Sensor (extractive gas detector) · Modbus register map

New Cosmos Electric PS-8 series extractive gas detector (Modbus TCP) Modbus register map

Updated 17 November 2026

Short answer

The PS-8 is a New Cosmos pump-sampling gas detector for semiconductor process and flammable gases, holding up to 16 sensor units. Its Ethernet port is a Modbus TCP server with all data in holding registers. This map covers the integer gas readings, decimal points and flow for all 16 channels, relay states, heartbeat, alarm reset, clock, and the channel 1 settings block (other channels repeat every 101 registers).

This page lists 117 Modbus registers for the New Cosmos Electric PS-8 series extractive gas detector (Modbus TCP) — 34 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from New Cosmos Electric’s own free documentation (linked below) and checked against it.

Manufacturer
New Cosmos Electric
Model
PS-8 series extractive gas detector (Modbus TCP)
Equipment type
Sensor (extractive gas detector)
Registers
117 (34 writable)
Transport
Modbus TCP
Default unit ID
Not stated
TCP port
502
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
PS-8, PS-8 series, New Cosmos PS-8
Source document
PS-8 Series Gas Detector Instruction Manual for Communication · GAE-180-00 · rev. 2024-12
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: New Cosmos Electric PS-8 series extractive gas detector (Modbus TCP)

Integration in brief

Connect over Ethernet to 192.168.0.101 port 502 and read holding registers 0-111 (seven words per sensor) with function 03; use the integer concentration and decimal registers for each channel.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 4Sensor 1 concentration (integer)UINT16Sensor 1 concentrationRead
HR 5Sensor 1 decimal pointUINT16Sensor 1 decimal pointRead
HR 6Sensor 1 flow rateUINT16Sensor 1 flowRead
HR 112HeartbeatUINT16HeartbeatRead
HR 113Relay output monitor sensors 1/2UINT16Relay states sensors 1/2Read
HR 318Sensor 1 unitUINT16Sensor 1 unitRead/write

Enable Modbus control & writes

Menu > Device Information > Modbus: select TCP/IP. Set IP and subnet (or DHCP) under Device Information.

Byte order & addressing

Network setup

Watch out for

New Cosmos Electric PS-8 series extractive gas detector (Modbus TCP) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

