Northern Design Cube & Rail IP Meter (Ethernet, Modbus TCP) Modbus register map

Updated 19 November 2026

Short answer

The Cube and Rail IP meters are Northern Design three-phase meters with a built-in Ethernet port and a Modbus TCP server on port 502. The manual recommends polling the read-only amalgamated data table, which packs energy, volts, amps, power, power factor, demand and the scale exponents into one block of integers. Energy counters are also in a writable 32-bit table.

This page lists 64 Modbus registers for the Northern Design Cube & Rail IP Meter (Ethernet, Modbus TCP) — 8 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Northern Design’s own free documentation (linked below) and checked against it.

Manufacturer
Northern Design
Model
Cube & Rail IP Meter (Ethernet, Modbus TCP)
Equipment type
Power meter
Registers
64 (8 writable)
Transport
Modbus TCP
Default unit ID
Not stated
TCP port
502
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
Cube 350I IP, Cube 350V IP, Cube 400I IP, Cube 400V IP, Rail 350V IP, Cube IP meter V2
Source document
Cube & Rail IP Meter - Ethernet System Meter Installation and Operation Manual · Revision 1.07p · rev. 2013-12 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Northern Design Cube & Rail IP Meter (Ethernet, Modbus TCP)

Integration in brief

Connect to port 502 and read the amalgamated table 7680-7737 with function 03 (split into requests your client accepts). Read the scale exponents at 7733-7737 first, then apply raw x 10^(K-3) to each instantaneous value and 10^(Ke-6) to the energy counts.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 7736Power Scale KpUINT16Power scale KpRead
HR 7705System kWINT16System kW (raw)Read
HR 7691Phase 1 VoltsINT16Phase 1 volts (raw)Read
HR 7688Phase 1 AmpsINT16Phase 1 amps (raw)Read
HR 7697FrequencyINT16FrequencyRead
HR 7701System PFINT16System power factorRead
HR 7737Energy Scale KeUINT16Energy scale KeRead
HR 7680kWhUINT32 ABCDkWh counterRead

Enable Modbus control & writes

The manual describes no enable step: the Modbus TCP server answers on port 502 at the meter's IP address. By default the meter takes its IP settings from DHCP and falls back to 192.168.1.127 if none is found; the address can also be set on the front panel or the Network Settings web page.

Byte order & addressing

Network setup

Watch out for

Northern Design Cube & Rail IP Meter (Ethernet, Modbus TCP) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

