Sensor (humidity / temperature transmitter) · Modbus register map
Dwyer Series RHPX communicating humidity/temperature transmitter Modbus register map
Updated 17 November 2026
The Dwyer RHPX is a duct or wall humidity and temperature transmitter that talks BACnet MS/TP or Modbus RTU on RS-485, chosen by DIP switch. Measurements are 32-bit floats in input registers: relative humidity, dew point, enthalpy and absolute humidity in two unit sets, and temperature. Offsets and display units are holding registers. This map covers every published register.
This page lists 18 Modbus registers for the Dwyer Series RHPX communicating humidity/temperature transmitter — 4 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Dwyer’s own free documentation (linked below) and checked against it.
- Manufacturer
- Dwyer
- Model
- Series RHPX communicating humidity/temperature transmitter
- Equipment type
- Sensor (humidity / temperature transmitter)
- Registers
- 18 (4 writable)
- Transport
- Modbus RTU
- Default unit ID
- 127
- Documented addressing
- 1-based (subtract 1 for the wire address)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- RHPX, Dwyer RHPX BACnet/Modbus, 607xxx
Integration notes: Dwyer Series RHPX communicating humidity/temperature transmitter
Set the address with DIP switches 1-8 and switch 9 to Modbus, power up and let the transmitter auto-detect the line settings from the master's traffic, then read input registers 0-17 as big-endian floats.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 0 | Relative humidity | FLOAT32 ABCD | Relative humidity | Read |
| IR 16 | Temperature (°C) | FLOAT32 ABCD | Temperature °C | Read |
| IR 14 | Temperature (°F) | FLOAT32 ABCD | Temperature °F | Read |
| IR 4 | Dew point (°C) | FLOAT32 ABCD | Dew point °C | Read |
| IR 18 | Error flags | UINT32 ABCD | Error flags | Read |
Enable Modbus control & writes
DIP switch 9 ON selects Modbus (OFF = BACnet); switches 1-8 set the address bits (128...1), switch 10 enables the 120 ohm terminator. Modbus addresses must be 1-247.
Byte order & addressing
- Register address = register number - 1.
- Pick the byte order by address range (+2000/+4000/+6000) instead of configuring the master.
- The red LED blinks until the transmitter has locked onto the bus settings; if the bus settings change, power-cycle it.
Network setup
- Terminate the RS-485 line at both ends with 120 ohm (switch 10 on an end device).
- If the transmitter is set up offline, send read requests to it so it can detect the baud rate.
Watch out for
- The factory DIP setting is address 127; change it before putting several units on one bus.
Dwyer Series RHPX communicating humidity/temperature transmitter Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 0doc 0001-0002 | Relative humidity | FLOAT32 | ABCD | %RH | Read | |||
| IR | 2doc 0003-0004 | Dew point (°F) | FLOAT32 | ABCD | °F | Read | |||
| IR | 4doc 0005-0006 | Dew point (°C) | FLOAT32 | ABCD | °C | Read | |||
| IR | 6doc 0007-0008 | Enthalpy (BTU/lb) | FLOAT32 | ABCD | BTU/lb | Read | |||
| IR | 8doc 0009-0010 | Enthalpy (kJ/kg) | FLOAT32 | ABCD | kJ/kg | Read | |||
| IR | 10doc 0011-0012 | Absolute humidity (g/m3) | FLOAT32 | ABCD | g/m3 | Read | |||
| IR | 12doc 0013-0014 | Absolute humidity (lb/million ft3) | FLOAT32 | ABCD | lb/MMCF | Read | |||
| IR | 14doc 0015-0016 | Temperature (°F) | FLOAT32 | ABCD | °F | Read | |||
| IR | 16doc 0017-0018 | Temperature (°C) | FLOAT32 | ABCD | °C | Read | |||
| IR | 18doc 0019-0020 | Error flags | Bit-coded errors (bits 0-7 used). | UINT32 | ABCD | Read | bit 0 = Invalid address; bit 1 = Sensor range exceeded; bit 2 = Sensor error; bit 3 = No sensor; bit 4 = User settings invalid; bit 5 = Factory settings invalid; bit 6 = External memory failure; bit 7 = Internal memory failure | ||
| IR | 8000doc 8001-8016 | Model number | ASCII, 32 characters, e.g. 'RHPX-XXX'. | STRING[32] | Read | ||||
| IR | 8016doc 8017-8020 | Serial number | ASCII, 8 characters. | STRING[8] | Read | ||||
| IR | 8020doc 8021-8028 | Firmware version | ASCII, 16 characters. | STRING[16] | Read | ||||
| IR | 8028doc 8029-8032 | Date code | ASCII, 8 characters. | STRING[8] | Read | ||||
| HR | 0doc 0001-0002 | Humidity offset | -3.5 to +3.5 %RH. | FLOAT32 | ABCD | %RH | Read/write | ||
| HR | 2doc 0003-0004 | Temperature offset | -5.0 to +5.0 °F. | FLOAT32 | ABCD | °F | Read/write | ||
| HR | 4doc 0005 | Humidity display unit | UINT16 | Read/write | 0 = Dew point (°F); 1 = Dew point (°C); 2 = Relative humidity (%RH); 3 = Enthalpy (BTU/lb); 4 = Enthalpy (lb/million ft3); 5 = Absolute humidity (kJ/kg); 6 = Absolute humidity (g/m3) | ||||
| HR | 5doc 0006 | Temperature display unit | UINT16 | Read/write | 0 = °F; 1 = °C |
Notes on this map
- Byte order: addresses 1-2000 use big-endian order (ABCD for floats). Adding 2000 gives byte-swapped (BADC), 4000 word-swapped (CDAB) and 6000 little-endian (DCBA) copies; the info registers (8001+) exist only big-endian.
