- Enercept H8035 / H8036 networked power transducer (Modbus RTU)
Power meter · Modbus register map
Veris Enercept H8035 / H8036 networked power transducer (Modbus RTU) Modbus register map
Updated 17 November 2026
The Veris Enercept H8035/H8036 is a three-phase power transducer with integral split-core CTs and an RS-485 Modbus RTU port, addressed by DIP switches (1-63). Every data point is offered twice: as a scaled integer from 40001 and as an IEEE 754 float from 40257. This map lists the float block, which needs no model-dependent multiplier; the H8035 provides energy and real power only.
This page lists 26 Modbus registers for the Veris Enercept H8035 / H8036 networked power transducer (Modbus RTU) — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Veris’s own free documentation (linked below) and checked against it.
- Manufacturer
- Veris
- Model
- Enercept H8035 / H8036 networked power transducer (Modbus RTU)
- Equipment type
- Power meter
- Registers
- 26 (0 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- Enercept H8035, Enercept H8036, H8035-0100-2, H8035-0300-2, H8035-0400-3, H8035-0800-3, H8035-0800-4, H8035-1600-4, H8035-2400-4, H8036-0100-2, H8036-0300-2, H8036-0400-3, H8036-0800-3, H8036-0800-4, H8036-1600-4, H8036-2400-4
Integration notes: Veris Enercept H8035 / H8036 networked power transducer (Modbus RTU)
Set a unique address 1-63 on the DIP switches, wire RS-485 (+, -, shield) and read the float block from 40257 with function 03 as high-word-first floats.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 256 | Energy Consumption | FLOAT32 ABCD | Energy consumption (kWh) | Read |
| HR 260 | Real Power | FLOAT32 ABCD | Total real power (kW) | Read |
| HR 266 | Power Factor | FLOAT32 ABCD | Power factor | Read |
| HR 272 | Current | FLOAT32 ABCD | Average current | Read |
| HR 268 | Voltage, line to line | FLOAT32 ABCD | Voltage line to line | Read |
Enable Modbus control & writes
No enable step; set the Modbus address on the DIP switches before connecting to the bus.
Byte order & addressing
- Use the float block (40257 on); the integer block needs CT-size multipliers.
- Floats are ABCD (MSW at the lower address).
Network setup
- Only addresses 1 to 63 can be set on the DIP switches.
- Daisy-chain the bus with a 120 ohm terminator at the first and last device; shielded twisted pair such as Belden 1120A.
- Do not ground the shield inside the electrical panel.
Watch out for
- The meter is powered from its voltage leads; connect them on the line side so it stays online when the load is switched off.
- Colour-match each CT to its voltage lead; the status LED blinks red slowly on wrong wiring or PF below 0.5.
Veris Enercept H8035 / H8036 networked power transducer (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 256doc 40257 | Energy Consumption | H8035 and H8036. | FLOAT32 | ABCD | kWh | Read | ||
| HR | 260doc 40261 | Real Power | H8035 and H8036 (demand kW on H8035). | FLOAT32 | ABCD | kW | Read | ||
| HR | 262doc 40263 | Reactive Power | H8036 only. | FLOAT32 | ABCD | kvar | Read | ||
| HR | 264doc 40265 | Apparent Power | H8036 only. | FLOAT32 | ABCD | kVA | Read | ||
| HR | 266doc 40267 | Power Factor | H8036 only. | FLOAT32 | ABCD | Read | |||
| HR | 268doc 40269 | Voltage, line to line | H8036 only. | FLOAT32 | ABCD | V | Read | ||
| HR | 270doc 40271 | Voltage, line to neutral | H8036 only. | FLOAT32 | ABCD | V | Read | ||
| HR | 272doc 40273 | Current | Average current. | FLOAT32 | ABCD | A | Read | ||
| HR | 274doc 40275 | Real Power, phase A | H8036 only. | FLOAT32 | ABCD | kW | Read | ||
| HR | 276doc 40277 | Real Power, phase B | H8036 only. | FLOAT32 | ABCD | kW | Read | ||
| HR | 278doc 40279 | Real Power, phase C | H8036 only. | FLOAT32 | ABCD | kW | Read | ||
| HR | 280doc 40281 | Power Factor, phase A | H8036 only. | FLOAT32 | ABCD | Read | |||
| HR | 282doc 40283 | Power Factor, phase B | H8036 only. | FLOAT32 | ABCD | Read | |||
| HR | 284doc 40285 | Power Factor, phase C | H8036 only. | FLOAT32 | ABCD | Read | |||
| HR | 286doc 40287 | Voltage, phase A-B | H8036 only. | FLOAT32 | ABCD | V | Read | ||
| HR | 288doc 40289 | Voltage, phase B-C | H8036 only. | FLOAT32 | ABCD | V | Read | ||
| HR | 290doc 40291 | Voltage, phase A-C | H8036 only. | FLOAT32 | ABCD | V | Read | ||
| HR | 292doc 40293 | Voltage, phase A-N | H8036 only. | FLOAT32 | ABCD | V | Read | ||
| HR | 294doc 40295 | Voltage, phase B-N | H8036 only. | FLOAT32 | ABCD | V | Read | ||
| HR | 296doc 40297 | Voltage, phase C-N | H8036 only. | FLOAT32 | ABCD | V | Read | ||
| HR | 298doc 40299 | Current, phase A | H8036 only. | FLOAT32 | ABCD | A | Read | ||
| HR | 300doc 40301 | Current, phase B | H8036 only. | FLOAT32 | ABCD | A | Read | ||
| HR | 302doc 40303 | Current, phase C | H8036 only. | FLOAT32 | ABCD | A | Read | ||
| HR | 304doc 40305 | Average Real Power | H8036 only. | FLOAT32 | ABCD | kW | Read | ||
| HR | 306doc 40307 | Minimum Real Power | H8036 only. | FLOAT32 | ABCD | kW | Read | ||
| HR | 308doc 40309 | Maximum Real Power | H8036 only. | FLOAT32 | ABCD | kW | Read |
Notes on this map
- Veris does not host this installation guide publicly at a reachable URL (veris.com refuses automated requests); the linked copy on distributor Stromquist's literature server is the unaltered Veris document Z201686-0K.
