- WebMaster WIND series Modbus TCP/IP option (s825)
Water treatment controller (Sensor / controller) · Modbus register map
Walchem WebMaster WIND series Modbus TCP/IP option (s825) Modbus register map
Updated 17 November 2026
The WIND-series WebMaster is an older Walchem water treatment controller. Its Modbus TCP/IP option serves holding registers on port 502. This map covers the live dynamic values: direct sensor readings and temperatures, 4-20 mA analog inputs and totals, analog outputs and the calculated RSI/LSI indices, all as word-swapped 32-bit floats.
This page lists 62 Modbus registers for the Walchem WebMaster WIND series Modbus TCP/IP option (s825) — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Walchem’s own free documentation (linked below) and checked against it.
- Manufacturer
- Walchem
- Model
- WebMaster WIND series Modbus TCP/IP option (s825)
- Equipment type
- Water treatment controller (Sensor / controller)
- Registers
- 62 (0 writable)
- Transport
- Modbus TCP
- Default unit ID
- 1
- TCP port
- 502
- Documented addressing
- 1-based (subtract 1 for the wire address)
- 32-bit word order
- CDAB low word first (word-swapped)
- Firmware
- s825v008 and higher
- Also known as
- WIND, WebMaster WIND, s825
Integration notes: Walchem WebMaster WIND series Modbus TCP/IP option (s825)
Connect to port 502 with unit ID 1 and read holding registers with FC3, decoding each value as a CDAB float pair. Data refreshes every 4 seconds; do not poll faster than that.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 3000 | Sensor 1 current reading | FLOAT32 CDAB | Sensor 1 current reading | Read |
| HR 3048 | Sensor 1 temperature reading | FLOAT32 CDAB | Sensor 1 temperature | Read |
| HR 3002 | Sensor 2 current reading | FLOAT32 CDAB | Sensor 2 current reading | Read |
| HR 3096 | Analog input 1 measured value | FLOAT32 CDAB | Analog input 1 measured value | Read |
| HR 3712 | Analog output 1 percent | FLOAT32 CDAB | Analog output 1 percent | Read |
| HR 3728 | RSI | FLOAT32 CDAB | RSI | Read |
Enable Modbus control & writes
The Modbus TCP/IP option must be fitted; set point writes need software s825v008 or higher.
Byte order & addressing
- Addresses are 1-based: subtract 1.
- Floats are word-swapped (CDAB).
Network setup
- Network settings are configured through the WebMaster browser interface.
- Read up to 125 registers per request.
Watch out for
- The controller refreshes Modbus data every 4 seconds; polling faster only returns the same values.
- An idle TCP connection is closed after 1 minute; up to 10 connections are accepted.
Walchem WebMaster WIND series Modbus TCP/IP option (s825) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 3000doc 3001 | Sensor 1 current reading | Calibrated sensor reading in configured units. | FLOAT32 | CDAB | Read | |||
| HR | 3002doc 3003 | Sensor 2 current reading | Calibrated sensor reading in configured units. | FLOAT32 | CDAB | Read | |||
| HR | 3004doc 3005 | Sensor 3 current reading | Calibrated sensor reading in configured units. | FLOAT32 | CDAB | Read | |||
| HR | 3006doc 3007 | Sensor 4 current reading | Calibrated sensor reading in configured units. | FLOAT32 | CDAB | Read | |||
| HR | 3016doc 3017 | Sensor 1 uncalibrated reading | FLOAT32 | CDAB | Read | ||||
| HR | 3018doc 3019 | Sensor 2 uncalibrated reading | FLOAT32 | CDAB | Read | ||||
| HR | 3020doc 3021 | Sensor 3 uncalibrated reading | FLOAT32 | CDAB | Read | ||||
| HR | 3022doc 3023 | Sensor 4 uncalibrated reading | FLOAT32 | CDAB | Read | ||||
