- Home
- Modbus register maps
- Yaskawa
- P7B drive/bypass (legacy) - Modbus RTU
Variable frequency drive (fan / pump bypass package) · Modbus register map
Yaskawa P7B drive/bypass (legacy) - Modbus RTU Modbus register map
Updated 17 November 2026
The P7B is a P7 fan/pump drive packaged with a bypass contactor panel and HAND/OFF/AUTO switch. Modbus RTU is served by the drive itself (option V, native protocol) using the same hex register layout as the P7, except that 0001H bits 0/1 are run/stop and direction. This map covers the Appendix D reference and monitor data and the Enter commands.
This page lists 25 Modbus registers for the Yaskawa P7B drive/bypass (legacy) - Modbus RTU — 9 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Yaskawa’s own free documentation (linked below) and checked against it.
- Manufacturer
- Yaskawa
- Model
- P7B drive/bypass (legacy) - Modbus RTU
- Equipment type
- Variable frequency drive (fan / pump bypass package)
- Registers
- 25 (9 writable)
- Transport
- Modbus RTU
- Default unit ID
- 31
- Default serial
- 9600 baud, 8N1
- Documented addressing
- hexadecimal, 0-based
- Also known as
- P7B, P7 Bypass
Integration notes: Yaskawa P7B drive/bypass (legacy) - Modbus RTU
Put the HAND/OFF/AUTO switch in AUTO, set H5-01..H5-03 at the keypad and power-cycle, set the drive's reference and run source to serial, then write 0001H/0002H with function 10H and poll 0020H-002DH.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 1 | Operation command | BITMAP16 | Run/stop and fault reset | Read/write |
| HR 2 | Frequency reference | UINT16 | Frequency reference | Read/write |
| HR 32 | Drive status | BITMAP16 | Drive status | Read |
| HR 33 | Fault details | BITMAP16 | Fault details | Read |
| HR 36 | Output frequency (U1-02) | UINT16 | Output frequency | Read |
| HR 44 | Drive status 2 | BITMAP16 | Drive status 2 incl. comm timeout | Read |
Enable Modbus control & writes
Set H5-01 (default 1F hex), H5-02 (default 3 = 9600) and H5-03 (default none) and cycle power. The HAND/OFF/AUTO switch must be in AUTO for serial run/stop and speed control; OFF overrides a serial run command. For monitoring only, just the H5 parameters are needed.
Communication loss & watchdog
H5-05 = 1 enables CE detection after the H5-09 time; H5-04 sets the reaction. 002CH bit F shows a comm time-out.
Byte order & addressing
- Registers are hex and 0-based.
- Function codes 03H, 06H, 08H and 10H.
- 0001H bit 0 is run/stop and bit 1 is direction, unlike the stand-alone P7 (bit 0 forward, bit 1 reverse).
- Parameter writes need 0 written to 0900H (EEPROM) or 0910H (RAM).
Network setup
- Drive terminals S+, S-, R+, R-; for RS-485 jumper S+ to R+ and S- to R-. Up to 31 drives.
- Terminating resistor: DIP switch S1-1 on the drive terminal board, ON only at the end of the line.
- 8 data bits, 1 stop bit; 1200-19200 baud.
Watch out for
- The OFF position of the HAND/OFF/AUTO switch takes precedence over a serial run command.