117 of 117 shown
New Cosmos Electric PS-8 series extractive gas detector (Modbus TCP) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR4doc 40005Sensor 1 concentration (integer)Gas reading x 10^decimal (next register).UINT16Read
HR5doc 40006Sensor 1 decimal pointUINT16Read0 = No decimal; 1 = 1 decimal place; 2 = 2 decimal places; 3 = 3 decimal places
HR6doc 40007Sensor 1 flow rateSample flow as an FL value (0x1F4 = FL500).UINT16Read
HR11doc 40012Sensor 2 concentration (integer)Gas reading x 10^decimal (next register).UINT16Read
HR12doc 40013Sensor 2 decimal pointUINT16Read0 = No decimal; 1 = 1 decimal place; 2 = 2 decimal places; 3 = 3 decimal places
HR13doc 40014Sensor 2 flow rateSample flow as an FL value (0x1F4 = FL500).UINT16Read
HR18doc 40019Sensor 3 concentration (integer)Gas reading x 10^decimal (next register).UINT16Read
HR19doc 40020Sensor 3 decimal pointUINT16Read0 = No decimal; 1 = 1 decimal place; 2 = 2 decimal places; 3 = 3 decimal places
HR20doc 40021Sensor 3 flow rateSample flow as an FL value (0x1F4 = FL500).UINT16Read
HR25doc 40026Sensor 4 concentration (integer)Gas reading x 10^decimal (next register).UINT16Read
HR26doc 40027Sensor 4 decimal pointUINT16Read0 = No decimal; 1 = 1 decimal place; 2 = 2 decimal places; 3 = 3 decimal places
HR27doc 40028Sensor 4 flow rateSample flow as an FL value (0x1F4 = FL500).UINT16Read
HR32doc 40033Sensor 5 concentration (integer)Gas reading x 10^decimal (next register).UINT16Read
HR33doc 40034Sensor 5 decimal pointUINT16Read0 = No decimal; 1 = 1 decimal place; 2 = 2 decimal places; 3 = 3 decimal places
HR34doc 40035Sensor 5 flow rateSample flow as an FL value (0x1F4 = FL500).UINT16Read
HR39doc 40040Sensor 6 concentration (integer)Gas reading x 10^decimal (next register).UINT16Read
HR40doc 40041Sensor 6 decimal pointUINT16Read0 = No decimal; 1 = 1 decimal place; 2 = 2 decimal places; 3 = 3 decimal places
HR41doc 40042Sensor 6 flow rateSample flow as an FL value (0x1F4 = FL500).UINT16Read
HR46doc 40047Sensor 7 concentration (integer)Gas reading x 10^decimal (next register).UINT16Read
HR47doc 40048Sensor 7 decimal pointUINT16Read0 = No decimal; 1 = 1 decimal place; 2 = 2 decimal places; 3 = 3 decimal places
HR48doc 40049Sensor 7 flow rateSample flow as an FL value (0x1F4 = FL500).UINT16Read
HR53doc 40054Sensor 8 concentration (integer)Gas reading x 10^decimal (next register).UINT16Read
HR54doc 40055Sensor 8 decimal pointUINT16Read0 = No decimal; 1 = 1 decimal place; 2 = 2 decimal places; 3 = 3 decimal places
HR55doc 40056Sensor 8 flow rateSample flow as an FL value (0x1F4 = FL500).UINT16Read
HR60doc 40061Sensor 9 concentration (integer)Gas reading x 10^decimal (next register).UINT16Read
HR61doc 40062Sensor 9 decimal pointUINT16Read0 = No decimal; 1 = 1 decimal place; 2 = 2 decimal places; 3 = 3 decimal places
HR62doc 40063Sensor 9 flow rateSample flow as an FL value (0x1F4 = FL500).UINT16Read
HR67doc 40068Sensor 10 concentration (integer)Gas reading x 10^decimal (next register).UINT16Read
HR68doc 40069Sensor 10 decimal pointUINT16Read0 = No decimal; 1 = 1 decimal place; 2 = 2 decimal places; 3 = 3 decimal places
HR69doc 40070Sensor 10 flow rateSample flow as an FL value (0x1F4 = FL500).UINT16Read
HR74doc 40075Sensor 11 concentration (integer)Gas reading x 10^decimal (next register).UINT16Read
HR75doc 40076Sensor 11 decimal pointUINT16Read0 = No decimal; 1 = 1 decimal place; 2 = 2 decimal places; 3 = 3 decimal places
HR76doc 40077Sensor 11 flow rateSample flow as an FL value (0x1F4 = FL500).UINT16Read
HR81doc 40082Sensor 12 concentration (integer)Gas reading x 10^decimal (next register).UINT16Read
HR82doc 40083Sensor 12 decimal pointUINT16Read0 = No decimal; 1 = 1 decimal place; 2 = 2 decimal places; 3 = 3 decimal places
HR83doc 40084Sensor 12 flow rateSample flow as an FL value (0x1F4 = FL500).UINT16Read
HR88doc 40089Sensor 13 concentration (integer)Gas reading x 10^decimal (next register).UINT16Read
HR89doc 40090Sensor 13 decimal pointUINT16Read0 = No decimal; 1 = 1 decimal place; 2 = 2 decimal places; 3 = 3 decimal places
HR90doc 40091Sensor 13 flow rateSample flow as an FL value (0x1F4 = FL500).UINT16Read
HR95doc 40096Sensor 14 concentration (integer)Gas reading x 10^decimal (next register).UINT16Read
HR96doc 40097Sensor 14 decimal pointUINT16Read0 = No decimal; 1 = 1 decimal place; 2 = 2 decimal places; 3 = 3 decimal places
HR97doc 40098Sensor 14 flow rateSample flow as an FL value (0x1F4 = FL500).UINT16Read
