- SAB RVU ventilation unit controller (D150 Compact, Energy Plus)
Air handler (residential heat recovery ventilation) · Modbus register map
Vasco SAB RVU ventilation unit controller (D150 Compact, Energy Plus) Modbus register map
Updated 17 November 2026
The SAB RVU board in Vasco D150 Compact and Energy Plus heat recovery units speaks Modbus RTU on its RS485 port (connector M19), using holding registers only. The map covers identification, the live machine state (temperatures, fan speeds, pressures, CO2, RH, alarms, run hours), the main parameters and the command block for on/off, mode, speed and external RH/CO2 values.
This page lists 96 Modbus registers for the Vasco SAB RVU ventilation unit controller (D150 Compact, Energy Plus) — 66 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Vasco’s own free documentation (linked below) and checked against it.
- Manufacturer
- Vasco
- Model
- SAB RVU ventilation unit controller (D150 Compact, Energy Plus)
- Equipment type
- Air handler (residential heat recovery ventilation)
- Registers
- 96 (66 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 9600 baud, 8N1
- Documented addressing
- hexadecimal, 0-based
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- Protocol release 0x0006
- Also known as
- D150 Compact, Energy Plus ENY-P1, ENY-P2, ENY-P3, ENY-P4, ESP170V, ESP270, ESP360, ESP460
Integration notes: Vasco SAB RVU ventilation unit controller (D150 Compact, Energy Plus)
Read 0x0100-0x0114 for temperatures, state, fan speeds, alarms, CO2 and RH. Switch with 0x0300, pick the mode with 0x0307 and the manual speed with 0x0309; a BMS humidity or CO2 sensor can be fed through 0x030A/0x030B.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 256 | Temperature probe T1 | INT16 | T1 temperature | Read |
| HR 261 | Machine state and mode | BITMAP16 | Machine state and mode | Read |
| HR 272 | Alarms | BITMAP16 | Alarms | Read |
| HR 267 | Fan1 Speed | UINT16 | Fan 1 speed | Read |
| HR 768 | ON-OFF Command | UINT16 | On/off command | Read/write |
| HR 775 | Mode Selection | UINT16 | Mode selection | Read/write |
| HR 777 | Manual speed | UINT16 | Manual speed | Read/write |
| HR 784 | Reset Filter Counter | UINT16 | Filter counter reset | Read/write |
Enable Modbus control & writes
Set the Modbus address (1-60) on the ADDRESS DIP switches (DIP 2); on residential 0x52xx controllers DIP 1 switch 10 selects 9600 (off) or 38400 baud (on).
Byte order & addressing
- Only holding registers (FC 03, 06, 16) are supported.
- A multi-register write is refused unless every register in the range is writable.
- Writing the Manual Speed parameter (0x0212) switches the unit to manual speed mode.
Network setup
- RS485 on connector M19, 8 data bits, no parity, 1 stop bit.
Watch out for
- The Options/info register is printed as '0x0111F' in the manual; it is the register between 0x011E and 0x0120.
Vasco SAB RVU ventilation unit controller (D150 Compact, Energy Plus) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 0x0000 | Serial Number | Machine ID for customer use, 20 characters. | STRING[20] | Read/write | ||||
| HR | 10doc 0x000A | Controller model | UINT16 | Read | 20992 = 0x5200 ESP170V; 20993 = 0x5201 ESP270; 20994 = 0x5202 ESP360; 20995 = 0x5203 ESP460; 20996 = 0x5204 ESP170H; 20997 = 0x5205 ESP180; 20998 = 0x5206 ESP280; 20999 = 0x5207 ESP370; 21248 = 0x5300 ENYP1; 21249 = 0x5301 ENYP2; 21250 = 0x5302 ENYP3; 21251 = 0x5303 ENYP4 | ||||
| HR | 11doc 0x000B | Firmware Release | High byte major, low byte minor release. | UINT16 | Read | ||||
