- Z-3AO 3-channel analog output module
Actuator / valve driver (I/O module, 3 analog outputs) · Modbus register map
Seneca Z-3AO 3-channel analog output module Modbus register map
Updated 17 November 2026
The Z-3AO drives three analog outputs (voltage or current, chosen per channel by DIP switch) from normalized values written over RS-485 Modbus RTU. All registers are single 16-bit holding registers; a bus-timeout fault mode can force preset output values.
This page lists 26 Modbus registers for the Seneca Z-3AO 3-channel analog output module — 22 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Seneca’s own free documentation (linked below) and checked against it.
- Manufacturer
- Seneca
- Model
- Z-3AO 3-channel analog output module
- Equipment type
- Actuator / valve driver (I/O module, 3 analog outputs)
- Registers
- 26 (22 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 38400 baud, 8N1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- Z-3AO
- Source document
- Z-3AO User Manual · MI00260-2-EN
Integration notes: Seneca Z-3AO 3-channel analog output module
Write normalized values to 40005-40007 (wire 4-6): 0-10000 maps to the electrical start/end scale of each output.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 4 | OUT1 normalized value | INT16 | OUT1 setpoint | Read/write |
| HR 5 | OUT2 normalized value | INT16 | OUT2 setpoint | Read/write |
| HR 6 | OUT3 normalized value | INT16 | OUT3 setpoint | Read/write |
| HR 7 | Errors | BITMAP16 | Error bits | Read |
| HR 2 | Communication timeout | UINT16 | Bus timeout | Read/write |
Enable Modbus control & writes
Set the baud rate with DIP switches 1-2 and the address with switches 3-8, or set switches 3-8 OFF to use the EEPROM values in 40002/40004.
Communication loss & watchdog
With 40004 bit 7 set, if no bus traffic arrives for the time in 40003 (0.1 s units, default 20 s) the module sets 40008 bit 2 and copies 40069-40071 to the outputs.
Byte order & addressing
- 40002 packs baud code and address into one register.
- Output type follows the per-channel DIP switch.
Network setup
- Write 0xBAB0 to 40009 to store settings in EEPROM.
Watch out for
- Bit 12 of 40004 selects old or new Z-3AO behaviour.
Seneca Z-3AO 3-channel analog output module Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 40001 | Machine ID | High byte = module ID code (0x0F), low byte = module version. | UINT16 | Read | ||||
| HR | 1doc 40002 | Baud rate and address | High byte = baud code (0=4800,1=9600,2=19200,3=38400,4=57600,5=115200,6=1200,7=2400), low byte = address; EEPROM mode. | UINT16 | Read/write | ||||
| HR | 2doc 40003 | Communication timeout | 0-250 (0-25 s), default 200; applies when 40004 bit 7 is set. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 3doc 40004 | EEPROM flags | BITMAP16 | Read/write | bit 2 = RS-485 reply delay on; bit 3 = RS-485 parity on; bit 4 = Parity odd (0 = even); bit 7 = On bus timeout, copy fault values 40069-40071 to the outputs; bit 12 = New Z-3AO mode (0 = old mode) | ||||
| HR | 4doc 40005 | OUT1 normalized value | -10000..10000 (voltage) or 0..10000 (current). | INT16 | Read/write | ||||
| HR | 5doc 40006 | OUT2 normalized value | -10000..10000 (voltage) or 0..10000 (current). | INT16 | Read/write | ||||
| HR | 6doc 40007 | OUT3 normalized value | -10000..10000 (voltage) or 0..10000 (current). | INT16 | Read/write | ||||
| HR | 7doc 40008 | Errors | BITMAP16 | Read | bit 2 = Bus communication fault (timeout); bit 4 = EEPROM data lost | ||||
| HR | 8doc 40009 | Command | UINT16 | Read/write | 47792 = 0xBAB0 save configuration to EEPROM; 49568 = 0xC1A0 reset module; 51904 = 0xCAC0 copy DIP switch state to 40010 | ||||
| HR | 9doc 40010 | DIP switch state | Filled after writing 0xCAC0 to 40009. | BITMAP16 | Read | bit 8 = OUT1 DIP set to voltage (0 = current); bit 9 = OUT2 DIP set to voltage; bit 10 = OUT3 DIP set to voltage | |||
| HR | 10doc 40011 | Firmware code | UINT16 | Read | |||||
| HR | 11doc 40012 | OUT1 mV at normalized 0 | -11000..11000 mV, default 0 mV (voltage outputs). | INT16 | mV | Read/write | |||
| HR | 12doc 40013 | OUT1 mV at normalized 10000 | Electrical end scale, default 10000 mV. | INT16 | mV | Read/write | |||
| HR | 13doc 40014 | OUT2 mV at normalized 0 | -11000..11000 mV, default 0 mV (voltage outputs). | INT16 | mV | Read/write | |||
