Gas detection controller (sensor) · Modbus register map
Gas Detection Australia GDA 4022 Modbus register map
Updated 17 November 2026
The GDA 4022 is a two-channel gas detection controller whose isolated RS-485 port runs as a Modbus RTU slave by default. Gas concentrations are input registers, alarm states and the system fault are coils, and configuration (gas type, units, alarm behaviour, location names, mA outputs) sits in holding registers. All values are 16-bit, signed unless the document says otherwise.
This page lists 29 Modbus registers for the Gas Detection Australia GDA 4022 — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Gas Detection Australia’s own free documentation (linked below) and checked against it.
- Manufacturer
- Gas Detection Australia
- Model
- GDA 4022
- Equipment type
- Gas detection controller (sensor)
- Registers
- 29 (0 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 9600 baud, 8N1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Firmware
- V4.2
- Also known as
- 4022 V4.2, GDA-4022
Integration notes: Gas Detection Australia GDA 4022
Read input registers 0-1 (function 04) for concentrations, coils 100-400 (function 01) for alarms and fault, and holding registers 200/201 once to learn the units.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 0 | Sensor 1 concentration | INT16 | Sensor 1 concentration | Read |
| IR 1 | Sensor 2 concentration | INT16 | Sensor 2 concentration | Read |
| CO 100 | Sensor 1 alarm 1 | BIT | Sensor 1 alarm 1 | Read |
| CO 400 | System fault | BIT | System fault | Read |
| HR 200 | Sensor 1 units of concentration | INT16 | Sensor 1 units (sets the x10 rule) | Read |
| HR 100 | Sensor 1 gas type | INT16 | Sensor 1 gas type | Read |
Enable Modbus control & writes
The RS-485 port is a Modbus slave in the factory configuration; no enable step is needed.
Byte order & addressing
- The controller normally answers within 20 ms; keep at least 3.5 characters (>3.7 ms) between frames.
Network setup
- Fixed serial format: 9600 baud, 8 data bits, no parity, 1 stop bit.
- Fit termination at both bus ends for runs over 30 m or noisy sites; enable master bias resistors if communication is unreliable.
Watch out for
- Ring or star wiring is not recommended for the RS-485 bus.
Gas Detection Australia GDA 4022 Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 100doc 00101 | Sensor 1 alarm 1 | 1 = alarm on. | BIT | Read | ||||
| CO | 101doc 00102 | Sensor 2 alarm 1 | 1 = alarm on. | BIT | Read | ||||
| CO | 200doc 00201 | Sensor 1 alarm 2 | 1 = alarm on. | BIT | Read | ||||
| CO | 201doc 00202 | Sensor 2 alarm 2 | 1 = alarm on. | BIT | Read | ||||
| CO | 300doc 00301 | Sensor 1 alarm 3 | 1 = alarm on. | BIT | Read | ||||
| CO | 301doc 00302 | Sensor 2 alarm 3 | 1 = alarm on. | BIT | Read | ||||
| CO | 400doc 00401 | System fault | 1 = system in fault. | BIT | Read | ||||
| IR | 0doc 30001 | Sensor 1 concentration | Raw value; divide by 10 when the sensor unit is % LEL or % Vol. | INT16 | Read | ||||
| IR | 1doc 30002 | Sensor 2 concentration | Raw value; divide by 10 when the sensor unit is % LEL or % Vol. | INT16 | Read | ||||
| HR | 100doc 40101 | Sensor 1 gas type | INT16 | Read | 0 = CO; 1 = O2; 2 = CO2; 3 = FLM; 4 = H2; 5 = CH4; 6 = LNG; 7 = Prop; 8 = LPG; 9 = H2S; 10 = NH3; 11 = NO2; 12 = Gas; 13 = R22; 14 = R123; 15 = R134a; 16 = R407c; 17 = R410a; 18 = Refrg; 19 = (blank) | ||||
| HR | 101doc 40102 | Sensor 2 gas type | INT16 | Read | 0 = CO; 1 = O2; 2 = CO2; 3 = FLM; 4 = H2; 5 = CH4; 6 = LNG; 7 = Prop; 8 = LPG; 9 = H2S; 10 = NH3; 11 = NO2; 12 = Gas; 13 = R22; 14 = R123; 15 = R134a; 16 = R407c; 17 = R410a; 18 = Refrg; 19 = (blank) | ||||
| HR | 200doc 40201 | Sensor 1 units of concentration | INT16 | Read | 0 = PPM; 1 = % Vol; 2 = % LEL; 3 = PPB | ||||
| HR | 201doc 40202 | Sensor 2 units of concentration | INT16 | Read | 0 = PPM; 1 = % Vol; 2 = % LEL; 3 = PPB | ||||
| HR | 300doc 40301 | Sensor 1 enabled | INT16 | Read | 0 = Off; 1 = On | ||||
| HR | 301doc 40302 | Sensor 2 enabled | INT16 | Read | 0 = Off; 1 = On | ||||
| HR | 400doc 40401 | System equipment ID | Returns 4020. | INT16 | Read | ||||
| HR | 1100doc 41101 | Sensor 1 alarm threshold direction | INT16 | Read | 0 = Rising; 1 = Falling; 2 = Range (AL1 rising, AL2 falling, AL3 unused) | ||||
| HR | 1101doc 41102 | Sensor 2 alarm threshold direction | INT16 | Read | 0 = Rising; 1 = Falling; 2 = Range (AL1 rising, AL2 falling, AL3 unused) | ||||
| HR | 1200doc 41201 | Sensor 1 latching alarms | INT16 | Read | 0 = Non-latching; 1 = Latching | ||||
| HR | 1201doc 41202 | Sensor 2 latching alarms | INT16 | Read | 0 = Non-latching; 1 = Latching | ||||
| HR | 1300doc 41301 | Sensor 1 alarm validation delay | 0-999 s. | INT16 | s | Read | |||
| HR | 1301doc 41302 | Sensor 2 alarm validation delay | 0-999 s. | INT16 | s | Read | |||
| HR | 1400doc 41401 | Sensor 1 alarm run-on time | 0-3600 s. | INT16 | s | Read | |||
| HR | 1401doc 41402 | Sensor 2 alarm run-on time | 0-3600 s. | INT16 | s | Read | |||
| HR | 1600doc 41601 | Sensor 1 location name | 16 characters over registers 41601-41616. | STRING[32] | Read | ||||
| HR | 1700doc 41701 | Sensor 2 location name | 16 characters over registers 41701-41716. | STRING[32] | Read | ||||
| HR | 2000doc 42001 | mA output 1 range | INT16 | Read | 0 = 4-20 mA; 1 = 0-20 mA | ||||
| HR | 2001doc 42002 | mA output 2 range | INT16 | Read | 0 = 4-20 mA; 1 = 0-20 mA | ||||
| HR | 2002doc 42003 | mA output 3 range | INT16 | Read | 0 = 4-20 mA; 1 = 0-20 mA |
Notes on this map
- Coils are read with function 01, holding registers with 03 and the concentrations with 04, as listed in the table's function-code column.
