  4. SAB RVU ventilation unit controller (D150 Compact, Energy Plus)

Air handler (residential heat recovery ventilation) · Modbus register map

Vasco SAB RVU ventilation unit controller (D150 Compact, Energy Plus) Modbus register map

Updated 17 November 2026

Short answer

The SAB RVU board in Vasco D150 Compact and Energy Plus heat recovery units speaks Modbus RTU on its RS485 port (connector M19), using holding registers only. The map covers identification, the live machine state (temperatures, fan speeds, pressures, CO2, RH, alarms, run hours), the main parameters and the command block for on/off, mode, speed and external RH/CO2 values.

This page lists 96 Modbus registers for the Vasco SAB RVU ventilation unit controller (D150 Compact, Energy Plus) — 66 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Vasco’s own free documentation (linked below) and checked against it.

Manufacturer
Vasco
Model
SAB RVU ventilation unit controller (D150 Compact, Energy Plus)
Equipment type
Air handler (residential heat recovery ventilation)
Registers
96 (66 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
9600 baud, 8N1
Documented addressing
hexadecimal, 0-based
32-bit word order
ABCD high word first (big-endian)
Firmware
Protocol release 0x0006
Also known as
D150 Compact, Energy Plus ENY-P1, ENY-P2, ENY-P3, ENY-P4, ESP170V, ESP270, ESP360, ESP460
Source document
SAB RVU Ventilation Unit - Manual Modbus Protocol (D150 Compact, Energy Plus ENY-P1/2/3/4) · 90.01.06.53
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Vasco SAB RVU ventilation unit controller (D150 Compact, Energy Plus)

Integration in brief

Read 0x0100-0x0114 for temperatures, state, fan speeds, alarms, CO2 and RH. Switch with 0x0300, pick the mode with 0x0307 and the manual speed with 0x0309; a BMS humidity or CO2 sensor can be fed through 0x030A/0x030B.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 256Temperature probe T1INT16T1 temperatureRead
HR 261Machine state and modeBITMAP16Machine state and modeRead
HR 272AlarmsBITMAP16AlarmsRead
HR 267Fan1 SpeedUINT16Fan 1 speedRead
HR 768ON-OFF CommandUINT16On/off commandRead/write
HR 775Mode SelectionUINT16Mode selectionRead/write
HR 777Manual speedUINT16Manual speedRead/write
HR 784Reset Filter CounterUINT16Filter counter resetRead/write

Enable Modbus control & writes

Set the Modbus address (1-60) on the ADDRESS DIP switches (DIP 2); on residential 0x52xx controllers DIP 1 switch 10 selects 9600 (off) or 38400 baud (on).

Byte order & addressing

Network setup

Watch out for

Vasco SAB RVU ventilation unit controller (D150 Compact, Energy Plus) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

