- XMW85 CO2, humidity and temperature wall transmitter (Modbus RTU)
Sensor (CO2/humidity wall transmitter) · Modbus register map
Vaisala XMW85 CO2, humidity and temperature wall transmitter (Modbus RTU) Modbus register map
Updated 19 November 2026
The XMW85 is a Vaisala wall transmitter that measures CO2, humidity and temperature for building automation over Modbus RTU. Address, bit rate and parity are set with DIP switches. This map covers the metric and imperial measurement blocks in float and integer form, status registers and integer and float test registers.
This page lists 18 Modbus registers for the Vaisala XMW85 CO2, humidity and temperature wall transmitter (Modbus RTU) — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Vaisala’s own free documentation (linked below) and checked against it.
- Manufacturer
- Vaisala
- Model
- XMW85 CO2, humidity and temperature wall transmitter (Modbus RTU)
- Equipment type
- Sensor (CO2/humidity wall transmitter)
- Registers
- 18 (0 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- 1-based (subtract 1 for the wire address)
- 32-bit word order
- CDAB low word first (word-swapped)
- Also known as
- XMW85
- Source document
- XMW85 User Guide · M213257EN-B · rev. 2026-02
Integration notes: Vaisala XMW85 CO2, humidity and temperature wall transmitter (Modbus RTU)
Read holding registers 1-6 in one request for CO2, RH and temperature (CDAB floats), or 257-259 as integers (RH and T x10).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Measured CO2 | FLOAT32 CDAB | CO2 ppm | Read |
| HR 2 | Measured humidity | FLOAT32 CDAB | Relative humidity | Read |
| HR 4 | Measured temperature | FLOAT32 CDAB | Temperature | Read |
| HR 512 | Device status | UINT16 | Device status | Read |
Enable Modbus control & writes
Set the Modbus address, bit rate and parity with the DIP switches before power-up.
Byte order & addressing
- Floats are low word first (CDAB); pick "word-swapped" float in masters that default to high word first.
- Read each 32-bit value in one transaction.
Network setup
- Address (1-247), bit rate (4800, 9600, 19200, 38400 or 57600; 76800 and 115200 are not supported) and parity (None or Even) are set with DIP switches; the guide gives no factory default.
- 1 and 2 stop bits are both accepted automatically.
- Up to 8 transmitters per RS-485 line; turn on the 120 ohm termination DIP switch only on the last device if the bus has no other terminator.
Watch out for
- Use test registers 7937 (reads -12345) and 7938 (reads -123.45) to confirm float format and addressing before trusting readings.
Vaisala XMW85 CO2, humidity and temperature wall transmitter (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 1 | Measured CO2 | FLOAT32 | CDAB | ppm | Read | |||
| HR | 2doc 3 | Measured humidity | FLOAT32 | CDAB | %RH | Read | |||
| HR | 4doc 5 | Measured temperature | FLOAT32 | CDAB | °C | Read | |||
| HR | 256doc 257 | Measured CO2 (integer) | INT16 | ppm | Read | ||||
| HR | 257doc 258 | Measured humidity (integer) | INT16 | × 0.1 | %RH | Read | |||
| HR | 258doc 259 | Measured temperature (integer) | INT16 | × 0.1 | °C | Read | |||
| HR | 512doc 513 | Device status | 0 = OK; other values are listed in troubleshooting. | UINT16 | Read | ||||
| HR | 517doc 518 | Humidity measurement status | 0 = OK. | BITMAP16 | Read | bit 0 = Measurement not supported; bit 2 = Under range; bit 3 = Over range; bit 7 = Sensor failure; bit 8 = Measurement not ready (CO2 only) | |||
| HR | 518doc 519 | Temperature measurement status | BITMAP16 | Read | bit 0 = Measurement not supported; bit 2 = Under range; bit 3 = Over range; bit 7 = Sensor failure; bit 8 = Measurement not ready (CO2 only) | ||||
| HR | 519doc 520 | CO2 measurement status | BITMAP16 | Read | bit 0 = Measurement not supported; bit 2 = Under range; bit 3 = Over range; bit 7 = Sensor failure; bit 8 = Measurement not ready (CO2 only) | ||||
| HR | 6400doc 6401 | Measured CO2 (imperial block) | FLOAT32 | CDAB | ppm | Read | |||
| HR | 6402doc 6403 | Measured humidity (imperial block) | FLOAT32 | CDAB | %RH | Read | |||
| HR | 6404doc 6405 | Measured temperature (imperial block) | FLOAT32 | CDAB | °F | Read | |||
| HR | 6656doc 6657 | Measured CO2 (imperial block, integer) | INT16 | ppm | Read | ||||
| HR | 6657doc 6658 | Measured humidity (imperial block, integer) | INT16 | × 0.1 | %RH | Read | |||
| HR | 6658doc 6659 | Measured temperature (imperial block, integer) | INT16 | × 0.1 | °F | Read | |||
| HR | 7936doc 7937 | Signed integer test | Always reads -12345. | INT16 | Read | ||||
| HR | 7937doc 7938 | Floating point test | Always reads -123.45. | FLOAT32 | CDAB | Read |
Notes on this map
- Registers are read with function 03 (holding). Function 04 (input registers) is also accepted and returns the same registers. The guide lists no write function.
