- LD5200 leak detection controller (Modbus RTU / Modbus TCP slave)
Sensor (leak detection controller) · Modbus register map
RLE Technologies LD5200 leak detection controller (Modbus RTU / Modbus TCP slave) Modbus register map
Updated 17 November 2026
The LD5200 monitors a water-sensing cable and reports where along the cable a leak is. As a Modbus slave on its EIA-485 ports (or Modbus over Ethernet) it gives leak, cable-break and contamination status, leak distance and current, cable resistances, virtual-zone alarms and the status of the slave panels it polls as a Modbus master. Thresholds and alarm delays are writable holding registers.
This page lists 47 Modbus registers for the RLE Technologies LD5200 leak detection controller (Modbus RTU / Modbus TCP slave) — 4 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from RLE Technologies’s own free documentation (linked below) and checked against it.
- Manufacturer
- RLE Technologies
- Model
- LD5200 leak detection controller (Modbus RTU / Modbus TCP slave)
- Equipment type
- Sensor (leak detection controller)
- Registers
- 47 (4 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- Default serial
- 9600 baud, 8N1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- Documented with firmware 2.3.1
- Also known as
- LD5200
- Source document
- LD5200 User Guide · Version 04.22 · rev. 2022-04
Integration notes: RLE Technologies LD5200 leak detection controller (Modbus RTU / Modbus TCP slave)
Read input registers 30001-30011 with FC4: status bits for leak / cable break / contamination, leak distance and unit, leak current and cable data. Read 38001-38002 for the leak position as a float in meters.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 0 | Status | BITMAP16 | Leak / cable break / contamination status | Read |
| IR 1 | Leak distance | UINT16 | Leak distance | Read |
| IR 2 | Distance units | UINT16 | Distance unit | Read |
| IR 3 | Leak current | UINT16 | Leak current | Read |
| IR 8000 | Leak location (float) | FLOAT32 ABCD | Leak location in meters (float) | Read |
| IR 9 | Virtual zone alarm status, zones 1-16 | BITMAP16 | Virtual zone alarms 1-16 | Read |
Enable Modbus control & writes
Set an EIA-485 port function to Modbus-Slave and give it a slave address (1-254, 0 = disabled) and baud rate in the Comm Port Settings menu (LCD) or the Modbus/EIA-485 web page. For Ethernet, set the Modbus/TCP/UDP slave unit identifier on the same page.
Byte order & addressing
- RTU only on the serial ports, fixed 8 data bits, no parity, 1 stop bit; baud 9600 (default), 19200 or 38400.
- As a slave the LD5200 accepts only one master.
Network setup
- Three EIA-485 ports (TB5/TB6); port 2 can also be BACnet MS/TP or N2.
- When the LD5200 is a master for distance-read panels, the first slave must use address 2, the next 3, and so on.
Watch out for
- A missing end-of-line terminator on the sensing cable shows as a cable fault.
RLE Technologies LD5200 leak detection controller (Modbus RTU / Modbus TCP slave) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 0doc 30001 | Status | BITMAP16 | Read | bit 0 = Leak detected; bit 1 = Cable break alarm; bit 2 = Contamination detected | ||||
| IR | 1doc 30002 | Leak distance | Location of the leak; unit per register 30003. | UINT16 | ft or m | Read | |||
| IR | 2doc 30003 | Distance units | UINT16 | Read | 0 = Meters; 1 = Feet | ||||
| IR | 3doc 30004 | Leak current | Leakage current on the sensing cable. | UINT16 | uA | Read | |||
| IR | 4doc 30005 | Cable length | Installed sensing-cable length. | UINT16 | ft or m | Read | |||
| IR | 5doc 30006 | Loop 1 resistance | UINT16 | ohm | Read | ||||
| IR | 6doc 30007 | Loop 2 resistance | UINT16 | ohm | Read | ||||
| IR | 7doc 30008 | Resistance per foot | Published as ohms x 1000. | UINT16 | × 0.001 | ohm | Read | ||