Yaskawa P7B drive/bypass (legacy) - Modbus RTU Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1doc 0001H | Operation command | Run/stop, direction, external fault, fault reset, virtual inputs. | BITMAP16 | Read/write | bit 0 = Run (0 = stop); bit 1 = Reverse (0 = forward); bit 2 = External fault (EFO); bit 3 = Fault reset; bit 4 = ComNet; bit 5 = ComCtrl; bit 6 = Multi-function input command 3; bit 7 = Multi-function input command 4; bit 8 = Multi-function input command 5; bit 9 = Multi-function input command 6; bit 10 = Multi-function input command 7 | |||
| HR | 2doc 0002H | Frequency reference | Units set by o1-03; unscaled here. | UINT16 | Read/write | ||||
| HR | 6doc 0006H | PI setpoint | Used when 000FH bit 1 is set. | UINT16 | Read/write | ||||
| HR | 7doc 0007H | Analog output 1 setting | -11 V = -726 ... 11 V = 726 (10 V = 660). | INT16 | Read/write | ||||
| HR | 8doc 0008H | Analog output 2 setting | -11 V = -726 ... 11 V = 726 (10 V = 660). | INT16 | Read/write | ||||
| HR | 9doc 0009H | Multi-function contact output setting | Network control of M1-M2, M3-M4 and fault contact. | BITMAP16 | Read/write | bit 0 = Digital output 1 (M1-M2) on; bit 1 = Digital output 2 (M3-M4) on; bit 6 = Use bit 7 to drive fault contact MA-MC; bit 7 = Fault contact (MA-MC) on | |||
| HR | 15doc 000FH | Reference selection settings | Enables network PI setpoint and broadcast S5-S7 inputs. | BITMAP16 | Read/write | bit 1 = Input PI setpoint (0006H) enabled; bit 12 = Broadcast terminal S5 input enabled; bit 13 = Broadcast terminal S6 input enabled; bit 14 = Broadcast terminal S7 input enabled | |||
| HR | 32doc 0020H | Drive status | BITMAP16 | Read | bit 0 = Running; bit 1 = Reverse operation; bit 2 = Drive startup complete; bit 3 = Fault; bit 4 = Data setting error; bit 5 = Multi-function output 1 (M1-M2) on; bit 6 = Multi-function output 2 (M3-M4) on | ||||
| HR | 33doc 0021H | Fault details | BITMAP16 | Read | bit 0 = Overcurrent (OC) / ground fault (GF); bit 1 = Main circuit overvoltage (OV); bit 2 = Drive overload (OL2); bit 3 = Drive overheat (OH1, OH2); bit 5 = Fuse blown (PUF); bit 6 = PI feedback reference lost (FbL); bit 7 = External error (EF, EFO); bit 8 = Hardware error (CPF); bit 9 = Motor overload (OL1) or overtorque 1 (OL3); bit 10 = PG broken wire (PGO), overspeed (OS), speed deviation (DEV); bit 11 = Main circuit undervoltage (UV) detected; bit 12 = Undervoltage UV1, control power UV2, inrush circuit UV3, power loss; bit 13 = Missing output phase (LF); bit 14 = Modbus communications error (CE); bit 15 = Operator disconnected (OPR) | ||||
| HR | 34doc 0022H | Data link status | BITMAP16 | Read | bit 0 = Writing data; bit 3 = Upper/lower limit error; bit 4 = Data integrity error | ||||
| HR | 35doc 0023H | Frequency reference (U1-01) | Raw; units follow o1-03. | UINT16 | Read | ||||
| HR | 36doc 0024H | Output frequency (U1-02) | Raw value; the data table gives no resolution. | UINT16 | Read | ||||
| HR | 43doc 002BH | Sequence input status | Terminals S1-S7. | BITMAP16 | Read | bit 0 = S1 on; bit 1 = S2 on; bit 2 = S3 on; bit 3 = S4 on; bit 4 = S5 on; bit 5 = S6 on; bit 6 = S7 on | |||
| HR | 44doc 002CH | Drive status 2 | BITMAP16 | Read | bit 0 = Operating; bit 1 = Zero speed; bit 2 = Frequency agree; bit 3 = Desired frequency agree; bit 4 = Frequency detection 1 (output <= L4-01); bit 5 = Frequency detection 2 (output >= L4-01); bit 6 = Drive startup completed; bit 7 = Low voltage detected; bit 8 = Baseblock; bit 9 = Frequency reference not from communication; bit 10 = Run command not from communication; bit 11 = Overtorque detected; bit 12 = Frequency reference lost; bit 13 = Retrying error; bit 14 = Error (incl. Modbus time-out); bit 15 = Modbus communications time-out | ||||