- 32-bit floats put the least significant word at the listed register (CDAB). The guide states this and its worked read example (607.6 ppm) confirms it.
- Unavailable data reads as quiet NaN (float) or 0x8000 (16-bit integer) rather than an exception.
- The 6401-6659 block repeats the readings with temperature in °F.
- Left out: error code register 514, a 32-bit integer meant for Vaisala support; the guide states the word order only for 32-bit floats.
- DIP-switch address 0 puts the device offline (Modbus disabled).
- Left out: text string test register 7940, because the guide does not give its length in registers.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Vaisala XMW85 CO2, humidity and temperature wall transmitter (Modbus RTU)
What Modbus registers does the Vaisala XMW85 CO2, humidity and temperature wall transmitter (Modbus RTU) have?
This map lists 18 registers: 18 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Vaisala XMW85 CO2, humidity and temperature wall transmitter (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide numbers registers in decimal starting at 1 and also prints the 0-based hex address used in the request; register number 1 is address 0x0000 on the wire.
What byte order does the Vaisala XMW85 CO2, humidity and temperature wall transmitter (Modbus RTU) use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Vaisala XMW85 CO2, humidity and temperature wall transmitter (Modbus RTU)?
Start with HR 0 Measured CO2 (CO2 ppm); HR 2 Measured humidity (Relative humidity); HR 4 Measured temperature (Temperature); HR 512 Device status (Device status).
How do I enable Modbus control of the Vaisala XMW85 CO2, humidity and temperature wall transmitter (Modbus RTU)?
Set the Modbus address, bit rate and parity with the DIP switches before power-up.
Where is the official Vaisala XMW85 CO2, humidity and temperature wall transmitter (Modbus RTU) Modbus documentation?
The source is XMW85 User Guide (M213257EN-B), revision 2026-02, published free by Vaisala at https://docs.vaisala.com/r/M213257EN-B/en-US.
More Vaisala Modbus register maps
- Sensor (dew point probe)
Vaisala DMP Series dew point probes (DMP5, DMP6, DMP7, DMP8) (Modbus RTU)
Vaisala DMP5, DMP6, DMP7 and DMP8 dew point and temperature probes, Modbus RTU interface (user guide M212357EN-F).
Also known as: DMP5, DMP6, DMP7, DMP8, DRYCAP DMP series - Sensor (dew point transmitter)
Vaisala DMT143 miniature dew point transmitter (Modbus RTU)
DMT143 dew point transmitters ordered with the Modbus RTU option (user guide M211435EN-L).
Also known as: DMT143, DRYCAP DMT143 - Sensor (dew point transmitter)
Vaisala DMT153 dew point transmitter (Modbus RTU)
DMT153 trace-moisture dew point transmitter, Modbus RTU interface (user guide M213149EN-B).
Also known as: DMT153, DRYCAP DMT153 - Sensor (CO2 duct transmitter)
Vaisala GMD110 duct CO2 transmitter (Modbus RTU)
GMD110 duct-mount CO2 transmitter, Modbus RTU interface (user guide M212885EN-B).