HR102doc 40103Sensor 15 concentration (integer)Gas reading x 10^decimal (next register).UINT16Read
HR103doc 40104Sensor 15 decimal pointUINT16Read0 = No decimal; 1 = 1 decimal place; 2 = 2 decimal places; 3 = 3 decimal places
HR104doc 40105Sensor 15 flow rateSample flow as an FL value (0x1F4 = FL500).UINT16Read
HR109doc 40110Sensor 16 concentration (integer)Gas reading x 10^decimal (next register).UINT16Read
HR110doc 40111Sensor 16 decimal pointUINT16Read0 = No decimal; 1 = 1 decimal place; 2 = 2 decimal places; 3 = 3 decimal places
HR111doc 40112Sensor 16 flow rateSample flow as an FL value (0x1F4 = FL500).UINT16Read
HR112doc 40113HeartbeatCounts up once a second, 0-255 then wraps.UINT16Read
HR113doc 40114Relay output monitor sensors 1/2High byte sensor 1, low byte sensor 2; bits 0/1/2 = AL1/AL2/fault relay.UINT16Read
HR114doc 40115Relay output monitor sensors 3/4High byte sensor 3, low byte sensor 4; bits 0/1/2 = AL1/AL2/fault relay.UINT16Read
HR115doc 40116Relay output monitor sensors 5/6High byte sensor 5, low byte sensor 6; bits 0/1/2 = AL1/AL2/fault relay.UINT16Read
HR116doc 40117Relay output monitor sensors 7/8High byte sensor 7, low byte sensor 8; bits 0/1/2 = AL1/AL2/fault relay.UINT16Read
HR117doc 40118Relay output monitor sensors 9/10High byte sensor 9, low byte sensor 10; bits 0/1/2 = AL1/AL2/fault relay.UINT16Read
HR118doc 40119Relay output monitor sensors 11/12High byte sensor 11, low byte sensor 12; bits 0/1/2 = AL1/AL2/fault relay.UINT16Read
HR119doc 40120Relay output monitor sensors 13/14High byte sensor 13, low byte sensor 14; bits 0/1/2 = AL1/AL2/fault relay.UINT16Read
HR120doc 40121Relay output monitor sensors 15/16High byte sensor 15, low byte sensor 16; bits 0/1/2 = AL1/AL2/fault relay.UINT16Read
HR123doc 40124Setting change channel flagsBit n set when channel n+1 settings changed; write 0 after reading.BITMAP16Read/writebit 0 = Channel 1 changed; bit 1 = Channel 2 changed; bit 2 = Channel 3 changed; bit 3 = Channel 4 changed; bit 4 = Channel 5 changed; bit 5 = Channel 6 changed; bit 6 = Channel 7 changed; bit 7 = Channel 8 changed; bit 8 = Channel 9 changed; bit 9 = Channel 10 changed; bit 10 = Channel 11 changed; bit 11 = Channel 12 changed; bit 12 = Channel 13 changed; bit 13 = Channel 14 changed; bit 14 = Channel 15 changed; bit 15 = Channel 16 changed
HR250doc 40251Alarm cancellationWrite 1 to cancel a latched alarm (manual-reset mode only).UINT16Write
HR253doc 40254Alarm cancellation modeUINT16Read0 = Auto-resetting; 1 = Manual-resetting
HR254doc 40255Collective contact AL1 settingUINT16Read0 = Normally not energized; 1 = Normally energized
HR255doc 40256Collective contact AL2 settingUINT16Read0 = Normally not energized; 1 = Normally energized
HR256doc 40257Collective fault contact settingUINT16Read0 = Normally not energized; 1 = Normally energized
HR258doc 40259Date/time: month and yearHigh byte month, low byte year 0-99; access the 3 date words together.UINT16Read/write
HR259doc 40260Date/time: hour and dayHigh byte hour (24 h), low byte day.UINT16Read/write
HR260doc 40261Date/time: seconds and minutesHigh byte seconds, low byte minutes.UINT16Read/write
HR308doc 40309Sensor 1 alarm AL1 setting (integer)Setpoint x 10^decimal.UINT16Read/write
HR309doc 40310Sensor 1 alarm AL2 setting (integer)Setpoint x 10^decimal.UINT16Read/write
HR314doc 40315Sensor 1 full scale (integer)Writable only with AI module allocation.UINT16Read/write
HR315doc 40316Sensor 1 decimal point (settings)Writable only with AI module allocation.UINT16Read/write0 = No decimal; 1 = 1 decimal place; 2 = 2 decimal places; 3 = 3 decimal places
HR318doc 40319Sensor 1 unitWritable only with AI module allocation.UINT16Read/write0 = No unit; 1 = ppm; 2 = ppb; 3 = vol%; 4 = %LEL; 5 = %
HR319doc 40320Sensor 1 alarm modeUINT16Read0 = AL1 high / AL2 high; 1 = AL1 low / AL2 low; 2 = AL1 low / AL2 high
HR336doc 40337Sensor 1 alarm delay AL1UINT16sRead/write
HR337doc 40338Sensor 1 alarm delay AL2UINT16sRead/write
HR349doc 40350DO module allocationUINT16Read0 = Off; 1 = On
HR350doc 403514-20 mA analog input allocationUINT16Read0 = Off; 1 = On
HR356doc 40357Sensor 1 sensor days of useUINT16daysRead
HR357doc 40358Sensor 1 pump days of useUINT16daysRead
HR358doc 40359Sensor 1 pump dutyPump control value 0-100.UINT16%Read
HR382doc 40383Sensor 1 relay AL1 settingUINT16Read/write0 = Normally not energized; 1 = Normally energized
HR383doc 40384Sensor 1 relay AL2 settingUINT16Read/write0 = Normally not energized; 1 = Normally energized
