- Home
- Modbus register maps
- Seneca
- R-SG3 Ethernet load cell converter
Sensor (load cell / strain gauge converter) · Modbus register map
Seneca R-SG3 Ethernet load cell converter Modbus register map
Updated 17 November 2026
The R-SG3 is a Seneca R-series converter for 4- or 6-wire strain-gauge load cells with two digital outputs. It serves Modbus TCP on one Ethernet port and Modbus RTU as a slave. This map covers net/gross/tare weight, status, the command register used for tare and calibration, thresholds and filter setup.
This page lists 34 Modbus registers for the Seneca R-SG3 Ethernet load cell converter — 25 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Seneca’s own free documentation (linked below) and checked against it.
- Manufacturer
- Seneca
- Model
- R-SG3 Ethernet load cell converter
- Equipment type
- Sensor (load cell / strain gauge converter)
- Registers
- 34 (25 writable)
- Transport
- Modbus TCP, Modbus RTU
- Default unit ID
- 1
- Default serial
- 38400 baud, 8N1
- TCP port
- 502
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- RSG3, R-SG3, Seneca R series strain gauge
Integration notes: Seneca R-SG3 Ethernet load cell converter
Poll net weight (63) and status (77); bit 4 of status says the weight is stable. Tare and calibration are done by writing codes to the command register at 79.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 63 | Net weight | FLOAT32 ABCD | Net weight | Read |
| HR 65 | Gross weight | FLOAT32 ABCD | Gross weight | Read |
| HR 67 | Tare weight | FLOAT32 ABCD | Tare weight | Read |
| HR 77 | Status | BITMAP16 | Status (stable, full scale, negative) | Read/write |
| HR 79 | Command | UINT16 | Command register (tare, reboot) | Read/write |
| HR 2 | Measurement unit | UINT16 | Engineering unit in use | Read/write |
Enable Modbus control & writes
Modbus TCP and RTU are active by default; network settings are changed in the web server or Seneca's discovery tool. DIP switches 1-2 select normal operation, factory reset or web server disabled.
Byte order & addressing
- Offsets are the wire addresses.
- Floats are MSW first.
- Bits 5-6 of the status register only drive the outputs when the output mode is 'from Modbus' (40033).
Network setup
- Factory IP is 192.168.90.101; change it before adding a second unit.
- Field tare: write 49914 to the command register with the empty platform loaded.
Watch out for
- Tare taken with code 49594 lives in RAM and is lost at reboot; use 49914 to store it in flash.
- Output mode codes in 40033 bits 8-11 (DO1) and 12-15 (DO2): 0 full scale, 1 threshold, 2 stable weight, 3 from Modbus, 4 threshold with hysteresis.
- Filter level 7 hands control to the advanced filter registers.
Seneca R-SG3 Ethernet load cell converter Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 40001 | Machine ID | Device identification code. | UINT16 | Read | ||||
| HR | 1doc 40002 | Firmware revision | UINT16 | Read | |||||
| HR | 2doc 40003 | Measurement unit | Engineering unit used for weight values. | UINT16 | Read/write | 0 = kg; 1 = g; 2 = t; 3 = lb; 4 = l; 5 = N; 6 = bar; 7 = atm; 8 = Other | |||
| HR | 3doc 40004 | Unipolar mode | UINT16 | Read/write | 0 = Bipolar (compression and traction); 1 = Unipolar (balance) | ||||
| HR | 6doc 40007 | Calibration mode | UINT16 | Read/write | 0 = Factory calibration; 1 = Calibration with standard weight | ||||
| HR | 13doc 40014 | Cell sensitivity | Load cell rated output. | FLOAT32 | ABCD | mV/V | Read/write | ||
| HR | 15doc 40016 | Cell full scale | Load cell capacity in the selected unit. | FLOAT32 | ABCD | eng. units | Read/write | ||
| HR | 17doc 40018 | Standard weight | Reference weight used for standard-weight calibration. | FLOAT32 | ABCD | eng. units | Read/write | ||
| HR | 19doc 40020 | DO1 threshold | Alarm threshold for digital output 1. | FLOAT32 | ABCD | eng. units | Read/write | ||
| HR | 29doc 40030 | Delta weight | Band the weight must stay within to count as stable. | FLOAT32 | ABCD | eng. units | Read/write | ||
