- Falcon F200 environment and leak monitoring appliance (Modbus TCP)
Sensor (environmental / leak monitor) · Modbus register map
RLE Technologies Falcon F200 environment and leak monitoring appliance (Modbus TCP) Modbus register map
Updated 17 November 2026
The Falcon F200 is a small monitoring appliance for data rooms: up to four external temperature/humidity sensors, a leak-detection cable input and eight digital inputs. It is a Modbus TCP server only. All values are 16-bit holding registers: temperatures in hundredths of a degree (C and F copies), humidity in %RH, leak and cable status flags and digital input states and alarms.
This page lists 71 Modbus registers for the RLE Technologies Falcon F200 environment and leak monitoring appliance (Modbus TCP) — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from RLE Technologies’s own free documentation (linked below) and checked against it.
- Manufacturer
- RLE Technologies
- Model
- Falcon F200 environment and leak monitoring appliance (Modbus TCP)
- Equipment type
- Sensor (environmental / leak monitor)
- Registers
- 71 (0 writable)
- Transport
- Modbus TCP
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Firmware
- 4100.1 and above
- Also known as
- F200, Falcon F200
- Source document
- F200 - Modbus Communications · v06.21 · rev. 2021-06
Integration notes: RLE Technologies Falcon F200 environment and leak monitoring appliance (Modbus TCP)
Poll the F200 over Modbus TCP with FC3. Read 40071-40073 for leak, missing cable and cable break, 40010/40013 for sensor 1 temperature and humidity, and 40004/40005 for digital input alarm and state bitfields.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 70 | Leak detected | UINT16 | Leak detected | Read |
| HR 72 | Cable break alarm | UINT16 | Cable break | Read |
| HR 71 | No sensing cable connected | UINT16 | No sensing cable connected | Read |
| HR 9 | Sensor 1 temperature | UINT16 | Sensor 1 temperature (°C x 100) | Read |
| HR 12 | Sensor 1 humidity | UINT16 | Sensor 1 humidity | Read |
| HR 3 | Digital input alarm status (all inputs) | BITMAP16 | Digital input alarm bitfield | Read |
Enable Modbus control & writes
The guide only says the F200 acts as a Modbus TCP server; it does not describe enabling or configuring Modbus.
Byte order & addressing
- Digital input alarm registers 40090-40097 stay 0 unless the input's notification option in the web interface is set to something other than Disabled.
Watch out for
- Each external sensor has its own fixed block of registers; 40006 reports whether sensors are connected.
RLE Technologies Falcon F200 environment and leak monitoring appliance (Modbus TCP) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 2doc 40003 | Digital input alarm condition (all inputs) | Per input: 1 = alarms when closed, 0 = alarms when open. | BITMAP16 | Read | bit 0 = Digital input 1 alarms when closed; bit 1 = Digital input 2 alarms when closed; bit 2 = Digital input 3 alarms when closed; bit 3 = Digital input 4 alarms when closed; bit 4 = Digital input 5 alarms when closed; bit 5 = Digital input 6 alarms when closed; bit 6 = Digital input 7 alarms when closed; bit 7 = Digital input 8 alarms when closed | |||
| HR | 3doc 40004 | Digital input alarm status (all inputs) | BITMAP16 | Read | bit 0 = Digital input 1 in alarm; bit 1 = Digital input 2 in alarm; bit 2 = Digital input 3 in alarm; bit 3 = Digital input 4 in alarm; bit 4 = Digital input 5 in alarm; bit 5 = Digital input 6 in alarm; bit 6 = Digital input 7 in alarm; bit 7 = Digital input 8 in alarm | ||||