HR384doc 40385Sensor 1 fault relay settingUINT16Read/write0 = Normally not energized; 1 = Normally energized
HR389doc 40390Sensor 1 maintenance modeUINT16Read/write0 = Off; 1 = Maintenance mode 1; 2 = Maintenance mode 2
HR390doc 40391Sensor 1 alarm test on/offUINT16Read/write0 = End alarm test; 1 = Start alarm test
HR391doc 40392Sensor 1 alarm test concentrationTest value in %FS using the fixed-point setting.UINT16Read/write
HR2628doc 42629Sensor 1 unit (grouped)UINT16Read/write0 = No unit; 1 = ppm; 2 = ppb; 3 = vol%; 4 = %LEL; 5 = %
HR2629doc 42630Sensor 2 unit (grouped)UINT16Read/write0 = No unit; 1 = ppm; 2 = ppb; 3 = vol%; 4 = %LEL; 5 = %
HR2630doc 42631Sensor 3 unit (grouped)UINT16Read/write0 = No unit; 1 = ppm; 2 = ppb; 3 = vol%; 4 = %LEL; 5 = %
HR2631doc 42632Sensor 4 unit (grouped)UINT16Read/write0 = No unit; 1 = ppm; 2 = ppb; 3 = vol%; 4 = %LEL; 5 = %
HR2632doc 42633Sensor 5 unit (grouped)UINT16Read/write0 = No unit; 1 = ppm; 2 = ppb; 3 = vol%; 4 = %LEL; 5 = %
HR2633doc 42634Sensor 6 unit (grouped)UINT16Read/write0 = No unit; 1 = ppm; 2 = ppb; 3 = vol%; 4 = %LEL; 5 = %
HR2634doc 42635Sensor 7 unit (grouped)UINT16Read/write0 = No unit; 1 = ppm; 2 = ppb; 3 = vol%; 4 = %LEL; 5 = %
HR2635doc 42636Sensor 8 unit (grouped)UINT16Read/write0 = No unit; 1 = ppm; 2 = ppb; 3 = vol%; 4 = %LEL; 5 = %
HR2636doc 42637Sensor 9 unit (grouped)UINT16Read/write0 = No unit; 1 = ppm; 2 = ppb; 3 = vol%; 4 = %LEL; 5 = %
HR2637doc 42638Sensor 10 unit (grouped)UINT16Read/write0 = No unit; 1 = ppm; 2 = ppb; 3 = vol%; 4 = %LEL; 5 = %
HR2638doc 42639Sensor 11 unit (grouped)UINT16Read/write0 = No unit; 1 = ppm; 2 = ppb; 3 = vol%; 4 = %LEL; 5 = %
HR2639doc 42640Sensor 12 unit (grouped)UINT16Read/write0 = No unit; 1 = ppm; 2 = ppb; 3 = vol%; 4 = %LEL; 5 = %
HR2640doc 42641Sensor 13 unit (grouped)UINT16Read/write0 = No unit; 1 = ppm; 2 = ppb; 3 = vol%; 4 = %LEL; 5 = %
HR2641doc 42642Sensor 14 unit (grouped)UINT16Read/write0 = No unit; 1 = ppm; 2 = ppb; 3 = vol%; 4 = %LEL; 5 = %
HR2642doc 42643Sensor 15 unit (grouped)UINT16Read/write0 = No unit; 1 = ppm; 2 = ppb; 3 = vol%; 4 = %LEL; 5 = %
HR2643doc 42644Sensor 16 unit (grouped)UINT16Read/write0 = No unit; 1 = ppm; 2 = ppb; 3 = vol%; 4 = %LEL; 5 = %
HR2728doc 42729Sensor 1 concentration (integer, grouped)Same value as the periodic block; scale by the decimal register.UINT16Read
HR2729doc 42730Sensor 2 concentration (integer, grouped)Same value as the periodic block; scale by the decimal register.UINT16Read
HR2730doc 42731Sensor 3 concentration (integer, grouped)Same value as the periodic block; scale by the decimal register.UINT16Read
HR2731doc 42732Sensor 4 concentration (integer, grouped)Same value as the periodic block; scale by the decimal register.UINT16Read
HR2732doc 42733Sensor 5 concentration (integer, grouped)Same value as the periodic block; scale by the decimal register.UINT16Read
HR2733doc 42734Sensor 6 concentration (integer, grouped)Same value as the periodic block; scale by the decimal register.UINT16Read
HR2734doc 42735Sensor 7 concentration (integer, grouped)Same value as the periodic block; scale by the decimal register.UINT16Read
HR2735doc 42736Sensor 8 concentration (integer, grouped)Same value as the periodic block; scale by the decimal register.UINT16Read
HR2736doc 42737Sensor 9 concentration (integer, grouped)Same value as the periodic block; scale by the decimal register.UINT16Read
HR2737doc 42738Sensor 10 concentration (integer, grouped)Same value as the periodic block; scale by the decimal register.UINT16Read
HR2738doc 42739Sensor 11 concentration (integer, grouped)Same value as the periodic block; scale by the decimal register.UINT16Read
HR2739doc 42740Sensor 12 concentration (integer, grouped)Same value as the periodic block; scale by the decimal register.UINT16Read
HR2740doc 42741Sensor 13 concentration (integer, grouped)Same value as the periodic block; scale by the decimal register.UINT16Read
HR2741doc 42742Sensor 14 concentration (integer, grouped)Same value as the periodic block; scale by the decimal register.UINT16Read
HR2742doc 42743Sensor 15 concentration (integer, grouped)Same value as the periodic block; scale by the decimal register.UINT16Read
HR2743doc 42744Sensor 16 concentration (integer, grouped)Same value as the periodic block; scale by the decimal register.UINT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the New Cosmos Electric PS-8 series extractive gas detector (Modbus TCP)