| HR | 31doc 40032 | Delta time | Time the weight must stay in band to count as stable. | UINT16 | × 100 | ms | Read/write | ||
| HR | 32doc 40033 | Digital output mode | Bits 0-1 contact type; bits 8-11 DO1 mode, bits 12-15 DO2 mode. | BITMAP16 | Read/write | bit 0 = DO1 normally closed (0 = normally open); bit 1 = DO2 normally closed (0 = normally open) | |||
| HR | 33doc 40034 | Advanced ADC speed | Used only at filter level 7 (advanced). | UINT16 | Read/write | 0 = 960 Hz; 1 = 300 Hz; 2 = 150 Hz; 3 = 100 Hz; 4 = 60 Hz; 5 = 12 Hz; 6 = 4.7 Hz | |||
| HR | 34doc 40035 | Automatic tare reset band | 0 disables the tare tracker; otherwise the ADC band for automatic re-tare. | UINT32 | ABCD | ADC points | Read/write | ||
| HR | 36doc 40037 | DO1 threshold hysteresis | FLOAT32 | ABCD | eng. units | Read/write | |||
| HR | 38doc 40039 | Advanced denoise filter variation | Noise-only change in ADC points; filter level 7 only. | FLOAT32 | ABCD | ADC points | Read/write | ||
| HR | 40doc 40041 | Advanced denoise filter response | 0.001 (slowest) to 1 (fastest); filter level 7 only. | FLOAT32 | ABCD | Read/write | |||
| HR | 42doc 40043 | Denoise filter level | Preset filter level; 7 selects the advanced parameters. | UINT16 | Read/write | ||||
| HR | 43doc 40044 | Resolution mode | UINT16 | Read/write | 0 = Automatic (about 20000 points of full scale); 1 = Manual (from manual resolution register); 2 = Maximum (full 24-bit resolution) | ||||
| HR | 44doc 40045 | Denoise filter enable | UINT16 | Read/write | 0 = Disabled (advanced mode enabled); 1 = Enabled | ||||
| HR | 45doc 40046 | Manual resolution | Display resolution of the weight when manual mode is chosen. | FLOAT32 | ABCD | eng. units | Read/write | ||
| HR | 47doc 40048 | Single piece weight | Used by the piece counter. | FLOAT32 | ABCD | eng. units | Read/write | ||
| HR | 49doc 40050 | DO2 threshold | Alarm threshold for digital output 2. | FLOAT32 | ABCD | eng. units | Read/write | ||
| HR | 51doc 40052 | DO2 threshold hysteresis | FLOAT32 | ABCD | eng. units | Read/write | |||
| HR | 62doc 40063 | ADC filtered (16-bit) | Filtered converter value scaled to 16 bits. | UINT16 | Read | ||||
| HR | 63doc 40064 | Net weight | Net weight in the selected unit. | FLOAT32 | ABCD | eng. units | Read | ||
| HR | 65doc 40066 | Gross weight | FLOAT32 | ABCD | eng. units | Read | |||
| HR | 67doc 40068 | Tare weight | FLOAT32 | ABCD | eng. units | Read | |||
| HR | 75doc 40076 | Factory manual tare | Tare entered by hand for factory-calibration mode. | FLOAT32 | ABCD | eng. units | Read/write | ||
| HR | 77doc 40078 | Status | Weighing status; bits 5-6 drive the outputs when they are set to Modbus mode. | BITMAP16 | Read/write | bit 0 = Threshold and stable weight, DO1; bit 1 = Cell at full scale; bit 2 = Net weight below zero; bit 3 = Threshold and stable weight, DO2; bit 4 = Stable weight; bit 5 = Digital output 2 on (Modbus mode, writable); bit 6 = Digital output 1 on (Modbus mode, writable); bit 7 = Threshold with hysteresis, DO1; bit 8 = Tare tracker acted; bit 9 = Threshold with hysteresis, DO2 | |||
| HR | 79doc 40080 | Command | Write a command code; the register returns to 0 when done. | UINT16 | Read/write | 43948 = Reboot; 45056 = Reset minimum net weight; 49151 = Reset maximum net weight; 49594 = Acquire tare in RAM (lost at reboot); 49914 = Acquire tare in flash for calibration; 50700 = Acquire standard weight in flash; 50773 = Take tare from the factory manual tare register | |||
| HR | 80doc 40081 | Piece count | UINT16 | Read | |||||
| HR | 81doc 40082 | Maximum net weight | Highest net weight since the last reboot. | FLOAT32 | ABCD | eng. units | Read | ||
| HR | 83doc 40084 | Minimum net weight | Lowest net weight since the last reboot. | FLOAT32 | ABCD | eng. units | Read |
Notes on this map
- Every 32-bit row in the R-SG3 table marks the first register MSW and the second LSW, so the map uses ABCD.
