Water treatment controller (Sensor / controller) · Modbus register map

Walchem WebMaster WIND series Modbus TCP/IP option (s825) Modbus register map

Updated 17 November 2026

Short answer

The WIND-series WebMaster is an older Walchem water treatment controller. Its Modbus TCP/IP option serves holding registers on port 502. This map covers the live dynamic values: direct sensor readings and temperatures, 4-20 mA analog inputs and totals, analog outputs and the calculated RSI/LSI indices, all as word-swapped 32-bit floats.

This page lists 62 Modbus registers for the Walchem WebMaster WIND series Modbus TCP/IP option (s825) — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Walchem’s own free documentation (linked below) and checked against it.

Manufacturer
Walchem
Model
WebMaster WIND series Modbus TCP/IP option (s825)
Equipment type
Water treatment controller (Sensor / controller)
Registers
62 (0 writable)
Transport
Modbus TCP
Default unit ID
1
TCP port
502
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
CDAB low word first (word-swapped)
Firmware
s825v008 and higher
Also known as
WIND, WebMaster WIND, s825
Source document
WebMaster Modbus TCP/IP Option Instruction Manual (WIND series) · 180413 Rev A1
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Walchem WebMaster WIND series Modbus TCP/IP option (s825)

Integration in brief

Connect to port 502 with unit ID 1 and read holding registers with FC3, decoding each value as a CDAB float pair. Data refreshes every 4 seconds; do not poll faster than that.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 3000Sensor 1 current readingFLOAT32 CDABSensor 1 current readingRead
HR 3048Sensor 1 temperature readingFLOAT32 CDABSensor 1 temperatureRead
HR 3002Sensor 2 current readingFLOAT32 CDABSensor 2 current readingRead
HR 3096Analog input 1 measured valueFLOAT32 CDABAnalog input 1 measured valueRead
HR 3712Analog output 1 percentFLOAT32 CDABAnalog output 1 percentRead
HR 3728RSIFLOAT32 CDABRSIRead

Enable Modbus control & writes

The Modbus TCP/IP option must be fitted; set point writes need software s825v008 or higher.

Byte order & addressing

Network setup

Watch out for

Walchem WebMaster WIND series Modbus TCP/IP option (s825) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

