Sensor (infrared gas analyzer) · Modbus register map

Teledyne Analytical Instruments 7500 / 7600 infrared gas analyzer (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

The Teledyne 7500 and 7600 are multi-component infrared gas analyzers with a Modbus RTU port on RS-232 (RS-485 through an external converter). Each channel reports an integer concentration plus separate decimal-point and unit registers. This map covers all channel readings, range selection and the key/display command registers.

This page lists 43 Modbus registers for the Teledyne Analytical Instruments 7500 / 7600 infrared gas analyzer (Modbus RTU) — 7 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Teledyne Analytical Instruments’s own free documentation (linked below) and checked against it.

Manufacturer
Teledyne Analytical Instruments
Model
7500 / 7600 infrared gas analyzer (Modbus RTU)
Equipment type
Sensor (infrared gas analyzer)
Registers
43 (7 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
9600 baud, 8N1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
Teledyne 7500, Teledyne 7600, Model 7500, Model 7600
Source document
Instruction Manual - Infrared Gas Analyzer Communication Functions (Modbus), Type 7500 / 7600
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Teledyne Analytical Instruments 7500 / 7600 infrared gas analyzer (Modbus RTU)

Integration in brief

Read input registers 0-23 (7500) or 0-35 (7600) in one function-04 request; for each channel combine concentration, decimal position and unit.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 0CH1 concentrationINT16CH1 concentrationRead
IR 1CH1 decimal point positionUINT16CH1 decimal positionRead
IR 2CH1 measurement unitUINT16CH1 unitRead
IR 3CH2 concentrationINT16CH2 concentrationRead
IR 4CH2 decimal point positionUINT16CH2 decimal positionRead

Enable Modbus control & writes

Set the analyzer's station number in its communication settings menu; all other serial settings are fixed.

Byte order & addressing

Network setup

Watch out for

Teledyne Analytical Instruments 7500 / 7600 infrared gas analyzer (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