| HR | 4doc 40005 | Digital input current state (all inputs) | BITMAP16 | Read | bit 0 = Digital input 1 closed; bit 1 = Digital input 2 closed; bit 2 = Digital input 3 closed; bit 3 = Digital input 4 closed; bit 4 = Digital input 5 closed; bit 5 = Digital input 6 closed; bit 6 = Digital input 7 closed; bit 7 = Digital input 8 closed | ||||
| HR | 5doc 40006 | Sensors connected status | UINT16 | Read | 0 = Not connected; 1 = Connected | ||||
| HR | 8doc 40009 | Sensor 1 family code | Identifies the external sensor type. | UINT16 | Read | ||||
| HR | 9doc 40010 | Sensor 1 temperature | UINT16 | × 0.01 | °C | Read | |||
| HR | 10doc 40011 | Sensor 1 high temperature threshold | UINT16 | × 0.01 | °C | Read | |||
| HR | 11doc 40012 | Sensor 1 low temperature threshold | UINT16 | × 0.01 | °C | Read | |||
| HR | 12doc 40013 | Sensor 1 humidity | UINT16 | %RH | Read | ||||
| HR | 13doc 40014 | Sensor 1 high humidity threshold | UINT16 | %RH | Read | ||||
| HR | 14doc 40015 | Sensor 1 low humidity threshold | UINT16 | %RH | Read | ||||
| HR | 15doc 40016 | Sensor 2 family code | Identifies the external sensor type. | UINT16 | Read | ||||
| HR | 16doc 40017 | Sensor 2 temperature | UINT16 | × 0.01 | °C | Read | |||
| HR | 17doc 40018 | Sensor 2 high temperature threshold | UINT16 | × 0.01 | °C | Read | |||
| HR | 18doc 40019 | Sensor 2 low temperature threshold | UINT16 | × 0.01 | °C | Read | |||
| HR | 19doc 40020 | Sensor 2 humidity | UINT16 | %RH | Read | ||||
| HR | 20doc 40021 | Sensor 2 high humidity threshold | UINT16 | %RH | Read | ||||
| HR | 21doc 40022 | Sensor 2 low humidity threshold | UINT16 | %RH | Read | ||||
| HR | 22doc 40023 | Sensor 3 family code | Identifies the external sensor type. | UINT16 | Read | ||||
| HR | 23doc 40024 | Sensor 3 temperature | UINT16 | × 0.01 | °C | Read | |||
| HR | 24doc 40025 | Sensor 3 high temperature threshold | UINT16 | × 0.01 | °C | Read | |||
| HR | 25doc 40026 | Sensor 3 low temperature threshold | UINT16 | × 0.01 | °C | Read | |||
| HR | 26doc 40027 | Sensor 3 humidity | UINT16 | %RH | Read | ||||
| HR | 27doc 40028 | Sensor 3 high humidity threshold | UINT16 | %RH | Read | ||||
| HR | 28doc 40029 | Sensor 3 low humidity threshold | UINT16 | %RH | Read | ||||
| HR | 29doc 40030 | Sensor 4 family code | Identifies the external sensor type. | UINT16 | Read | ||||
| HR | 30doc 40031 | Sensor 4 temperature | UINT16 | × 0.01 | °C | Read | |||
| HR | 31doc 40032 | Sensor 4 high temperature threshold | UINT16 | × 0.01 | °C | Read | |||
| HR | 32doc 40033 | Sensor 4 low temperature threshold | UINT16 | × 0.01 | °C | Read | |||
| HR | 33doc 40034 | Sensor 4 humidity | UINT16 | %RH | Read | ||||
| HR | 34doc 40035 | Sensor 4 high humidity threshold | UINT16 | %RH | Read | ||||
| HR | 35doc 40036 | Sensor 4 low humidity threshold | UINT16 | %RH | Read | ||||
| HR | 37doc 40038 | Sensor 1 temperature (°F) | UINT16 | × 0.01 | °F | Read | |||
| HR | 38doc 40039 | Sensor 1 high temperature threshold (°F) | UINT16 | × 0.01 | °F | Read | |||
| HR | 39doc 40040 | Sensor 1 low temperature threshold (°F) | UINT16 | × 0.01 | °F | Read | |||
| HR | 44doc 40045 | Sensor 2 temperature (°F) | UINT16 | × 0.01 | °F | Read | |||
| HR | 45doc 40046 | Sensor 2 high temperature threshold (°F) | UINT16 | × 0.01 | °F | Read | |||
| HR | 46doc 40047 | Sensor 2 low temperature threshold (°F) | UINT16 | × 0.01 | °F | Read | |||
| HR | 51doc 40052 | Sensor 3 temperature (°F) | UINT16 | × 0.01 | °F | Read | |||
| HR | 52doc 40053 | Sensor 3 high temperature threshold (°F) | UINT16 | × 0.01 | °F | Read | |||
| HR | 53doc 40054 | Sensor 3 low temperature threshold (°F) | UINT16 | × 0.01 | °F | Read | |||
| HR | 58doc 40059 | Sensor 4 temperature (°F) | UINT16 | × 0.01 | °F | Read | |||
| HR | 59doc 40060 | Sensor 4 high temperature threshold (°F) | UINT16 | × 0.01 | °F | Read | |||