62 of 62 shown
Walchem WebMaster WIND series Modbus TCP/IP option (s825) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR3000doc 3001Sensor 1 current readingCalibrated sensor reading in configured units.FLOAT32CDABRead
HR3002doc 3003Sensor 2 current readingCalibrated sensor reading in configured units.FLOAT32CDABRead
HR3004doc 3005Sensor 3 current readingCalibrated sensor reading in configured units.FLOAT32CDABRead
HR3006doc 3007Sensor 4 current readingCalibrated sensor reading in configured units.FLOAT32CDABRead
HR3016doc 3017Sensor 1 uncalibrated readingFLOAT32CDABRead
HR3018doc 3019Sensor 2 uncalibrated readingFLOAT32CDABRead
HR3020doc 3021Sensor 3 uncalibrated readingFLOAT32CDABRead
HR3022doc 3023Sensor 4 uncalibrated readingFLOAT32CDABRead
HR3032doc 3033Sensor 1 mV outputFLOAT32CDABmVRead
HR3034doc 3035Sensor 2 mV outputFLOAT32CDABmVRead
HR3036doc 3037Sensor 3 mV outputFLOAT32CDABmVRead
HR3038doc 3039Sensor 4 mV outputFLOAT32CDABmVRead
HR3048doc 3049Sensor 1 temperature readingFLOAT32CDABRead
HR3050doc 3051Sensor 2 temperature readingFLOAT32CDABRead
HR3052doc 3053Sensor 3 temperature readingFLOAT32CDABRead
HR3054doc 3055Sensor 4 temperature readingFLOAT32CDABRead
HR3064doc 3065Sensor 1 uncalibrated temperatureFLOAT32CDABRead
HR3066doc 3067Sensor 2 uncalibrated temperatureFLOAT32CDABRead
HR3068doc 3069Sensor 3 uncalibrated temperatureFLOAT32CDABRead
HR3070doc 3071Sensor 4 uncalibrated temperatureFLOAT32CDABRead
HR3080doc 3081Sensor 1 temperature mVFLOAT32CDABmVRead
HR3082doc 3083Sensor 2 temperature mVFLOAT32CDABmVRead
HR3084doc 3085Sensor 3 temperature mVFLOAT32CDABmVRead
HR3086doc 3087Sensor 4 temperature mVFLOAT32CDABmVRead
HR3096doc 3097Analog input 1 measured value4-20 mA input in engineering units.FLOAT32CDABRead
HR3098doc 3099Analog input 2 measured value4-20 mA input in engineering units.FLOAT32CDABRead
HR3100doc 3101Analog input 3 measured value4-20 mA input in engineering units.FLOAT32CDABRead
HR3102doc 3103Analog input 4 measured value4-20 mA input in engineering units.FLOAT32CDABRead
HR3104doc 3105Analog input 5 measured value4-20 mA input in engineering units.FLOAT32CDABRead
HR3106doc 3107Analog input 6 measured value4-20 mA input in engineering units.FLOAT32CDABRead
HR3108doc 3109Analog input 7 measured value4-20 mA input in engineering units.FLOAT32CDABRead
HR3110doc 3111Analog input 8 measured value4-20 mA input in engineering units.FLOAT32CDABRead
HR3128doc 3129Analog input 1 raw mAFLOAT32CDABmARead
HR3130doc 3131Analog input 2 raw mAFLOAT32CDABmARead
HR3132doc 3133Analog input 3 raw mAFLOAT32CDABmARead
HR3134doc 3135Analog input 4 raw mAFLOAT32CDABmARead
HR3136doc 3137Analog input 5 raw mAFLOAT32CDABmARead
HR3138doc 3139Analog input 6 raw mAFLOAT32CDABmARead
HR3140doc 3141Analog input 7 raw mAFLOAT32CDABmARead
HR3142doc 3143Analog input 8 raw mAFLOAT32CDABmARead
HR3160doc 3161Analog input 1 totalFlow meter type analog inputs only.FLOAT32CDABRead
HR3162doc 3163Analog input 2 totalFlow meter type analog inputs only.FLOAT32CDABRead
HR3164doc 3165Analog input 3 totalFlow meter type analog inputs only.FLOAT32CDABRead
HR3166doc 3167Analog input 4 totalFlow meter type analog inputs only.FLOAT32CDABRead
HR3168doc 3169Analog input 5 totalFlow meter type analog inputs only.FLOAT32CDABRead
HR3170doc 3171Analog input 6 totalFlow meter type analog inputs only.FLOAT32CDABRead
HR3172doc 3173Analog input 7 totalFlow meter type analog inputs only.FLOAT32CDABRead
HR3174doc 3175Analog input 8 totalFlow meter type analog inputs only.FLOAT32CDABRead
HR3680doc 3681Analog output 1 scaled input valueValue of the input driving the output.FLOAT32CDABRead
HR3682doc 3683Analog output 2 scaled input valueValue of the input driving the output.FLOAT32CDABRead
HR3684doc 3685Analog output 3 scaled input valueValue of the input driving the output.FLOAT32CDABRead
HR3686doc 3687Analog output 4 scaled input valueValue of the input driving the output.FLOAT32CDABRead
HR3696doc 3697Analog output 1 mA outputFLOAT32CDABmARead
HR3698doc 3699Analog output 2 mA outputFLOAT32CDABmARead
HR3700doc 3701Analog output 3 mA outputFLOAT32CDABmARead
HR3702doc 3703Analog output 4 mA outputFLOAT32CDABmARead
HR3712doc 3713Analog output 1 percentFLOAT32CDAB%Read
HR3714doc 3715Analog output 2 percentFLOAT32CDAB%Read
HR3716doc 3717Analog output 3 percentFLOAT32CDAB%Read
HR3718doc 3719Analog output 4 percentFLOAT32CDAB%Read
HR3728doc 3729RSICalculated water stability index value.FLOAT32CDABRead
HR3730doc 3731LSICalculated water saturation index value.FLOAT32CDABRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Walchem WebMaster WIND series Modbus TCP/IP option (s825)

What Modbus registers does the Walchem WebMaster WIND series Modbus TCP/IP option (s825) have?

This map lists 62 registers: 62 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Walchem WebMaster WIND series Modbus TCP/IP option (s825) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Section 4.5.1 says the published addresses are 1-based and the packet is 0-based; subtract 1 on the wire (sensor 1 current reading 3001 / 43001 is wire address 3000).

What byte order does the Walchem WebMaster WIND series Modbus TCP/IP option (s825) use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Walchem WebMaster WIND series Modbus TCP/IP option (s825)?

Start with HR 3000 Sensor 1 current reading (Sensor 1 current reading); HR 3048 Sensor 1 temperature reading (Sensor 1 temperature); HR 3002 Sensor 2 current reading (Sensor 2 current reading); HR 3096 Analog input 1 measured value (Analog input 1 measured value); HR 3712 Analog output 1 percent (Analog output 1 percent); HR 3728 RSI (RSI).

How do I enable Modbus control of the Walchem WebMaster WIND series Modbus TCP/IP option (s825)?

The Modbus TCP/IP option must be fitted; set point writes need software s825v008 or higher.

Where is the official Walchem WebMaster WIND series Modbus TCP/IP option (s825) Modbus documentation?

The source is WebMaster Modbus TCP/IP Option Instruction Manual (WIND series) (180413 Rev A1), published free by Walchem at https://walchem.com/literature/Controllers/WM/180413_WIND%20Modbus%20Manual_V08-10.pdf.

More Walchem Modbus register maps

Other valves, actuators & sensors register maps

All valves, actuators & sensors Modbus register maps →

Source: WebMaster Modbus TCP/IP Option Instruction Manual (WIND series) · 180413 Rev A1. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.