| HR | 14doc 40015 | OUT2 mV at normalized 10000 | Electrical end scale, default 10000 mV. | INT16 | mV | Read/write | |||
| HR | 15doc 40016 | OUT3 mV at normalized 0 | -11000..11000 mV, default 0 mV (voltage outputs). | INT16 | mV | Read/write | |||
| HR | 16doc 40017 | OUT3 mV at normalized 10000 | Electrical end scale, default 10000 mV. | INT16 | mV | Read/write | |||
| HR | 17doc 40018 | OUT1 µA at normalized 0 | 0..22000 µA, default 4000 µA (current outputs). | UINT16 | µA | Read/write | |||
| HR | 18doc 40019 | OUT1 µA at normalized 10000 | Electrical end scale, default 20000 µA. | UINT16 | µA | Read/write | |||
| HR | 19doc 40020 | OUT2 µA at normalized 0 | 0..22000 µA, default 4000 µA (current outputs). | UINT16 | µA | Read/write | |||
| HR | 20doc 40021 | OUT2 µA at normalized 10000 | Electrical end scale, default 20000 µA. | UINT16 | µA | Read/write | |||
| HR | 21doc 40022 | OUT3 µA at normalized 0 | 0..22000 µA, default 4000 µA (current outputs). | UINT16 | µA | Read/write | |||
| HR | 22doc 40023 | OUT3 µA at normalized 10000 | Electrical end scale, default 20000 µA. | UINT16 | µA | Read/write | |||
| HR | 68doc 40069 | OUT1 fault value | Normalized value applied on bus timeout when fault mode is on. | INT16 | Read/write | ||||
| HR | 69doc 40070 | OUT2 fault value | Normalized value applied on bus timeout when fault mode is on. | INT16 | Read/write | ||||
| HR | 70doc 40071 | OUT3 fault value | Normalized value applied on bus timeout when fault mode is on. | INT16 | Read/write |
Notes on this map
- All registers are single 16-bit words; there are no 32-bit values.
- Address 1 and 38400 baud are the EEPROM defaults, used when the address DIP switches select memory mode.
- Command values for 40009 are listed in decimal in 'values' with the hex code in the text.
- The output scaling registers are signed for mV (-11000..11000) and unsigned for µA (0..22000), following the ranges in the table.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Seneca Z-3AO 3-channel analog output module
What Modbus registers does the Seneca Z-3AO 3-channel analog output module have?
This map lists 26 registers: 26 holding registers. 22 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Seneca Z-3AO 3-channel analog output module Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The register table prints 4xxxx numbers (40001 = first holding register), so 40005 is wire address 4.
What are the minimum Modbus registers to integrate the Seneca Z-3AO 3-channel analog output module?
Start with HR 4 OUT1 normalized value (OUT1 setpoint); HR 5 OUT2 normalized value (OUT2 setpoint); HR 6 OUT3 normalized value (OUT3 setpoint); HR 7 Errors (Error bits); HR 2 Communication timeout (Bus timeout).
How do I enable Modbus control of the Seneca Z-3AO 3-channel analog output module?
Set the baud rate with DIP switches 1-2 and the address with switches 3-8, or set switches 3-8 OFF to use the EEPROM values in 40002/40004.
What happens when the Seneca Z-3AO 3-channel analog output module loses Modbus communication?
With 40004 bit 7 set, if no bus traffic arrives for the time in 40003 (0.1 s units, default 20 s) the module sets 40008 bit 2 and copies 40069-40071 to the outputs.
Where is the official Seneca Z-3AO 3-channel analog output module Modbus documentation?
The source is Z-3AO User Manual (MI00260-2-EN), published free by Seneca at https://www.seneca.it/media/1340/mi00260-2-en.pdf.
More Seneca Modbus register maps
- Sensor (remote I/O module, digital inputs/outputs)
Seneca R-16DI-8DO Ethernet I/O (16 digital inputs, 8 digital outputs)
R-16DI-8DO in the Series R I/O manual MI-00604-29-EN.
Also known as: R16DI8DO, R-16DI-8DO, Seneca R series 16DI 8DO - Sensor (remote I/O module, digital inputs/outputs)
Seneca R-32DIDO Ethernet I/O (32 digital inputs/outputs)
R-32DIDO (R-32DIDO-1 / R-32DIDO-2) in the Series R I/O manual MI-00604-29-EN.
Also known as: R32DIDO, R-32DIDO-1, R-32DIDO-2, Seneca R series 32DIDO - Sensor (remote I/O module, analog outputs)
Seneca R-4AO-8DIDO Ethernet I/O (4 analog outputs, 8 digital I/O)
R-4AO-8DIDO in the Series R I/O manual MI-00604-29-EN.
Also known as: R4AO8DIDO, R-4AO-8DIDO, Seneca R series 4AO - Sensor (remote I/O module, RTD inputs)
Seneca R-4RTD-8DIDO Ethernet I/O (4 RTD inputs, 8 digital I/O)
R-4RTD-8DIDO in the Series R I/O manual MI-00604-29-EN.
