- Z-10-D-IN 10-channel digital input / counter module (HW2)
Sensor (I/O module, 10 digital inputs and counters) · Modbus register map
Seneca Z-10-D-IN 10-channel digital input / counter module (HW2) Modbus register map
Updated 17 November 2026
The Z-10-D-IN reads ten digital inputs and counts pulses on each, with counters kept in non-volatile FeRAM. Over RS-485 Modbus RTU it exposes input states, 16- and 32-bit counters, and per-input period, frequency and high time.
This page lists 55 Modbus registers for the Seneca Z-10-D-IN 10-channel digital input / counter module (HW2) — 21 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Seneca’s own free documentation (linked below) and checked against it.
- Manufacturer
- Seneca
- Model
- Z-10-D-IN 10-channel digital input / counter module (HW2)
- Equipment type
- Sensor (I/O module, 10 digital inputs and counters)
- Registers
- 55 (21 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 38400 baud, 8N1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- Z-10-D-IN, Z-10-D-IN HW2
- Source document
- Z-10-D-IN HW2 User Manual · MI00253-10-EN
Integration notes: Seneca Z-10-D-IN 10-channel digital input / counter module (HW2)
Read 40002 for input states and 40101-40120 (wire 100-119) for the ten 32-bit counters, high word first.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 1 | Input states | BITMAP16 | Input states | Read |
| HR 100 | Counter 1 (full 32-bit) | UINT32 ABCD | Counter 1 | Read/write |
| HR 102 | Counter 2 (full 32-bit) | UINT32 ABCD | Counter 2 | Read/write |
| HR 130 | IN1 frequency | UINT16 | IN1 frequency | Read |
| HR 21 | Command | UINT16 | Command | Read/write |
Enable Modbus control & writes
Supported functions are 3, 6 and 16; address and baud come from the DIP switches, or from EEPROM when all are OFF.
Byte order & addressing
- Counters 1-8 also appear as 16-bit values at 40003-40010; the full 32-bit copies are at 40101 on.
Network setup
- Write 1 to 40022 to save R/W settings to EEPROM, 2 to reset.
Watch out for
- Older firmware lacks the full 32-bit counter area.
Seneca Z-10-D-IN 10-channel digital input / counter module (HW2) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 40001 | Machine ID | UINT16 | Read | |||||
| HR | 1doc 40002 | Input states | Unfiltered state of inputs 1-10. | BITMAP16 | Read | bit 0 = IN1; bit 1 = IN2; bit 2 = IN3; bit 3 = IN4; bit 4 = IN5; bit 5 = IN6; bit 6 = IN7; bit 7 = IN8; bit 8 = IN9; bit 9 = IN10 | |||
| HR | 2doc 40003 | Counter 1 (16-bit) | 0-65535, kept in FeRAM; write to preset. | UINT16 | Read/write | ||||
| HR | 3doc 40004 | Counter 2 (16-bit) | 0-65535, kept in FeRAM; write to preset. | UINT16 | Read/write | ||||
| HR | 4doc 40005 | Counter 3 (16-bit) | 0-65535, kept in FeRAM; write to preset. | UINT16 | Read/write | ||||
| HR | 5doc 40006 | Counter 4 (16-bit) | 0-65535, kept in FeRAM; write to preset. | UINT16 | Read/write | ||||
| HR | 6doc 40007 | Counter 5 (16-bit) | 0-65535, kept in FeRAM; write to preset. | UINT16 | Read/write | ||||
| HR | 7doc 40008 | Counter 6 (16-bit) | 0-65535, kept in FeRAM; write to preset. | UINT16 | Read/write | ||||
| HR | 8doc 40009 | Counter 7 (16-bit) | 0-65535, kept in FeRAM; write to preset. | UINT16 | Read/write | ||||
| HR | 9doc 40010 | Counter 8 (16-bit) | 0-65535, kept in FeRAM; write to preset. | UINT16 | Read/write | ||||
| HR | 10doc 40011 (MSW) / 40012 (LSW) | Counter 9 (32-bit) | Kept in FeRAM; write to preset. | UINT32 | ABCD | Read/write | |||
| HR | 12doc 40013 (MSW) / 40014 (LSW) | Counter 10 (32-bit) | Kept in FeRAM; write to preset. | UINT32 | ABCD | Read/write | |||
| HR | 21doc 40022 | Command | UINT16 | Read/write | 1 = Copy R/W* registers to EEPROM; 2 = Reset | ||||