| HR | 3032doc 3033 | Sensor 1 mV output | FLOAT32 | CDAB | mV | Read | |||
| HR | 3034doc 3035 | Sensor 2 mV output | FLOAT32 | CDAB | mV | Read | |||
| HR | 3036doc 3037 | Sensor 3 mV output | FLOAT32 | CDAB | mV | Read | |||
| HR | 3038doc 3039 | Sensor 4 mV output | FLOAT32 | CDAB | mV | Read | |||
| HR | 3048doc 3049 | Sensor 1 temperature reading | FLOAT32 | CDAB | Read | ||||
| HR | 3050doc 3051 | Sensor 2 temperature reading | FLOAT32 | CDAB | Read | ||||
| HR | 3052doc 3053 | Sensor 3 temperature reading | FLOAT32 | CDAB | Read | ||||
| HR | 3054doc 3055 | Sensor 4 temperature reading | FLOAT32 | CDAB | Read | ||||
| HR | 3064doc 3065 | Sensor 1 uncalibrated temperature | FLOAT32 | CDAB | Read | ||||
| HR | 3066doc 3067 | Sensor 2 uncalibrated temperature | FLOAT32 | CDAB | Read | ||||
| HR | 3068doc 3069 | Sensor 3 uncalibrated temperature | FLOAT32 | CDAB | Read | ||||
| HR | 3070doc 3071 | Sensor 4 uncalibrated temperature | FLOAT32 | CDAB | Read | ||||
| HR | 3080doc 3081 | Sensor 1 temperature mV | FLOAT32 | CDAB | mV | Read | |||
| HR | 3082doc 3083 | Sensor 2 temperature mV | FLOAT32 | CDAB | mV | Read | |||
| HR | 3084doc 3085 | Sensor 3 temperature mV | FLOAT32 | CDAB | mV | Read | |||
| HR | 3086doc 3087 | Sensor 4 temperature mV | FLOAT32 | CDAB | mV | Read | |||
| HR | 3096doc 3097 | Analog input 1 measured value | 4-20 mA input in engineering units. | FLOAT32 | CDAB | Read | |||
| HR | 3098doc 3099 | Analog input 2 measured value | 4-20 mA input in engineering units. | FLOAT32 | CDAB | Read | |||
| HR | 3100doc 3101 | Analog input 3 measured value | 4-20 mA input in engineering units. | FLOAT32 | CDAB | Read | |||
| HR | 3102doc 3103 | Analog input 4 measured value | 4-20 mA input in engineering units. | FLOAT32 | CDAB | Read | |||
| HR | 3104doc 3105 | Analog input 5 measured value | 4-20 mA input in engineering units. | FLOAT32 | CDAB | Read | |||
| HR | 3106doc 3107 | Analog input 6 measured value | 4-20 mA input in engineering units. | FLOAT32 | CDAB | Read | |||
| HR | 3108doc 3109 | Analog input 7 measured value | 4-20 mA input in engineering units. | FLOAT32 | CDAB | Read | |||
| HR | 3110doc 3111 | Analog input 8 measured value | 4-20 mA input in engineering units. | FLOAT32 | CDAB | Read | |||
| HR | 3128doc 3129 | Analog input 1 raw mA | FLOAT32 | CDAB | mA | Read | |||
| HR | 3130doc 3131 | Analog input 2 raw mA | FLOAT32 | CDAB | mA | Read | |||
| HR | 3132doc 3133 | Analog input 3 raw mA | FLOAT32 | CDAB | mA | Read | |||
| HR | 3134doc 3135 | Analog input 4 raw mA | FLOAT32 | CDAB | mA | Read | |||
| HR | 3136doc 3137 | Analog input 5 raw mA | FLOAT32 | CDAB | mA | Read | |||
| HR | 3138doc 3139 | Analog input 6 raw mA | FLOAT32 | CDAB | mA | Read | |||
| HR | 3140doc 3141 | Analog input 7 raw mA | FLOAT32 | CDAB | mA | Read | |||
| HR | 3142doc 3143 | Analog input 8 raw mA | FLOAT32 | CDAB | mA | Read | |||
| HR | 3160doc 3161 | Analog input 1 total | Flow meter type analog inputs only. | FLOAT32 | CDAB | Read | |||
| HR | 3162doc 3163 | Analog input 2 total | Flow meter type analog inputs only. | FLOAT32 | CDAB | Read | |||
| HR | 3164doc 3165 | Analog input 3 total | Flow meter type analog inputs only. | FLOAT32 | CDAB | Read | |||
| HR | 3166doc 3167 | Analog input 4 total | Flow meter type analog inputs only. | FLOAT32 | CDAB | Read | |||
| HR | 3168doc 3169 | Analog input 5 total | Flow meter type analog inputs only. | FLOAT32 | CDAB | Read | |||