| HR | 60doc 40061 | Sensor 4 low temperature threshold (°F) | UINT16 | × 0.01 | °F | Read | |||
| HR | 70doc 40071 | Leak detected | UINT16 | Read | 0 = No leak; 1 = Leak detected | ||||
| HR | 71doc 40072 | No sensing cable connected | UINT16 | Read | 0 = Cable connected; 1 = No cable | ||||
| HR | 72doc 40073 | Cable break alarm | UINT16 | Read | 0 = No cable break; 1 = Cable break | ||||
| HR | 79doc 40080 | Digital input 1 state | UINT16 | Read | 0 = Open; 1 = Closed | ||||
| HR | 80doc 40081 | Digital input 2 state | UINT16 | Read | 0 = Open; 1 = Closed | ||||
| HR | 81doc 40082 | Digital input 3 state | UINT16 | Read | 0 = Open; 1 = Closed | ||||
| HR | 82doc 40083 | Digital input 4 state | UINT16 | Read | 0 = Open; 1 = Closed | ||||
| HR | 83doc 40084 | Digital input 5 state | UINT16 | Read | 0 = Open; 1 = Closed | ||||
| HR | 84doc 40085 | Digital input 6 state | UINT16 | Read | 0 = Open; 1 = Closed | ||||
| HR | 85doc 40086 | Digital input 7 state | UINT16 | Read | 0 = Open; 1 = Closed | ||||
| HR | 86doc 40087 | Digital input 8 state | UINT16 | Read | 0 = Open; 1 = Closed | ||||
| HR | 89doc 40090 | Digital input 1 alarm | Only reports alarms when the input's notification is not 'Disabled'. | UINT16 | Read | 0 = Normal; 1 = In alarm | |||
| HR | 90doc 40091 | Digital input 2 alarm | Only reports alarms when the input's notification is not 'Disabled'. | UINT16 | Read | 0 = Normal; 1 = In alarm | |||
| HR | 91doc 40092 | Digital input 3 alarm | Only reports alarms when the input's notification is not 'Disabled'. | UINT16 | Read | 0 = Normal; 1 = In alarm | |||
| HR | 92doc 40093 | Digital input 4 alarm | Only reports alarms when the input's notification is not 'Disabled'. | UINT16 | Read | 0 = Normal; 1 = In alarm | |||
| HR | 93doc 40094 | Digital input 5 alarm | Only reports alarms when the input's notification is not 'Disabled'. | UINT16 | Read | 0 = Normal; 1 = In alarm | |||
| HR | 94doc 40095 | Digital input 6 alarm | Only reports alarms when the input's notification is not 'Disabled'. | UINT16 | Read | 0 = Normal; 1 = In alarm | |||
| HR | 95doc 40096 | Digital input 7 alarm | Only reports alarms when the input's notification is not 'Disabled'. | UINT16 | Read | 0 = Normal; 1 = In alarm | |||
| HR | 96doc 40097 | Digital input 8 alarm | Only reports alarms when the input's notification is not 'Disabled'. | UINT16 | Read | 0 = Normal; 1 = In alarm | |||
| HR | 99doc 40100 | Digital input 1 alarm polarity | UINT16 | Read | 0 = Alarm when input open; 1 = Alarm when input closed | ||||
| HR | 100doc 40101 | Digital input 2 alarm polarity | UINT16 | Read | 0 = Alarm when input open; 1 = Alarm when input closed | ||||
| HR | 101doc 40102 | Digital input 3 alarm polarity | UINT16 | Read | 0 = Alarm when input open; 1 = Alarm when input closed | ||||
| HR | 102doc 40103 | Digital input 4 alarm polarity | UINT16 | Read | 0 = Alarm when input open; 1 = Alarm when input closed | ||||
| HR | 103doc 40104 | Digital input 5 alarm polarity | UINT16 | Read | 0 = Alarm when input open; 1 = Alarm when input closed | ||||
| HR | 104doc 40105 | Digital input 6 alarm polarity | UINT16 | Read | 0 = Alarm when input open; 1 = Alarm when input closed | ||||
| HR | 105doc 40106 | Digital input 7 alarm polarity | UINT16 | Read | 0 = Alarm when input open; 1 = Alarm when input closed | ||||
| HR | 106doc 40107 | Digital input 8 alarm polarity | UINT16 | Read | 0 = Alarm when input open; 1 = Alarm when input closed |
Notes on this map
- Temperature registers are 'Celsius x 100' or 'Fahrenheit x 100' with range 0-65535 (unsigned as published), so 2150 = 21.50 °C. The guide does not say how sub-zero temperatures are reported.
