Energy meter · Modbus register map

Eastron SDM230-Modbus Modbus register map

Updated 17 November 2026

Short answer

The SDM230-Modbus is a single-phase, two-module DIN-rail kWh meter with an RS485 Modbus RTU port and two tariffs. Live values and energy counters, including per-tariff energy and maximum demand, are IEEE-754 floats in input register pairs (function 04). Holding registers cover address, baud, parity, pulse output and the energy measurement mode.

This page lists 53 Modbus registers for the Eastron SDM230-Modbus — 9 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Eastron’s own free documentation (linked below) and checked against it.

Manufacturer
Eastron
Model
SDM230-Modbus
Equipment type
Energy meter
Registers
53 (9 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8N1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
SDM230Modbus, SDM230-2T, SDM230-M
Source document
Eastron SDM230Modbus Protocol V1.1 (SDM230-2T Smart Meter Modbus Protocol Implementation) · V1.1
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Eastron SDM230-Modbus

Integration in brief

Read input registers with function 04 in two-register pairs; values are floats, high word first. Voltage is 0x0000, current 0x0006, power 0x000C, import kWh 0x0048 and total kWh 0x0156. Tariff energy starts at 0x130C.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 0VoltageFLOAT32 ABCDVoltageRead
IR 6CurrentFLOAT32 ABCDCurrentRead
IR 12Active powerFLOAT32 ABCDActive powerRead
IR 30Power factorFLOAT32 ABCDPower factorRead
IR 70Frequency of supply voltagesFLOAT32 ABCDFrequencyRead
IR 72Import active energy since last resetFLOAT32 ABCDImport kWhRead
IR 342Total active energyFLOAT32 ABCDTotal kWhRead

Enable Modbus control & writes

Modbus RTU is always active on the RS485 terminals; no enable step is documented.