| HR | 12doc 0x000C | Protocol Release | The tables apply when this reads 0x0006. | UINT16 | Read | ||||
| HR | 13doc 0x000D | T-EP Firmware Release | High byte major, low byte minor release. | UINT16 | Read | ||||
| HR | 256doc 0x0100 | Temperature probe T1 | Part of the Sig16[4] block at 0x0100. | INT16 | × 0.1 | °C | Read | ||
| HR | 257doc 0x0101 | Temperature probe T2 | Part of the Sig16[4] block at 0x0100. | INT16 | × 0.1 | °C | Read | ||
| HR | 258doc 0x0102 | Temperature probe T3 | Part of the Sig16[4] block at 0x0100. | INT16 | × 0.1 | °C | Read | ||
| HR | 259doc 0x0103 | Temperature probe T4 | Part of the Sig16[4] block at 0x0100. | INT16 | × 0.1 | °C | Read | ||
| HR | 260doc 0x0104 | Dips Configuration | 1 = DIP on. | BITMAP16 | Read | bit 0 = Inverted configuration; bit 1 = Pre-heating present; bit 2 = Pre-heating with water (0 = heat exchanger); bit 3 = Post treatment on; bit 4 = Post treatment also in summer; bit 5 = RL5 = IAQ (0 = fault signalling); bit 6 = Pre treatment; bit 7 = IN3 boiler pressure booster; bit 8 = Post treatment external heat exchanger; bit 9 = 0x53xx controllers: post treatment on T2 (0 = on T3) | |||
| HR | 261doc 0x0105 | Machine state and mode | Bits 9-10 mode (0 holiday, 1 auto, 2 program, 3 manual); bit 11 winter; bits 12-15 program. | BITMAP16 | Read | bit 0 = Remote OFF active; bit 1 = Bypass active; bit 2 = Electric pre-heater active; bit 3 = Water pre-heating active; bit 4 = Boost active; bit 5 = Defrost cycle active; bit 7 = Party mode on; bit 8 = Unit on; bit 11 = Season winter (0 = summer) | |||
| HR | 262doc 0x0106 | Humidity setpoint | UINT16 | × 0.1 | %RH | Read | |||
| HR | 263doc 0x0107 | Filter counter | Counts in 15-minute steps. | UINT16 | Read | ||||
| HR | 264doc 0x0108 | Digital output | 8-bit value in the high byte; bit 2 damper clockwise, bit 3 counter-clockwise. | UINT16 | Read | ||||
| HR | 265doc 0x0109 | Relay state | 8-bit value in the high byte; bits 0-4 IAQ/fault, preheat, postheat, fans, postcool/postheat2. | UINT16 | Read | ||||
| HR | 266doc 0x010A | Digital Inputs | 8-bit value in the high byte; bits 1-4 = inputs C1-C4 active. | UINT16 | Read | ||||
| HR | 267doc 0x010B | Fan1 Speed | UINT16 | rpm | Read | ||||
| HR | 268doc 0x010C | Fan2 Speed | UINT16 | rpm | Read | ||||
| HR | 269doc 0x010D | Duty Cycle Fan 1 | PWM drive. | UINT16 | × 0.1 | % | Read | ||
| HR | 270doc 0x010E | Duty Cycle Fan 2 | PWM drive. | UINT16 | × 0.1 | % | Read | ||
| HR | 271doc 0x010F | Duty Cycle El. Preheater | UINT16 | % | Read | ||||
| HR | 272doc 0x0110 | Alarms | 1 = active. | BITMAP16 | Read | bit 0 = T1 probe failure; bit 1 = T2 probe failure; bit 2 = T3 probe failure; bit 3 = T4 probe failure; bit 4 = Timekeeper failure; bit 5 = Frost alarm; bit 6 = Frost alarm (T2 probe); bit 7 = Fireplace alarm; bit 8 = Pressure transducer failure; bit 9 = Filter alarm; bit 10 = Fans failure; bit 11 = RH or CO2 sensor failure; bit 12 = Fan thermal input alarm; bit 14 = Pre-heating alarm; bit 15 = Pre-frost alarm (T2) | |||
| HR | 273doc 0x0111 | Diff Pressure Sensor 1 | INT16 | × 0.1 | Pa | Read | |||
| HR | 274doc 0x0112 | Diff Pressure Sensor 2 | INT16 | × 0.1 | Pa | Read | |||
| HR | 275doc 0x0113 | CO2 reading | UINT16 | ppm | Read | ||||
| HR | 276doc 0x0114 | RH reading | UINT16 | × 0.1 | %RH | Read | |||
| HR | 285doc 0x011D | Cspeed 1 | Speed coefficient 1, multiplied by 0x4000. | UINT16 | Read | ||||
| HR | 286doc 0x011E | Cspeed 2 | Speed coefficient 2, multiplied by 0x4000. | UINT16 | Read | ||||
