Sensor (fixed gas detector) · Modbus register map
Teledyne Detcon Model TP-700 MOS (metal oxide) H2S sensor (RS-485 Modbus) Modbus register map
Updated 17 November 2026
The TP-700 is a Teledyne Detcon fixed MOS (metal oxide) H2S sensor that reports over a 4-20 mA loop and a Modbus RTU RS-485 port at the same time. It exposes 22 holding registers: range, gas reading, span level, sensor life, fault bits, loop current, supply voltage, model-specific diagnostics, a calibration command register and the gas/units text. This map covers all of them except temperature and sensor resistance.
This page lists 15 Modbus registers for the Teledyne Detcon Model TP-700 MOS (metal oxide) H2S sensor (RS-485 Modbus) — 6 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Teledyne Detcon’s own free documentation (linked below) and checked against it.
- Manufacturer
- Teledyne Detcon
- Model
- Model TP-700 MOS (metal oxide) H2S sensor (RS-485 Modbus)
- Equipment type
- Sensor (fixed gas detector)
- Registers
- 15 (6 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8N1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- TP-700, Detcon TP-700, Teledyne Detcon TP-700
Integration notes: Teledyne Detcon Model TP-700 MOS (metal oxide) H2S sensor (RS-485 Modbus)
Give each sensor its own serial ID from the magnetic-switch menu, wire RS-485 at 9600 8N1 and poll holding registers 0-9 with function 03; read 40005 for faults.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 2 | Gas concentration | UINT16 | Gas concentration | Read |
| HR 1 | Detectable range | UINT16 | Detectable range (full scale) | Read/write |
| HR 5 | Fault status bits | BITMAP16 | Fault status bits | Read |
| HR 4 | Sensor life | UINT16 | Sensor life | Read |
| HR 8 | 4-20 mA output | UINT16 | Loop current | Read |
| HR 16 | Gas/units notation string | STRING[12] | Gas and units text | Read |
Enable Modbus control & writes
The manual describes no separate enable step; set a unique serial ID in Program Mode (Set Serial ID).
Byte order & addressing
- Register numbers start at 40000 = wire address 0.
- The text names function 03 as the only supported code, but the register table lists function 06 for writing the R/W registers.
- Text characters are low byte first.
Network setup
- 9600 baud, 8 data bits, no parity, 1 stop bit.
- Serial ID is entered in hexadecimal (01, 02 ... 0A ...).
Watch out for
- Bit 14 of the fault register is set while the sensor is in calibration.
Teledyne Detcon Model TP-700 MOS (metal oxide) H2S sensor (RS-485 Modbus) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 40000 | Device type | Reads 8 for a 700-series sensor. | UINT16 | Read | 8 = 700 series sensor | |||
| HR | 1doc 40001 | Detectable range | Full scale in the units of the notation string. | UINT16 | Read/write | ||||
| HR | 2doc 40002 | Gas concentration | Gas reading in the units of the notation string. | UINT16 | Read | ||||
| HR | 3doc 40003 | AutoSpan level | Span gas concentration used for calibration. | UINT16 | Read/write | ||||
| HR | 4doc 40004 | Sensor life | Remaining sensor life. | UINT16 | % | Read | |||
| HR | 5doc 40005 | Fault status bits | Faults clear themselves when the condition clears. | BITMAP16 | Read | bit 0 = Global fault; bit 1 = AutoSpan fault; bit 2 = Temperature fault; bit 3 = 4-20 mA fault; bit 4 = Input voltage fault; bit 5 = Memory fault; bit 6 = Processor fault; bit 7 = Clearing fault; bit 8 = Stability fault; bit 9 = Range fault; bit 10 = Sensor fault; bit 11 = Zero fault; bit 12 = Sensor fault 2; bit 14 = In calibration; bit 15 = Communication error | |||
| HR | 6doc 40006 | Model number | UINT16 | Read | 1 = DM; 2 = FP; 3 = IR; 4 = TP; 5 = PID | ||||
| HR | 7doc 40007 | Days since calibration | UINT16 | days | Read | ||||
| HR | 8doc 40008 | 4-20 mA output | Current loop output value. | UINT16 | × 0.01 | mA | Read | ||
| HR | 9doc 40009 | Input voltage | UINT16 | × 0.01 | V | Read | |||
| HR | 11doc 40011 | Heater power | UINT16 | mW | Read/write | ||||
| HR | 12doc 40012 | Heater voltage | UINT16 | mV | Read/write | ||||
| HR | 14doc 40014 | Heater current | UINT16 | mA | Read/write | ||||
| HR | 15doc 40015 | Calibration status / enable | Read gives status; write starts an action. | UINT16 | Read/write | 0 = Read: idle; 1 = Read: zero calibration started / Write: set zero; 2 = Read: span calibration started / Write: set span; 3 = Read: span set; 4 = Read: span calibration unsuccessful; 8 = Write: signal simulation mode; 9 = Write: set FP bridge voltage; 10 = Write: set TP heater power; 11 = Write: set IR gain | |||
| HR | 16doc 40016-40021 | Gas/units notation string | Units, a space, then gas name, null-terminated; first character in the low byte of each register. | STRING[12] | Read |
Notes on this map
- All registers are single 16-bit holding registers; the manual shares one table across DM, FP, IR, TP and PI sensors and model register 40006 tells them apart. Registers 40011-40014 change meaning with the model; only the TP-700 meanings are given here.