| IR | 8doc 30009 | Firmware version | xx.xx x 100. | UINT16 | × 0.01 | Read | |||
| IR | 9doc 30010 | Virtual zone alarm status, zones 1-16 | BITMAP16 | Read | bit 0 = Zone 1 in alarm; bit 1 = Zone 2 in alarm; bit 2 = Zone 3 in alarm; bit 3 = Zone 4 in alarm; bit 4 = Zone 5 in alarm; bit 5 = Zone 6 in alarm; bit 6 = Zone 7 in alarm; bit 7 = Zone 8 in alarm; bit 8 = Zone 9 in alarm; bit 9 = Zone 10 in alarm; bit 10 = Zone 11 in alarm; bit 11 = Zone 12 in alarm; bit 12 = Zone 13 in alarm; bit 13 = Zone 14 in alarm; bit 14 = Zone 15 in alarm; bit 15 = Zone 16 in alarm | ||||
| IR | 10doc 30011 | Virtual zone alarm status, zones 17-32 | BITMAP16 | Read | bit 0 = Zone 17 in alarm; bit 1 = Zone 18 in alarm; bit 2 = Zone 19 in alarm; bit 3 = Zone 20 in alarm; bit 4 = Zone 21 in alarm; bit 5 = Zone 22 in alarm; bit 6 = Zone 23 in alarm; bit 7 = Zone 24 in alarm; bit 8 = Zone 25 in alarm; bit 9 = Zone 26 in alarm; bit 10 = Zone 27 in alarm; bit 11 = Zone 28 in alarm; bit 12 = Zone 29 in alarm; bit 13 = Zone 30 in alarm; bit 14 = Zone 31 in alarm; bit 15 = Zone 32 in alarm | ||||
| IR | 11doc 30012 | Modbus zone enabled flags, zones 2-16 | One bit per zone 2-16; the guide's bit labels (0 = zone 2, 15 = zone 16) do not add up. | BITMAP16 | Read | ||||
| IR | 12doc 30013 | Modbus zone 2 status | Slave leak-detection panel on the LD5200's master port. | BITMAP16 | Read | bit 0 = Leak detected; bit 1 = Cable break; bit 2 = Contamination; bit 7 = Communication loss | |||
| IR | 13doc 30014 | Modbus zone 2 distance | Leak location reported by that slave. | UINT16 | ft or m | Read | |||
| IR | 14doc 30015 | Modbus zone 3 status | Slave leak-detection panel on the LD5200's master port. | BITMAP16 | Read | bit 0 = Leak detected; bit 1 = Cable break; bit 2 = Contamination; bit 7 = Communication loss | |||
| IR | 15doc 30016 | Modbus zone 3 distance | Leak location reported by that slave. | UINT16 | ft or m | Read | |||
| IR | 16doc 30017 | Modbus zone 4 status | Slave leak-detection panel on the LD5200's master port. | BITMAP16 | Read | bit 0 = Leak detected; bit 1 = Cable break; bit 2 = Contamination; bit 7 = Communication loss | |||
| IR | 17doc 30018 | Modbus zone 4 distance | Leak location reported by that slave. | UINT16 | ft or m | Read | |||
| IR | 18doc 30019 | Modbus zone 5 status | Slave leak-detection panel on the LD5200's master port. | BITMAP16 | Read | bit 0 = Leak detected; bit 1 = Cable break; bit 2 = Contamination; bit 7 = Communication loss | |||
| IR | 19doc 30020 | Modbus zone 5 distance | Leak location reported by that slave. | UINT16 | ft or m | Read | |||
| IR | 20doc 30021 | Modbus zone 6 status | Slave leak-detection panel on the LD5200's master port. | BITMAP16 | Read | bit 0 = Leak detected; bit 1 = Cable break; bit 2 = Contamination; bit 7 = Communication loss | |||
| IR | 21doc 30022 | Modbus zone 6 distance | Leak location reported by that slave. | UINT16 | ft or m | Read | |||
| IR | 22doc 30023 | Modbus zone 7 status | Slave leak-detection panel on the LD5200's master port. | BITMAP16 | Read | bit 0 = Leak detected; bit 1 = Cable break; bit 2 = Contamination; bit 7 = Communication loss | |||
| IR | 23doc 30024 | Modbus zone 7 distance | Leak location reported by that slave. | UINT16 | ft or m | Read | |||
| IR | 24doc 30025 | Modbus zone 8 status | Slave leak-detection panel on the LD5200's master port. | BITMAP16 | Read | bit 0 = Leak detected; bit 1 = Cable break; bit 2 = Contamination; bit 7 = Communication loss | |||
| IR | 25doc 30026 | Modbus zone 8 distance | Leak location reported by that slave. | UINT16 | ft or m | Read | |||
| IR | 26doc 30027 | Modbus zone 9 status | Slave leak-detection panel on the LD5200's master port. | BITMAP16 | Read | bit 0 = Leak detected; bit 1 = Cable break; bit 2 = Contamination; bit 7 = Communication loss | |||