| HR | 287doc 0x0111F | Options/info | Printed as 0x0111F, between 0x011E and 0x0120. | BITMAP16 | Read | bit 1 = RPM too high detected; bit 8 = IAQ used; bit 9 = Post treatment used; bit 10 = Heat exchanger used; bit 11 = Boiler boost mode used; bit 12 = CO2 sensor present; bit 13 = Differential pressure sensor present; bit 14 = RH sensor present; bit 15 = Reverse mounting | |||
| HR | 288doc 0x0120 | Hours of operation | Fans-on hour counter. | UINT32 | ABCD | h | Read | ||
| HR | 290doc 0x0122 | FreeCooling/FreeHeating | UINT16 | Read | 0 = None; 1 = Free cooling; 2 = Free heating | ||||
| HR | 512doc 0x0200 | Parameters Flags | BITMAP16 | Read/write | bit 1 = Stop mode fans on (0 = fans off); bit 2 = Flush mode on; bit 3 = Modbus speed 38400 (0 = 9600); bit 4 = High RH management on | ||||
| HR | 513doc 0x0201 | Temp probe 1 offset | INT16 | × 0.1 | °C | Read/write | |||
| HR | 514doc 0x0202 | Temp probe 2 offset | INT16 | × 0.1 | °C | Read/write | |||
| HR | 515doc 0x0203 | Temp probe 3 offset | INT16 | × 0.1 | °C | Read/write | |||
| HR | 516doc 0x0204 | Temp probe 4 offset | INT16 | × 0.1 | °C | Read/write | |||
| HR | 517doc 0x0205 | Fan min voltage | INT16 | × 0.01 | V | Read/write | |||
| HR | 518doc 0x0206 | Fan max voltage | INT16 | × 0.01 | V | Read/write | |||
| HR | 519doc 0x0207 | Fan1 Nominal V drive | INT16 | × 0.01 | V | Read/write | |||
| HR | 520doc 0x0208 | Fan2 Nominal V drive | INT16 | × 0.01 | V | Read/write | |||
| HR | 521doc 0x0209 | Fan min speed | INT16 | rpm | Read/write | ||||
| HR | 522doc 0x020A | Fan max speed | Range 1000-4000 rpm. | INT16 | rpm | Read/write | |||
| HR | 523doc 0x020B | Fan1 nominal speed | INT16 | rpm | Read/write | ||||
| HR | 524doc 0x020C | Fan2 nominal speed | INT16 | rpm | Read/write | ||||
| HR | 525doc 0x020D | Fan1 installation speed | INT16 | rpm | Read/write | ||||
| HR | 526doc 0x020E | K coefficient 1 | INT16 | × 0.01 | Read/write | ||||
| HR | 527doc 0x020F | K coefficient 2 | INT16 | × 0.01 | Read/write | ||||
| HR | 528doc 0x0210 | Air flow 1 | INT16 | m³/h | Read/write | ||||
| HR | 529doc 0x0211 | Air flow 2 | INT16 | m³/h | Read/write | ||||
| HR | 530doc 0x0212 | Manual Speed (parameter) | 0-3 = speed 1-4; writing it switches to manual speed mode. | INT16 | Read/write | ||||
| HR | 531doc 0x0213 | Speed 1 % | INT16 | % | Read/write | ||||
| HR | 532doc 0x0214 | Speed 2 % | INT16 | % | Read/write | ||||
| HR | 533doc 0x0215 | Speed 3 % | INT16 | % | Read/write | ||||
| HR | 534doc 0x0216 | Speed 4 % | INT16 | % | Read/write | ||||
| HR | 535doc 0x0217 | Boost Speed % | INT16 | % | Read/write | ||||
| HR | 536doc 0x0218 | Summer T Setpoint | INT16 | × 0.1 | °C | Read/write | |||
| HR | 537doc 0x0219 | Winter T setpoint | INT16 | × 0.1 | °C | Read/write | |||
| HR | 538doc 0x021A | Air coefficients recalc. interval | INT16 | min | Read/write | ||||
| HR | 539doc 0x021B | Temp for free cooling | INT16 | × 0.1 | °C | Read/write | |||
| HR | 540doc 0x021C | Temp for free heating | INT16 | × 0.1 | °C | Read/write | |||
| HR | 541doc 0x021D | Fan2 unbalance % | INT16 | % | Read/write | ||||
| HR | 542doc 0x021E | Humidity samples for setpoint | INT16 | Read/write | |||||
| HR | 543doc 0x021F | Boost time | INT16 | min | Read/write | ||||
| HR | 544doc 0x0220 | P constant for humidity regulator | INT16 | Read/write | |||||
| HR | 545doc 0x0221 | Filter life | INT16 | days | Read/write | ||||
| HR | 546doc 0x0222 | CO2 ppm min | INT16 | ppm | Read/write | ||||