Byte order & addressing

Network setup

Watch out for

Eastron SDM230-Modbus Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

53 of 53 shown
Eastron SDM230-Modbus Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR0doc 30001VoltageFLOAT32ABCDVRead
IR6doc 30007CurrentFLOAT32ABCDARead
IR12doc 30013Active powerFLOAT32ABCDWRead
IR18doc 30019Apparent powerFLOAT32ABCDVARead
IR24doc 30025Reactive powerFLOAT32ABCDVArRead
IR30doc 30031Power factorFLOAT32ABCDRead
IR36doc 30037Phase angleFLOAT32ABCD°Read
IR70doc 30071Frequency of supply voltagesFLOAT32ABCDHzRead
IR72doc 30073Import active energy since last resetFLOAT32ABCDkWhRead
IR74doc 30075Export active energy since last resetFLOAT32ABCDkWhRead
IR76doc 30077Import reactive energy since last resetFLOAT32ABCDkVArhRead
IR78doc 30079Export reactive energy since last resetFLOAT32ABCDkVArhRead
IR84doc 30085Active power demandFLOAT32ABCDWRead
IR86doc 30087Max active power demandFLOAT32ABCDWRead
IR88doc 30089Import active power demandFLOAT32ABCDWRead
IR90doc 30091Max import active power demandFLOAT32ABCDWRead
IR92doc 30093Export active power demandFLOAT32ABCDWRead
IR94doc 30095Max export active power demandFLOAT32ABCDWRead
IR258doc 30259Current demandFLOAT32ABCDARead
IR264doc 30265Max current demandFLOAT32ABCDARead
IR342doc 30343Total active energyPer the Measurement mode setting (default import + export).FLOAT32ABCDkWhRead
IR344doc 30345Total reactive energyPer the Measurement mode setting (default import + export).FLOAT32ABCDkVArhRead
IR384doc 30385Current resettable total active energyFLOAT32ABCDkWhRead
IR386doc 30387Current resettable total reactive energyUnit printed as kWh in the source although this is a reactive energy value.FLOAT32ABCDkWhRead
IR4876doc 34877Total active Energy Rate 1FLOAT32ABCDkWhRead
IR4878doc 34879Total active Energy Rate 2FLOAT32ABCDkWhRead
IR4884doc 34885Import active Energy Rate 1FLOAT32ABCDkWhRead
IR4886doc 34887Import active Energy Rate 2FLOAT32ABCDkWhRead
IR4892doc 34893Export active Energy Rate 1FLOAT32ABCDkWhRead
IR4894doc 34895Export active Energy Rate 2FLOAT32ABCDkWhRead
IR4900doc 34901Total reactive Energy Rate 1FLOAT32ABCDkVArhRead
IR4902doc 34903Total reactive Energy Rate 2FLOAT32ABCDkVArhRead
IR4908doc 34909Import reactive Energy Rate 1FLOAT32ABCDkVArhRead
IR4910doc 34911Import reactive Energy Rate 2FLOAT32ABCDkVArhRead
IR4916doc 34917Export reactive Energy Rate 1FLOAT32ABCDkVArhRead
IR4918doc 34919Export reactive Energy Rate 2FLOAT32ABCDkVArhRead
IR5074doc 35075Maximum system positive active power demand of tariff 1FLOAT32ABCDkWRead
IR5076doc 35077Maximum system positive active power demand of tariff 2FLOAT32ABCDkWRead
IR5204doc 35205Maximum system reverse active power demand of tariff 1FLOAT32ABCDkWRead
IR5206doc 35207Maximum system reverse active power demand of tariff 2FLOAT32ABCDkWRead
IR5472doc 35473Tariff1 total active Maximum Power DemandFLOAT32ABCDWRead
IR5478doc 35479Tariff 1 L1 Maximum Current DemandFLOAT32ABCDARead
IR5486doc 35487Tariff 2 total active Maximum Power DemandFLOAT32ABCDWRead
IR5492doc 35493Tariff 2 L1 Maximum Current DemandFLOAT32ABCDARead
HR12doc 40013Pulse output 1 width60, 100 or 200 ms (default 100).FLOAT32ABCDmsRead/write
HR18doc 40019Network parity / stop bitsFLOAT32ABCDRead/write0 = No parity, 1 stop bit (default); 1 = Even parity, 1 stop bit; 2 = Odd parity, 1 stop bit; 3 = No parity, 2 stop bits
HR20doc 40021Network node address1-247, default 1.FLOAT32ABCDRead/write
HR28doc 40029Network baud rateFLOAT32ABCDRead/write0 = 2400; 1 = 4800; 2 = 9600 (default); 5 = 1200
HR86doc 40087Pulse 1 energy typeFLOAT32ABCDRead/write1 = Import active energy; 2 = Total active energy; 4 = Export active energy (default); 5 = Import reactive energy; 6 = Total reactive energy; 8 = Export reactive energy
HR61456doc 461457Clear history dataWrite 0x0000 to clear maximum demand.UINT16Write0 = Clear maximum demand
HR63760doc 463761Pulse 1 divisorUINT16Read/write0 = 0.001 kWh(kVArh)/imp (default); 1 = 0.01 kWh(kVArh)/imp; 2 = 0.1 kWh(kVArh)/imp; 3 = 1 kWh(kVArh)/imp
HR63776doc 463777Measurement modeHow total energy is calculated.UINT16Read/write1 = Total = import; 2 = Total = import + export (default); 3 = Total = import - export
HR63792doc 463793Running timeContinuous working period in hours.FLOAT32ABCDhRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Eastron SDM230-Modbus

What Modbus registers does the Eastron SDM230-Modbus have?

This map lists 53 registers: 44 input registers, 9 holding registers. 9 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Eastron SDM230-Modbus Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The tables print 30001/40001-style numbers (six-digit 46xxxx for the F0xx/F9xx block) beside the hex start address sent on the wire, e.g. 30073 = 0x0048 and 463777 = 0xF920. Wire address = printed number minus 30001, 40001 or 400001.

What byte order does the Eastron SDM230-Modbus use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Eastron SDM230-Modbus?

Start with IR 0 Voltage (Voltage); IR 6 Current (Current); IR 12 Active power (Active power); IR 30 Power factor (Power factor); IR 70 Frequency of supply voltages (Frequency); IR 72 Import active energy since last reset (Import kWh); IR 342 Total active energy (Total kWh).

How do I enable Modbus control of the Eastron SDM230-Modbus?

Modbus RTU is always active on the RS485 terminals; no enable step is documented.

Where is the official Eastron SDM230-Modbus Modbus documentation?

The source is Eastron SDM230Modbus Protocol V1.1 (SDM230-2T Smart Meter Modbus Protocol Implementation) (V1.1), published free by Eastron at https://res.cloudinary.com/fastron-electronics/image/upload/v1619064123/Eastron%20Europe/SDM230-MODBUS_Protocol.pdf.

More Eastron Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: Eastron SDM230Modbus Protocol V1.1 (SDM230-2T Smart Meter Modbus Protocol Implementation) · V1.1. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.