Also known as: GMD110, CARBOCAP GMD110 - Sensor (CO2 probe)
Vaisala GMP251 CARBOCAP carbon dioxide probe (Modbus RTU)
GMP251 probe in Modbus RTU mode, user guide M211799EN-N.
Also known as: GMP251, CARBOCAP GMP251, Vaisala GMP251 - Sensor (CO2 probe)
Vaisala GMP252 CARBOCAP carbon dioxide probe (Modbus RTU)
GMP252 probe in Modbus RTU mode, user guide M211897EN-G.
Also known as: GMP252, CARBOCAP GMP252, Vaisala GMP252 - Sensor (CO2 wall transmitter)
Vaisala GMW87 CO2 and temperature wall transmitter (Modbus RTU)
GMW87, the RS-485 Modbus RTU model of the GMW80 series (user guide M211748EN-H).
Also known as: GMW87, GMW80 series Modbus - Sensor (humidity and temperature transmitter)
Vaisala HMDW110 series humidity and temperature transmitters with TMI110 (Modbus RTU)
HMDW110-series duct, wall and outdoor transmitters and TMI110 ordered with the Modbus RTU option (user guide M211726EN-L).
Also known as: HMD110, HMD112, HMW110, HMW112, HMW112D, HMS110, HMS112, TMW110, TMW112, TMW112D, TMI110 - Sensor (humidity and temperature module)
Vaisala HMM170 humidity module (Modbus RTU)
HMM170 OEM humidity and temperature module with the Modbus RTU interface (user guide M212259EN-D).
Also known as: HMM170, HUMICAP HMM170 - Sensor (humidity and temperature probe)
Vaisala HMP Series (HMP1-HMP9) with MMP8 and TMP1 probes (Modbus RTU)
Vaisala HMP1/3/4/5/7/8/9, TMP1 and MMP8 probes with the Modbus RTU interface (user guide M212022EN-M).
Also known as: HMP1, HMP3, HMP4, HMP5, HMP7, HMP8, HMP9, TMP1, MMP8 - Sensor (humidity and temperature probe)
Vaisala HMP60 / HMP110 series humidity and temperature probes (Modbus RTU)
HMP60/HMP110-series probes ordered with the Modbus RTU option (user guide M211060EN-N).
Also known as: HMP110, HMP113, HMP115, TMP115, HMP60, HMP63, HUMICAP HMP110, HMP110T, HMP63T, HMP115T - Sensor (humidity and temperature transmitter)
Vaisala HMW87 / HMW87D wall humidity and temperature transmitters (Modbus RTU)
HMW87 and HMW87D wall transmitters of the HMDW80 series (the Modbus models in user guide M211510EN-J).
Also known as: HMW87, HMW87D, HMDW80 Modbus - Sensor (H2O2 probe)
Vaisala HPP271 hydrogen peroxide probe (Modbus RTU)
HPP271 vaporized hydrogen peroxide probe, Modbus RTU interface (user guide M211888EN-E).
Also known as: HPP271, PEROXCAP HPP271 - Sensor (H2O2 / humidity probe)
Vaisala HPP272 hydrogen peroxide, humidity and temperature probe (Modbus RTU)
HPP272 vaporized hydrogen peroxide probe, Modbus RTU interface (user guide M211972EN-G).
Also known as: HPP272, PEROXCAP HPP272 - Sensor transmitter (host for Vaisala probes)
Vaisala Indigo510 / Indigo520 transmitters (Modbus TCP)
Indigo510 and Indigo520 transmitter registers (unit ID 240) over Modbus TCP (user guide M212287EN-AJ).
Also known as: Indigo510, Indigo520, Indigo500 series - Sensor (transformer oil monitor)
Vaisala MHT410 moisture, hydrogen and temperature transmitter for transformer oil (Modbus RTU)
MHT410 transformer oil monitor, Modbus RTU on the RS-485 screw terminals (user guide M211737EN-J).
Also known as: MHT410 - Sensor (moisture in oil transmitter)
Vaisala MMT143 moisture in oil transmitter (Modbus RTU)
MMT143 moisture-in-oil transmitter ordered with the Modbus RTU option (user guide M213308EN-B).