- The document says all integers are signed unless stated, so registers are typed INT16.
- Left out: sensor range, scale, alarm thresholds, hysteresis, mA output mode/scaling/update period and value/status display mode. The range/threshold formulas (value x 10 to a power taken from the scale register) are not legible in the published PDF text.
- Concentration readings are raw; the document says the value is x10 when the gas range is % LEL or % Vol, so use the units register (40201/40202) to pick the divisor.
- Documented addresses use the legacy (Modicon-style) column; coils use 0xxxx numbers.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Gas Detection Australia GDA 4022
What Modbus registers does the Gas Detection Australia GDA 4022 have?
This map lists 29 registers: 7 coils, 2 input registers, 20 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Gas Detection Australia GDA 4022 Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The table gives three columns per register: the physical (wire) address, the 1-based offset and the legacy Modicon address, e.g. physical 00000 = offset 00001 = 30001. Wire addresses here are the physical column; 'documented' shows the legacy number.
What are the minimum Modbus registers to integrate the Gas Detection Australia GDA 4022?
Start with IR 0 Sensor 1 concentration (Sensor 1 concentration); IR 1 Sensor 2 concentration (Sensor 2 concentration); CO 100 Sensor 1 alarm 1 (Sensor 1 alarm 1); CO 400 System fault (System fault); HR 200 Sensor 1 units of concentration (Sensor 1 units (sets the x10 rule)); HR 100 Sensor 1 gas type (Sensor 1 gas type).
How do I enable Modbus control of the Gas Detection Australia GDA 4022?
The RS-485 port is a Modbus slave in the factory configuration; no enable step is needed.
Where is the official Gas Detection Australia GDA 4022 Modbus documentation?
The source is 4022 V4.2 RS-485 (Modbus/Mimic) (4022 V4.2 Rev 2.0), revision 2022-11-16, published free by Gas Detection Australia at https://www.gasdetectionaustralia.com.au/wp-content/uploads/2025/04/GDA-4022-V4.2-Modbus.pdf.
Other gas detectors register maps
- Sensor (infrared gas analyzer)
Teledyne Analytical Instruments 7500 / 7600 infrared gas analyzer (Modbus RTU)
Teledyne 7500 and 7600 infrared gas analyzers with the Modbus communication function; channel registers CH1-CH8 apply to both models, CH9-CH12 to the 7600 only.
Also known as: Teledyne 7500, Teledyne 7600, Model 7500, Model 7600 - Sensor (fixed gas detector)
Teledyne Detcon Model TP-700 MOS (metal oxide) H2S sensor (RS-485 Modbus)
Teledyne Detcon TP-700 smart sensors with the 4-20 mA and RS-485 Modbus outputs, instruction manual Document #3150, Rev. 4.6.
Also known as: TP-700, Detcon TP-700, Teledyne Detcon TP-700 - Sensor (CO2 / gas)
CO2Meter CM500 CO2 sensor / controller (RS-485 Modbus RTU)
CO2Meter.com CM500 with the RS-485 Modbus RTU interface, per the vendor's 'RS485 Communications Modbus Protocol' sheet (no document number).
Also known as: CM500, CO2Meter CM500 - Sensor (environmental / leak monitor)
RLE Technologies Falcon F200 environment and leak monitoring appliance (Modbus TCP)
RLE Falcon F200 with firmware 4100.1 or later; register guide v06.21.
Also known as: F200, Falcon F200 - Sensor (fixed gas detector)
Teledyne Detcon Model IR-700 infrared combustible / CO2 gas sensor (RS-485 Modbus)
Teledyne Detcon IR-700 smart sensors with the 4-20 mA and RS-485 Modbus outputs, instruction manual Document #3169, Rev. 4.9.
Also known as: IR-700, Detcon IR-700, Teledyne Detcon IR-700 - Sensor (refrigerant leak detector)
Amphenol Telaire T3400 series refrigerant (A2L) leak sensor
Amphenol Telaire T3400 series refrigerant sensors (R454B / R32) with RS-485 Modbus RTU, user instructions AS-T63381B (04/2025, marked provisional).
Also known as: Telaire T3400, T3400 R454B, T3400 R32
All gas detectors Modbus register maps →
Source: 4022 V4.2 RS-485 (Modbus/Mimic) · 4022 V4.2 Rev 2.0 · rev. 2022-11-16. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.