| IR | 27doc 30028 | Modbus zone 9 distance | Leak location reported by that slave. | UINT16 | ft or m | Read | |||
| IR | 28doc 30029 | Modbus zone 10 status | Slave leak-detection panel on the LD5200's master port. | BITMAP16 | Read | bit 0 = Leak detected; bit 1 = Cable break; bit 2 = Contamination; bit 7 = Communication loss | |||
| IR | 29doc 30030 | Modbus zone 10 distance | Leak location reported by that slave. | UINT16 | ft or m | Read | |||
| IR | 30doc 30031 | Modbus zone 11 status | Slave leak-detection panel on the LD5200's master port. | BITMAP16 | Read | bit 0 = Leak detected; bit 1 = Cable break; bit 2 = Contamination; bit 7 = Communication loss | |||
| IR | 31doc 30032 | Modbus zone 11 distance | Leak location reported by that slave. | UINT16 | ft or m | Read | |||
| IR | 32doc 30033 | Modbus zone 12 status | Slave leak-detection panel on the LD5200's master port. | BITMAP16 | Read | bit 0 = Leak detected; bit 1 = Cable break; bit 2 = Contamination; bit 7 = Communication loss | |||
| IR | 33doc 30034 | Modbus zone 12 distance | Leak location reported by that slave. | UINT16 | ft or m | Read | |||
| IR | 34doc 30035 | Modbus zone 13 status | Slave leak-detection panel on the LD5200's master port. | BITMAP16 | Read | bit 0 = Leak detected; bit 1 = Cable break; bit 2 = Contamination; bit 7 = Communication loss | |||
| IR | 35doc 30036 | Modbus zone 13 distance | Leak location reported by that slave. | UINT16 | ft or m | Read | |||
| IR | 36doc 30037 | Modbus zone 14 status | Slave leak-detection panel on the LD5200's master port. | BITMAP16 | Read | bit 0 = Leak detected; bit 1 = Cable break; bit 2 = Contamination; bit 7 = Communication loss | |||
| IR | 37doc 30038 | Modbus zone 14 distance | Leak location reported by that slave. | UINT16 | ft or m | Read | |||
| IR | 38doc 30039 | Modbus zone 15 status | Slave leak-detection panel on the LD5200's master port. | BITMAP16 | Read | bit 0 = Leak detected; bit 1 = Cable break; bit 2 = Contamination; bit 7 = Communication loss | |||
| IR | 39doc 30040 | Modbus zone 15 distance | Leak location reported by that slave. | UINT16 | ft or m | Read | |||
| IR | 40doc 30041 | Modbus zone 16 status | Slave leak-detection panel on the LD5200's master port. | BITMAP16 | Read | bit 0 = Leak detected; bit 1 = Cable break; bit 2 = Contamination; bit 7 = Communication loss | |||
| IR | 41doc 30042 | Modbus zone 16 distance | Leak location reported by that slave. | UINT16 | ft or m | Read | |||
| IR | 8000doc 38001 | Leak location (float) | Location of leak in meters; MSW at 38001, LSW at 38002. | FLOAT32 | ABCD | m | Read | ||
| HR | 0doc 40001 | Leak threshold | Trip current for a leak alarm. | UINT16 | uA | Read/write | |||
| HR | 1doc 40002 | Contamination threshold | Trip current for a contamination alarm, 20-295. | UINT16 | uA | Read/write | |||
| HR | 15doc 40016 | Leak alarm delay | 5-995 s. | UINT16 | s | Read/write | |||
| HR | 16doc 40017 | Contamination alarm delay | 5-995 s. | UINT16 | s | Read/write |
Notes on this map
- Float word order: the guide labels 38001 as the float MSW and 38002 as the LSW, so the leak-location float is ABCD.
- Only the first block of Modbus slave zones (2-16, registers 30012-30042) is listed. Later blocks cover 16 zones each: 30043 flags zones 17-32 with status/distance pairs from 30044, 30076 flags zones 33-48, and so on up to zone 128 at 30272/30273.
- Holding registers 40003-40015 are spare.
- Distance registers are in feet or meters depending on register 30003.
- The guide calls the Ethernet option 'Modbus/TCP/UDP' with its own slave unit identifier (1-254); it does not list a separate map, so the same registers are assumed to apply over Ethernet. The TCP port is not given.