- Humidity is published as '% Relative Humidity' with no multiplier; scale 1 is used.
- Only 16-bit registers exist; no word-order question arises.
- The guide gives no unit ID or TCP port.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the RLE Technologies Falcon F200 environment and leak monitoring appliance (Modbus TCP)
What Modbus registers does the RLE Technologies Falcon F200 environment and leak monitoring appliance (Modbus TCP) have?
This map lists 71 registers: 71 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the RLE Technologies Falcon F200 environment and leak monitoring appliance (Modbus TCP) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. RLE prints every register in 4xxxx form ('Read Output Registers', read with FC3). Under the Modicon convention 40010 is wire address 9. The guide has no example frame that confirms the offset.
What are the minimum Modbus registers to integrate the RLE Technologies Falcon F200 environment and leak monitoring appliance (Modbus TCP)?
Start with HR 70 Leak detected (Leak detected); HR 72 Cable break alarm (Cable break); HR 71 No sensing cable connected (No sensing cable connected); HR 9 Sensor 1 temperature (Sensor 1 temperature (°C x 100)); HR 12 Sensor 1 humidity (Sensor 1 humidity); HR 3 Digital input alarm status (all inputs) (Digital input alarm bitfield).
How do I enable Modbus control of the RLE Technologies Falcon F200 environment and leak monitoring appliance (Modbus TCP)?
The guide only says the F200 acts as a Modbus TCP server; it does not describe enabling or configuring Modbus.
Where is the official RLE Technologies Falcon F200 environment and leak monitoring appliance (Modbus TCP) Modbus documentation?
The source is F200 - Modbus Communications (v06.21), revision 2021-06, published free by RLE Technologies at https://WWW.RLETECH.COM/wp-content/uploads/2021/06/F200_Modbus_Registers-06.21.pdf.
More RLE Technologies Modbus register maps
Other gas detectors register maps
- Sensor (fixed gas detector)
Teledyne Detcon Model IR-700 infrared combustible / CO2 gas sensor (RS-485 Modbus)
Teledyne Detcon IR-700 smart sensors with the 4-20 mA and RS-485 Modbus outputs, instruction manual Document #3169, Rev. 4.9.
Also known as: IR-700, Detcon IR-700, Teledyne Detcon IR-700 - Sensor (refrigerant leak detector)
Amphenol Telaire T3400 series refrigerant (A2L) leak sensor
Amphenol Telaire T3400 series refrigerant sensors (R454B / R32) with RS-485 Modbus RTU, user instructions AS-T63381B (04/2025, marked provisional).
Also known as: Telaire T3400, T3400 R454B, T3400 R32 - Sensor (fixed gas detector)
New Cosmos Electric PS-7-M series extractive pump gas detector (Modbus RTU / TCP)
New Cosmos PS-7-M series extractive pump gas detectors (main unit with base unit) over RS-485 Modbus RTU or Ethernet Modbus TCP, communication specifications guide GAE-159-01.
Also known as: PS-7-M, PS-7 - Sensor (fixed gas detector)
Teledyne Detcon Model FP-624D MicroSafe combustible gas sensor (RS-485 Modbus)
Teledyne Detcon FP-624D MicroSafe catalytic LEL sensor with 4-20 mA, relays and RS-485 Modbus RTU, instruction manual Document #3598 Rev. 1.7.
Also known as: FP-624D, MicroSafe FP-624D, Detcon FP-624D - Sensor (fixed gas detector)
Teledyne Oldham Simtronics OLCT 700 / OLCT 710 IR infrared combustible / CO2 gas detector (RS-485 Modbus)
Teledyne Oldham Simtronics OLCT 700 and OLCT 710 IR detectors with 4-20 mA and RS-485 Modbus RTU, manual NP700IRIMEN Revision E.0.
Also known as: OLCT 700 IR, OLCT 710 IR, Oldham OLCT 700 IR, 700 IR series - Sensor (extractive gas detector)
Honeywell Midas gas detector (Modbus/TCP)
Honeywell Midas extractive gas detectors (original Midas platform, software V1.08), user manual 3010M5000 revision 32, Appendix A Modbus/TCP interface.
Also known as: Midas, MIDAS gas detector
All gas detectors Modbus register maps →
Source: F200 - Modbus Communications · v06.21 · rev. 2021-06. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.