Variable frequency drive · Modbus register map

Vacon VACON 10 AC drive (built-in Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

Danfoss/Vacon's micro AC drive with Modbus RTU built into the I/O terminals. Parameters and monitoring values are reached by their ID numbers, and IDs 2001-2011 / 2101-2111 form the fieldbus process data block with fixed output content (frequency, speed, current, torque, power, voltages, fault code). This map covers the control and status words, that output block and the Modbus and control-place settings.

This page lists 17 Modbus registers for the Vacon VACON 10 AC drive (built-in Modbus RTU) — 8 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Vacon’s own free documentation (linked below) and checked against it.

Manufacturer
Vacon
Model
VACON 10 AC drive (built-in Modbus RTU)
Equipment type
Variable frequency drive
Registers
17 (8 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8N1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Firmware
FW0135V010
Also known as
VACON 10, Vacon 10, VACON0010
Source document
VACON 10 AC drives Complete User Manual · DPD00717F1 · rev. 2014-04
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Vacon VACON 10 AC drive (built-in Modbus RTU)

Integration in brief

Set P2.2 = 1 (Modbus), address and baud in P2.3/P2.4, and P2.1 = 1. Write 2001 bit 0 = 1 to run; poll 2101 status, 2104 output frequency, 2106 current and 2111 fault code. The manual does not settle which ID carries the speed reference (see notes).

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 2000FB Control wordBITMAP16FB control wordRead/write
HR 2100FB Status wordBITMAP16FB status wordRead
HR 2103Output frequencyINT16Output frequency, 0.01 HzRead
HR 2105Motor currentUINT16Motor current, 0.01 ARead
HR 2110Active fault codeUINT16Active fault codeRead
HR 171P2.1 Remote control place selectionUINT16P2.1 control placeRead/write

Enable Modbus control & writes

In the system menu set P2.2 Fieldbus protocol = 1 (Modbus), P2.3 slave address (factory 1) and P2.4 baud rate (factory 9600). Set P2.1 = 1 (fieldbus control place); P2.5 must be on remote. P3.3 = 3 selects a fieldbus frequency reference.

Communication loss & watchdog

P2.7 Communication time out (ID 814): seconds, factory 10.

Byte order & addressing

Network setup

Watch out for

Vacon VACON 10 AC drive (built-in Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

17 of 17 shown
Vacon VACON 10 AC drive (built-in Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR116doc 40117P3.3 Remote control place frequency reference3 = fieldbus frequency reference.UINT16Read/write1 = Preset speed 0-7; 2 = Keypad; 3 = Fieldbus; 4 = AI1; 5 = AI2; 6 = PI
HR171doc 40172P2.1 Remote control place selectionSet 1 for Modbus control.UINT16Read/write0 = I/O terminals; 1 = Fieldbus
HR210doc 40211P2.5 Local / RemoteUINT16Read/write0 = Remote control; 1 = Local control
HR808doc 40809P2.2 Fieldbus protocolUINT16Read/write0 = Not used; 1 = Modbus used
HR809doc 40810P2.3 Slave address1-255, factory 1.UINT16Read/write
HR810doc 40811P2.4 Baud rateFactory 5 = 9600.UINT16Read/write0 = 300; 1 = 600; 2 = 1200; 3 = 2400; 4 = 4800; 5 = 9600
HR813doc 40814P2.7 Communication time out1 = 1 s, 2 = 2 s, etc.; factory 10.UINT16sRead/write
HR2000doc 42001FB Control wordBITMAP16Read/writebit 0 = Run (0 = stop); bit 1 = Direction (1 = counter-clockwise); bit 2 = Fault reset on rising edge
HR2100doc 42101FB Status wordBITMAP16Readbit 0 = Drive ready; bit 1 = Running; bit 2 = Counter-clockwise; bit 3 = Fault active; bit 4 = Alarm active; bit 5 = Speed reference reached; bit 6 = Running at zero speed
HR2103doc 42104Output frequencyINT16× 0.01HzRead
HR2104doc 42105Motor speedINT16rpmRead
HR2105doc 42106Motor currentUINT16× 0.01ARead
HR2106doc 42107Motor torquePercent of nominal.INT16× 0.1%Read
HR2107doc 42108Motor powerPercent of nominal.INT16× 0.1%Read
HR2108doc 42109Motor voltageUINT16× 0.1VRead
HR2109doc 42110DC link voltageUINT16VRead
HR2110doc 42111Active fault codeFault code per the manual's fault table; 0 = none.UINT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Vacon VACON 10 AC drive (built-in Modbus RTU)

What Modbus registers does the Vacon VACON 10 AC drive (built-in Modbus RTU) have?

This map lists 17 registers: 17 holding registers. 8 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Vacon VACON 10 AC drive (built-in Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints each process data item as two Modicon references (32101/42101 for ID 2101) and warns that some PLC drivers need 1 subtracted from the ID. So ID n is holding register 40000 + n, wire address n - 1 (status word 2101 -> address 2100; P2.1 ID 172 -> address 171). The same values can be read with function 04 as input registers.

What are the minimum Modbus registers to integrate the Vacon VACON 10 AC drive (built-in Modbus RTU)?

Start with HR 2000 FB Control word (FB control word); HR 2100 FB Status word (FB status word); HR 2103 Output frequency (Output frequency, 0.01 Hz); HR 2105 Motor current (Motor current, 0.01 A); HR 2110 Active fault code (Active fault code); HR 171 P2.1 Remote control place selection (P2.1 control place).

How do I enable Modbus control of the Vacon VACON 10 AC drive (built-in Modbus RTU)?

In the system menu set P2.2 Fieldbus protocol = 1 (Modbus), P2.3 slave address (factory 1) and P2.4 baud rate (factory 9600). Set P2.1 = 1 (fieldbus control place); P2.5 must be on remote. P3.3 = 3 selects a fieldbus frequency reference.

What happens when the Vacon VACON 10 AC drive (built-in Modbus RTU) loses Modbus communication?

P2.7 Communication time out (ID 814): seconds, factory 10.

Where is the official Vacon VACON 10 AC drive (built-in Modbus RTU) Modbus documentation?

The source is VACON 10 AC drives Complete User Manual (DPD00717F1), revision 2014-04, published free by Vacon at https://assets.danfoss.com/documents/latest/275077/AQ361182851694en-000301.pdf.

More Vacon Modbus register maps

Other variable frequency drives register maps

All variable frequency drives Modbus register maps →

Source: VACON 10 AC drives Complete User Manual · DPD00717F1 · rev. 2014-04. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.