Easy Modbus
  1. Home
  2. Modbus register maps
  3. RLE Technologies
  4. Falcon F200 environment and leak monitoring appliance (Modbus TCP)

Sensor (environmental / leak monitor) · Modbus register map

RLE Technologies Falcon F200 environment and leak monitoring appliance (Modbus TCP) Modbus register map

Updated 17 November 2026

Short answer

The Falcon F200 is a small monitoring appliance for data rooms: up to four external temperature/humidity sensors, a leak-detection cable input and eight digital inputs. It is a Modbus TCP server only. All values are 16-bit holding registers: temperatures in hundredths of a degree (C and F copies), humidity in %RH, leak and cable status flags and digital input states and alarms.

This page lists 71 Modbus registers for the RLE Technologies Falcon F200 environment and leak monitoring appliance (Modbus TCP) — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from RLE Technologies’s own free documentation (linked below) and checked against it.

Manufacturer
RLE Technologies
Model
Falcon F200 environment and leak monitoring appliance (Modbus TCP)
Equipment type
Sensor (environmental / leak monitor)
Registers
71 (0 writable)
Transport
Modbus TCP
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Firmware
4100.1 and above
Also known as
F200, Falcon F200
Source document
F200 - Modbus Communications · v06.21 · rev. 2021-06
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: RLE Technologies Falcon F200 environment and leak monitoring appliance (Modbus TCP)

Integration in brief

Poll the F200 over Modbus TCP with FC3. Read 40071-40073 for leak, missing cable and cable break, 40010/40013 for sensor 1 temperature and humidity, and 40004/40005 for digital input alarm and state bitfields.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 70Leak detectedUINT16Leak detectedRead
HR 72Cable break alarmUINT16Cable breakRead
HR 71No sensing cable connectedUINT16No sensing cable connectedRead
HR 9Sensor 1 temperatureUINT16Sensor 1 temperature (°C x 100)Read
HR 12Sensor 1 humidityUINT16Sensor 1 humidityRead
HR 3Digital input alarm status (all inputs)BITMAP16Digital input alarm bitfieldRead

Enable Modbus control & writes

The guide only says the F200 acts as a Modbus TCP server; it does not describe enabling or configuring Modbus.

Byte order & addressing

Watch out for

RLE Technologies Falcon F200 environment and leak monitoring appliance (Modbus TCP) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