What Modbus registers does the New Cosmos Electric PS-8 series extractive gas detector (Modbus TCP) have?

This map lists 117 registers: 117 holding registers. 34 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the New Cosmos Electric PS-8 series extractive gas detector (Modbus TCP) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are printed as 40001-42984 with a relative (wire) address column; 40005 = relative address 4, confirmed by the function 03 example frame that reads 40005 with start address 0x0004.

What are the minimum Modbus registers to integrate the New Cosmos Electric PS-8 series extractive gas detector (Modbus TCP)?

Start with HR 4 Sensor 1 concentration (integer) (Sensor 1 concentration); HR 5 Sensor 1 decimal point (Sensor 1 decimal point); HR 6 Sensor 1 flow rate (Sensor 1 flow); HR 112 Heartbeat (Heartbeat); HR 113 Relay output monitor sensors 1/2 (Relay states sensors 1/2); HR 318 Sensor 1 unit (Sensor 1 unit).

How do I enable Modbus control of the New Cosmos Electric PS-8 series extractive gas detector (Modbus TCP)?

Menu > Device Information > Modbus: select TCP/IP. Set IP and subnet (or DHCP) under Device Information.

Where is the official New Cosmos Electric PS-8 series extractive gas detector (Modbus TCP) Modbus documentation?

The source is PS-8 Series Gas Detector Instruction Manual for Communication (GAE-180-00), revision 2024-12, published free by New Cosmos Electric at https://new-cosmos.co.jp/wp/wp-content/uploads/ind/ps8_signalsetting_manu_en.pdf.

More New Cosmos Electric Modbus register maps

Other gas detectors register maps

All gas detectors Modbus register maps →

Source: PS-8 Series Gas Detector Instruction Manual for Communication · GAE-180-00 · rev. 2024-12. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.