- Strings are read as a stream: first character in the high byte of the first register; unused bytes are zero.
- Holding register 0007-0023 Device name (String(32), default 'RHPX') is left out: the printed range spans 17 registers while a 32-character string needs 16.
- Supported functions: 03 (read holding), 04 (read input), 06 and 16.
- Default address 127 comes from the default DIP setting (switches 1-7 on). Baud, parity and stop bits are detected automatically ('Intelligent Serial Configuration'); supported: 9600-115200 baud, even/odd/none, 1 or 2 stop bits.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Dwyer Series RHPX communicating humidity/temperature transmitter
What Modbus registers does the Dwyer Series RHPX communicating humidity/temperature transmitter have?
This map lists 18 registers: 14 input registers, 4 holding registers. 4 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Dwyer Series RHPX communicating humidity/temperature transmitter Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Tables list register numbers starting at 0001 and state that the register address is one less than the register number, so 0001-0002 (relative humidity) is read at address 0. Float registers 1-2000 are big-endian; the same values can be read with other byte orders by adding 2000 (byte swap), 4000 (word swap) or 6000 (little-endian).
What byte order does the Dwyer Series RHPX communicating humidity/temperature transmitter use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Dwyer Series RHPX communicating humidity/temperature transmitter?
Start with IR 0 Relative humidity (Relative humidity); IR 16 Temperature (°C) (Temperature °C); IR 14 Temperature (°F) (Temperature °F); IR 4 Dew point (°C) (Dew point °C); IR 18 Error flags (Error flags).
How do I enable Modbus control of the Dwyer Series RHPX communicating humidity/temperature transmitter?
DIP switch 9 ON selects Modbus (OFF = BACnet); switches 1-8 set the address bits (128...1), switch 10 enables the 120 ohm terminator. Modbus addresses must be 1-247.
Where is the official Dwyer Series RHPX communicating humidity/temperature transmitter Modbus documentation?
The source is Series RHPX Humidity/Temperature Communicating Transmitter - Specifications, Installation and Operating Instructions (Bulletin AQ-RHPX-C), revision 2024-03, published free by Dwyer at https://assets.dwyeromega.com/manuals-do/AQ_RHPX_C.pdf.
Other valves, actuators & sensors register maps
- Sensor (turbidity)
JUMO ecoLine NTU digital turbidity sensor (Modbus RTU)
JUMO ecoLine NTU type 202670 with RS-485 Modbus RTU (interface description V1.01).
Also known as: 202670, JUMO ecoLine NTU, ecoLine NTU type 202670 - Sensor (vibration / temperature)
Machine Saver TriVibe vibration and temperature sensor (Modbus RTU)
Machine Saver TriVibe triaxial vibration sensors on RS-485 Modbus RTU, per the 'Modbus Registers Map' page of the Machine Saver online library (revision #12).
Also known as: TriVibe, Machine Saver TriVibe - Sensor (conductivity controller)
Shinko Technos AER-102-ECH conductivity indicating controller (C5 option)
Shinko AER-102-ECH electrical conductivity controller with the C5 RS-485 option; manual No. AER11CECE5.
Also known as: AER-102-ECH - Sensor (flow transmitter)
Siemens SITRANS F M MAG 6000 with USM II Modbus RTU module
SITRANS F M MAG 6000 / MAG 6000 I electromagnetic flow transmitters fitted with the USM II Modbus RTU RS-485 add-on module (operating instructions 03/2021).
Also known as: MAG 6000, MAG 6000 I, SITRANS FM MAG 6000 - Sensor (humidity / temperature)
Teracom TSH300v3 RS-485 humidity and temperature sensor
TSH300v3 per the Teracom TSH300v3 user manual Revision R1.17.
Also known as: TSH300, TSH300v3 - Sensor (gas density)
Trafag 8775 gas density sensor / 879x hybrid gas density monitor (legacy Modbus map)
Trafag 8775 and 879x (8791/8792/8793) running the 'Legacy' Modbus configuration of software description H73622a (10/2025).
Also known as: 8775, 8791, 8792, 8793, 879x, Trafag gas density monitor