| HR | 22doc 40023 | Firmware build | UINT16 | Read | |||||
| HR | 23doc 40024 | Firmware revision | UINT16 | Read | |||||
| HR | 100doc 40101 (MSW) / 40102 (LSW) | Counter 1 (full 32-bit) | 32-bit pulse counter in FeRAM. | UINT32 | ABCD | Read/write | |||
| HR | 102doc 40103 (MSW) / 40104 (LSW) | Counter 2 (full 32-bit) | 32-bit pulse counter in FeRAM. | UINT32 | ABCD | Read/write | |||
| HR | 104doc 40105 (MSW) / 40106 (LSW) | Counter 3 (full 32-bit) | 32-bit pulse counter in FeRAM. | UINT32 | ABCD | Read/write | |||
| HR | 106doc 40107 (MSW) / 40108 (LSW) | Counter 4 (full 32-bit) | 32-bit pulse counter in FeRAM. | UINT32 | ABCD | Read/write | |||
| HR | 108doc 40109 (MSW) / 40110 (LSW) | Counter 5 (full 32-bit) | 32-bit pulse counter in FeRAM. | UINT32 | ABCD | Read/write | |||
| HR | 110doc 40111 (MSW) / 40112 (LSW) | Counter 6 (full 32-bit) | 32-bit pulse counter in FeRAM. | UINT32 | ABCD | Read/write | |||
| HR | 112doc 40113 (MSW) / 40114 (LSW) | Counter 7 (full 32-bit) | 32-bit pulse counter in FeRAM. | UINT32 | ABCD | Read/write | |||
| HR | 114doc 40115 (MSW) / 40116 (LSW) | Counter 8 (full 32-bit) | 32-bit pulse counter in FeRAM. | UINT32 | ABCD | Read/write | |||
| HR | 116doc 40117 (MSW) / 40118 (LSW) | Counter 9 (full 32-bit) | 32-bit pulse counter in FeRAM. | UINT32 | ABCD | Read/write | |||
| HR | 118doc 40119 (MSW) / 40120 (LSW) | Counter 10 (full 32-bit) | 32-bit pulse counter in FeRAM. | UINT32 | ABCD | Read/write | |||
| HR | 120doc 40121 | IN1 period | Ton + Toff. | UINT16 | ms | Read | |||
| HR | 121doc 40122 | IN2 period | Ton + Toff. | UINT16 | ms | Read | |||
| HR | 122doc 40123 | IN3 period | Ton + Toff. | UINT16 | ms | Read | |||
| HR | 123doc 40124 | IN4 period | Ton + Toff. | UINT16 | ms | Read | |||
| HR | 124doc 40125 | IN5 period | Ton + Toff. | UINT16 | ms | Read | |||
| HR | 125doc 40126 | IN6 period | Ton + Toff. | UINT16 | ms | Read | |||
| HR | 126doc 40127 | IN7 period | Ton + Toff. | UINT16 | ms | Read | |||
| HR | 127doc 40128 | IN8 period | Ton + Toff. | UINT16 | ms | Read | |||
| HR | 128doc 40129 | IN9 period | Ton + Toff. | UINT16 | ms | Read | |||
| HR | 129doc 40130 | IN10 period | Ton + Toff. | UINT16 | ms | Read | |||
| HR | 130doc 40131 | IN1 frequency | UINT16 | Hz | Read | ||||
| HR | 131doc 40132 | IN2 frequency | UINT16 | Hz | Read | ||||
| HR | 132doc 40133 | IN3 frequency | UINT16 | Hz | Read | ||||
| HR | 133doc 40134 | IN4 frequency | UINT16 | Hz | Read | ||||
| HR | 134doc 40135 | IN5 frequency | UINT16 | Hz | Read | ||||
| HR | 135doc 40136 | IN6 frequency | UINT16 | Hz | Read | ||||
| HR | 136doc 40137 | IN7 frequency | UINT16 | Hz | Read | ||||
| HR | 137doc 40138 | IN8 frequency | UINT16 | Hz | Read | ||||
| HR | 138doc 40139 | IN9 frequency | UINT16 | Hz | Read | ||||
| HR | 139doc 40140 | IN10 frequency | UINT16 | Hz | Read | ||||
| HR | 140doc 40141 | IN1 high time | UINT16 | ms | Read | ||||
| HR | 141doc 40142 | IN2 high time | UINT16 | ms | Read | ||||
| HR | 142doc 40143 | IN3 high time | UINT16 | ms | Read | ||||
| HR | 143doc 40144 | IN4 high time | UINT16 | ms | Read | ||||
| HR | 144doc 40145 | IN5 high time | UINT16 | ms | Read | ||||
| HR | 145doc 40146 | IN6 high time | UINT16 | ms | Read | ||||
| HR | 146doc 40147 | IN7 high time | UINT16 | ms | Read | ||||
| HR | 147doc 40148 | IN8 high time | UINT16 | ms | Read | ||||
| HR | 148doc 40149 | IN9 high time | UINT16 | ms | Read | ||||
| HR | 149doc 40150 | IN10 high time | UINT16 | ms | Read |
Notes on this map
- 32-bit counters are marked MSW at the lower address and LSW at the next, so they are high word first (ABCD).
