Veris Enercept H8035 / H8036 networked power transducer (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

The Veris Enercept H8035/H8036 is a three-phase power transducer with integral split-core CTs and an RS-485 Modbus RTU port, addressed by DIP switches (1-63). Every data point is offered twice: as a scaled integer from 40001 and as an IEEE 754 float from 40257. This map lists the float block, which needs no model-dependent multiplier; the H8035 provides energy and real power only.

This page lists 26 Modbus registers for the Veris Enercept H8035 / H8036 networked power transducer (Modbus RTU) — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Veris’s own free documentation (linked below) and checked against it.

Manufacturer
Veris
Model
Enercept H8035 / H8036 networked power transducer (Modbus RTU)
Equipment type
Power meter
Registers
26 (0 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
Enercept H8035, Enercept H8036, H8035-0100-2, H8035-0300-2, H8035-0400-3, H8035-0800-3, H8035-0800-4, H8035-1600-4, H8035-2400-4, H8036-0100-2, H8036-0300-2, H8036-0400-3, H8036-0800-3, H8036-0800-4, H8036-1600-4, H8036-2400-4
Source document
Enercept H8035/H8036 Networked Power Transducer (Modbus RTU) - Installation Guide · Z201686-0K · rev. 2010 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Veris Enercept H8035 / H8036 networked power transducer (Modbus RTU)

Integration in brief

Set a unique address 1-63 on the DIP switches, wire RS-485 (+, -, shield) and read the float block from 40257 with function 03 as high-word-first floats.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 256Energy ConsumptionFLOAT32 ABCDEnergy consumption (kWh)Read
HR 260Real PowerFLOAT32 ABCDTotal real power (kW)Read
HR 266Power FactorFLOAT32 ABCDPower factorRead
HR 272CurrentFLOAT32 ABCDAverage currentRead
HR 268Voltage, line to lineFLOAT32 ABCDVoltage line to lineRead

Enable Modbus control & writes

No enable step; set the Modbus address on the DIP switches before connecting to the bus.

Byte order & addressing

Network setup

Watch out for

Veris Enercept H8035 / H8036 networked power transducer (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

26 of 26 shown
Veris Enercept H8035 / H8036 networked power transducer (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR256doc 40257Energy ConsumptionH8035 and H8036.FLOAT32ABCDkWhRead
HR260doc 40261Real PowerH8035 and H8036 (demand kW on H8035).FLOAT32ABCDkWRead
HR262doc 40263Reactive PowerH8036 only.FLOAT32ABCDkvarRead
HR264doc 40265Apparent PowerH8036 only.FLOAT32ABCDkVARead
HR266doc 40267Power FactorH8036 only.FLOAT32ABCDRead
HR268doc 40269Voltage, line to lineH8036 only.FLOAT32ABCDVRead
HR270doc 40271Voltage, line to neutralH8036 only.FLOAT32ABCDVRead
HR272doc 40273CurrentAverage current.FLOAT32ABCDARead
HR274doc 40275Real Power, phase AH8036 only.FLOAT32ABCDkWRead
HR276doc 40277Real Power, phase BH8036 only.FLOAT32ABCDkWRead
HR278doc 40279Real Power, phase CH8036 only.FLOAT32ABCDkWRead
HR280doc 40281Power Factor, phase AH8036 only.FLOAT32ABCDRead
HR282doc 40283Power Factor, phase BH8036 only.FLOAT32ABCDRead
HR284doc 40285Power Factor, phase CH8036 only.FLOAT32ABCDRead
HR286doc 40287Voltage, phase A-BH8036 only.FLOAT32ABCDVRead
HR288doc 40289Voltage, phase B-CH8036 only.FLOAT32ABCDVRead
HR290doc 40291Voltage, phase A-CH8036 only.FLOAT32ABCDVRead
HR292doc 40293Voltage, phase A-NH8036 only.FLOAT32ABCDVRead
HR294doc 40295Voltage, phase B-NH8036 only.FLOAT32ABCDVRead
HR296doc 40297Voltage, phase C-NH8036 only.FLOAT32ABCDVRead
HR298doc 40299Current, phase AH8036 only.FLOAT32ABCDARead
HR300doc 40301Current, phase BH8036 only.FLOAT32ABCDARead
HR302doc 40303Current, phase CH8036 only.FLOAT32ABCDARead
HR304doc 40305Average Real PowerH8036 only.FLOAT32ABCDkWRead
HR306doc 40307Minimum Real PowerH8036 only.FLOAT32ABCDkWRead
HR308doc 40309Maximum Real PowerH8036 only.FLOAT32ABCDkWRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Veris Enercept H8035 / H8036 networked power transducer (Modbus RTU)

What Modbus registers does the Veris Enercept H8035 / H8036 networked power transducer (Modbus RTU) have?

This map lists 26 registers: 26 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Veris Enercept H8035 / H8036 networked power transducer (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The table prints Modicon 4xxxx holding registers read with function 03; the guide says the address actually sent is the printed value minus 40001, so 40257 is wire address 256.

What byte order does the Veris Enercept H8035 / H8036 networked power transducer (Modbus RTU) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Veris Enercept H8035 / H8036 networked power transducer (Modbus RTU)?

Start with HR 256 Energy Consumption (Energy consumption (kWh)); HR 260 Real Power (Total real power (kW)); HR 266 Power Factor (Power factor); HR 272 Current (Average current); HR 268 Voltage, line to line (Voltage line to line).

How do I enable Modbus control of the Veris Enercept H8035 / H8036 networked power transducer (Modbus RTU)?

No enable step; set the Modbus address on the DIP switches before connecting to the bus.

Where is the official Veris Enercept H8035 / H8036 networked power transducer (Modbus RTU) Modbus documentation?

The source is Enercept H8035/H8036 Networked Power Transducer (Modbus RTU) - Installation Guide (Z201686-0K), revision 2010. Veris doesn't publish it on its own website, so this map was re-typed from a free copy at https://lit.stromquist.com/docs/VerisAltaLabs/LinkedLit/h8035_h8036_i0k2.pdf. It may be an older revision, so check it against the live unit.

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: Enercept H8035/H8036 Networked Power Transducer (Modbus RTU) - Installation Guide · Z201686-0K · rev. 2010 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.