Modbus timeout (67, 15-1800 s) and number of synchronisation timeouts (68) are provided; the guide does not describe the fallback action.

Where is the official Neptronic CMU compact make-up air unit (Modbus communication module) Modbus documentation?

The source is Compact Make-up Air Unit - Modbus Communication Module User Guide (CMU-Modbus Guide-211125), revision 2021-11-25, published free by Neptronic at https://www.neptronic.com/Heaters/pdf/20211206/CMU-Modbus%20Guide-211125.pdf.

More Neptronic Modbus register maps

Other hvac equipment register maps

All hvac equipment Modbus register maps →

Source: Compact Make-up Air Unit - Modbus Communication Module User Guide · CMU-Modbus Guide-211125 · rev. 2021-11-25. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.