Sensor (load cell / strain gauge converter) · Modbus register map

Seneca R-SG3 Ethernet load cell converter Modbus register map

Updated 17 November 2026

Short answer

The R-SG3 is a Seneca R-series converter for 4- or 6-wire strain-gauge load cells with two digital outputs. It serves Modbus TCP on one Ethernet port and Modbus RTU as a slave. This map covers net/gross/tare weight, status, the command register used for tare and calibration, thresholds and filter setup.

This page lists 34 Modbus registers for the Seneca R-SG3 Ethernet load cell converter — 25 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Seneca’s own free documentation (linked below) and checked against it.

Manufacturer
Seneca
Model
R-SG3 Ethernet load cell converter
Equipment type
Sensor (load cell / strain gauge converter)
Registers
34 (25 writable)
Transport
Modbus TCP, Modbus RTU
Default unit ID
1
Default serial
38400 baud, 8N1
TCP port
502
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
RSG3, R-SG3, Seneca R series strain gauge
Source document
Series R I/O with protocol - User Manual · MI-00604-29-EN · rev. 2026-09-03
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Seneca R-SG3 Ethernet load cell converter

Integration in brief

Poll net weight (63) and status (77); bit 4 of status says the weight is stable. Tare and calibration are done by writing codes to the command register at 79.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 63Net weightFLOAT32 ABCDNet weightRead
HR 65Gross weightFLOAT32 ABCDGross weightRead
HR 67Tare weightFLOAT32 ABCDTare weightRead
HR 77StatusBITMAP16Status (stable, full scale, negative)Read/write
HR 79CommandUINT16Command register (tare, reboot)Read/write
HR 2Measurement unitUINT16Engineering unit in useRead/write

Enable Modbus control & writes

Modbus TCP and RTU are active by default; network settings are changed in the web server or Seneca's discovery tool. DIP switches 1-2 select normal operation, factory reset or web server disabled.

Byte order & addressing

Network setup

Watch out for

Seneca R-SG3 Ethernet load cell converter Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