- Weight values are IEEE floats in the unit chosen at 40003.
- Left out: the signed 32-bit integer weights (40070-40075), because the manual does not say how they are scaled; the analog output settings 40005 and 40022-40029, which apply to the Z-SG3 / ZE-SG3 only; the digital input register 40006, whose text is cut off in the table; reserved and password registers.
- Factory settings in the R-SG3 web-server chapter: static IP 192.168.90.101, Modbus TCP port 502, RTU station address 1, 38400 baud, no parity, 1 stop bit (data bits are not listed for this model).
- RW* registers live in flash and tolerate about 10,000 writes.
- Left out: the raw 24-bit ADC readings (40092-40095), which are typed unsigned 32-bit but carry no MSW/LSW marking.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Seneca R-SG3 Ethernet load cell converter
What Modbus registers does the Seneca R-SG3 Ethernet load cell converter have?
This map lists 34 registers: 34 holding registers. 25 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Seneca R-SG3 Ethernet load cell converter Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The R-SG3 table prints the 4x number (40001) and a 0-based offset (0) on every row; the manual's numbering chapter says the offset is the 0-based address to put on the wire.
What byte order does the Seneca R-SG3 Ethernet load cell converter use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Seneca R-SG3 Ethernet load cell converter?
Start with HR 63 Net weight (Net weight); HR 65 Gross weight (Gross weight); HR 67 Tare weight (Tare weight); HR 77 Status (Status (stable, full scale, negative)); HR 79 Command (Command register (tare, reboot)); HR 2 Measurement unit (Engineering unit in use).
How do I enable Modbus control of the Seneca R-SG3 Ethernet load cell converter?
Modbus TCP and RTU are active by default; network settings are changed in the web server or Seneca's discovery tool. DIP switches 1-2 select normal operation, factory reset or web server disabled.
Where is the official Seneca R-SG3 Ethernet load cell converter Modbus documentation?
The source is Series R I/O with protocol - User Manual (MI-00604-29-EN), revision 2026-09-03, published free by Seneca at https://www.seneca.it/media/6848135/mi00604-29-en.pdf.
More Seneca Modbus register maps
- Sensor (remote I/O module, digital inputs/outputs)
Seneca R-16DI-8DO Ethernet I/O (16 digital inputs, 8 digital outputs)
R-16DI-8DO in the Series R I/O manual MI-00604-29-EN.
Also known as: R16DI8DO, R-16DI-8DO, Seneca R series 16DI 8DO - Sensor (remote I/O module, digital inputs/outputs)
Seneca R-32DIDO Ethernet I/O (32 digital inputs/outputs)
R-32DIDO (R-32DIDO-1 / R-32DIDO-2) in the Series R I/O manual MI-00604-29-EN.
Also known as: R32DIDO, R-32DIDO-1, R-32DIDO-2, Seneca R series 32DIDO - Sensor (remote I/O module, analog outputs)
Seneca R-4AO-8DIDO Ethernet I/O (4 analog outputs, 8 digital I/O)
R-4AO-8DIDO in the Series R I/O manual MI-00604-29-EN.
Also known as: R4AO8DIDO, R-4AO-8DIDO, Seneca R series 4AO - Sensor (remote I/O module, RTD inputs)
Seneca R-4RTD-8DIDO Ethernet I/O (4 RTD inputs, 8 digital I/O)
R-4RTD-8DIDO in the Series R I/O manual MI-00604-29-EN.
Also known as: R4RTD8DIDO, R-4RTD-8DIDO, Seneca R series 4RTD - Power meter (three-phase network analyzer)
Seneca R203 three-phase power analyzer (Ethernet + RS-485)
R203-1 and R203-2 as covered by user manual MI-00591-4-EN.
