Easy Modbus
  1. Home
  2. Modbus register maps
  3. Teledyne Detcon
  4. Model TP-700 MOS (metal oxide) H2S sensor (RS-485 Modbus)

Sensor (fixed gas detector) · Modbus register map

Teledyne Detcon Model TP-700 MOS (metal oxide) H2S sensor (RS-485 Modbus) Modbus register map

Updated 17 November 2026

Short answer

The TP-700 is a Teledyne Detcon fixed MOS (metal oxide) H2S sensor that reports over a 4-20 mA loop and a Modbus RTU RS-485 port at the same time. It exposes 22 holding registers: range, gas reading, span level, sensor life, fault bits, loop current, supply voltage, model-specific diagnostics, a calibration command register and the gas/units text. This map covers all of them except temperature and sensor resistance.

This page lists 15 Modbus registers for the Teledyne Detcon Model TP-700 MOS (metal oxide) H2S sensor (RS-485 Modbus) — 6 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Teledyne Detcon’s own free documentation (linked below) and checked against it.

Manufacturer
Teledyne Detcon
Model
Model TP-700 MOS (metal oxide) H2S sensor (RS-485 Modbus)
Equipment type
Sensor (fixed gas detector)
Registers
15 (6 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8N1
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
TP-700, Detcon TP-700, Teledyne Detcon TP-700
Source document
TP-700 Instruction Manual · Document #3150, Rev. 4.6 · rev. 2022-10-04
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Teledyne Detcon Model TP-700 MOS (metal oxide) H2S sensor (RS-485 Modbus)

Integration in brief

Give each sensor its own serial ID from the magnetic-switch menu, wire RS-485 at 9600 8N1 and poll holding registers 0-9 with function 03; read 40005 for faults.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 2Gas concentrationUINT16Gas concentrationRead
HR 1Detectable rangeUINT16Detectable range (full scale)Read/write
HR 5Fault status bitsBITMAP16Fault status bitsRead
HR 4Sensor lifeUINT16Sensor lifeRead
HR 84-20 mA outputUINT16Loop currentRead
HR 16Gas/units notation stringSTRING[12]Gas and units textRead

Enable Modbus control & writes

The manual describes no separate enable step; set a unique serial ID in Program Mode (Set Serial ID).

Byte order & addressing

Network setup

Watch out for

Teledyne Detcon Model TP-700 MOS (metal oxide) H2S sensor (RS-485 Modbus) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

15 of 15 shown
Teledyne Detcon Model TP-700 MOS (metal oxide) H2S sensor (RS-485 Modbus) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 40000Device typeReads 8 for a 700-series sensor.UINT16Read8 = 700 series sensor
HR1doc 40001Detectable rangeFull scale in the units of the notation string.UINT16Read/write
HR2doc 40002Gas concentrationGas reading in the units of the notation string.UINT16Read
HR3doc 40003AutoSpan levelSpan gas concentration used for calibration.UINT16Read/write
HR4doc 40004Sensor lifeRemaining sensor life.UINT16%Read
HR5doc 40005Fault status bitsFaults clear themselves when the condition clears.BITMAP16Readbit 0 = Global fault; bit 1 = AutoSpan fault; bit 2 = Temperature fault; bit 3 = 4-20 mA fault; bit 4 = Input voltage fault; bit 5 = Memory fault; bit 6 = Processor fault; bit 7 = Clearing fault; bit 8 = Stability fault; bit 9 = Range fault; bit 10 = Sensor fault; bit 11 = Zero fault; bit 12 = Sensor fault 2; bit 14 = In calibration; bit 15 = Communication error
HR6doc 40006Model numberUINT16Read1 = DM; 2 = FP; 3 = IR; 4 = TP; 5 = PID
HR7doc 40007Days since calibrationUINT16daysRead
HR8doc 400084-20 mA outputCurrent loop output value.UINT16× 0.01mARead
HR9doc 40009Input voltageUINT16× 0.01VRead
HR11doc 40011Heater powerUINT16mWRead/write
HR12doc 40012Heater voltageUINT16mVRead/write
HR14doc 40014Heater currentUINT16mARead/write
HR15doc 40015Calibration status / enableRead gives status; write starts an action.UINT16Read/write0 = Read: idle; 1 = Read: zero calibration started / Write: set zero; 2 = Read: span calibration started / Write: set span; 3 = Read: span set; 4 = Read: span calibration unsuccessful; 8 = Write: signal simulation mode; 9 = Write: set FP bridge voltage; 10 = Write: set TP heater power; 11 = Write: set IR gain
HR16doc 40016-40021Gas/units notation stringUnits, a space, then gas name, null-terminated; first character in the low byte of each register.STRING[12]Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Teledyne Detcon Model TP-700 MOS (metal oxide) H2S sensor (RS-485 Modbus)

What Modbus registers does the Teledyne Detcon Model TP-700 MOS (metal oxide) H2S sensor (RS-485 Modbus) have?

This map lists 15 registers: 15 holding registers. 6 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Teledyne Detcon Model TP-700 MOS (metal oxide) H2S sensor (RS-485 Modbus) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints registers as 40000-40021, starting at 40000, so the digits after the leading 4 are the 0-based wire address: 40000 (device type) is address 0 and 40002 (gas reading) is address 2. Only function 03 reads them; writable ones use function 06.

What are the minimum Modbus registers to integrate the Teledyne Detcon Model TP-700 MOS (metal oxide) H2S sensor (RS-485 Modbus)?

Start with HR 2 Gas concentration (Gas concentration); HR 1 Detectable range (Detectable range (full scale)); HR 5 Fault status bits (Fault status bits); HR 4 Sensor life (Sensor life); HR 8 4-20 mA output (Loop current); HR 16 Gas/units notation string (Gas and units text).

How do I enable Modbus control of the Teledyne Detcon Model TP-700 MOS (metal oxide) H2S sensor (RS-485 Modbus)?

The manual describes no separate enable step; set a unique serial ID in Program Mode (Set Serial ID).

Where is the official Teledyne Detcon Model TP-700 MOS (metal oxide) H2S sensor (RS-485 Modbus) Modbus documentation?

The source is TP-700 Instruction Manual (Document #3150, Rev. 4.6), revision 2022-10-04, published free by Teledyne Detcon at https://www.teledynegasandflamedetection.com/en-us/Products/docs/fixedgas-700series-tp-usermanual-english.pdf.

More Teledyne Detcon Modbus register maps

Other gas detectors register maps

All gas detectors Modbus register maps →

Source: TP-700 Instruction Manual · Document #3150, Rev. 4.6 · rev. 2022-10-04. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.