- TP-700 ranges are only 20, 50, 100 or 200 (register 40001); the manual says no range divisor is needed, so the reading is whole units.
- Range, reading and span level are in the units of the notation string (PPM, PPB or %).
- Register 40010 (temperature, °C) is left out: the manual gives no data type, so it is unclear how readings below 0 °C are coded.
- The notation string stores the first character in the low byte of each register (low byte, high byte, ...), the reverse of the usual Modbus string order.
- Bit 13 of the fault register is reserved.
- Factory serial ID is 01; it is set in the sensor menu (Set Serial ID) in hexadecimal.
- Register 40013 (sensor resistance, printed as "x100 Ω") is left out: the same table uses "x100" to mean the raw value is 100 times the reading (mA x100, V x100), so whether to multiply or divide by 100 is unclear.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Teledyne Detcon Model TP-700 MOS (metal oxide) H2S sensor (RS-485 Modbus)
What Modbus registers does the Teledyne Detcon Model TP-700 MOS (metal oxide) H2S sensor (RS-485 Modbus) have?
This map lists 15 registers: 15 holding registers. 6 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Teledyne Detcon Model TP-700 MOS (metal oxide) H2S sensor (RS-485 Modbus) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints registers as 40000-40021, starting at 40000, so the digits after the leading 4 are the 0-based wire address: 40000 (device type) is address 0 and 40002 (gas reading) is address 2. Only function 03 reads them; writable ones use function 06.
What are the minimum Modbus registers to integrate the Teledyne Detcon Model TP-700 MOS (metal oxide) H2S sensor (RS-485 Modbus)?
Start with HR 2 Gas concentration (Gas concentration); HR 1 Detectable range (Detectable range (full scale)); HR 5 Fault status bits (Fault status bits); HR 4 Sensor life (Sensor life); HR 8 4-20 mA output (Loop current); HR 16 Gas/units notation string (Gas and units text).
How do I enable Modbus control of the Teledyne Detcon Model TP-700 MOS (metal oxide) H2S sensor (RS-485 Modbus)?
The manual describes no separate enable step; set a unique serial ID in Program Mode (Set Serial ID).
Where is the official Teledyne Detcon Model TP-700 MOS (metal oxide) H2S sensor (RS-485 Modbus) Modbus documentation?
The source is TP-700 Instruction Manual (Document #3150, Rev. 4.6), revision 2022-10-04, published free by Teledyne Detcon at https://www.teledynegasandflamedetection.com/en-us/Products/docs/fixedgas-700series-tp-usermanual-english.pdf.
More Teledyne Detcon Modbus register maps
- Sensor (fixed gas detector)
Teledyne Detcon Model CX-IR infrared combustible gas sensor (Modbus RTU)
Teledyne Detcon CX-IR wired infrared gas sensors (RS-485 Modbus RTU and 4-20 mA), instruction manual Document #4428 Rev. 1.9.
Also known as: CX-IR, Detcon CX-IR - Sensor (fixed gas detector)
Teledyne Detcon Model DM-700 electrochemical toxic gas / oxygen sensor (RS-485 Modbus)
Teledyne Detcon DM-700 smart sensors with the 4-20 mA and RS-485 Modbus outputs, instruction manual Document #3207, Rev. 5.9.