71 of 71 shown
RLE Technologies Falcon F200 environment and leak monitoring appliance (Modbus TCP) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR2doc 40003Digital input alarm condition (all inputs)Per input: 1 = alarms when closed, 0 = alarms when open.BITMAP16Readbit 0 = Digital input 1 alarms when closed; bit 1 = Digital input 2 alarms when closed; bit 2 = Digital input 3 alarms when closed; bit 3 = Digital input 4 alarms when closed; bit 4 = Digital input 5 alarms when closed; bit 5 = Digital input 6 alarms when closed; bit 6 = Digital input 7 alarms when closed; bit 7 = Digital input 8 alarms when closed
HR3doc 40004Digital input alarm status (all inputs)BITMAP16Readbit 0 = Digital input 1 in alarm; bit 1 = Digital input 2 in alarm; bit 2 = Digital input 3 in alarm; bit 3 = Digital input 4 in alarm; bit 4 = Digital input 5 in alarm; bit 5 = Digital input 6 in alarm; bit 6 = Digital input 7 in alarm; bit 7 = Digital input 8 in alarm
HR4doc 40005Digital input current state (all inputs)BITMAP16Readbit 0 = Digital input 1 closed; bit 1 = Digital input 2 closed; bit 2 = Digital input 3 closed; bit 3 = Digital input 4 closed; bit 4 = Digital input 5 closed; bit 5 = Digital input 6 closed; bit 6 = Digital input 7 closed; bit 7 = Digital input 8 closed
HR5doc 40006Sensors connected statusUINT16Read0 = Not connected; 1 = Connected
HR8doc 40009Sensor 1 family codeIdentifies the external sensor type.UINT16Read
HR9doc 40010Sensor 1 temperatureUINT16× 0.01°CRead
HR10doc 40011Sensor 1 high temperature thresholdUINT16× 0.01°CRead
HR11doc 40012Sensor 1 low temperature thresholdUINT16× 0.01°CRead
HR12doc 40013Sensor 1 humidityUINT16%RHRead
HR13doc 40014Sensor 1 high humidity thresholdUINT16%RHRead
HR14doc 40015Sensor 1 low humidity thresholdUINT16%RHRead
HR15doc 40016Sensor 2 family codeIdentifies the external sensor type.UINT16Read
HR16doc 40017Sensor 2 temperatureUINT16× 0.01°CRead
HR17doc 40018Sensor 2 high temperature thresholdUINT16× 0.01°CRead
HR18doc 40019Sensor 2 low temperature thresholdUINT16× 0.01°CRead
HR19doc 40020Sensor 2 humidityUINT16%RHRead
HR20doc 40021Sensor 2 high humidity thresholdUINT16%RHRead
HR21doc 40022Sensor 2 low humidity thresholdUINT16%RHRead
HR22doc 40023Sensor 3 family codeIdentifies the external sensor type.UINT16Read
HR23doc 40024Sensor 3 temperatureUINT16× 0.01°CRead
HR24doc 40025Sensor 3 high temperature thresholdUINT16× 0.01°CRead
HR25doc 40026Sensor 3 low temperature thresholdUINT16× 0.01°CRead
HR26doc 40027Sensor 3 humidityUINT16%RHRead
HR27doc 40028Sensor 3 high humidity thresholdUINT16%RHRead
HR28doc 40029Sensor 3 low humidity thresholdUINT16%RHRead
HR29doc 40030Sensor 4 family codeIdentifies the external sensor type.UINT16Read
HR30doc 40031Sensor 4 temperatureUINT16× 0.01°CRead
HR31doc 40032Sensor 4 high temperature thresholdUINT16× 0.01°CRead
HR32doc 40033Sensor 4 low temperature thresholdUINT16× 0.01°CRead
HR33doc 40034Sensor 4 humidityUINT16%RHRead
HR34doc 40035Sensor 4 high humidity thresholdUINT16%RHRead
HR35doc 40036Sensor 4 low humidity thresholdUINT16%RHRead
HR37doc 40038Sensor 1 temperature (°F)UINT16× 0.01°FRead
HR38doc 40039Sensor 1 high temperature threshold (°F)UINT16× 0.01°FRead
HR39doc 40040Sensor 1 low temperature threshold (°F)UINT16× 0.01°FRead
HR44doc 40045Sensor 2 temperature (°F)UINT16× 0.01°FRead
HR45doc 40046Sensor 2 high temperature threshold (°F)UINT16× 0.01°FRead
HR46doc 40047Sensor 2 low temperature threshold (°F)UINT16× 0.01°FRead
HR51doc 40052Sensor 3 temperature (°F)UINT16× 0.01°FRead
HR52doc 40053Sensor 3 high temperature threshold (°F)UINT16× 0.01°FRead
HR53doc 40054Sensor 3 low temperature threshold (°F)UINT16× 0.01°FRead
HR58doc 40059Sensor 4 temperature (°F)UINT16× 0.01°FRead
HR59doc 40060Sensor 4 high temperature threshold (°F)UINT16× 0.01°FRead
HR60doc 40061Sensor 4 low temperature threshold (°F)UINT16× 0.01°FRead
HR70doc 40071Leak detectedUINT16Read0 = No leak; 1 = Leak detected
HR71doc 40072No sensing cable connectedUINT16Read0 = Cable connected; 1 = No cable
HR72doc 40073Cable break alarmUINT16Read0 = No cable break; 1 = Cable break
HR79doc 40080Digital input 1 stateUINT16Read0 = Open; 1 = Closed
HR80doc 40081Digital input 2 stateUINT16Read0 = Open; 1 = Closed
HR81doc 40082Digital input 3 stateUINT16Read0 = Open; 1 = Closed
HR82doc 40083Digital input 4 stateUINT16Read0 = Open; 1 = Closed
HR83doc 40084Digital input 5 stateUINT16Read0 = Open; 1 = Closed
HR84doc 40085Digital input 6 stateUINT16Read0 = Open; 1 = Closed
HR85doc 40086Digital input 7 stateUINT16Read0 = Open; 1 = Closed
HR86doc 40087Digital input 8 stateUINT16Read0 = Open; 1 = Closed
HR89doc 40090Digital input 1 alarmOnly reports alarms when the input's notification is not 'Disabled'.UINT16Read0 = Normal; 1 = In alarm
HR90doc 40091Digital input 2 alarmOnly reports alarms when the input's notification is not 'Disabled'.UINT16Read0 = Normal; 1 = In alarm
HR91doc 40092Digital input 3 alarmOnly reports alarms when the input's notification is not 'Disabled'.UINT16Read0 = Normal; 1 = In alarm
HR92doc 40093Digital input 4 alarmOnly reports alarms when the input's notification is not 'Disabled'.UINT16Read0 = Normal; 1 = In alarm
HR93doc 40094Digital input 5 alarmOnly reports alarms when the input's notification is not 'Disabled'.UINT16Read0 = Normal; 1 = In alarm
HR94doc 40095Digital input 6 alarmOnly reports alarms when the input's notification is not 'Disabled'.UINT16Read0 = Normal; 1 = In alarm
HR95doc 40096Digital input 7 alarmOnly reports alarms when the input's notification is not 'Disabled'.UINT16Read0 = Normal; 1 = In alarm
HR96doc 40097Digital input 8 alarmOnly reports alarms when the input's notification is not 'Disabled'.UINT16Read0 = Normal; 1 = In alarm
HR99doc 40100Digital input 1 alarm polarityUINT16Read0 = Alarm when input open; 1 = Alarm when input closed
HR100doc 40101Digital input 2 alarm polarityUINT16Read0 = Alarm when input open; 1 = Alarm when input closed
HR101doc 40102Digital input 3 alarm polarityUINT16Read0 = Alarm when input open; 1 = Alarm when input closed
HR102doc 40103Digital input 4 alarm polarityUINT16Read0 = Alarm when input open; 1 = Alarm when input closed
HR103doc 40104Digital input 5 alarm polarityUINT16Read0 = Alarm when input open; 1 = Alarm when input closed
HR104doc 40105Digital input 6 alarm polarityUINT16Read0 = Alarm when input open; 1 = Alarm when input closed
HR105doc 40106Digital input 7 alarm polarityUINT16Read0 = Alarm when input open; 1 = Alarm when input closed
HR106doc 40107Digital input 8 alarm polarityUINT16Read0 = Alarm when input open; 1 = Alarm when input closed

