Gas detection controller (sensor) · Modbus register map

Gas Detection Australia GDA 4022 Modbus register map

Updated 17 November 2026

Short answer

The GDA 4022 is a two-channel gas detection controller whose isolated RS-485 port runs as a Modbus RTU slave by default. Gas concentrations are input registers, alarm states and the system fault are coils, and configuration (gas type, units, alarm behaviour, location names, mA outputs) sits in holding registers. All values are 16-bit, signed unless the document says otherwise.

This page lists 29 Modbus registers for the Gas Detection Australia GDA 4022 — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Gas Detection Australia’s own free documentation (linked below) and checked against it.

Manufacturer
Gas Detection Australia
Model
GDA 4022
Equipment type
Gas detection controller (sensor)
Registers
29 (0 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
9600 baud, 8N1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Firmware
V4.2
Also known as
4022 V4.2, GDA-4022
Source document
4022 V4.2 RS-485 (Modbus/Mimic) · 4022 V4.2 Rev 2.0 · rev. 2022-11-16
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Gas Detection Australia GDA 4022

Integration in brief

Read input registers 0-1 (function 04) for concentrations, coils 100-400 (function 01) for alarms and fault, and holding registers 200/201 once to learn the units.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 0Sensor 1 concentrationINT16Sensor 1 concentrationRead
IR 1Sensor 2 concentrationINT16Sensor 2 concentrationRead
CO 100Sensor 1 alarm 1BITSensor 1 alarm 1Read
CO 400System faultBITSystem faultRead
HR 200Sensor 1 units of concentrationINT16Sensor 1 units (sets the x10 rule)Read
HR 100Sensor 1 gas typeINT16Sensor 1 gas typeRead

Enable Modbus control & writes

The RS-485 port is a Modbus slave in the factory configuration; no enable step is needed.

Byte order & addressing

Network setup

Watch out for

Gas Detection Australia GDA 4022 Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

29 of 29 shown
Gas Detection Australia GDA 4022 Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO100doc 00101Sensor 1 alarm 11 = alarm on.BITRead
CO101doc 00102Sensor 2 alarm 11 = alarm on.BITRead
CO200doc 00201Sensor 1 alarm 21 = alarm on.BITRead
CO201doc 00202Sensor 2 alarm 21 = alarm on.BITRead
CO300doc 00301Sensor 1 alarm 31 = alarm on.BITRead
CO301doc 00302Sensor 2 alarm 31 = alarm on.BITRead
CO400doc 00401System fault1 = system in fault.BITRead
IR0doc 30001Sensor 1 concentrationRaw value; divide by 10 when the sensor unit is % LEL or % Vol.INT16Read
IR1doc 30002Sensor 2 concentrationRaw value; divide by 10 when the sensor unit is % LEL or % Vol.INT16Read
HR100doc 40101Sensor 1 gas typeINT16Read0 = CO; 1 = O2; 2 = CO2; 3 = FLM; 4 = H2; 5 = CH4; 6 = LNG; 7 = Prop; 8 = LPG; 9 = H2S; 10 = NH3; 11 = NO2; 12 = Gas; 13 = R22; 14 = R123; 15 = R134a; 16 = R407c; 17 = R410a; 18 = Refrg; 19 = (blank)
HR101doc 40102Sensor 2 gas typeINT16Read0 = CO; 1 = O2; 2 = CO2; 3 = FLM; 4 = H2; 5 = CH4; 6 = LNG; 7 = Prop; 8 = LPG; 9 = H2S; 10 = NH3; 11 = NO2; 12 = Gas; 13 = R22; 14 = R123; 15 = R134a; 16 = R407c; 17 = R410a; 18 = Refrg; 19 = (blank)
HR200doc 40201Sensor 1 units of concentrationINT16Read0 = PPM; 1 = % Vol; 2 = % LEL; 3 = PPB
HR201doc 40202Sensor 2 units of concentrationINT16Read0 = PPM; 1 = % Vol; 2 = % LEL; 3 = PPB
HR300doc 40301Sensor 1 enabledINT16Read0 = Off; 1 = On
HR301doc 40302Sensor 2 enabledINT16Read0 = Off; 1 = On
HR400doc 40401System equipment IDReturns 4020.INT16Read
HR1100doc 41101Sensor 1 alarm threshold directionINT16Read0 = Rising; 1 = Falling; 2 = Range (AL1 rising, AL2 falling, AL3 unused)
HR1101doc 41102Sensor 2 alarm threshold directionINT16Read0 = Rising; 1 = Falling; 2 = Range (AL1 rising, AL2 falling, AL3 unused)
HR1200doc 41201Sensor 1 latching alarmsINT16Read0 = Non-latching; 1 = Latching
HR1201doc 41202Sensor 2 latching alarmsINT16Read0 = Non-latching; 1 = Latching
HR1300doc 41301Sensor 1 alarm validation delay0-999 s.INT16sRead
HR1301doc 41302Sensor 2 alarm validation delay0-999 s.INT16sRead
HR1400doc 41401Sensor 1 alarm run-on time0-3600 s.INT16sRead
HR1401doc 41402Sensor 2 alarm run-on time0-3600 s.INT16sRead
HR1600doc 41601Sensor 1 location name16 characters over registers 41601-41616.STRING[32]Read
HR1700doc 41701Sensor 2 location name16 characters over registers 41701-41716.STRING[32]Read
HR2000doc 42001mA output 1 rangeINT16Read0 = 4-20 mA; 1 = 0-20 mA
HR2001doc 42002mA output 2 rangeINT16Read0 = 4-20 mA; 1 = 0-20 mA
HR2002doc 42003mA output 3 rangeINT16Read0 = 4-20 mA; 1 = 0-20 mA

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Gas Detection Australia GDA 4022

What Modbus registers does the Gas Detection Australia GDA 4022 have?

This map lists 29 registers: 7 coils, 2 input registers, 20 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Gas Detection Australia GDA 4022 Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The table gives three columns per register: the physical (wire) address, the 1-based offset and the legacy Modicon address, e.g. physical 00000 = offset 00001 = 30001. Wire addresses here are the physical column; 'documented' shows the legacy number.

What are the minimum Modbus registers to integrate the Gas Detection Australia GDA 4022?

Start with IR 0 Sensor 1 concentration (Sensor 1 concentration); IR 1 Sensor 2 concentration (Sensor 2 concentration); CO 100 Sensor 1 alarm 1 (Sensor 1 alarm 1); CO 400 System fault (System fault); HR 200 Sensor 1 units of concentration (Sensor 1 units (sets the x10 rule)); HR 100 Sensor 1 gas type (Sensor 1 gas type).

How do I enable Modbus control of the Gas Detection Australia GDA 4022?

The RS-485 port is a Modbus slave in the factory configuration; no enable step is needed.

Where is the official Gas Detection Australia GDA 4022 Modbus documentation?

The source is 4022 V4.2 RS-485 (Modbus/Mimic) (4022 V4.2 Rev 2.0), revision 2022-11-16, published free by Gas Detection Australia at https://www.gasdetectionaustralia.com.au/wp-content/uploads/2025/04/GDA-4022-V4.2-Modbus.pdf.