| HR | 45doc 002DH | Multi-function digital output status | BITMAP16 | Read | bit 0 = Output 1 (M1-M2) on; bit 1 = Output 2 (M3-M4) on | ||||
| HR | 56doc 0038H | PI feedback level | Unsigned, 10 = 1 % of max output frequency. | UINT16 | × 0.1 | % | Read | ||
| HR | 57doc 0039H | PI input level | Signed, 10 = 1 % of max output frequency. | INT16 | × 0.1 | % | Read | ||
| HR | 58doc 003AH | PI output level | Signed, 10 = 1 % of max output frequency. | INT16 | × 0.1 | % | Read | ||
| HR | 59doc 003BH | CPU software number | UINT16 | Read | |||||
| HR | 60doc 003CH | Flash software number | UINT16 | Read | |||||
| HR | 61doc 003DH | Communication error details | Latched until a fault reset. | BITMAP16 | Read | bit 0 = CRC error; bit 1 = Invalid data length; bit 3 = Parity error; bit 4 = Overrun error; bit 5 = Framing error; bit 6 = Time-out | |||
| HR | 62doc 003EH | kVA setting | UINT16 | Read | |||||
| HR | 63doc 003FH | Control method | UINT16 | Read | |||||
| HR | 2304doc 0900H | Enter command (EEPROM) | Write 0 to store written parameters in EEPROM and RAM. | UINT16 | Write | ||||
| HR | 2320doc 0910H | Enter command (RAM only) | Write 0 to activate written parameters in RAM only. | UINT16 | Write |
Notes on this map
- TM.P7B.01 does not print Modbus addresses for parameters (b1, H5) or the U monitors, so only the Appendix D data-table registers are included; set H5 at the keypad.
- 0023H/0024H are listed raw: U1-01/U1-02 units change with o1-03 and the data table gives no resolution.
- Left out because the manual prints no units or resolution: 0025H output voltage, 0026H output current, 0027H output power, 0028H torque reference and 0031H DC bus voltage.
- The Enter command text in TM.P7B.01 names registers 0900H or 0901H but its table lists 0900H and 0910H; the table addresses are used here.
- Broadcast (address 0) accepts only 0001H and 0002H (30000 = 100 %).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Yaskawa P7B drive/bypass (legacy) - Modbus RTU
What Modbus registers does the Yaskawa P7B drive/bypass (legacy) - Modbus RTU have?
This map lists 25 registers: 25 holding registers. 9 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Yaskawa P7B drive/bypass (legacy) - Modbus RTU Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register numbers are hex and are sent unchanged: the 03H example reads starting address 00 20 (drive status) and the 10H example writes from 00 01.
What are the minimum Modbus registers to integrate the Yaskawa P7B drive/bypass (legacy) - Modbus RTU?
Start with HR 1 Operation command (Run/stop and fault reset); HR 2 Frequency reference (Frequency reference); HR 32 Drive status (Drive status); HR 33 Fault details (Fault details); HR 36 Output frequency (U1-02) (Output frequency); HR 44 Drive status 2 (Drive status 2 incl. comm timeout).
How do I enable Modbus control of the Yaskawa P7B drive/bypass (legacy) - Modbus RTU?
Set H5-01 (default 1F hex), H5-02 (default 3 = 9600) and H5-03 (default none) and cycle power. The HAND/OFF/AUTO switch must be in AUTO for serial run/stop and speed control; OFF overrides a serial run command. For monitoring only, just the H5 parameters are needed.
What happens when the Yaskawa P7B drive/bypass (legacy) - Modbus RTU loses Modbus communication?
H5-05 = 1 enables CE detection after the H5-09 time; H5-04 sets the reaction. 002CH bit F shows a comm time-out.
Where is the official Yaskawa P7B drive/bypass (legacy) - Modbus RTU Modbus documentation?
The source is P7B Drive/Bypass Technical Manual (Appendix D Communications) (TM.P7B.01), published free by Yaskawa at https://www.yaskawa.com/delegate/getAttachment?documentId=TM.P7B.01&cmd=documents&documentName=TM.P7B.01.pdf.
