- PS-7-M series extractive pump gas detector (Modbus RTU / TCP)
Sensor (fixed gas detector) · Modbus register map
New Cosmos Electric PS-7-M series extractive pump gas detector (Modbus RTU / TCP) Modbus register map
Updated 17 November 2026
The New Cosmos PS-7-M is a pump-type fixed gas detector whose base unit has RS-485 Modbus RTU and Ethernet Modbus TCP ports. All data are 16-bit holding registers: current gas concentration, full-scale code, a packed device status word with alarm and fault flags, alarm settings, test and maintenance mode controls and identity data. This map covers the main published registers.
This page lists 30 Modbus registers for the New Cosmos Electric PS-7-M series extractive pump gas detector (Modbus RTU / TCP) — 10 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from New Cosmos Electric’s own free documentation (linked below) and checked against it.
- Manufacturer
- New Cosmos Electric
- Model
- PS-7-M series extractive pump gas detector (Modbus RTU / TCP)
- Equipment type
- Sensor (fixed gas detector)
- Registers
- 30 (10 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- Default serial
- 9600 baud, 8N1
- TCP port
- 502
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- PS-7-M, PS-7
Integration notes: New Cosmos Electric PS-7-M series extractive pump gas detector (Modbus RTU / TCP)
Read 41039-41040 for concentration and full-scale code and 40516 for alarms and faults; check 40011 once for the unit. Write AL set values and modes at 40051-40055 when needed.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 1038 | Gas concentration | UINT16 | Gas concentration | Read |
| HR 1039 | F.S. code | UINT16 | Full-scale code | Read |
| HR 515 | Device status | BITMAP16 | Status: alarms, faults, sign | Read |
| HR 10 | Measurement unit code | UINT16 | Measurement unit code | Read |
| HR 0 | Flow rate | UINT16 | Pump flow rate | Read |
Enable Modbus control & writes
Turn the base unit power switch OFF, select RS485 or ETHERNET with the mode DIP switch and set the unit ID on the address DIP switches (binary, 1-254), then switch the power back on.
Byte order & addressing
- Concentration has no sign in the register itself; read status bit 15.
- Use relative (0-based) addresses on the wire: 41039 -> 1038.
Network setup
- RS-485: up to 32 devices, 1.2 km at 9600 baud, built-in 120 ohm terminator switchable.
- Modbus TCP: fixed port 502.
Watch out for
- Reading or writing at 41321 and above returns an illegal address error.
New Cosmos Electric PS-7-M series extractive pump gas detector (Modbus RTU / TCP) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 40001 | Flow rate | Current pump flow (e.g. 500 = 500 ml). | UINT16 | ml | Read | |||
| HR | 1doc 40002 | AL1 set value | Percent of full scale. | UINT16 | %F.S. | Read | |||
| HR | 2doc 40003 | AL2 set value | Percent of full scale. | UINT16 | %F.S. | Read | |||
| HR | 3doc 40004 | Alarm mode combination | UINT16 | Read | 0 = High-High limit; 1 = Low-Low limit; 2 = High-Low limit | ||||
| HR | 4doc 40005 | AL1 delay time | UINT16 | s | Read | ||||
| HR | 5doc 40006 | AL2 delay time | UINT16 | s | Read | ||||
| HR | 6doc 40007 | Zero suppression value | 21 vol% suppression value for oxygen sensors. | UINT16 | % | Read | |||
| HR | 8doc 40009-40010 | Target gas | Up to 4 ASCII characters, first character in the high byte. | STRING[4] | Read | ||||
| HR | 10doc 40011 | Measurement unit code | UINT16 | Read | 0 = None; 10 = ppm; 20 = ppb; 30 = %; 40 = %LEL | ||||
| HR | 12doc 40013-40016 | Sensor unit Mfg. No. | 8 ASCII characters, first in the high byte. | STRING[8] | Read | ||||