- The leak trip range differs inside the guide: the Modbus table shows 25-295 uA, the LCD settings page says 25-175 uA.
- Bit 15 of 30012 is labeled zone 16 although bit 0 is zone 2, so the bits of 30012 are not listed.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the RLE Technologies LD5200 leak detection controller (Modbus RTU / Modbus TCP slave)
What Modbus registers does the RLE Technologies LD5200 leak detection controller (Modbus RTU / Modbus TCP slave) have?
This map lists 47 registers: 43 input registers, 4 holding registers. 4 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the RLE Technologies LD5200 leak detection controller (Modbus RTU / Modbus TCP slave) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. RLE says the start register is numbered from zero: 40001 = 0, 30001 = 0. So input register 30002 (leak distance) is wire address 1 with FC4, holding register 40016 is address 15 with FC3/FC6/FC16.
What byte order does the RLE Technologies LD5200 leak detection controller (Modbus RTU / Modbus TCP slave) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the RLE Technologies LD5200 leak detection controller (Modbus RTU / Modbus TCP slave)?
Start with IR 0 Status (Leak / cable break / contamination status); IR 1 Leak distance (Leak distance); IR 2 Distance units (Distance unit); IR 3 Leak current (Leak current); IR 8000 Leak location (float) (Leak location in meters (float)); IR 9 Virtual zone alarm status, zones 1-16 (Virtual zone alarms 1-16).
How do I enable Modbus control of the RLE Technologies LD5200 leak detection controller (Modbus RTU / Modbus TCP slave)?
Set an EIA-485 port function to Modbus-Slave and give it a slave address (1-254, 0 = disabled) and baud rate in the Comm Port Settings menu (LCD) or the Modbus/EIA-485 web page. For Ethernet, set the Modbus/TCP/UDP slave unit identifier on the same page.
Where is the official RLE Technologies LD5200 leak detection controller (Modbus RTU / Modbus TCP slave) Modbus documentation?
The source is LD5200 User Guide (Version 04.22), revision 2022-04, published free by RLE Technologies at https://WWW.RLETECH.COM/wp-content/uploads/2022/04/LD5200_UserGuide-04-22.pdf.
More RLE Technologies Modbus register maps
Other valves, actuators & sensors register maps
- Sensor (signal conditioner)
Shinko Technos SGxL signal conditioner series (Modbus RTU)
Shinko SGxL signal conditioners (SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL); SGFL and SGJL are not covered. Manual No.SGxL1CE3.
Also known as: SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL - Sensor (flame detector)
Teledyne Gas and Flame Detection Spyglass SG50-F flame detector (Modbus RTU)
Teledyne Spyglass SG50-F optical flame detectors (IR3, UV-IR, IR3-H2 and HD video variants) with RS-485 Modbus RTU, communication manual SG50FMODBUS-EN rev 1.0.
Also known as: SG50-F, Spyglass SG50-F, IR3-HD, UV-IR, IR3, UV-IR-HD, IR3-H2-HD, IR3-H2, UV-IR-F, UV-IR-F-HD - Sensor (CO2 / humidity / temperature / pressure)
Teracom TSM400-4-CPTH Modbus CO2, humidity, temperature and pressure multi-sensor
TSM400-4-CPTH per the Teracom TSM400-4-CPTH user manual TSM400-4-CPTH-R1.9.
Also known as: TSM400-4-CPTH - Sensor (dew point transmitter)
Vaisala DMT153 dew point transmitter (Modbus RTU)
DMT153 trace-moisture dew point transmitter, Modbus RTU interface (user guide M213149EN-B).
Also known as: DMT153, DRYCAP DMT153 - Sensor (humidity and temperature probe)
Vaisala HMP Series (HMP1-HMP9) with MMP8 and TMP1 probes (Modbus RTU)
Vaisala HMP1/3/4/5/7/8/9, TMP1 and MMP8 probes with the Modbus RTU interface (user guide M212022EN-M).
Also known as: HMP1, HMP3, HMP4, HMP5, HMP7, HMP8, HMP9, TMP1, MMP8 - Sensor (moisture in oil transmitter)
Vaisala MMT143 moisture in oil transmitter (Modbus RTU)
MMT143 moisture-in-oil transmitter ordered with the Modbus RTU option (user guide M213308EN-B).
Also known as: MMT143
All valves, actuators & sensors Modbus register maps →
Source: LD5200 User Guide · Version 04.22 · rev. 2022-04. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.