Also known as: DM-700, Detcon DM-700, Teledyne Detcon DM-700 - Sensor (fixed gas detector)
Teledyne Detcon Model FP-624D MicroSafe combustible gas sensor (RS-485 Modbus)
Teledyne Detcon FP-624D MicroSafe catalytic LEL sensor with 4-20 mA, relays and RS-485 Modbus RTU, instruction manual Document #3598 Rev. 1.7.
Also known as: FP-624D, MicroSafe FP-624D, Detcon FP-624D - Sensor (fixed gas detector)
Teledyne Detcon Model FP-700 catalytic bead combustible gas sensor (RS-485 Modbus)
Teledyne Detcon FP-700 smart sensors with the 4-20 mA and RS-485 Modbus outputs, instruction manual Document #3168, Rev. 5.7.
Also known as: FP-700, Detcon FP-700, Teledyne Detcon FP-700 - Sensor (fixed gas detector)
Teledyne Detcon Model IR-700 infrared combustible / CO2 gas sensor (RS-485 Modbus)
Teledyne Detcon IR-700 smart sensors with the 4-20 mA and RS-485 Modbus outputs, instruction manual Document #3169, Rev. 4.9.
Also known as: IR-700, Detcon IR-700, Teledyne Detcon IR-700 - Sensor (fixed gas detector)
Teledyne Detcon Model PI-700 photoionization (PID) VOC sensor (RS-485 Modbus)
Teledyne Detcon PI-700 smart sensors with the 4-20 mA and RS-485 Modbus outputs, instruction manual Document #3228, Rev. 4.0.
Also known as: PI-700, Detcon PI-700, Teledyne Detcon PI-700 - Sensor controller (gas detection)
Teledyne Detcon Model X40 integrated alarm and control system (Modbus slave port)
Teledyne Detcon X40 gas detection controllers (8 and 32 channel, N4X and N1P enclosures), instruction manual Document #3672 Rev. 3.8, slave port register map.
Also known as: X40-08-N4X, X40-32-N4X, X40-32-N1P, X40 controller
Other gas detectors register maps
- Sensor (CO2 / gas)
CO2Meter CM500 CO2 sensor / controller (RS-485 Modbus RTU)
CO2Meter.com CM500 with the RS-485 Modbus RTU interface, per the vendor's 'RS485 Communications Modbus Protocol' sheet (no document number).
Also known as: CM500, CO2Meter CM500 - Sensor (environmental / leak monitor)
RLE Technologies Falcon F200 environment and leak monitoring appliance (Modbus TCP)
RLE Falcon F200 with firmware 4100.1 or later; register guide v06.21.
Also known as: F200, Falcon F200 - Sensor (refrigerant leak detector)
Amphenol Telaire T3400 series refrigerant (A2L) leak sensor
Amphenol Telaire T3400 series refrigerant sensors (R454B / R32) with RS-485 Modbus RTU, user instructions AS-T63381B (04/2025, marked provisional).
Also known as: Telaire T3400, T3400 R454B, T3400 R32 - Sensor (fixed gas detector)
New Cosmos Electric PS-7-M series extractive pump gas detector (Modbus RTU / TCP)
New Cosmos PS-7-M series extractive pump gas detectors (main unit with base unit) over RS-485 Modbus RTU or Ethernet Modbus TCP, communication specifications guide GAE-159-01.
Also known as: PS-7-M, PS-7 - Sensor (fixed gas detector)
Teledyne Oldham Simtronics OLCT 700 / OLCT 710 IR infrared combustible / CO2 gas detector (RS-485 Modbus)
Teledyne Oldham Simtronics OLCT 700 and OLCT 710 IR detectors with 4-20 mA and RS-485 Modbus RTU, manual NP700IRIMEN Revision E.0.
Also known as: OLCT 700 IR, OLCT 710 IR, Oldham OLCT 700 IR, 700 IR series - Sensor (extractive gas detector)
Honeywell Midas gas detector (Modbus/TCP)
Honeywell Midas extractive gas detectors (original Midas platform, software V1.08), user manual 3010M5000 revision 32, Appendix A Modbus/TCP interface.
Also known as: Midas, MIDAS gas detector
All gas detectors Modbus register maps →
Source: TP-700 Instruction Manual · Document #3150, Rev. 4.6 · rev. 2022-10-04. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.