| HR | 16doc 40017 | Test mode status | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 17doc 40018 | Test gas concentration | UINT16 | % | Read | ||||
| HR | 18doc 40019 | Sensor current value | 2.00-6.00 mA. | UINT16 | × 0.01 | mA | Read | ||
| HR | 22doc 40023 | Calibration gas concentration | UINT16 | % | Read | ||||
| HR | 30doc 40031 | Main unit software version | e.g. 112 = ver. 1.12. | UINT16 | × 0.01 | Read | |||
| HR | 31doc 40032 | Base unit software version | e.g. 110 = ver. 1.10. | UINT16 | × 0.01 | Read | |||
| HR | 47doc 40048 | Test mode on/off | UINT16 | Write | 0 = Off; 1 = On | ||||
| HR | 48doc 40049 | Test gas concentration (set) | UINT16 | % | Write | ||||
| HR | 49doc 40050 | Host maintenance mode | UINT16 | Write | 0 = Off; 1 = On (no self-reset); 17 = On (self-resets after 10 min) | ||||
| HR | 50doc 40051 | AL1 set value (set) | Always %F.S. | UINT16 | %F.S. | Write | |||
| HR | 51doc 40052 | AL2 set value (set) | Always %F.S. | UINT16 | %F.S. | Write | |||
| HR | 52doc 40053 | Alarm mode combination (set) | UINT16 | Write | 0 = High-High limit; 1 = Low-Low limit; 2 = High-Low limit | ||||
| HR | 53doc 40054 | AL1 delay time (set) | UINT16 | s | Write | ||||
| HR | 54doc 40055 | AL2 delay time (set) | UINT16 | s | Write | ||||
| HR | 55doc 40056 | Zero suppression value (set) | UINT16 | % | Write | ||||
| HR | 56doc 40057 | Calibration gas concentration (set) | UINT16 | % | Write | ||||
| HR | 515doc 40516 | Device status | High byte = status byte 1, low byte = status byte 2. | BITMAP16 | Read | bit 0 = Maintenance mode 1 on; bit 1 = Maintenance mode 2 on; bit 2 = Test mode on; bit 3 = Reserved; bit 4 = Host maintenance mode on; bit 5 = Reserved; bit 6 = Reserved; bit 7 = Device setup changed; bit 8 = AL2 alarm on; bit 9 = AL1 alarm on; bit 10 = Sensor fault (1 = not good); bit 11 = Broken pyrolyzer wire (1 = not good); bit 12 = Low flow rate 2 (1 = not good); bit 13 = Low flow rate 1 (1 = not good); bit 14 = Reserved; bit 15 = Sign of gas concentration (1 = negative) | |||
| HR | 1038doc 41039 | Gas concentration | Magnitude; sign in status bit 15; unit per 40011. | UINT16 | Read | ||||
| HR | 1039doc 41040 | F.S. code | 3-digit full-scale code (e.g. 101 = 100); see manual table 7.5. | UINT16 | Read | ||||
| HR | 1296doc 41297 | Modbus TCP port number | UINT16 | Read |
Notes on this map
- The guide is a New Cosmos document hosted by the US distributor DOD Technologies; New Cosmos does not offer it as a public download.
- All registers are single 16-bit words. Strings carry two ASCII characters per register, first character in the high byte.
- Gas concentration (41039) is an unsigned magnitude; status bit 15 (bit 7 of status byte 1) gives the sign (manual example: 5 with the sign bit set = -5 %). Its unit comes from register 40011 and its full scale from the F.S. code at 41040.
- Device status 40516: status byte 1 is the high byte and status byte 2 the low byte (manual example 0x0302 = AL1 and AL2 active while in maintenance mode 2).
- Left out: f-value and calibration gas code (ASCII), linear table X/Y pairs (two 8-bit values per register), 41284 Modbus setting change permit (meaning of the value not given), and the IP address/mask/gateway registers 41291-41299.
- RS-485 settings are fixed: 9600 baud, 8 data bits, no parity, 1 stop bit. The unit ID (1-254) is set on DIP switches and is also the last octet of the IP address for Modbus TCP.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the New Cosmos Electric PS-7-M series extractive pump gas detector (Modbus RTU / TCP)
What Modbus registers does the New Cosmos Electric PS-7-M series extractive pump gas detector (Modbus RTU / TCP) have?