More Yaskawa Modbus register maps
- Variable frequency drive
Yaskawa A1000 AC drive (MEMOBUS/Modbus RTU)
Yaskawa A1000 drives (CIMR-AU; 200 V, 400 V and 600 V classes) using the built-in RS-422/485 MEMOBUS/Modbus terminals (TB5), per Technical Manual SIEP C710616 41H.
Also known as: CIMR-AU, CIMR-AUA, A1000 High Performance Vector Control Drive - Variable frequency drive (HVAC)
Yaskawa E7 HVAC drive (CIMR-E7U) - Modbus RTU
Yaskawa E7 (CIMR-E7U) HVAC fan and pump drives using the built-in RS-422/485 terminals with H5-08 = 0 (Memobus/Modbus), per Parameter Access Technical Manual TM.E7.11 (rev 3016).
Also known as: CIMR-E7U, E7U, E7 Drive - Variable frequency drive
Yaskawa F7 drive (CIMR-F7U, legacy) - Modbus RTU
Yaskawa F7 (CIMR-F7U) general-purpose drives using the built-in RS-422/485 terminals R+/R-/S+/S-, per user manual TM.F7.01 Appendix D, with parameter and monitor addresses from TM.F7.11.
Also known as: CIMR-F7U, F7U, F7 Drive - Variable frequency drive
Yaskawa FP605 enclosed bypass (MEMOBUS/Modbus RTU)
Yaskawa FP605 enclosed bypass packages using the bypass board RS-485 port (TB3) with H5-08 = 0 (MEMOBUS/Modbus); Technical Reference SIEPYAIF6B01C, section 10.6.
Also known as: FP605 Enclosed Bypass, FP605 bypass package - Variable frequency drive
Yaskawa FP605 industrial fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa FP605 drives using the built-in RS-485 port (MEMOBUS/Modbus RTU), per technical reference SIEPC7106171F.
Also known as: CIPR-FP6, FP605 drive, FP605 AC Drive for Industrial Fan and Pump Applications - Variable frequency drive
Yaskawa G7 drive (CIMR-G7U, legacy) - Modbus RTU
Yaskawa G7 (CIMR-G7U) drives using built-in Modbus RTU on terminals R+/R-/S+/S-, per the Modbus Communication Manual G7 TM.G7.11 (rev 07-01).
Also known as: CIMR-G7U, G7U, G7 Drive - Variable frequency drive
Yaskawa GA500 AC drive (MEMOBUS/Modbus RTU)
Yaskawa GA500 drives using the built-in RS-485 MEMOBUS/Modbus port (terminal TB4), per technical reference SIEPC71061752 revision C.
Also known as: CIPR-GA50U, GA500 Versatile Compact - Variable frequency drive
Yaskawa GA800 AC drive (MEMOBUS/Modbus RTU)
Yaskawa GA800 drives using the built-in RS-485 MEMOBUS/Modbus port, per technical reference SIEPC71061737 revision G.
Also known as: CIPR-GA80, GA800 Industrial AC Microdrive - Variable frequency drive
Yaskawa HV305 HVAC micro drive (MEMOBUS/Modbus RTU)
Yaskawa HV305 drives using the built-in RS-485 port with H5-08 = 0 (MEMOBUS/Modbus), per technical reference SIEPYAIHV3001B.
Also known as: HV35U, HV305 drive, HV305 Versatile Compact Drive - Variable frequency drive
Yaskawa HV600 HVAC fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa HV600 drives using the built-in RS-485 port with H5-08 = 0 (MEMOBUS/Modbus), per technical reference SIEPC71061732 revision F.
Also known as: CIPR-HV60, HV600 HVAC drive - Variable frequency drive (HVAC bypass package)
Yaskawa HV600 Narrow and Enclosed Bypass (MEMOBUS/Modbus RTU)
Yaskawa HV600 Narrow and Enclosed Bypass packages using the bypass board RS-485 port (TB3) with H5-08 = 0 (Modbus); Technical Reference SIEPYAIH6B01F, section 10.6.