64 of 64 shown
Northern Design Cube & Rail IP Meter (Ethernet, Modbus TCP) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR512doc 40513eScale (Ke) high wordAlways reads 0.UINT16Read
HR513doc 40514eScale (Ke)Energy decimal exponent; fixed by the CT and PT settings.UINT16Read
HR514doc 40515kWhRaw display count; kWh-type value = raw x 10^(Ke-6).UINT32ABCDRead/write
HR516doc 40517kVAhRaw display count; kWh-type value = raw x 10^(Ke-6).UINT32ABCDRead/write
HR518doc 40519kvarh inductiveRaw display count; kWh-type value = raw x 10^(Ke-6).UINT32ABCDRead/write
HR520doc 40521kvarh capacitiveRaw display count; kWh-type value = raw x 10^(Ke-6).UINT32ABCDRead/write
HR522doc 40523Import kvarhRaw display count; kWh-type value = raw x 10^(Ke-6).UINT32ABCDRead/write
HR524doc 40525Export kWhRaw display count; kWh-type value = raw x 10^(Ke-6).UINT32ABCDRead/write
HR526doc 40527Export kvarhRaw display count; kWh-type value = raw x 10^(Ke-6).UINT32ABCDRead/write
HR528doc 40529Hours RunHours-run counter; resolution not stated.UINT32ABCDRead/write
HR7680doc 47681kWhRaw count; scale with Ke (7737).UINT32ABCDRead
HR7682doc 47683kVAhRaw count; scale with Ke (7737).UINT32ABCDRead
HR7684doc 47685kvarhRaw count; scale with Ke (7737).UINT32ABCDRead
HR7686doc 47687Export kWhRaw count; scale with Ke (7737).UINT32ABCDRead
HR7688doc 47689Phase 1 AmpsRaw signed count; value = raw x 10^(Ki-3), Ki at 7733.INT16Read
HR7689doc 47690Phase 2 AmpsRaw signed count; value = raw x 10^(Ki-3), Ki at 7733.INT16Read
HR7690doc 47691Phase 3 AmpsRaw signed count; value = raw x 10^(Ki-3), Ki at 7733.INT16Read
HR7691doc 47692Phase 1 VoltsRaw signed count; value = raw x 10^(Kvp-3), Kvp at 7734.INT16Read
HR7692doc 47693Phase 2 VoltsRaw signed count; value = raw x 10^(Kvp-3), Kvp at 7734.INT16Read
HR7693doc 47694Phase 3 VoltsRaw signed count; value = raw x 10^(Kvp-3), Kvp at 7734.INT16Read
HR7694doc 47695Ph1-Ph2 VoltsRaw signed count; value = raw x 10^(Kvl-3), Kvl at 7735.INT16Read
HR7695doc 47696Ph2-Ph3 VoltsRaw signed count; value = raw x 10^(Kvl-3), Kvl at 7735.INT16Read
HR7696doc 47697Ph3-Ph1 VoltsRaw signed count; value = raw x 10^(Kvl-3), Kvl at 7735.INT16Read
HR7697doc 47698FrequencyPrinted scaling: 500 = 50.00.INT16× 0.1HzRead
HR7698doc 47699Phase 1 PFPrinted scaling: 1000 = 1.000.INT16× 0.001Read
HR7699doc 47700Phase 2 PFPrinted scaling: 1000 = 1.000.INT16× 0.001Read
HR7700doc 47701Phase 3 PFPrinted scaling: 1000 = 1.000.INT16× 0.001Read
HR7701doc 47702System PFPrinted scaling: 1000 = 1.000.INT16× 0.001Read
HR7702doc 47703Phase 1 kWRaw signed count; value in W/VA/var = raw x 10^(Kp-3), Kp at 7736.INT16Read
HR7703doc 47704Phase 2 kWRaw signed count; value in W/VA/var = raw x 10^(Kp-3), Kp at 7736.INT16Read
HR7704doc 47705Phase 3 kWRaw signed count; value in W/VA/var = raw x 10^(Kp-3), Kp at 7736.INT16Read
HR7705doc 47706System kWRaw signed count; value in W/VA/var = raw x 10^(Kp-3), Kp at 7736.INT16Read
HR7706doc 47707Phase 1 kVARaw signed count; value in W/VA/var = raw x 10^(Kp-3), Kp at 7736.INT16Read
HR7707doc 47708Phase 2 kVARaw signed count; value in W/VA/var = raw x 10^(Kp-3), Kp at 7736.INT16Read
HR7708doc 47709Phase 3 kVARaw signed count; value in W/VA/var = raw x 10^(Kp-3), Kp at 7736.INT16Read
HR7709doc 47710System kVARaw signed count; value in W/VA/var = raw x 10^(Kp-3), Kp at 7736.INT16Read
HR7710doc 47711Phase 1 kvarRaw signed count; value in W/VA/var = raw x 10^(Kp-3), Kp at 7736.INT16Read
HR7711doc 47712Phase 2 kvarRaw signed count; value in W/VA/var = raw x 10^(Kp-3), Kp at 7736.INT16Read
HR7712doc 47713Phase 3 kvarRaw signed count; value in W/VA/var = raw x 10^(Kp-3), Kp at 7736.INT16Read
HR7713doc 47714System kvarRaw signed count; value in W/VA/var = raw x 10^(Kp-3), Kp at 7736.INT16Read
HR7714doc 47715Ph1 Amps DemandRaw count; value = raw x 10^(Ki-3), Ki at 7733.INT16Read
HR7715doc 47716Ph2 Amps DemandRaw count; value = raw x 10^(Ki-3), Ki at 7733.INT16Read
HR7716doc 47717Ph3 Amps DemandRaw count; value = raw x 10^(Ki-3), Ki at 7733.INT16Read
HR7717doc 47718Ph1 Volts DemandRaw count; value = raw x 10^(Kvp-3), Kvp at 7734.INT16Read
HR7718doc 47719Ph2 Volts DemandRaw count; value = raw x 10^(Kvp-3), Kvp at 7734.INT16Read
HR7719doc 47720Ph3 Volts DemandRaw count; value = raw x 10^(Kvp-3), Kvp at 7734.INT16Read
HR7720doc 47721Peak Ph1 AmpsRaw count; value = raw x 10^(Ki-3), Ki at 7733.INT16Read
HR7721doc 47722Peak Ph2 AmpsRaw count; value = raw x 10^(Ki-3), Ki at 7733.INT16Read
HR7722doc 47723Peak Ph3 AmpsRaw count; value = raw x 10^(Ki-3), Ki at 7733.INT16Read
HR7723doc 47724Peak Ph1 VoltsRaw count; value = raw x 10^(Kvp-3), Kvp at 7734.INT16Read
HR7724doc 47725Peak Ph2 VoltsRaw count; value = raw x 10^(Kvp-3), Kvp at 7734.INT16Read
HR7725doc 47726Peak Ph3 VoltsRaw count; value = raw x 10^(Kvp-3), Kvp at 7734.INT16Read
HR7726doc 47727kW DemandRaw count; scale is Kp + 1: value = raw x 10^(Kp-2).INT16Read
HR7727doc 47728kVA DemandRaw count; scale is Kp + 1: value = raw x 10^(Kp-2).INT16Read
HR7728doc 47729kvar DemandRaw count; scale is Kp + 1: value = raw x 10^(Kp-2).INT16Read
HR7729doc 47730Peak Hold kW DemandRaw count; scale is Kp + 1: value = raw x 10^(Kp-2).INT16Read
HR7730doc 47731Peak Hold kVA DemandRaw count; scale is Kp + 1: value = raw x 10^(Kp-2).INT16Read
HR7731doc 47732Peak Hold kvar DemandRaw count; scale is Kp + 1: value = raw x 10^(Kp-2).INT16Read
HR7732doc 47733Neutral CurrentRaw count; value = raw x 10^(Ki-3), Ki at 7733.INT16Read
HR7733doc 47734Amps Scale KiDecimal exponent used by the scaling formulas.UINT16Read
HR7734doc 47735Phase Volts Scale KvpDecimal exponent used by the scaling formulas.UINT16Read
HR7735doc 47736Line Volts Scale KvlDecimal exponent used by the scaling formulas.UINT16Read
HR7736doc 47737Power Scale KpDecimal exponent used by the scaling formulas.UINT16Read
HR7737doc 47738Energy Scale KeDecimal exponent used by the scaling formulas.UINT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Northern Design Cube & Rail IP Meter (Ethernet, Modbus TCP)

