Easy Modbus
  1. Home
  2. Modbus register maps
  3. Seneca
  4. Z-3AO 3-channel analog output module

Actuator / valve driver (I/O module, 3 analog outputs) · Modbus register map

Seneca Z-3AO 3-channel analog output module Modbus register map

Updated 17 November 2026

Short answer

The Z-3AO drives three analog outputs (voltage or current, chosen per channel by DIP switch) from normalized values written over RS-485 Modbus RTU. All registers are single 16-bit holding registers; a bus-timeout fault mode can force preset output values.

This page lists 26 Modbus registers for the Seneca Z-3AO 3-channel analog output module — 22 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Seneca’s own free documentation (linked below) and checked against it.

Manufacturer
Seneca
Model
Z-3AO 3-channel analog output module
Equipment type
Actuator / valve driver (I/O module, 3 analog outputs)
Registers
26 (22 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
38400 baud, 8N1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
Z-3AO
Source document
Z-3AO User Manual · MI00260-2-EN
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Seneca Z-3AO 3-channel analog output module

Integration in brief

Write normalized values to 40005-40007 (wire 4-6): 0-10000 maps to the electrical start/end scale of each output.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 4OUT1 normalized valueINT16OUT1 setpointRead/write
HR 5OUT2 normalized valueINT16OUT2 setpointRead/write
HR 6OUT3 normalized valueINT16OUT3 setpointRead/write
HR 7ErrorsBITMAP16Error bitsRead
HR 2Communication timeoutUINT16Bus timeoutRead/write

Enable Modbus control & writes

Set the baud rate with DIP switches 1-2 and the address with switches 3-8, or set switches 3-8 OFF to use the EEPROM values in 40002/40004.

Communication loss & watchdog

With 40004 bit 7 set, if no bus traffic arrives for the time in 40003 (0.1 s units, default 20 s) the module sets 40008 bit 2 and copies 40069-40071 to the outputs.

Byte order & addressing

Network setup

Watch out for

Seneca Z-3AO 3-channel analog output module Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

26 of 26 shown
Seneca Z-3AO 3-channel analog output module Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 40001Machine IDHigh byte = module ID code (0x0F), low byte = module version.UINT16Read
HR1doc 40002Baud rate and addressHigh byte = baud code (0=4800,1=9600,2=19200,3=38400,4=57600,5=115200,6=1200,7=2400), low byte = address; EEPROM mode.UINT16Read/write
HR2doc 40003Communication timeout0-250 (0-25 s), default 200; applies when 40004 bit 7 is set.UINT16× 0.1sRead/write
HR3doc 40004EEPROM flagsBITMAP16Read/writebit 2 = RS-485 reply delay on; bit 3 = RS-485 parity on; bit 4 = Parity odd (0 = even); bit 7 = On bus timeout, copy fault values 40069-40071 to the outputs; bit 12 = New Z-3AO mode (0 = old mode)
HR4doc 40005OUT1 normalized value-10000..10000 (voltage) or 0..10000 (current).INT16Read/write
HR5doc 40006OUT2 normalized value-10000..10000 (voltage) or 0..10000 (current).INT16Read/write
HR6doc 40007OUT3 normalized value-10000..10000 (voltage) or 0..10000 (current).INT16Read/write
HR7doc 40008ErrorsBITMAP16Readbit 2 = Bus communication fault (timeout); bit 4 = EEPROM data lost
HR8doc 40009CommandUINT16Read/write47792 = 0xBAB0 save configuration to EEPROM; 49568 = 0xC1A0 reset module; 51904 = 0xCAC0 copy DIP switch state to 40010
HR9doc 40010DIP switch stateFilled after writing 0xCAC0 to 40009.BITMAP16Readbit 8 = OUT1 DIP set to voltage (0 = current); bit 9 = OUT2 DIP set to voltage; bit 10 = OUT3 DIP set to voltage
HR10doc 40011Firmware codeUINT16Read
HR11doc 40012OUT1 mV at normalized 0-11000..11000 mV, default 0 mV (voltage outputs).INT16mVRead/write
HR12doc 40013OUT1 mV at normalized 10000Electrical end scale, default 10000 mV.INT16mVRead/write
HR13doc 40014OUT2 mV at normalized 0-11000..11000 mV, default 0 mV (voltage outputs).INT16mVRead/write
HR14doc 40015OUT2 mV at normalized 10000Electrical end scale, default 10000 mV.INT16mVRead/write
HR15doc 40016OUT3 mV at normalized 0-11000..11000 mV, default 0 mV (voltage outputs).INT16mVRead/write
HR16doc 40017OUT3 mV at normalized 10000Electrical end scale, default 10000 mV.INT16mVRead/write
HR17doc 40018OUT1 µA at normalized 00..22000 µA, default 4000 µA (current outputs).UINT16µARead/write
HR18doc 40019OUT1 µA at normalized 10000Electrical end scale, default 20000 µA.UINT16µARead/write
HR19doc 40020OUT2 µA at normalized 00..22000 µA, default 4000 µA (current outputs).UINT16µARead/write
HR20doc 40021OUT2 µA at normalized 10000Electrical end scale, default 20000 µA.UINT16µARead/write
HR21doc 40022OUT3 µA at normalized 00..22000 µA, default 4000 µA (current outputs).UINT16µARead/write
HR22doc 40023OUT3 µA at normalized 10000Electrical end scale, default 20000 µA.UINT16µARead/write
HR68doc 40069OUT1 fault valueNormalized value applied on bus timeout when fault mode is on.INT16Read/write
HR69doc 40070OUT2 fault valueNormalized value applied on bus timeout when fault mode is on.INT16Read/write
HR70doc 40071OUT3 fault valueNormalized value applied on bus timeout when fault mode is on.INT16Read/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Seneca Z-3AO 3-channel analog output module

What Modbus registers does the Seneca Z-3AO 3-channel analog output module have?

This map lists 26 registers: 26 holding registers. 22 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Seneca Z-3AO 3-channel analog output module Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The register table prints 4xxxx numbers (40001 = first holding register), so 40005 is wire address 4.

What are the minimum Modbus registers to integrate the Seneca Z-3AO 3-channel analog output module?

Start with HR 4 OUT1 normalized value (OUT1 setpoint); HR 5 OUT2 normalized value (OUT2 setpoint); HR 6 OUT3 normalized value (OUT3 setpoint); HR 7 Errors (Error bits); HR 2 Communication timeout (Bus timeout).

How do I enable Modbus control of the Seneca Z-3AO 3-channel analog output module?

Set the baud rate with DIP switches 1-2 and the address with switches 3-8, or set switches 3-8 OFF to use the EEPROM values in 40002/40004.

What happens when the Seneca Z-3AO 3-channel analog output module loses Modbus communication?

With 40004 bit 7 set, if no bus traffic arrives for the time in 40003 (0.1 s units, default 20 s) the module sets 40008 bit 2 and copies 40069-40071 to the outputs.

Where is the official Seneca Z-3AO 3-channel analog output module Modbus documentation?

The source is Z-3AO User Manual (MI00260-2-EN), published free by Seneca at https://www.seneca.it/media/1340/mi00260-2-en.pdf.

More Seneca Modbus register maps

Other variable frequency drives register maps

All variable frequency drives Modbus register maps →

Source: Z-3AO User Manual · MI00260-2-EN. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.