- Left out: 40015 overflow flags, the measure A/B registers 40016-40018, the filter and IN9/IN10 mode registers 40019-40020, and 40021 (address and baud packed with DIP-switch dependent meaning), because their bit layouts did not extract cleanly.
- Counters marked RW** can be written to preset them.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Seneca Z-10-D-IN 10-channel digital input / counter module (HW2)
What Modbus registers does the Seneca Z-10-D-IN 10-channel digital input / counter module (HW2) have?
This map lists 55 registers: 55 holding registers. 21 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Seneca Z-10-D-IN 10-channel digital input / counter module (HW2) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual states that the first register (offset 0) is 40001 and prints both columns.
What byte order does the Seneca Z-10-D-IN 10-channel digital input / counter module (HW2) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Seneca Z-10-D-IN 10-channel digital input / counter module (HW2)?
Start with HR 1 Input states (Input states); HR 100 Counter 1 (full 32-bit) (Counter 1); HR 102 Counter 2 (full 32-bit) (Counter 2); HR 130 IN1 frequency (IN1 frequency); HR 21 Command (Command).
How do I enable Modbus control of the Seneca Z-10-D-IN 10-channel digital input / counter module (HW2)?
Supported functions are 3, 6 and 16; address and baud come from the DIP switches, or from EEPROM when all are OFF.
Where is the official Seneca Z-10-D-IN 10-channel digital input / counter module (HW2) Modbus documentation?
The source is Z-10-D-IN HW2 User Manual (MI00253-10-EN), published free by Seneca at https://www.seneca.it/media/4184/mi00253-10-en.pdf.
More Seneca Modbus register maps
- Sensor (remote I/O module, digital inputs/outputs)
Seneca R-16DI-8DO Ethernet I/O (16 digital inputs, 8 digital outputs)
R-16DI-8DO in the Series R I/O manual MI-00604-29-EN.
Also known as: R16DI8DO, R-16DI-8DO, Seneca R series 16DI 8DO - Sensor (remote I/O module, digital inputs/outputs)
Seneca R-32DIDO Ethernet I/O (32 digital inputs/outputs)
R-32DIDO (R-32DIDO-1 / R-32DIDO-2) in the Series R I/O manual MI-00604-29-EN.
Also known as: R32DIDO, R-32DIDO-1, R-32DIDO-2, Seneca R series 32DIDO - Sensor (remote I/O module, analog outputs)
Seneca R-4AO-8DIDO Ethernet I/O (4 analog outputs, 8 digital I/O)
R-4AO-8DIDO in the Series R I/O manual MI-00604-29-EN.
Also known as: R4AO8DIDO, R-4AO-8DIDO, Seneca R series 4AO - Sensor (remote I/O module, RTD inputs)
Seneca R-4RTD-8DIDO Ethernet I/O (4 RTD inputs, 8 digital I/O)
R-4RTD-8DIDO in the Series R I/O manual MI-00604-29-EN.