Also known as: R4RTD8DIDO, R-4RTD-8DIDO, Seneca R series 4RTD - Sensor (load cell / strain gauge converter)
Seneca R-SG3 Ethernet load cell converter
R-SG3 in the Series R I/O manual MI-00604-29-EN.
Also known as: RSG3, R-SG3, Seneca R series strain gauge - Power meter (three-phase network analyzer)
Seneca R203 three-phase power analyzer (Ethernet + RS-485)
R203-1 and R203-2 as covered by user manual MI-00591-4-EN.
Also known as: R203-1, R203-2, Seneca R203 - Power meter
Seneca T203PM single-phase AC/DC power meter (Modbus RTU)
T203PM100-MU / T203PM300-MU / T203PM600-MU per user manual MI00571-3-EN.
Also known as: T203PM100-MU, T203PM300-MU, T203PM600-MU, T203PM-MU, T-203PM - Sensor (I/O module, 10 digital inputs and counters)
Seneca Z-10-D-IN 10-channel digital input / counter module (HW2)
Seneca Z-10-D-IN hardware 2 with the 32-bit counter firmware, per user manual MI00253-10-EN.
Also known as: Z-10-D-IN, Z-10-D-IN HW2 - Sensor (I/O module, 4 analog inputs)
Seneca Z-4AI 4-channel analog input module
Seneca Z-4AI DIN-rail module with 4 voltage/current inputs and RS-485 Modbus RTU, per user manual MI002572-E.
Also known as: Z-4AI - Sensor (RTD temperature input module)
Seneca Z-4RTD2-SI 4-channel RTD input module (Modbus RTU)
Z-4RTD2-SI per user manual MI00584-4-EN.
Also known as: Z-4RTD2, Z4RTD2-SI, Seneca Z-4RTD2-SI - Sensor (I/O module, 4 thermocouple inputs)
Seneca Z-4TC 4-channel thermocouple input module
Seneca Z-4TC DIN-rail module with four thermocouple/mV inputs and RS-485 Modbus RTU, per user manual MI00258-3-EN.
Also known as: Z-4TC - Sensor (I/O module, 8 analog inputs)
Seneca Z-8AI 8-channel analog input module
Seneca Z-8AI DIN-rail module with 8 voltage/current inputs and RS-485 Modbus RTU, per user manual MI00259-3-EN.
Also known as: Z-8AI - Sensor (digital input / counter I/O module)
Seneca Z-D-IN 5-channel digital input / counter module (Modbus RTU)
Z-D-IN DIN-rail module, user manual MI00252-3-EN (revision 3, 13/01/2022).
Also known as: ZDIN, Z D IN, Seneca Z-D-IN
Other variable frequency drives register maps
- Variable frequency drive
TECO-Westinghouse E510 Compact (E510N1) inverter (Modbus RTU/ASCII)
TECO-Westinghouse E510 Compact (E510N1) inverters with the built-in RS-485 port (CON2), per communication addendum DOCUMENT-TECO-E510N1-AC002 Ver01 (2017-08).
Also known as: E510N1, E510s, TECO E510 Compact - Variable frequency drive
Vacon VACON 10 AC drive (built-in Modbus RTU)
VACON 10 micro drives on the built-in RS-485 Modbus RTU port, per complete user manual DPD00717F1 (software FW0135V010).
Also known as: VACON 10, Vacon 10, VACON0010 - Variable frequency drive
Yaskawa FP605 industrial fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa FP605 drives using the built-in RS-485 port (MEMOBUS/Modbus RTU), per technical reference SIEPC7106171F.
Also known as: CIPR-FP6, FP605 drive, FP605 AC Drive for Industrial Fan and Pump Applications - Variable frequency drive (pump)
Yaskawa iQpump drive (P7U-based, legacy) - Modbus RTU
Legacy Yaskawa iQpump drives built on the P7U platform (CIMR-P7U...), per user manual TM.iQp.01, using the built-in RS-422/485 terminals R+/R-/S+/S-.
Also known as: iQpump, CIMR-P7U iQpump, iQpump Drive - Variable frequency drive (fan / pump)
Yaskawa P7 fan/pump drive (CIMR-P7U, legacy) - Modbus RTU
Yaskawa P7 (CIMR-P7U) fan and pump drives using the built-in RS-422/485 terminals R+/R-/S+/S-, per user manual TM.P7.01 Appendix D.
Also known as: CIMR-P7U, P7U, P7 Drive - Variable frequency drive
Yaskawa Z1000U HVAC matrix drive (MEMOBUS/Modbus RTU)
Yaskawa Z1000U HVAC matrix drives using the built-in serial terminals with H5-08 = 0 (MEMOBUS/Modbus), per programming manual SIEP C710636 10D.
Also known as: Z1000U HVAC MATRIX Drive, Z1000U Matrix
All variable frequency drives Modbus register maps →
Source: Z-3AO User Manual · MI00260-2-EN. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.