96 of 96 shown
Vasco SAB RVU ventilation unit controller (D150 Compact, Energy Plus) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 0x0000Serial NumberMachine ID for customer use, 20 characters.STRING[20]Read/write
HR10doc 0x000AController modelUINT16Read20992 = 0x5200 ESP170V; 20993 = 0x5201 ESP270; 20994 = 0x5202 ESP360; 20995 = 0x5203 ESP460; 20996 = 0x5204 ESP170H; 20997 = 0x5205 ESP180; 20998 = 0x5206 ESP280; 20999 = 0x5207 ESP370; 21248 = 0x5300 ENYP1; 21249 = 0x5301 ENYP2; 21250 = 0x5302 ENYP3; 21251 = 0x5303 ENYP4
HR11doc 0x000BFirmware ReleaseHigh byte major, low byte minor release.UINT16Read
HR12doc 0x000CProtocol ReleaseThe tables apply when this reads 0x0006.UINT16Read
HR13doc 0x000DT-EP Firmware ReleaseHigh byte major, low byte minor release.UINT16Read
HR256doc 0x0100Temperature probe T1Part of the Sig16[4] block at 0x0100.INT16× 0.1°CRead
HR257doc 0x0101Temperature probe T2Part of the Sig16[4] block at 0x0100.INT16× 0.1°CRead
HR258doc 0x0102Temperature probe T3Part of the Sig16[4] block at 0x0100.INT16× 0.1°CRead
HR259doc 0x0103Temperature probe T4Part of the Sig16[4] block at 0x0100.INT16× 0.1°CRead
HR260doc 0x0104Dips Configuration1 = DIP on.BITMAP16Readbit 0 = Inverted configuration; bit 1 = Pre-heating present; bit 2 = Pre-heating with water (0 = heat exchanger); bit 3 = Post treatment on; bit 4 = Post treatment also in summer; bit 5 = RL5 = IAQ (0 = fault signalling); bit 6 = Pre treatment; bit 7 = IN3 boiler pressure booster; bit 8 = Post treatment external heat exchanger; bit 9 = 0x53xx controllers: post treatment on T2 (0 = on T3)
HR261doc 0x0105Machine state and modeBits 9-10 mode (0 holiday, 1 auto, 2 program, 3 manual); bit 11 winter; bits 12-15 program.BITMAP16Readbit 0 = Remote OFF active; bit 1 = Bypass active; bit 2 = Electric pre-heater active; bit 3 = Water pre-heating active; bit 4 = Boost active; bit 5 = Defrost cycle active; bit 7 = Party mode on; bit 8 = Unit on; bit 11 = Season winter (0 = summer)
HR262doc 0x0106Humidity setpointUINT16× 0.1%RHRead
HR263doc 0x0107Filter counterCounts in 15-minute steps.UINT16Read
HR264doc 0x0108Digital output8-bit value in the high byte; bit 2 damper clockwise, bit 3 counter-clockwise.UINT16Read
HR265doc 0x0109Relay state8-bit value in the high byte; bits 0-4 IAQ/fault, preheat, postheat, fans, postcool/postheat2.UINT16Read
HR266doc 0x010ADigital Inputs8-bit value in the high byte; bits 1-4 = inputs C1-C4 active.UINT16Read
HR267doc 0x010BFan1 SpeedUINT16rpmRead
HR268doc 0x010CFan2 SpeedUINT16rpmRead
HR269doc 0x010DDuty Cycle Fan 1PWM drive.UINT16× 0.1%Read
HR270doc 0x010EDuty Cycle Fan 2PWM drive.UINT16× 0.1%Read
HR271doc 0x010FDuty Cycle El. PreheaterUINT16%Read
HR272doc 0x0110Alarms1 = active.BITMAP16Readbit 0 = T1 probe failure; bit 1 = T2 probe failure; bit 2 = T3 probe failure; bit 3 = T4 probe failure; bit 4 = Timekeeper failure; bit 5 = Frost alarm; bit 6 = Frost alarm (T2 probe); bit 7 = Fireplace alarm; bit 8 = Pressure transducer failure; bit 9 = Filter alarm; bit 10 = Fans failure; bit 11 = RH or CO2 sensor failure; bit 12 = Fan thermal input alarm; bit 14 = Pre-heating alarm; bit 15 = Pre-frost alarm (T2)
HR273doc 0x0111Diff Pressure Sensor 1INT16× 0.1PaRead
HR274doc 0x0112Diff Pressure Sensor 2INT16× 0.1PaRead
HR275doc 0x0113CO2 readingUINT16ppmRead
HR276doc 0x0114RH readingUINT16× 0.1%RHRead
HR285doc 0x011DCspeed 1Speed coefficient 1, multiplied by 0x4000.UINT16Read
HR286doc 0x011ECspeed 2Speed coefficient 2, multiplied by 0x4000.UINT16Read
HR287doc 0x0111FOptions/infoPrinted as 0x0111F, between 0x011E and 0x0120.BITMAP16Readbit 1 = RPM too high detected; bit 8 = IAQ used; bit 9 = Post treatment used; bit 10 = Heat exchanger used; bit 11 = Boiler boost mode used; bit 12 = CO2 sensor present; bit 13 = Differential pressure sensor present; bit 14 = RH sensor present; bit 15 = Reverse mounting
HR288doc 0x0120Hours of operationFans-on hour counter.UINT32ABCDhRead
HR290doc 0x0122FreeCooling/FreeHeatingUINT16Read0 = None; 1 = Free cooling; 2 = Free heating
HR512doc 0x0200Parameters FlagsBITMAP16Read/writebit 1 = Stop mode fans on (0 = fans off); bit 2 = Flush mode on; bit 3 = Modbus speed 38400 (0 = 9600); bit 4 = High RH management on
HR513doc 0x0201Temp probe 1 offsetINT16× 0.1°CRead/write