- Floats: the guide states 32-bit IEEE 754 values with the most significant word in the lower address of each register pair (ABCD).
- Left out: the integer block 40001-40027. Each integer needs a multiplier that depends on the CT size (100 A to 2400 A tables on pp. 8-9), and energy is split over an LSW/MSW pair with separate multipliers.
- 40259/40260 repeat Energy Consumption (same as 40257/40258) and are not listed separately.
- Supported function codes: 3 (read holding), 6 (preset single register) and 17 (report slave ID). The guide gives no baud or parity defaults; those are in the separate Veris Modbus protocol specification.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Veris Enercept H8035 / H8036 networked power transducer (Modbus RTU)
What Modbus registers does the Veris Enercept H8035 / H8036 networked power transducer (Modbus RTU) have?
This map lists 26 registers: 26 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Veris Enercept H8035 / H8036 networked power transducer (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The table prints Modicon 4xxxx holding registers read with function 03; the guide says the address actually sent is the printed value minus 40001, so 40257 is wire address 256.
What byte order does the Veris Enercept H8035 / H8036 networked power transducer (Modbus RTU) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Veris Enercept H8035 / H8036 networked power transducer (Modbus RTU)?
Start with HR 256 Energy Consumption (Energy consumption (kWh)); HR 260 Real Power (Total real power (kW)); HR 266 Power Factor (Power factor); HR 272 Current (Average current); HR 268 Voltage, line to line (Voltage line to line).
How do I enable Modbus control of the Veris Enercept H8035 / H8036 networked power transducer (Modbus RTU)?
No enable step; set the Modbus address on the DIP switches before connecting to the bus.
Where is the official Veris Enercept H8035 / H8036 networked power transducer (Modbus RTU) Modbus documentation?
The source is Enercept H8035/H8036 Networked Power Transducer (Modbus RTU) - Installation Guide (Z201686-0K), revision 2010. Veris doesn't publish it on its own website, so this map was re-typed from a free copy at https://lit.stromquist.com/docs/VerisAltaLabs/LinkedLit/h8035_h8036_i0k2.pdf. It may be an older revision, so check it against the live unit.
Other power & energy meters register maps
- Power meter (DC circuit breaker trip unit)
ABB SACE Emax DC PR122DC / PR123DC trip units with PR120/D-M (Modbus RTU)
ABB SACE PR122DC and PR123DC DC protection trip units with the PR120/D-M communication module, document rev 02 (04/04/2014, SW 3.01 and later).
Also known as: PR122DC, PR123DC, PR120/D-M, Emax DC, SACE Emax DC - Actuator / valve (pressure-independent control valve with energy metering)
Belimo Energy Valve DN 15-50 (Version 4) Modbus RTU / TCP
Belimo Energy Valve Version 4, DN 15-50 (EV..R2+(K)BAC, EV..R2+MID, EV..R3+BAC), per Energy Valve Modbus interface description en-gb 2023-08.
Also known as: EV..R2+BAC, EV..R2+KBAC, EV..R2+MID, EV..R3+BAC, Energy Valve 4 - Energy meter (energy analyzer)
Carlo Gavazzi EM210 (AV versions)
EM210 three-phase energy analyzers, AV input versions with the RS485 Modbus RTU option, protocol version 4 revision 3 (newest variables need firmware A.5/A.6).
Also known as: EM210, EM210-72D, EM210 AV - Energy meter
Carlo Gavazzi EM511 single-phase energy meter (Modbus RTU)
EM511 direct-connected single-phase DIN meters with RS485 and digital input (X, PFA, PFB, SFA versions), protocol rev. 1.8.
Also known as: EM511-IS, EM511DINAV81XS1X, EM511DINAV81XS1PFA, EM511DINAV81XS1PFB, EM511DINAV81XS1SFA - Power meter (power factor regulator with network analyzer)
Circutor Computer SMART III
Circutor Computer SMART III reactive energy regulators (6 and 12 step models), RS-485 Modbus RTU, manual M015B01-03-25B.
Also known as: Computer SMART III 6, Computer SMART III 12, SMART III - Power meter
Crompton Instruments Integra 1530 / 1560 / 1580
Crompton Instruments (Tyco Electronics) Integra 1530, 1560 and 1580 panel meters fitted with the RS485 Modbus RTU option, per Integra Comms Issue 1 (Jan 2006).
Also known as: Integra 1530, Integra 1560, Integra 1580
All power & energy meters Modbus register maps →
Source: Enercept H8035/H8036 Networked Power Transducer (Modbus RTU) - Installation Guide · Z201686-0K · rev. 2010 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.