Also known as: MMT143 - Sensor (HVAC humidity, temperature and CO2 transmitter)
Vaisala Origo10 transmitters for HVAC (Origo10A, Modbus RTU)
Origo10A duct and wall transmitters ordered with the Modbus RTU output (user guide M213293EN-B). Origo10L has no Modbus.
Also known as: Origo10, Origo10A, Origo 10, Vaisala Origo10 duct transmitter, Vaisala Origo10 wall transmitter - Sensor (precipitation)
Vaisala RM60 PRECICAP radar precipitation sensor (Modbus RTU)
RM60 sensors ordered with communication option 1 (RS-485 Modbus RTU) or switched to Modbus, per user guide M213218EN-B.
Also known as: RM60, PRECICAP RM60, Vaisala RM60 - Sensor (ultrasonic wind)
Vaisala WM80 ultrasonic wind sensor (Modbus RTU)
WM80 sensors with RS-485 in Modbus mode (e.g. ordering option C), per user guide M212995EN-F.
Also known as: WM80, Vaisala WM80, Ultrasonic Wind Sensor WM80 - Sensor (weather transmitter)
Vaisala WXT530 series weather transmitters (Modbus RTU)
WXT531-WXT536 weather transmitters with firmware 3.85 or later in Modbus RTU mode (user guide M211840EN-G).
Also known as: WXT531, WXT532, WXT533, WXT534, WXT535, WXT536 - Sensor (humidity and temperature probe)
Vaisala XMP10 humidity and temperature probe (Modbus RTU)
XMP10 probes ordered with (or switched to) Modbus RTU output, user guide M213279EN-A.
Also known as: XMP10, HUMICAP XMP10, Vaisala XMP10
Other valves, actuators & sensors register maps
- Sensor (digital indicator with alarms)
Yokogawa UTAdvanced UM33A digital indicator with alarms
Yokogawa UM33A indicators with RS-485 (Modbus RTU/ASCII); process monitoring D registers from IM 05P07A01-01EN chapter 10.
Also known as: UM33A - Actuator / valve (pressure-independent characterised control valve)
Belimo 2-way EPIV DN 15-50 (Version 4.2) Modbus RTU
Belimo 2-way EPIV DN 15-50 Version 4 (EP..R2+(K)BAC) on Modbus RTU, per interface description edition 2025-09 / V4.2.
Also known as: EP..R2+BAC, EP..R2+KBAC, Electronic pressure-independent valve - Sensor (water analysis transmitter)
Endress+Hauser Liquiline CM44x multichannel transmitter (Modbus RS485 / TCP)
Liquiline CM44x with the Modbus RS485 or Modbus TCP option, software 1.11.00 and later (SD01189C/07/EN/07.22). The CSFxx sampler and CA80xx analyzer blocks of the same guide are not included.
Also known as: CM442, CM444, CM448, CM44P, CM44R, Liquiline CM442, Liquiline CM444, Liquiline CM448 - Sensor (pressure transmitter)
KELLER X-Line digital pressure transmitters, Series 30 / 40 (Modbus RTU)
KELLER X-Line transmitters with RS-485, Class.Group firmware 5.20-10.40 or later, 5.21 and 5.24 (protocol document version 3.7).
Also known as: Series 30X, Series 33X, Series 35X, Series 36X, Series 46X, PAA-33X, PR-33X, PA-36XW, Class.Group 5.20, Class.Group 5.21, Class.Group 5.24 - Sensor (leak detection controller)
RLE Technologies LD5200 leak detection controller (Modbus RTU / Modbus TCP slave)
RLE LD5200 distance-read leak detection controller, user guide version 04.22 (firmware 2.3.1).
Also known as: LD5200 - Sensor (signal conditioner)
Shinko Technos SGxL signal conditioner series (Modbus RTU)
Shinko SGxL signal conditioners (SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL); SGFL and SGJL are not covered. Manual No.SGxL1CE3.
Also known as: SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL
All valves, actuators & sensors Modbus register maps →
Source: XMW85 User Guide · M213257EN-B · rev. 2026-02. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.