This map lists 30 registers: 30 holding registers. 10 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the New Cosmos Electric PS-7-M series extractive pump gas detector (Modbus RTU / TCP) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The table gives each register as a Modicon number (40001-41321) plus a relative address in hex that goes on the wire: 40001 = relative 0, 41039 = relative 0x40E (1038). The manual's examples read 41039 at relative address 1038.
What are the minimum Modbus registers to integrate the New Cosmos Electric PS-7-M series extractive pump gas detector (Modbus RTU / TCP)?
Start with HR 1038 Gas concentration (Gas concentration); HR 1039 F.S. code (Full-scale code); HR 515 Device status (Status: alarms, faults, sign); HR 10 Measurement unit code (Measurement unit code); HR 0 Flow rate (Pump flow rate).
How do I enable Modbus control of the New Cosmos Electric PS-7-M series extractive pump gas detector (Modbus RTU / TCP)?
Turn the base unit power switch OFF, select RS485 or ETHERNET with the mode DIP switch and set the unit ID on the address DIP switches (binary, 1-254), then switch the power back on.
Where is the official New Cosmos Electric PS-7-M series extractive pump gas detector (Modbus RTU / TCP) Modbus documentation?
The source is PS-7-M Communication Specifications Guide (GAE-159-01), revision 2024-04. New Cosmos Electric doesn't publish it on its own website, so this map was re-typed from a free copy at https://dodtec.com/amfile/file/download/file/357/product/351/. It may be an older revision, so check it against the live unit.
More New Cosmos Electric Modbus register maps
Other gas detectors register maps
- Sensor (fixed gas detector)
Teledyne Detcon Model FP-624D MicroSafe combustible gas sensor (RS-485 Modbus)
Teledyne Detcon FP-624D MicroSafe catalytic LEL sensor with 4-20 mA, relays and RS-485 Modbus RTU, instruction manual Document #3598 Rev. 1.7.
Also known as: FP-624D, MicroSafe FP-624D, Detcon FP-624D - Sensor (fixed gas detector)
Teledyne Oldham Simtronics OLCT 700 / OLCT 710 IR infrared combustible / CO2 gas detector (RS-485 Modbus)
Teledyne Oldham Simtronics OLCT 700 and OLCT 710 IR detectors with 4-20 mA and RS-485 Modbus RTU, manual NP700IRIMEN Revision E.0.
Also known as: OLCT 700 IR, OLCT 710 IR, Oldham OLCT 700 IR, 700 IR series - Sensor (extractive gas detector)
Honeywell Midas gas detector (Modbus/TCP)
Honeywell Midas extractive gas detectors (original Midas platform, software V1.08), user manual 3010M5000 revision 32, Appendix A Modbus/TCP interface.
Also known as: Midas, MIDAS gas detector - Sensor (fixed gas detector)
Teledyne Detcon Model CX-IR infrared combustible gas sensor (Modbus RTU)
Teledyne Detcon CX-IR wired infrared gas sensors (RS-485 Modbus RTU and 4-20 mA), instruction manual Document #4428 Rev. 1.9.
Also known as: CX-IR, Detcon CX-IR - Sensor controller (gas detection)
Teledyne Detcon Model X40 integrated alarm and control system (Modbus slave port)
Teledyne Detcon X40 gas detection controllers (8 and 32 channel, N4X and N1P enclosures), instruction manual Document #3672 Rev. 3.8, slave port register map.
Also known as: X40-08-N4X, X40-32-N4X, X40-32-N1P, X40 controller - Sensor (refrigerant / toxic gas detector)
Danfoss Gas Detection Units GD Basic / Premium / Heavy Duty (Modbus RTU)
Danfoss GD Basic, Premium and Heavy Duty gas detection units on their own RS-485 Modbus port (Part 2 of the guide). The gas detection controller's X-bus map in Part 1 is not included.
Also known as: GDA, GDC, GDHC, GDHF, GDH, GD Basic, GD Premium, GD Heavy Duty
All gas detectors Modbus register maps →
Source: PS-7-M Communication Specifications Guide · GAE-159-01 · rev. 2024-04 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.