| HR | 3170doc 3171 | Analog input 6 total | Flow meter type analog inputs only. | FLOAT32 | CDAB | Read | |||
| HR | 3172doc 3173 | Analog input 7 total | Flow meter type analog inputs only. | FLOAT32 | CDAB | Read | |||
| HR | 3174doc 3175 | Analog input 8 total | Flow meter type analog inputs only. | FLOAT32 | CDAB | Read | |||
| HR | 3680doc 3681 | Analog output 1 scaled input value | Value of the input driving the output. | FLOAT32 | CDAB | Read | |||
| HR | 3682doc 3683 | Analog output 2 scaled input value | Value of the input driving the output. | FLOAT32 | CDAB | Read | |||
| HR | 3684doc 3685 | Analog output 3 scaled input value | Value of the input driving the output. | FLOAT32 | CDAB | Read | |||
| HR | 3686doc 3687 | Analog output 4 scaled input value | Value of the input driving the output. | FLOAT32 | CDAB | Read | |||
| HR | 3696doc 3697 | Analog output 1 mA output | FLOAT32 | CDAB | mA | Read | |||
| HR | 3698doc 3699 | Analog output 2 mA output | FLOAT32 | CDAB | mA | Read | |||
| HR | 3700doc 3701 | Analog output 3 mA output | FLOAT32 | CDAB | mA | Read | |||
| HR | 3702doc 3703 | Analog output 4 mA output | FLOAT32 | CDAB | mA | Read | |||
| HR | 3712doc 3713 | Analog output 1 percent | FLOAT32 | CDAB | % | Read | |||
| HR | 3714doc 3715 | Analog output 2 percent | FLOAT32 | CDAB | % | Read | |||
| HR | 3716doc 3717 | Analog output 3 percent | FLOAT32 | CDAB | % | Read | |||
| HR | 3718doc 3719 | Analog output 4 percent | FLOAT32 | CDAB | % | Read | |||
| HR | 3728doc 3729 | RSI | Calculated water stability index value. | FLOAT32 | CDAB | Read | |||
| HR | 3730doc 3731 | LSI | Calculated water saturation index value. | FLOAT32 | CDAB | Read |
Notes on this map
- Floats use the 'float inverse' format: the manual shows 0x12345678 transmitted as 0x56 0x78 0x12 0x34, i.e. low word first (CDAB).
- Left out: digital input states, which the manual describes both as single bits and as 0 = open / 256 = closed, so the encoding is unclear; also relay interlock and volume values on pp. 28-31, whose table layout could not be read reliably.
- Left out: status, alarm and header/custom-name registers, and all set point writes (pp. 32-80). The write addresses depend on how each input is configured.
- This is the older WIND-series manual; WebMaster ONE / WM1 uses manual 180422 and has a different analog output layout (3681 = % output there).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Walchem WebMaster WIND series Modbus TCP/IP option (s825)
What Modbus registers does the Walchem WebMaster WIND series Modbus TCP/IP option (s825) have?
This map lists 62 registers: 62 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Walchem WebMaster WIND series Modbus TCP/IP option (s825) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Section 4.5.1 says the published addresses are 1-based and the packet is 0-based; subtract 1 on the wire (sensor 1 current reading 3001 / 43001 is wire address 3000).
What byte order does the Walchem WebMaster WIND series Modbus TCP/IP option (s825) use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Walchem WebMaster WIND series Modbus TCP/IP option (s825)?
Start with HR 3000 Sensor 1 current reading (Sensor 1 current reading); HR 3048 Sensor 1 temperature reading (Sensor 1 temperature); HR 3002 Sensor 2 current reading (Sensor 2 current reading); HR 3096 Analog input 1 measured value (Analog input 1 measured value); HR 3712 Analog output 1 percent (Analog output 1 percent); HR 3728 RSI (RSI).