43 of 43 shown
Teledyne Analytical Instruments 7500 / 7600 infrared gas analyzer (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR0doc 30001CH1 concentrationReading without decimal point (-9999 to 9999); apply the CH1 decimal register.INT16Read
IR1doc 30002CH1 decimal point positionDecimal places of the CH1 reading.UINT16Read0 = No decimals; 1 = Divide by 10; 2 = Divide by 100; 3 = Divide by 1000
IR2doc 30003CH1 measurement unitUINT16Read0 = vol%; 1 = ppm; 2 = mg/m3; 3 = g/m3
IR3doc 30004CH2 concentrationReading without decimal point (-9999 to 9999); apply the CH2 decimal register.INT16Read
IR4doc 30005CH2 decimal point positionDecimal places of the CH2 reading.UINT16Read0 = No decimals; 1 = Divide by 10; 2 = Divide by 100; 3 = Divide by 1000
IR5doc 30006CH2 measurement unitUINT16Read0 = vol%; 1 = ppm; 2 = mg/m3; 3 = g/m3
IR6doc 30007CH3 concentrationReading without decimal point (-9999 to 9999); apply the CH3 decimal register.INT16Read
IR7doc 30008CH3 decimal point positionDecimal places of the CH3 reading.UINT16Read0 = No decimals; 1 = Divide by 10; 2 = Divide by 100; 3 = Divide by 1000
IR8doc 30009CH3 measurement unitUINT16Read0 = vol%; 1 = ppm; 2 = mg/m3; 3 = g/m3
IR9doc 30010CH4 concentrationReading without decimal point (-9999 to 9999); apply the CH4 decimal register.INT16Read
IR10doc 30011CH4 decimal point positionDecimal places of the CH4 reading.UINT16Read0 = No decimals; 1 = Divide by 10; 2 = Divide by 100; 3 = Divide by 1000
IR11doc 30012CH4 measurement unitUINT16Read0 = vol%; 1 = ppm; 2 = mg/m3; 3 = g/m3
IR12doc 30013CH5 concentrationReading without decimal point (-9999 to 9999); apply the CH5 decimal register.INT16Read
IR13doc 30014CH5 decimal point positionDecimal places of the CH5 reading.UINT16Read0 = No decimals; 1 = Divide by 10; 2 = Divide by 100; 3 = Divide by 1000
IR14doc 30015CH5 measurement unitUINT16Read0 = vol%; 1 = ppm; 2 = mg/m3; 3 = g/m3
IR15doc 30016CH6 concentrationReading without decimal point (-9999 to 9999); apply the CH6 decimal register.INT16Read
IR16doc 30017CH6 decimal point positionDecimal places of the CH6 reading.UINT16Read0 = No decimals; 1 = Divide by 10; 2 = Divide by 100; 3 = Divide by 1000
IR17doc 30018CH6 measurement unitUINT16Read0 = vol%; 1 = ppm; 2 = mg/m3; 3 = g/m3
IR18doc 30019CH7 concentrationReading without decimal point (-9999 to 9999); apply the CH7 decimal register.INT16Read
IR19doc 30020CH7 decimal point positionDecimal places of the CH7 reading.UINT16Read0 = No decimals; 1 = Divide by 10; 2 = Divide by 100; 3 = Divide by 1000
IR20doc 30021CH7 measurement unitUINT16Read0 = vol%; 1 = ppm; 2 = mg/m3; 3 = g/m3
IR21doc 30022CH8 concentrationReading without decimal point (-9999 to 9999); apply the CH8 decimal register.INT16Read
IR22doc 30023CH8 decimal point positionDecimal places of the CH8 reading.UINT16Read0 = No decimals; 1 = Divide by 10; 2 = Divide by 100; 3 = Divide by 1000
IR23doc 30024CH8 measurement unitUINT16Read0 = vol%; 1 = ppm; 2 = mg/m3; 3 = g/m3
IR24doc 30025CH9 concentrationReading without decimal point (-9999 to 9999); apply the CH9 decimal register (7600 only).INT16Read
IR25doc 30026CH9 decimal point positionDecimal places of the CH9 reading (7600 only).UINT16Read0 = No decimals; 1 = Divide by 10; 2 = Divide by 100; 3 = Divide by 1000
IR26doc 30027CH9 measurement unit7600 only.UINT16Read0 = vol%; 1 = ppm; 2 = mg/m3; 3 = g/m3
IR27doc 30028CH10 concentrationReading without decimal point (-9999 to 9999); apply the CH10 decimal register (7600 only).INT16Read
IR28doc 30029CH10 decimal point positionDecimal places of the CH10 reading (7600 only).UINT16Read0 = No decimals; 1 = Divide by 10; 2 = Divide by 100; 3 = Divide by 1000
IR29doc 30030CH10 measurement unit7600 only.UINT16Read0 = vol%; 1 = ppm; 2 = mg/m3; 3 = g/m3
IR30doc 30031CH11 concentrationReading without decimal point (-9999 to 9999); apply the CH11 decimal register (7600 only).INT16Read
IR31doc 30032CH11 decimal point positionDecimal places of the CH11 reading (7600 only).UINT16Read0 = No decimals; 1 = Divide by 10; 2 = Divide by 100; 3 = Divide by 1000
IR32doc 30033CH11 measurement unit7600 only.UINT16Read0 = vol%; 1 = ppm; 2 = mg/m3; 3 = g/m3
IR33doc 30034CH12 concentrationReading without decimal point (-9999 to 9999); apply the CH12 decimal register (7600 only).INT16Read
IR34doc 30035CH12 decimal point positionDecimal places of the CH12 reading (7600 only).UINT16Read0 = No decimals; 1 = Divide by 10; 2 = Divide by 100; 3 = Divide by 1000
IR35doc 30036CH12 measurement unit7600 only.UINT16Read0 = vol%; 1 = ppm; 2 = mg/m3; 3 = g/m3
HR105doc 40106CH1 range change settingIgnored while remote range is on.UINT16Read/write0 = Range 1; 1 = Range 2
HR106doc 40107CH2 range change settingIgnored while remote range is on.UINT16Read/write0 = Range 1; 1 = Range 2
HR107doc 40108CH3 range change settingIgnored while remote range is on.UINT16Read/write0 = Range 1; 1 = Range 2
HR108doc 40109CH4 range change settingIgnored while remote range is on.UINT16Read/write0 = Range 1; 1 = Range 2
HR109doc 40110CH5 range change settingIgnored while remote range is on. 7600 only.UINT16Read/write0 = Range 1; 1 = Range 2
HR2000doc 42001Keying commandSimulates a front-panel key press.UINT16Write1 = MODE; 2 = Side; 4 = Up; 8 = Down; 16 = ESC; 32 = ENT; 64 = ZERO; 128 = SPAN
HR2001doc 42002Display changeUINT16Write1 = Return to measurement display

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Teledyne Analytical Instruments 7500 / 7600 infrared gas analyzer (Modbus RTU)

What Modbus registers does the Teledyne Analytical Instruments 7500 / 7600 infrared gas analyzer (Modbus RTU) have?

This map lists 43 registers: 36 input registers, 7 holding registers. 7 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Teledyne Analytical Instruments 7500 / 7600 infrared gas analyzer (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints a register number (30001, 40001, 42001) and a relative address (0000H, 07D0H) and says the relative address sent in the message is the lower four digits of the register number minus 1.

What are the minimum Modbus registers to integrate the Teledyne Analytical Instruments 7500 / 7600 infrared gas analyzer (Modbus RTU)?

Start with IR 0 CH1 concentration (CH1 concentration); IR 1 CH1 decimal point position (CH1 decimal position); IR 2 CH1 measurement unit (CH1 unit); IR 3 CH2 concentration (CH2 concentration); IR 4 CH2 decimal point position (CH2 decimal position).

How do I enable Modbus control of the Teledyne Analytical Instruments 7500 / 7600 infrared gas analyzer (Modbus RTU)?

Set the analyzer's station number in its communication settings menu; all other serial settings are fixed.

Where is the official Teledyne Analytical Instruments 7500 / 7600 infrared gas analyzer (Modbus RTU) Modbus documentation?

The source is Instruction Manual - Infrared Gas Analyzer Communication Functions (Modbus), Type 7500 / 7600, published free by Teledyne Analytical Instruments at https://teledyne-ai.com/en-us/Products_/Documents/Manuals/man_75007600comm.pdf.

More Teledyne Analytical Instruments Modbus register maps

Other gas detectors register maps

All gas detectors Modbus register maps →

Source: Instruction Manual - Infrared Gas Analyzer Communication Functions (Modbus), Type 7500 / 7600. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.