Also known as: R4RTD8DIDO, R-4RTD-8DIDO, Seneca R series 4RTD - Sensor (load cell / strain gauge converter)
Seneca R-SG3 Ethernet load cell converter
R-SG3 in the Series R I/O manual MI-00604-29-EN.
Also known as: RSG3, R-SG3, Seneca R series strain gauge - Power meter (three-phase network analyzer)
Seneca R203 three-phase power analyzer (Ethernet + RS-485)
R203-1 and R203-2 as covered by user manual MI-00591-4-EN.
Also known as: R203-1, R203-2, Seneca R203 - Power meter
Seneca T203PM single-phase AC/DC power meter (Modbus RTU)
T203PM100-MU / T203PM300-MU / T203PM600-MU per user manual MI00571-3-EN.
Also known as: T203PM100-MU, T203PM300-MU, T203PM600-MU, T203PM-MU, T-203PM - Actuator / valve driver (I/O module, 3 analog outputs)
Seneca Z-3AO 3-channel analog output module
Seneca Z-3AO DIN-rail module with three voltage/current outputs and RS-485 Modbus RTU, per user manual MI00260-2-EN.
Also known as: Z-3AO - Sensor (I/O module, 4 analog inputs)
Seneca Z-4AI 4-channel analog input module
Seneca Z-4AI DIN-rail module with 4 voltage/current inputs and RS-485 Modbus RTU, per user manual MI002572-E.
Also known as: Z-4AI - Sensor (RTD temperature input module)
Seneca Z-4RTD2-SI 4-channel RTD input module (Modbus RTU)
Z-4RTD2-SI per user manual MI00584-4-EN.
Also known as: Z-4RTD2, Z4RTD2-SI, Seneca Z-4RTD2-SI - Sensor (I/O module, 4 thermocouple inputs)
Seneca Z-4TC 4-channel thermocouple input module
Seneca Z-4TC DIN-rail module with four thermocouple/mV inputs and RS-485 Modbus RTU, per user manual MI00258-3-EN.
Also known as: Z-4TC - Sensor (I/O module, 8 analog inputs)
Seneca Z-8AI 8-channel analog input module
Seneca Z-8AI DIN-rail module with 8 voltage/current inputs and RS-485 Modbus RTU, per user manual MI00259-3-EN.
Also known as: Z-8AI - Sensor (digital input / counter I/O module)
Seneca Z-D-IN 5-channel digital input / counter module (Modbus RTU)
Z-D-IN DIN-rail module, user manual MI00252-3-EN (revision 3, 13/01/2022).
Also known as: ZDIN, Z D IN, Seneca Z-D-IN
Other remote i/o modules register maps
- Sensor (Ethernet I/O module)
Teracom TCW241 Ethernet I/O module
TCW241 per the Teracom TCW241 user manual Revision R4.30, firmware v2.012 or later.
Also known as: TCW241 - Sensor (Ethernet digital I/O module)
Acromag BusWorks XT1121-000 16-channel sourcing digital I/O (Modbus TCP)
BusWorks XT1121-000 per user's manual 8500950P (revision P, 18 Nov 2022).
Also known as: XT1121-000, XT1121, BusWorks XT1121 - Sensor (PWM output and counter input module)
ICP DAS M-7088 8-channel PWM output / counter input module (Modbus RTU)
ICP DAS M-7088 eight-channel PWM output module with eight digital inputs and counters, Modbus RTU firmware.
Also known as: M-7088, M7088 - Sensor (remote I/O module)
Unipi Technology Unipi Extension xS51 I/O module
Unipi Extension xS51 RS-485 module per the Unipi Extension xS51 Modbus map v2.0.
Also known as: Unipi Extension xS51, xS51 - Sensor / remote I/O module
Brainboxes ED-538 Ethernet digital I/O (Modbus TCP)
Brainboxes ED-538 Ethernet I/O module with the protocol set to Modbus TCP.
Also known as: ED-538, ED538 - Sensor (remote I/O module)
Moxa ioLogik R1212 RS-485 remote I/O
ioLogik R1212 per the ioLogik R1200 Series User's Manual, Edition 3.4 (April 2021).
Also known as: ioLogik R1212, R1212, R1212-T
All remote i/o modules Modbus register maps →
Source: Z-10-D-IN HW2 User Manual · MI00253-10-EN. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.