How do I enable Modbus control of the Walchem WebMaster WIND series Modbus TCP/IP option (s825)?
The Modbus TCP/IP option must be fitted; set point writes need software s825v008 or higher.
Where is the official Walchem WebMaster WIND series Modbus TCP/IP option (s825) Modbus documentation?
The source is WebMaster Modbus TCP/IP Option Instruction Manual (WIND series) (180413 Rev A1), published free by Walchem at https://walchem.com/literature/Controllers/WM/180413_WIND%20Modbus%20Manual_V08-10.pdf.
More Walchem Modbus register maps
- Water treatment controller (Sensor / controller)
Walchem W600 water treatment controller (Modbus/TCP)
Walchem W600 controllers (software 3.01 and up) with the Modbus/TCP feature, per Modbus manual 180676.K. W900, Intuition-6 and Intuition-9 use the same type maps but different block start addresses.
Also known as: W600 series - Water treatment controller (Sensor / controller)
Walchem W900 water treatment controller (Modbus/TCP)
Walchem W900 controllers (software 3.01 and up) with the Modbus/TCP feature, per Modbus manual 180676.K. W600, Intuition-6 and Intuition-9 use the same type maps but different block start addresses.
Also known as: W900 series - Water treatment controller (Sensor / controller)
Walchem WebMaster / WebMaster ONE (WM1) Modbus TCP/IP option
Walchem WebMaster and WebMaster ONE controllers with the Modbus TCP/IP option, software s800/s801/s802/s811/s830 v017 and higher, per manual 180422 Rev G.
Also known as: WebMaster, WebMaster ONE, WM1, s800, s801, s802, s811, s830
Other valves, actuators & sensors register maps
- Actuator / valve
Armstrong International Brain DRV25 / DRV40 / DRV80 digital recirculation valve (Modbus RTU)
Armstrong International Brain digital recirculation (thermostatic mixing) valves DRV25, DRV40 and DRV80 on their RS-485 Modbus RTU port, per IOM-776 Brain Modbus Networking (2024).
Also known as: DRV25, DRV40, DRV80, Brain, IOM-776 - Sensor (humidity / temperature probe)
E+E Elektronik EE260 humidity and temperature probe for meteorology (RS-485 Modbus RTU)
EE260 meteorological RH/T probe with RS-485 Modbus RTU, per Quick Guide QG_EE260 v1.3 (10-2025).
Also known as: EE260, E+E EE260, EE 260 - Sensor (disinfectant / chlorine)
JUMO tecLine digital disinfection sensors (Cl2, TC, ClO2/O3, H2O2/PAA, Br, Cl2 OM) (Modbus RTU)
JUMO tecLine 202630, 202631, 202634, 202636, 202637 and 202681 sensors with RS-485 Modbus RTU (interface description V2.00, 2022-03-24).
Also known as: 202630, 202631, 202634, 202636, 202637, 202681, tecLine Cl2, tecLine TC, tecLine ClO2, tecLine O3, tecLine H2O2, tecLine PAA, tecLine Br, tecLine Cl2 OM - Sensor (weighing indicator)
Radwag PUE C32 / PUE HX7 / PUE HX5.EX weighing indicators
Radwag PUE C32, PUE HX7 and PUE HX5.EX weighing indicators per the May 2024 Modbus manual; platform 2 registers exist on PUE HX7 only.
Also known as: PUE C32, PUE HX7, PUE HX5.EX - Sensor (chart recorder)
Shinko Technos HR-700 hybrid recorder (Modbus RTU, firmware 4.00+)
Shinko HR-700 hybrid recorders (multipoint and pen types), body version 4.00 or later, Modbus map version 01; manual No. HR7CE4.
Also known as: HR-700 - Actuator / valve (comfort module air damper)
Swegon REACT Parasol Zenith with Belimo actuator (Modbus RTU)
Swegon REACT Parasol Zenith comfort modules fitted with the Belimo Modbus actuator; Swegon Modbus settings sheet dated 2022-08-10.
Also known as: Parasol Zenith REACT, REACT damper actuator
All valves, actuators & sensors Modbus register maps →
Source: WebMaster Modbus TCP/IP Option Instruction Manual (WIND series) · 180413 Rev A1. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.