Also known as: HV600 Bypass, HV600 Enclosed Bypass, HV600 Narrow Bypass - Variable frequency drive (pump)
Yaskawa iQpump drive (P7U-based, legacy) - Modbus RTU
Legacy Yaskawa iQpump drives built on the P7U platform (CIMR-P7U...), per user manual TM.iQp.01, using the built-in RS-422/485 terminals R+/R-/S+/S-.
Also known as: iQpump, CIMR-P7U iQpump, iQpump Drive - Variable frequency drive
Yaskawa iQpump Micro compact pump drive (MEMOBUS/Modbus RTU)
Yaskawa iQpump Micro drives using the built-in RS-485/422 MEMOBUS/Modbus terminals, per user manual TOEP YAIQPM 03B.
Also known as: CIMR-PW (iQpump Micro), iQpump Micro AC Drive, iQpump Micro Compact Intelligent Pump Controller - Variable frequency drive
Yaskawa iQpump1000 intelligent pump drive (MEMOBUS/Modbus RTU)
Yaskawa iQpump1000 drives (CIMR-PW) using the built-in RS-485/422 MEMOBUS/Modbus terminals, per user manual TOEPYAIP1W01G.
Also known as: CIMR-PW, CIMR-PWA, iQpump1000 AC Drive - Variable frequency drive
Yaskawa iQpump605 intelligent pump controller (MEMOBUS/Modbus RTU)
Yaskawa iQpump605 drives using the built-in RS-485 port (MEMOBUS/Modbus RTU), per user manual SIEPYAIWM6502D.
Also known as: WM65W, iQpump605 drive, iQpump605 Intelligent Pump Controller - Variable frequency drive
Yaskawa J1000 compact V/f drive (MEMOBUS/Modbus RTU)
Yaskawa J1000 drives (CIMR-JU/JC) with the optional RS-422/485 MEMOBUS/Modbus interface, per Technical Manual SIEP C710606 31D.
Also known as: CIMR-JU, CIMR-JC, J1000 Compact V/f Control Drive - Variable frequency drive (HVAC bypass package)
Yaskawa P1000 Bypass for industrial fans and pumps (MEMOBUS/Modbus RTU)
P1000 Bypass bypass controller RS-485 port with Z3-01 = 0 (Modbus); Technical Manual SIEP YAIP1B 01D, appendix D.
Also known as: P1000 Bypass, P1B - Variable frequency drive
Yaskawa P1000 industrial fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa P1000 drives using the built-in RS-485/422 MEMOBUS/Modbus port (terminals R+, R-, S+, S-), per technical manual SIEP YAIP1U 01C.
Also known as: CIMR-PU, P1000 Industrial Fan and Pump Drive - Variable frequency drive (fan / pump)
Yaskawa P7 fan/pump drive (CIMR-P7U, legacy) - Modbus RTU
Yaskawa P7 (CIMR-P7U) fan and pump drives using the built-in RS-422/485 terminals R+/R-/S+/S-, per user manual TM.P7.01 Appendix D.
Also known as: CIMR-P7U, P7U, P7 Drive - Variable frequency drive
Yaskawa U1000 Industrial MATRIX drive (MEMOBUS/Modbus RTU)
Yaskawa U1000 matrix drives using the built-in RS-422/485 MEMOBUS/Modbus port (terminals R+, R-, S+, S-), per technical manual SIEP C710636 04E.
Also known as: CIMR-UU, U1000 Industrial MATRIX Drive - Variable frequency drive
Yaskawa V1000 AC drive (MEMOBUS/Modbus RTU)
Yaskawa V1000 drives (CIMR-VU; 200 V single/three-phase and 400 V three-phase, 0.1-18.5 kW) using the built-in RS-422/485 MEMOBUS/Modbus terminals, per Technical Manual SIEP C710606 18F.