| HR | 547doc 0x0223 | CO2 ppm nom | INT16 | ppm | Read/write | ||||
| HR | 548doc 0x0224 | CO2 ppm max | INT16 | ppm | Read/write | ||||
| HR | 549doc 0x0225 | CO2 ppm prop constant | INT16 | Read/write | |||||
| HR | 550doc 0x0226 | Blocked functions | 1 = function blocked on the user panel. | BITMAP16 | Read/write | bit 0 = Manual mode not allowed; bit 1 = Party mode not allowed; bit 2 = Holiday mode not allowed; bit 3 = Auto mode not allowed; bit 4 = Weekly program mode not allowed; bit 5 = Time/day change not allowed; bit 6 = Off command not allowed | |||
| HR | 551doc 0x0227 | CO2 Sensor PPM Range | INT16 | ppm | Read/write | ||||
| HR | 552doc 0x0228 | Boiler boost time | INT16 | min | Read/write | ||||
| HR | 553doc 0x0229 | RH Low value | INT16 | × 0.1 | %RH | Read/write | |||
| HR | 554doc 0x022A | RH Standard value | INT16 | × 0.1 | %RH | Read/write | |||
| HR | 555doc 0x022B | RH Hi value | INT16 | × 0.1 | %RH | Read/write | |||
| HR | 556doc 0x022C | Fan Speed with RH Low | 0-3 = speed 1-4. | INT16 | Read/write | ||||
| HR | 557doc 0x022D | Heater K Coefficient | INT16 | × 0.1 | Read/write | ||||
| HR | 558doc 0x022E | Heater Power limit mode | INT16 | Read/write | 0 = Limit on RPM; 1 = None | ||||
| HR | 559doc 0x022F | Heater PID, P Coefficient | INT16 | Read/write | |||||
| HR | 560doc 0x0230 | Heater PID, I Coefficient | INT16 | Read/write | |||||
| HR | 561doc 0x0231 | Heater PID, D Coefficient | INT16 | Read/write | |||||
| HR | 562doc 0x0232 | T4 value for Heater ON | INT16 | × 0.1 | °C | Read/write | |||
| HR | 768doc 0x0300 | ON-OFF Command | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 769doc 0x0301 | Mode Command Manual | Write 1 for manual mode. | UINT16 | Read/write | ||||
| HR | 770doc 0x0302 | Mode Command Holiday | Write 1 for holiday mode. | UINT16 | Read/write | ||||
| HR | 771doc 0x0303 | Mode Command Party | Write 1 for party mode. | UINT16 | Read/write | ||||
| HR | 772doc 0x0304 | Mode Command Auto | Write 1 for auto mode. | UINT16 | Read/write | ||||
| HR | 773doc 0x0305 | Mode Command Program | Write 1 for program mode. | UINT16 | Read/write | ||||
| HR | 774doc 0x0306 | Timer prog selection | 0-7 = programs P1-P8. | UINT16 | Read/write | ||||
| HR | 775doc 0x0307 | Mode Selection | Single-register mode select. | UINT16 | Read/write | 0 = Holiday; 1 = Auto; 2 = Program; 3 = Manual; 4 = Party | |||
| HR | 776doc 0x0308 | Parameter reset | Write 0x005A (90) to restore factory parameters; reads 0. | UINT16 | Read/write | ||||
| HR | 777doc 0x0309 | Manual speed | 0-3 = speed 1-4. | UINT16 | Read/write | ||||
| HR | 778doc 0x030A | External RH Value | 0xFFFF on read = not yet valid. | UINT16 | × 0.1 | %RH | Read/write | ||
| HR | 779doc 0x030B | External CO2 Value | 0xFFFF on read = not yet valid. | UINT16 | ppm | Read/write | |||
| HR | 783doc 0x030F | Set Holiday mode days | Write N (1-60) for N holiday days; reads days left. | UINT16 | days | Read/write | |||
| HR | 784doc 0x0310 | Reset Filter Counter | Write 1 to reset. | UINT16 | Read/write |
Notes on this map
- 32-bit values use two registers with the most significant 16 bits first (data type table), so the hours counter is ABCD.
- Left out: the four float registers Rho 1-4 (0x0115-0x011B), because the type table states the word order only for 32-bit integers; the four weekly timer programs (blocks 4-7, 0x0400-0x0737) and block 8 time/date.
- Byte-type registers (0x0108-0x010A) carry their 8 bits in the most significant byte of the register.