Also known as: R203-1, R203-2, Seneca R203 - Power meter
Seneca T203PM single-phase AC/DC power meter (Modbus RTU)
T203PM100-MU / T203PM300-MU / T203PM600-MU per user manual MI00571-3-EN.
Also known as: T203PM100-MU, T203PM300-MU, T203PM600-MU, T203PM-MU, T-203PM - Sensor (I/O module, 10 digital inputs and counters)
Seneca Z-10-D-IN 10-channel digital input / counter module (HW2)
Seneca Z-10-D-IN hardware 2 with the 32-bit counter firmware, per user manual MI00253-10-EN.
Also known as: Z-10-D-IN, Z-10-D-IN HW2 - Actuator / valve driver (I/O module, 3 analog outputs)
Seneca Z-3AO 3-channel analog output module
Seneca Z-3AO DIN-rail module with three voltage/current outputs and RS-485 Modbus RTU, per user manual MI00260-2-EN.
Also known as: Z-3AO - Sensor (I/O module, 4 analog inputs)
Seneca Z-4AI 4-channel analog input module
Seneca Z-4AI DIN-rail module with 4 voltage/current inputs and RS-485 Modbus RTU, per user manual MI002572-E.
Also known as: Z-4AI - Sensor (RTD temperature input module)
Seneca Z-4RTD2-SI 4-channel RTD input module (Modbus RTU)
Z-4RTD2-SI per user manual MI00584-4-EN.
Also known as: Z-4RTD2, Z4RTD2-SI, Seneca Z-4RTD2-SI - Sensor (I/O module, 4 thermocouple inputs)
Seneca Z-4TC 4-channel thermocouple input module
Seneca Z-4TC DIN-rail module with four thermocouple/mV inputs and RS-485 Modbus RTU, per user manual MI00258-3-EN.
Also known as: Z-4TC - Sensor (I/O module, 8 analog inputs)
Seneca Z-8AI 8-channel analog input module
Seneca Z-8AI DIN-rail module with 8 voltage/current inputs and RS-485 Modbus RTU, per user manual MI00259-3-EN.
Also known as: Z-8AI - Sensor (digital input / counter I/O module)
Seneca Z-D-IN 5-channel digital input / counter module (Modbus RTU)
Z-D-IN DIN-rail module, user manual MI00252-3-EN (revision 3, 13/01/2022).
Also known as: ZDIN, Z D IN, Seneca Z-D-IN
Other valves, actuators & sensors register maps
- Sensor (duct humidity / temperature / CO2 / VOC)
Siemens QFM9150/MO and QPM9152/MO duct sensors (Modbus RTU)
Siemens QFM9150/MO duct humidity/temperature sensor and QPM9152/MO duct air quality (CO2, VOC, humidity, temperature) sensor, basic documentation edition a (2022-12).
Also known as: QFM9150/MO, QPM9152/MO, S55720-S584, S55720-S585 - Sensor (Ethernet analog / digital output module)
Teracom TCW280 Ethernet analog output module
TCW280 per the Teracom TCW280 user manual TCW280_R1.8.
Also known as: TCW280 - Sensor (temperature)
Teracom TST300v3 / TST300v4 RS-485 precision temperature sensor
TST300v3/v4 per the Teracom TST300v3/v4 user manual Revision R1.19.
Also known as: TST300, TST300v3, TST300v4 - Sensor (CO2 probe)
Vaisala GMP251 CARBOCAP carbon dioxide probe (Modbus RTU)
GMP251 probe in Modbus RTU mode, user guide M211799EN-N.
Also known as: GMP251, CARBOCAP GMP251, Vaisala GMP251 - Sensor (humidity and temperature transmitter)
Vaisala HMW87 / HMW87D wall humidity and temperature transmitters (Modbus RTU)
HMW87 and HMW87D wall transmitters of the HMDW80 series (the Modbus models in user guide M211510EN-J).
Also known as: HMW87, HMW87D, HMDW80 Modbus - Sensor (ultrasonic wind)
Vaisala WM80 ultrasonic wind sensor (Modbus RTU)
WM80 sensors with RS-485 in Modbus mode (e.g. ordering option C), per user guide M212995EN-F.
Also known as: WM80, Vaisala WM80, Ultrasonic Wind Sensor WM80
All valves, actuators & sensors Modbus register maps →
Source: Series R I/O with protocol - User Manual · MI-00604-29-EN · rev. 2026-09-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.