Variable frequency drive · Modbus register map
Vacon VACON 10 AC drive (built-in Modbus RTU) Modbus register map
Updated 17 November 2026
Danfoss/Vacon's micro AC drive with Modbus RTU built into the I/O terminals. Parameters and monitoring values are reached by their ID numbers, and IDs 2001-2011 / 2101-2111 form the fieldbus process data block with fixed output content (frequency, speed, current, torque, power, voltages, fault code). This map covers the control and status words, that output block and the Modbus and control-place settings.
This page lists 17 Modbus registers for the Vacon VACON 10 AC drive (built-in Modbus RTU) — 8 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Vacon’s own free documentation (linked below) and checked against it.
- Manufacturer
- Vacon
- Model
- VACON 10 AC drive (built-in Modbus RTU)
- Equipment type
- Variable frequency drive
- Registers
- 17 (8 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8N1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Firmware
- FW0135V010
- Also known as
- VACON 10, Vacon 10, VACON0010
Integration notes: Vacon VACON 10 AC drive (built-in Modbus RTU)
Set P2.2 = 1 (Modbus), address and baud in P2.3/P2.4, and P2.1 = 1. Write 2001 bit 0 = 1 to run; poll 2101 status, 2104 output frequency, 2106 current and 2111 fault code. The manual does not settle which ID carries the speed reference (see notes).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 2000 | FB Control word | BITMAP16 | FB control word | Read/write |
| HR 2100 | FB Status word | BITMAP16 | FB status word | Read |
| HR 2103 | Output frequency | INT16 | Output frequency, 0.01 Hz | Read |
| HR 2105 | Motor current | UINT16 | Motor current, 0.01 A | Read |
| HR 2110 | Active fault code | UINT16 | Active fault code | Read |
| HR 171 | P2.1 Remote control place selection | UINT16 | P2.1 control place | Read/write |
Enable Modbus control & writes
In the system menu set P2.2 Fieldbus protocol = 1 (Modbus), P2.3 slave address (factory 1) and P2.4 baud rate (factory 9600). Set P2.1 = 1 (fieldbus control place); P2.5 must be on remote. P3.3 = 3 selects a fieldbus frequency reference.
Communication loss & watchdog
P2.7 Communication time out (ID 814): seconds, factory 10.
Byte order & addressing
- IDs map to Modicon 4xxxx (and 3xxxx) references: wire address = ID - 1.
- Multi-register reads must cover consecutive IDs, at most 11 per request.
Network setup
- The built-in 120 ohm termination is switched by the right-hand DIP switch above the I/O terminals (off by default).
Watch out for
- Local control (P2.5 = 1 or the keypad Loc/Rem button) overrides the fieldbus control place.
Vacon VACON 10 AC drive (built-in Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 116doc 40117 | P3.3 Remote control place frequency reference | 3 = fieldbus frequency reference. | UINT16 | Read/write | 1 = Preset speed 0-7; 2 = Keypad; 3 = Fieldbus; 4 = AI1; 5 = AI2; 6 = PI | |||
| HR | 171doc 40172 | P2.1 Remote control place selection | Set 1 for Modbus control. | UINT16 | Read/write | 0 = I/O terminals; 1 = Fieldbus | |||
| HR | 210doc 40211 | P2.5 Local / Remote | UINT16 | Read/write | 0 = Remote control; 1 = Local control | ||||
| HR | 808doc 40809 | P2.2 Fieldbus protocol | UINT16 | Read/write | 0 = Not used; 1 = Modbus used | ||||
| HR | 809doc 40810 | P2.3 Slave address | 1-255, factory 1. | UINT16 | Read/write | ||||
| HR | 810doc 40811 | P2.4 Baud rate | Factory 5 = 9600. | UINT16 | Read/write | 0 = 300; 1 = 600; 2 = 1200; 3 = 2400; 4 = 4800; 5 = 9600 | |||
| HR | 813doc 40814 | P2.7 Communication time out | 1 = 1 s, 2 = 2 s, etc.; factory 10. | UINT16 | s | Read/write | |||
| HR | 2000doc 42001 | FB Control word | BITMAP16 | Read/write | bit 0 = Run (0 = stop); bit 1 = Direction (1 = counter-clockwise); bit 2 = Fault reset on rising edge | ||||
| HR | 2100doc 42101 | FB Status word | BITMAP16 | Read | bit 0 = Drive ready; bit 1 = Running; bit 2 = Counter-clockwise; bit 3 = Fault active; bit 4 = Alarm active; bit 5 = Speed reference reached; bit 6 = Running at zero speed | ||||
| HR | 2103doc 42104 | Output frequency | INT16 | × 0.01 | Hz | Read | |||
| HR | 2104doc 42105 | Motor speed | INT16 | rpm | Read | ||||
| HR | 2105doc 42106 | Motor current | UINT16 | × 0.01 | A | Read | |||
| HR | 2106doc 42107 | Motor torque | Percent of nominal. | INT16 | × 0.1 | % | Read | ||
| HR | 2107doc 42108 | Motor power | Percent of nominal. | INT16 | × 0.1 | % | Read | ||
| HR | 2108doc 42109 | Motor voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 2109doc 42110 | DC link voltage | UINT16 | V | Read | ||||
| HR | 2110doc 42111 | Active fault code | Fault code per the manual's fault table; 0 = none. | UINT16 | Read |
Notes on this map
- Left out: 2003 and 2103. The process data tables call them 'Reserved' (with a 0.01 % scale) while the text after the tables describes a speed reference (0-10000) and an actual speed (-10000 to 10000) in percent of the min-max range without naming their IDs. Because the manual contradicts itself, the fieldbus speed reference register is not listed.