- Out-of-range parameter writes are accepted but clipped to the allowed range.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Vasco SAB RVU ventilation unit controller (D150 Compact, Energy Plus)
What Modbus registers does the Vasco SAB RVU ventilation unit controller (D150 Compact, Energy Plus) have?
This map lists 96 registers: 96 holding registers. 66 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Vasco SAB RVU ventilation unit controller (D150 Compact, Energy Plus) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints hexadecimal register addresses and the first block starts at 0x0000 (serial number), which only fits addresses sent as printed. Use the hex value directly: 0x0110 = register 272 on the wire.
What byte order does the Vasco SAB RVU ventilation unit controller (D150 Compact, Energy Plus) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Vasco SAB RVU ventilation unit controller (D150 Compact, Energy Plus)?
Start with HR 256 Temperature probe T1 (T1 temperature); HR 261 Machine state and mode (Machine state and mode); HR 272 Alarms (Alarms); HR 267 Fan1 Speed (Fan 1 speed); HR 768 ON-OFF Command (On/off command); HR 775 Mode Selection (Mode selection); HR 777 Manual speed (Manual speed); HR 784 Reset Filter Counter (Filter counter reset).
How do I enable Modbus control of the Vasco SAB RVU ventilation unit controller (D150 Compact, Energy Plus)?
Set the Modbus address (1-60) on the ADDRESS DIP switches (DIP 2); on residential 0x52xx controllers DIP 1 switch 10 selects 9600 (off) or 38400 baud (on).
Where is the official Vasco SAB RVU ventilation unit controller (D150 Compact, Energy Plus) Modbus documentation?
The source is SAB RVU Ventilation Unit - Manual Modbus Protocol (D150 Compact, Energy Plus ENY-P1/2/3/4) (90.01.06.53), published free by Vasco at https://vasco.eu/files/downloads/manuel-modbus-protocol-energy-plus/90.01.06.53-Handleiding-Modbus-registers-SAB-RVU.pdf.
Other hvac equipment register maps
- Air handler (in-row data-centre cooling unit)
APC (Schneider Electric) InRow ACRD60x / ACRC60x cooling units (Modbus register map 990-5786)
APC / Schneider Electric InRow ACRD60x and ACRC60x in-row cooling units, register map part number 990-5786A.
Also known as: ACRD60x, ACRC60x, InRow ACRD60x, InRow ACRC60x, 990-5786 - Air handler humidifier (high-pressure room system)
Condair Vita high-pressure humidification system (Integrated Controller, Modbus RTU/TCP)
Condair Vita system with the Integrated Controller, per addendum 2603326-G.
Also known as: Condair Vita, Vita System Master - Rooftop unit / packaged wall-mount air conditioner
Eubank EAH / EGH wall-mount air conditioner control board (Modbus RTU)
Eubank EAH1020A-1060A, EGH1072A, EAH2024A-2060A and EGH2072A wall-mount air conditioners with the electronic control board (I&O manual rev. 7).
Also known as: EAH1020A, EAH1024A, EAH1030A, EAH1036A, EAH1042A, EAH1048A, EAH1060A, EGH1072A, EAH2024A, EAH2030A, EAH2036A, EAH2042A, EAH2048A, EAH2060A, EGH2072A, Eubank EAH, Eubank EGH - Thermostat
Johnson Controls PENN TC3224N9V refrigeration temperature controller (Modbus RTU)
PENN TC3224N9V electronic refrigeration controller with built-in Modbus RTU, per the TC3 Modbus Protocol Reference Guide LIT-12013523 (2020-04-28).
Also known as: TC3224N9V, TC3, PENN TC3, LIT-12013523, TC3224N9R, TC3224 - Thermostat / room controller (temperature, humidity, CO2, VOC)
Neptronic AROB series universal room controller (Modbus communication module)
Neptronic AROB24T / AROB24TH / AROB24TGH / AROB24TGVH universal room controllers with the Modbus module, ARO Modbus Guide_170824.
Also known as: AROB, AROB24T, AROB24TH, AROB24TGH, AROB24TGVH, ARO - Air handler humidifier (high-pressure atomizer)
Neptronic SKH4 high-pressure atomizer humidifier (Modbus communication module)
Neptronic SKH4 high-pressure atomizers with the Modbus communication module, guide SKH4-Modbus Guide-240126 (V.1.00).
Also known as: SKH4, SKH4 High-Pressure Atomizer, Neptronic SKH4 Modbus
All hvac equipment Modbus register maps →
Source: SAB RVU Ventilation Unit - Manual Modbus Protocol (D150 Compact, Energy Plus ENY-P1/2/3/4) · 90.01.06.53. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.