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the RLE Technologies Falcon F200 environment and leak monitoring appliance (Modbus TCP)

What Modbus registers does the RLE Technologies Falcon F200 environment and leak monitoring appliance (Modbus TCP) have?

This map lists 71 registers: 71 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the RLE Technologies Falcon F200 environment and leak monitoring appliance (Modbus TCP) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. RLE prints every register in 4xxxx form ('Read Output Registers', read with FC3). Under the Modicon convention 40010 is wire address 9. The guide has no example frame that confirms the offset.

What are the minimum Modbus registers to integrate the RLE Technologies Falcon F200 environment and leak monitoring appliance (Modbus TCP)?

Start with HR 70 Leak detected (Leak detected); HR 72 Cable break alarm (Cable break); HR 71 No sensing cable connected (No sensing cable connected); HR 9 Sensor 1 temperature (Sensor 1 temperature (°C x 100)); HR 12 Sensor 1 humidity (Sensor 1 humidity); HR 3 Digital input alarm status (all inputs) (Digital input alarm bitfield).

How do I enable Modbus control of the RLE Technologies Falcon F200 environment and leak monitoring appliance (Modbus TCP)?

The guide only says the F200 acts as a Modbus TCP server; it does not describe enabling or configuring Modbus.

Where is the official RLE Technologies Falcon F200 environment and leak monitoring appliance (Modbus TCP) Modbus documentation?

The source is F200 - Modbus Communications (v06.21), revision 2021-06, published free by RLE Technologies at https://WWW.RLETECH.COM/wp-content/uploads/2021/06/F200_Modbus_Registers-06.21.pdf.

More RLE Technologies Modbus register maps

Other gas detectors register maps

All gas detectors Modbus register maps →

Source: F200 - Modbus Communications · v06.21 · rev. 2021-06. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.