- 2004/2005 input words are assigned with P15.1/P15.4 (PI setpoint / feedback) and are not listed; 2002/2102 general control/status words are left out because their bits are not described.
- Up to 11 consecutive IDs can be read in one request. Supported functions: 03, 04, 06 and 16; broadcast only for writes.
- The slave address parameter note gives the default frame as no parity, 1 stop bit; this manual lists no parity parameter.
- Section 9.13.3 says fieldbus control is active when P2.1 = 3, but the P2.1 parameter table only allows 0 (I/O) and 1 (fieldbus); this map follows the parameter table.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Vacon VACON 10 AC drive (built-in Modbus RTU)
What Modbus registers does the Vacon VACON 10 AC drive (built-in Modbus RTU) have?
This map lists 17 registers: 17 holding registers. 8 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Vacon VACON 10 AC drive (built-in Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints each process data item as two Modicon references (32101/42101 for ID 2101) and warns that some PLC drivers need 1 subtracted from the ID. So ID n is holding register 40000 + n, wire address n - 1 (status word 2101 -> address 2100; P2.1 ID 172 -> address 171). The same values can be read with function 04 as input registers.
What are the minimum Modbus registers to integrate the Vacon VACON 10 AC drive (built-in Modbus RTU)?
Start with HR 2000 FB Control word (FB control word); HR 2100 FB Status word (FB status word); HR 2103 Output frequency (Output frequency, 0.01 Hz); HR 2105 Motor current (Motor current, 0.01 A); HR 2110 Active fault code (Active fault code); HR 171 P2.1 Remote control place selection (P2.1 control place).
How do I enable Modbus control of the Vacon VACON 10 AC drive (built-in Modbus RTU)?
In the system menu set P2.2 Fieldbus protocol = 1 (Modbus), P2.3 slave address (factory 1) and P2.4 baud rate (factory 9600). Set P2.1 = 1 (fieldbus control place); P2.5 must be on remote. P3.3 = 3 selects a fieldbus frequency reference.
What happens when the Vacon VACON 10 AC drive (built-in Modbus RTU) loses Modbus communication?
P2.7 Communication time out (ID 814): seconds, factory 10.
Where is the official Vacon VACON 10 AC drive (built-in Modbus RTU) Modbus documentation?
The source is VACON 10 AC drives Complete User Manual (DPD00717F1), revision 2014-04, published free by Vacon at https://assets.danfoss.com/documents/latest/275077/AQ361182851694en-000301.pdf.
More Vacon Modbus register maps
- Variable frequency drive
Danfoss VACON VACON 100 family (built-in Modbus RTU / Modbus TCP)
VACON 100 INDUSTRIAL, FLOW, HVAC and 100 X drives using the built-in RS-485 Modbus RTU or Ethernet Modbus TCP/UDP (manual DPD00156D); application IDs per the VACON 100 INDUSTRIAL application guide DPD00927L (FW0072V037).
Also known as: VACON 100 INDUSTRIAL, VACON 100 FLOW, VACON 100 HVAC, VACON 100 X, VACON0100 - Variable frequency drive
Vacon VACON 20 AC drive (built-in Modbus RTU)
VACON 20 compact drives with the standard Vacon 20 application on the built-in RS-485 Modbus RTU port, per complete user manual DPD00716H1 (software FW0107V012).
Also known as: VACON 20, Vacon 20, VACON0020
Other variable frequency drives register maps
- Variable frequency drive
Yaskawa FP605 industrial fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa FP605 drives using the built-in RS-485 port (MEMOBUS/Modbus RTU), per technical reference SIEPC7106171F.
Also known as: CIPR-FP6, FP605 drive, FP605 AC Drive for Industrial Fan and Pump Applications - Variable frequency drive (pump)
Yaskawa iQpump drive (P7U-based, legacy) - Modbus RTU
Legacy Yaskawa iQpump drives built on the P7U platform (CIMR-P7U...), per user manual TM.iQp.01, using the built-in RS-422/485 terminals R+/R-/S+/S-.
Also known as: iQpump, CIMR-P7U iQpump, iQpump Drive - Variable frequency drive (fan / pump)
Yaskawa P7 fan/pump drive (CIMR-P7U, legacy) - Modbus RTU
Yaskawa P7 (CIMR-P7U) fan and pump drives using the built-in RS-422/485 terminals R+/R-/S+/S-, per user manual TM.P7.01 Appendix D.
Also known as: CIMR-P7U, P7U, P7 Drive - Variable frequency drive
Yaskawa Z1000U HVAC matrix drive (MEMOBUS/Modbus RTU)
Yaskawa Z1000U HVAC matrix drives using the built-in serial terminals with H5-08 = 0 (MEMOBUS/Modbus), per programming manual SIEP C710636 10D.
Also known as: Z1000U HVAC MATRIX Drive, Z1000U Matrix - Variable frequency drive
ABB ACS355 machinery drive (embedded Modbus RTU)
ACS355 drives with firmware 5.110 or later using the embedded fieldbus (Modbus RTU) over an FMBA-01 adapter on terminal X3 (EIA-485) or the panel port (RS-232).
Also known as: ACS355-01E, ACS355-03E, ACS355-01U, ACS355-03U, ACS355 with FMBA-01 - Variable frequency drive (DC drive)
ABB DCS880 DC drive (embedded Modbus RTU)
DCS880 DC drives, firmware manual revision E, embedded fieldbus (EFB) Modbus RTU on control-board terminal XD2D, ABB Drives profile, 58.33 Addressing mode = Mode 0.
Also known as: DCS880-S01, DCS880-S02, DCS880-H, DCS880-R
All variable frequency drives Modbus register maps →
Source: VACON 10 AC drives Complete User Manual · DPD00717F1 · rev. 2014-04. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.