34 of 34 shown
Seneca R-SG3 Ethernet load cell converter Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 40001Machine IDDevice identification code.UINT16Read
HR1doc 40002Firmware revisionUINT16Read
HR2doc 40003Measurement unitEngineering unit used for weight values.UINT16Read/write0 = kg; 1 = g; 2 = t; 3 = lb; 4 = l; 5 = N; 6 = bar; 7 = atm; 8 = Other
HR3doc 40004Unipolar modeUINT16Read/write0 = Bipolar (compression and traction); 1 = Unipolar (balance)
HR6doc 40007Calibration modeUINT16Read/write0 = Factory calibration; 1 = Calibration with standard weight
HR13doc 40014Cell sensitivityLoad cell rated output.FLOAT32ABCDmV/VRead/write
HR15doc 40016Cell full scaleLoad cell capacity in the selected unit.FLOAT32ABCDeng. unitsRead/write
HR17doc 40018Standard weightReference weight used for standard-weight calibration.FLOAT32ABCDeng. unitsRead/write
HR19doc 40020DO1 thresholdAlarm threshold for digital output 1.FLOAT32ABCDeng. unitsRead/write
HR29doc 40030Delta weightBand the weight must stay within to count as stable.FLOAT32ABCDeng. unitsRead/write
HR31doc 40032Delta timeTime the weight must stay in band to count as stable.UINT16× 100msRead/write
HR32doc 40033Digital output modeBits 0-1 contact type; bits 8-11 DO1 mode, bits 12-15 DO2 mode.BITMAP16Read/writebit 0 = DO1 normally closed (0 = normally open); bit 1 = DO2 normally closed (0 = normally open)
HR33doc 40034Advanced ADC speedUsed only at filter level 7 (advanced).UINT16Read/write0 = 960 Hz; 1 = 300 Hz; 2 = 150 Hz; 3 = 100 Hz; 4 = 60 Hz; 5 = 12 Hz; 6 = 4.7 Hz
HR34doc 40035Automatic tare reset band0 disables the tare tracker; otherwise the ADC band for automatic re-tare.UINT32ABCDADC pointsRead/write
HR36doc 40037DO1 threshold hysteresisFLOAT32ABCDeng. unitsRead/write
HR38doc 40039Advanced denoise filter variationNoise-only change in ADC points; filter level 7 only.FLOAT32ABCDADC pointsRead/write
HR40doc 40041Advanced denoise filter response0.001 (slowest) to 1 (fastest); filter level 7 only.FLOAT32ABCDRead/write
HR42doc 40043Denoise filter levelPreset filter level; 7 selects the advanced parameters.UINT16Read/write
HR43doc 40044Resolution modeUINT16Read/write0 = Automatic (about 20000 points of full scale); 1 = Manual (from manual resolution register); 2 = Maximum (full 24-bit resolution)
HR44doc 40045Denoise filter enableUINT16Read/write0 = Disabled (advanced mode enabled); 1 = Enabled
HR45doc 40046Manual resolutionDisplay resolution of the weight when manual mode is chosen.FLOAT32ABCDeng. unitsRead/write
HR47doc 40048Single piece weightUsed by the piece counter.FLOAT32ABCDeng. unitsRead/write
HR49doc 40050DO2 thresholdAlarm threshold for digital output 2.FLOAT32ABCDeng. unitsRead/write
HR51doc 40052DO2 threshold hysteresisFLOAT32ABCDeng. unitsRead/write
HR62doc 40063ADC filtered (16-bit)Filtered converter value scaled to 16 bits.UINT16Read
HR63doc 40064Net weightNet weight in the selected unit.FLOAT32ABCDeng. unitsRead
HR65doc 40066Gross weightFLOAT32ABCDeng. unitsRead
HR67doc 40068Tare weightFLOAT32ABCDeng. unitsRead
HR75doc 40076Factory manual tareTare entered by hand for factory-calibration mode.FLOAT32ABCDeng. unitsRead/write
HR77doc 40078StatusWeighing status; bits 5-6 drive the outputs when they are set to Modbus mode.BITMAP16Read/writebit 0 = Threshold and stable weight, DO1; bit 1 = Cell at full scale; bit 2 = Net weight below zero; bit 3 = Threshold and stable weight, DO2; bit 4 = Stable weight; bit 5 = Digital output 2 on (Modbus mode, writable); bit 6 = Digital output 1 on (Modbus mode, writable); bit 7 = Threshold with hysteresis, DO1; bit 8 = Tare tracker acted; bit 9 = Threshold with hysteresis, DO2
HR79doc 40080CommandWrite a command code; the register returns to 0 when done.UINT16Read/write43948 = Reboot; 45056 = Reset minimum net weight; 49151 = Reset maximum net weight; 49594 = Acquire tare in RAM (lost at reboot); 49914 = Acquire tare in flash for calibration; 50700 = Acquire standard weight in flash; 50773 = Take tare from the factory manual tare register
HR80doc 40081Piece countUINT16Read
HR81doc 40082Maximum net weightHighest net weight since the last reboot.FLOAT32ABCDeng. unitsRead
HR83doc 40084Minimum net weightLowest net weight since the last reboot.FLOAT32ABCDeng. unitsRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Seneca R-SG3 Ethernet load cell converter

What Modbus registers does the Seneca R-SG3 Ethernet load cell converter have?

This map lists 34 registers: 34 holding registers. 25 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Seneca R-SG3 Ethernet load cell converter Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The R-SG3 table prints the 4x number (40001) and a 0-based offset (0) on every row; the manual's numbering chapter says the offset is the 0-based address to put on the wire.

What byte order does the Seneca R-SG3 Ethernet load cell converter use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Seneca R-SG3 Ethernet load cell converter?

Start with HR 63 Net weight (Net weight); HR 65 Gross weight (Gross weight); HR 67 Tare weight (Tare weight); HR 77 Status (Status (stable, full scale, negative)); HR 79 Command (Command register (tare, reboot)); HR 2 Measurement unit (Engineering unit in use).

How do I enable Modbus control of the Seneca R-SG3 Ethernet load cell converter?

Modbus TCP and RTU are active by default; network settings are changed in the web server or Seneca's discovery tool. DIP switches 1-2 select normal operation, factory reset or web server disabled.

Where is the official Seneca R-SG3 Ethernet load cell converter Modbus documentation?

The source is Series R I/O with protocol - User Manual (MI-00604-29-EN), revision 2026-09-03, published free by Seneca at https://www.seneca.it/media/6848135/mi00604-29-en.pdf.

More Seneca Modbus register maps

Other valves, actuators & sensors register maps

All valves, actuators & sensors Modbus register maps →

Source: Series R I/O with protocol - User Manual · MI-00604-29-EN · rev. 2026-09-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.