Also known as: CIMR-VU, V1000 Compact Vector Control Drive - Variable frequency drive
Yaskawa V7 / V74X compact drive (legacy) - Modbus RTU
Yaskawa V7 (CIMR-V7AM) and V74X (CIMR-V7CU) compact drives with built-in Modbus RTU (keypad RJ-45 or R+/R-/S+/S- terminals), per TM.V7.11 Rev 07-01.
Also known as: CIMR-V7AM, CIMR-V7CU, V74X - Variable frequency drive (HVAC bypass package)
Yaskawa Z1000 Bypass for HVAC fans and pumps (MEMOBUS/Modbus RTU)
Z1000 Bypass bypass controller RS-485 port with Z3-01 = 0 (Modbus); Technical Manual SIEP YAIZ1B 01F, appendix D.
Also known as: Z1000 Bypass, Z1B1 - Variable frequency drive (HVAC fan / pump)
Yaskawa Z1000 HVAC fan/pump drive (MEMOBUS/Modbus RTU)
Yaskawa Z1000 HVAC drives (CIMR-ZU) using the built-in RS-485 terminals with H5-08 = 0, per Programming Manual SIEP YAIZ1U 03C (the copy covers the 600 V class models 5A0007-5A0242).
Also known as: CIMR-ZU, Z1000 AC Drive for HVAC Fan and Pump - Variable frequency drive
Yaskawa Z1000U HVAC matrix drive (MEMOBUS/Modbus RTU)
Yaskawa Z1000U HVAC matrix drives using the built-in serial terminals with H5-08 = 0 (MEMOBUS/Modbus), per programming manual SIEP C710636 10D.
Also known as: Z1000U HVAC MATRIX Drive, Z1000U Matrix
Other variable frequency drives register maps
- Variable frequency drive
ABB ACH480 HVAC drive (embedded Modbus RTU)
ACH480 drives running the ACH480 HVAC control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000247134 Rev E.
Also known as: ACH480-04, ACH480 HVAC control program - Variable frequency drive
ABB ACS380 machinery drive (embedded Modbus RTU)
ACS380 drives running the machinery control program with the BMIO-01 I/O and Modbus RTU module, embedded fieldbus (EFB), addressing mode 0 (default); firmware manual 3AXD50000029275 Rev J.
Also known as: ACS380-04, ACS380 machinery control program, BMIO-01 - Pump (vertical in-line with integrated VFD)
Armstrong Fluid Technology Design Envelope 4300 / 4380 with DEPM IVS / DE IVS drive (map v2)
Armstrong Design Envelope 4300 and 4380 vertical in-line pumps with DEPM IVS or DE IVS drive, controller firmware v1.17 and newer (Modbus register map version 2).
Also known as: Design Envelope 4300, Design Envelope 4380, DEPM IVS, DE IVS, Design Envelope pump controller, DEPC - Variable frequency drive
Bonfiglioli Agile frequency inverter (Modbus RTU/ASCII)
Bonfiglioli Agile 230 V / 400 V frequency inverters, Modbus on the X21 RJ45 connection or a CM-232/CM-485 module, per Modbus communication manual VEC 691 R1 (02/2011).
Also known as: Agile, AGL, Bonfiglioli Agile - Variable frequency drive
Danfoss VLT HVAC Drive FC 102 (Modbus RTU)
VLT HVAC Drive FC 102 using the built-in RS-485 (FC) port with 8-30 Protocol = Modbus RTU and the FC control profile; parameter scaling checked against the software 7.61 programming guide.
Also known as: VLT HVAC Drive, FC102, FC-102 - Variable frequency drive
Eaton PowerXL DC1 compact drive (Modbus RTU)
Eaton PowerXL DC1 per the Modbus RTU communication manual MN040018EN, edition 12/22.
Also known as: DC1, PowerXL DC1, DC1-1D, DC1-12, DC1-32, DC1-34, DC1-S2
All variable frequency drives Modbus register maps →
Source: P7B Drive/Bypass Technical Manual (Appendix D Communications) · TM.P7B.01. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.