HR514doc 0x0202Temp probe 2 offsetINT16× 0.1°CRead/write
HR515doc 0x0203Temp probe 3 offsetINT16× 0.1°CRead/write
HR516doc 0x0204Temp probe 4 offsetINT16× 0.1°CRead/write
HR517doc 0x0205Fan min voltageINT16× 0.01VRead/write
HR518doc 0x0206Fan max voltageINT16× 0.01VRead/write
HR519doc 0x0207Fan1 Nominal V driveINT16× 0.01VRead/write
HR520doc 0x0208Fan2 Nominal V driveINT16× 0.01VRead/write
HR521doc 0x0209Fan min speedINT16rpmRead/write
HR522doc 0x020AFan max speedRange 1000-4000 rpm.INT16rpmRead/write
HR523doc 0x020BFan1 nominal speedINT16rpmRead/write
HR524doc 0x020CFan2 nominal speedINT16rpmRead/write
HR525doc 0x020DFan1 installation speedINT16rpmRead/write
HR526doc 0x020EK coefficient 1INT16× 0.01Read/write
HR527doc 0x020FK coefficient 2INT16× 0.01Read/write
HR528doc 0x0210Air flow 1INT16m³/hRead/write
HR529doc 0x0211Air flow 2INT16m³/hRead/write
HR530doc 0x0212Manual Speed (parameter)0-3 = speed 1-4; writing it switches to manual speed mode.INT16Read/write
HR531doc 0x0213Speed 1 %INT16%Read/write
HR532doc 0x0214Speed 2 %INT16%Read/write
HR533doc 0x0215Speed 3 %INT16%Read/write
HR534doc 0x0216Speed 4 %INT16%Read/write
HR535doc 0x0217Boost Speed %INT16%Read/write
HR536doc 0x0218Summer T SetpointINT16× 0.1°CRead/write
HR537doc 0x0219Winter T setpointINT16× 0.1°CRead/write
HR538doc 0x021AAir coefficients recalc. intervalINT16minRead/write
HR539doc 0x021BTemp for free coolingINT16× 0.1°CRead/write
HR540doc 0x021CTemp for free heatingINT16× 0.1°CRead/write
HR541doc 0x021DFan2 unbalance %INT16%Read/write
HR542doc 0x021EHumidity samples for setpointINT16Read/write
HR543doc 0x021FBoost timeINT16minRead/write
HR544doc 0x0220P constant for humidity regulatorINT16Read/write
HR545doc 0x0221Filter lifeINT16daysRead/write
HR546doc 0x0222CO2 ppm minINT16ppmRead/write
HR547doc 0x0223CO2 ppm nomINT16ppmRead/write
HR548doc 0x0224CO2 ppm maxINT16ppmRead/write
HR549doc 0x0225CO2 ppm prop constantINT16Read/write
HR550doc 0x0226Blocked functions1 = function blocked on the user panel.BITMAP16Read/writebit 0 = Manual mode not allowed; bit 1 = Party mode not allowed; bit 2 = Holiday mode not allowed; bit 3 = Auto mode not allowed; bit 4 = Weekly program mode not allowed; bit 5 = Time/day change not allowed; bit 6 = Off command not allowed
HR551doc 0x0227CO2 Sensor PPM RangeINT16ppmRead/write
HR552doc 0x0228Boiler boost timeINT16minRead/write
HR553doc 0x0229RH Low valueINT16× 0.1%RHRead/write
HR554doc 0x022ARH Standard valueINT16× 0.1%RHRead/write
HR555doc 0x022BRH Hi valueINT16× 0.1%RHRead/write
HR556doc 0x022CFan Speed with RH Low0-3 = speed 1-4.INT16Read/write
HR557doc 0x022DHeater K CoefficientINT16× 0.1Read/write
HR558doc 0x022EHeater Power limit modeINT16Read/write0 = Limit on RPM; 1 = None
HR559doc 0x022FHeater PID, P CoefficientINT16Read/write
HR560doc 0x0230Heater PID, I CoefficientINT16Read/write
HR561doc 0x0231Heater PID, D CoefficientINT16Read/write
HR562doc 0x0232T4 value for Heater ONINT16× 0.1°CRead/write
HR768doc 0x0300ON-OFF CommandUINT16Read/write0 = Off; 1 = On
HR769doc 0x0301Mode Command ManualWrite 1 for manual mode.UINT16Read/write
HR770doc 0x0302Mode Command HolidayWrite 1 for holiday mode.UINT16Read/write
HR771doc 0x0303Mode Command PartyWrite 1 for party mode.UINT16Read/write
HR772doc 0x0304Mode Command AutoWrite 1 for auto mode.UINT16Read/write
HR773doc 0x0305Mode Command ProgramWrite 1 for program mode.UINT16Read/write
HR774doc 0x0306Timer prog selection0-7 = programs P1-P8.UINT16Read/write
HR775doc 0x0307Mode SelectionSingle-register mode select.UINT16Read/write0 = Holiday; 1 = Auto; 2 = Program; 3 = Manual; 4 = Party
HR776doc 0x0308Parameter resetWrite 0x005A (90) to restore factory parameters; reads 0.UINT16Read/write
HR777doc 0x0309Manual speed0-3 = speed 1-4.UINT16Read/write
HR778doc 0x030AExternal RH Value0xFFFF on read = not yet valid.UINT16× 0.1%RHRead/write
HR779doc 0x030BExternal CO2 Value0xFFFF on read = not yet valid.UINT16ppmRead/write
HR783doc 0x030FSet Holiday mode daysWrite N (1-60) for N holiday days; reads days left.UINT16daysRead/write
HR784doc 0x0310Reset Filter CounterWrite 1 to reset.UINT16Read/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Vasco SAB RVU ventilation unit controller (D150 Compact, Energy Plus)