What Modbus registers does the Northern Design Cube & Rail IP Meter (Ethernet, Modbus TCP) have?

This map lists 64 registers: 64 holding registers. 8 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Northern Design Cube & Rail IP Meter (Ethernet, Modbus TCP) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Tables print a 0-based data address next to the Modicon register number (7680 = 47681). The data address is what goes on the wire: request 7680 to read 47681.

What byte order does the Northern Design Cube & Rail IP Meter (Ethernet, Modbus TCP) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Northern Design Cube & Rail IP Meter (Ethernet, Modbus TCP)?

Start with HR 7736 Power Scale Kp (Power scale Kp); HR 7705 System kW (System kW (raw)); HR 7691 Phase 1 Volts (Phase 1 volts (raw)); HR 7688 Phase 1 Amps (Phase 1 amps (raw)); HR 7697 Frequency (Frequency); HR 7701 System PF (System power factor); HR 7737 Energy Scale Ke (Energy scale Ke); HR 7680 kWh (kWh counter).

How do I enable Modbus control of the Northern Design Cube & Rail IP Meter (Ethernet, Modbus TCP)?

The manual describes no enable step: the Modbus TCP server answers on port 502 at the meter's IP address. By default the meter takes its IP settings from DHCP and falls back to 192.168.1.127 if none is found; the address can also be set on the front panel or the Network Settings web page.

Where is the official Northern Design Cube & Rail IP Meter (Ethernet, Modbus TCP) Modbus documentation?

The source is Cube & Rail IP Meter - Ethernet System Meter Installation and Operation Manual (Revision 1.07p), revision 2013-12. Northern Design doesn't publish it on its own website, so this map was re-typed from a free copy at https://res.cloudinary.com/fastron-electronics/image/upload/v1533449477/Northern%20Design/IP_Meter_Operating_Manual_Rev_1.07p.pdf. It may be an older revision, so check it against the live unit.

More Northern Design Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: Cube & Rail IP Meter - Ethernet System Meter Installation and Operation Manual · Revision 1.07p · rev. 2013-12 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.