What Modbus registers does the Vasco SAB RVU ventilation unit controller (D150 Compact, Energy Plus) have?

This map lists 96 registers: 96 holding registers. 66 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Vasco SAB RVU ventilation unit controller (D150 Compact, Energy Plus) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints hexadecimal register addresses and the first block starts at 0x0000 (serial number), which only fits addresses sent as printed. Use the hex value directly: 0x0110 = register 272 on the wire.

What byte order does the Vasco SAB RVU ventilation unit controller (D150 Compact, Energy Plus) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Vasco SAB RVU ventilation unit controller (D150 Compact, Energy Plus)?

Start with HR 256 Temperature probe T1 (T1 temperature); HR 261 Machine state and mode (Machine state and mode); HR 272 Alarms (Alarms); HR 267 Fan1 Speed (Fan 1 speed); HR 768 ON-OFF Command (On/off command); HR 775 Mode Selection (Mode selection); HR 777 Manual speed (Manual speed); HR 784 Reset Filter Counter (Filter counter reset).

How do I enable Modbus control of the Vasco SAB RVU ventilation unit controller (D150 Compact, Energy Plus)?

Set the Modbus address (1-60) on the ADDRESS DIP switches (DIP 2); on residential 0x52xx controllers DIP 1 switch 10 selects 9600 (off) or 38400 baud (on).

Where is the official Vasco SAB RVU ventilation unit controller (D150 Compact, Energy Plus) Modbus documentation?

The source is SAB RVU Ventilation Unit - Manual Modbus Protocol (D150 Compact, Energy Plus ENY-P1/2/3/4) (90.01.06.53), published free by Vasco at https://vasco.eu/files/downloads/manuel-modbus-protocol-energy-plus/90.01.06.53-Handleiding-Modbus-registers-SAB-RVU.pdf.

Other hvac equipment register maps

All hvac equipment Modbus register maps →

Source: SAB RVU Ventilation Unit - Manual Modbus Protocol (D150 Compact, Energy Plus ENY-P1/2/3/4) · 90.01.06.53. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.