Bonfiglioli Agile frequency inverter (Modbus RTU/ASCII) Modbus register map

Updated 17 November 2026

Short answer

Bonfiglioli's Agile general purpose inverter speaks Modbus RTU or ASCII on its X21 RJ45 port. The register address is the parameter number in the low 12 bits plus the data set number in the top 4 bits, and 32-bit parameters are read as two registers at a single parameter address. This map covers the control and status words, the RAM frequency and percentage references, error and warning readouts and the Modbus settings.

This page lists 17 Modbus registers for the Bonfiglioli Agile frequency inverter (Modbus RTU/ASCII) — 11 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Bonfiglioli’s own free documentation (linked below) and checked against it.

Manufacturer
Bonfiglioli
Model
Agile frequency inverter (Modbus RTU/ASCII)
Equipment type
Variable frequency drive
Registers
17 (11 writable)
Transport
Modbus RTU, Modbus ASCII
Default unit ID
1
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Also known as
Agile, AGL, Bonfiglioli Agile
Source document
Modbus Communication manual - Frequency inverter 230V / 400V Agile · VEC 691 R1 · rev. 2011-02
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Bonfiglioli Agile frequency inverter (Modbus RTU/ASCII)

Integration in brief

Set 395 so Modbus is on the port you use, set 1376/1504/1375, then 412 = 1 to control by statemachine. Write 484 (2 registers, 0.01 Hz) and drive control word 410 through Shutdown (0x0006), Switch on (0x0007) and Enable operation (0x000F); poll 411 status and 260 actual error.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 410Control wordBITMAP16Control wordRead/write
HR 411Status wordBITMAP16Status wordRead
HR 484Reference frequency RAMINT32 ABCDFrequency reference, 0.01 Hz (32-bit)Read/write
HR 412Local/RemoteUINT16Local/Remote: 1 = statemachineRead/write
HR 260Actual errorUINT16Actual errorRead
HR 270WarningsBITMAP16WarningsRead
HR 11VABus SST error registerUINT16Modbus error registerRead

Enable Modbus control & writes

Parameter 395 Protocol picks which port runs Modbus (factory 1: X21 RJ45 = Modbus). Set 1503 mode (RTU/ASCII), 1504 baud, 1375 parity and 1376 address; these take effect immediately without a restart. Set 412 Local/Remote = 1 for control-word operation (or 2 for remote contacts). The hardware release (STOA/STOB) and a Start Right/Left digital input must still be present to reach Operation enabled.

Communication loss & watchdog

1505 Modbus watchdog timer in seconds (factory 0 = off). If no correct exchange occurs within that time the inverter trips with a fault.

Byte order & addressing

Network setup

Watch out for

Bonfiglioli Agile frequency inverter (Modbus RTU/ASCII) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

17 of 17 shown
Bonfiglioli Agile frequency inverter (Modbus RTU/ASCII) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR11VABus SST error registerModbus/VABus error code (0-15); read it to acknowledge write errors.UINT16Read
HR249Active data setCurrently active data set 1-4.UINT16Read
HR260Actual errorCode of the current fault (0-0xFFFF).UINT16Read
HR270WarningsBit-coded warnings; several can be set at once.BITMAP16Readbit 0 = Warning Ixt (set with bit 1 or 2); bit 1 = Short-time Ixt; bit 2 = Long-time Ixt; bit 3 = Heat sink temperature; bit 4 = Inside temperature; bit 5 = Current limit; bit 6 = Init; bit 7 = Motor temperature; bit 8 = Mains phase failure; bit 9 = Motor protective switch; bit 10 = Fmax; bit 11 = Analog input MFI1A; bit 12 = Analog input MFI2A; bit 13 = Systembus slave in fault; bit 14 = DC link voltage (Udc); bit 15 = Application warning (see 274)
HR274Application warningsApplication warning status bits.UINT16Read
HR395Protocol (CM / X21)UINT16Read/write0 = CM: VABus / X21: VABus; 1 = CM: VABus / X21: Modbus; 2 = CM: Modbus / X21: VABus
HR410Control wordUsed when Local/Remote 412 = 1 (statemachine); write in data set 0.BITMAP16Read/writebit 0 = Switch on; bit 1 = Enable voltage; bit 2 = Quick stop (0 = quick stop); bit 3 = Enable operation; bit 7 = Reset fault (rising edge)
HR411Status wordBITMAP16Readbit 0 = Ready to switch on; bit 1 = Switched on; bit 2 = Operation enabled; bit 3 = Error; bit 4 = Voltage enabled (mains present); bit 5 = Quick stop; bit 6 = Switch on disabled; bit 7 = Warning (see 270); bit 9 = Remote; bit 10 = Reference value reached; bit 11 = Limit value reached; bit 15 = Warning 2 (fault switch-off imminent)
HR412Local/RemoteUINT16Read/write0 = Control via contacts; 1 = Control via statemachine (control word 410); 2 = Control via remote contacts
HR414Data set selection0 = digital inputs; 1-4 = set by bus; 5 = switch only when not released.UINT16Read/write
HR484Reference frequency RAMLong, two decimals: -999.99 to 999.99 Hz. Read/write 2 registers at 484.INT32ABCD× 0.01HzRead/write
HR524Reference percentage RAMLong, two decimals: -300.00 to 300.00 %. Read/write 2 registers at 524.INT32ABCD× 0.01%Read/write
HR1375Modbus parityUINT16Read/write0 = Even; 1 = Odd; 2 = None
HR1376Modbus address1-247, factory 1.UINT16Read/write
HR1503Modbus modeUINT16Read/write0 = RTU; 1 = ASCII
HR1504Modbus baud rateUINT16Read/write1 = 2400; 2 = 4800; 3 = 9600; 4 = 19200; 5 = 57600; 6 = 115200; 7 = 230400
HR1505Modbus watchdog timer0 = off (factory); fault if no valid exchange in this time.UINT16sRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Bonfiglioli Agile frequency inverter (Modbus RTU/ASCII)

What Modbus registers does the Bonfiglioli Agile frequency inverter (Modbus RTU/ASCII) have?

This map lists 17 registers: 17 holding registers. 11 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Bonfiglioli Agile frequency inverter (Modbus RTU/ASCII) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The start address field carries the parameter number (0-1599) in bits 0-11 and the data set (0-9) in bits 12-15, sent as-is: parameter 481 in data set 1 is 0x11E1, in data set 0 it is 0x01E1 (= 481). This map lists data set 0 addresses (parameter number). For another data set add 0x1000 x data set (data set 2 of parameter 372 = 0x2174).

What byte order does the Bonfiglioli Agile frequency inverter (Modbus RTU/ASCII) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Bonfiglioli Agile frequency inverter (Modbus RTU/ASCII)?

Start with HR 410 Control word (Control word); HR 411 Status word (Status word); HR 484 Reference frequency RAM (Frequency reference, 0.01 Hz (32-bit)); HR 412 Local/Remote (Local/Remote: 1 = statemachine); HR 260 Actual error (Actual error); HR 270 Warnings (Warnings); HR 11 VABus SST error register (Modbus error register).

How do I enable Modbus control of the Bonfiglioli Agile frequency inverter (Modbus RTU/ASCII)?

Parameter 395 Protocol picks which port runs Modbus (factory 1: X21 RJ45 = Modbus). Set 1503 mode (RTU/ASCII), 1504 baud, 1375 parity and 1376 address; these take effect immediately without a restart. Set 412 Local/Remote = 1 for control-word operation (or 2 for remote contacts). The hardware release (STOA/STOB) and a Start Right/Left digital input must still be present to reach Operation enabled.

What happens when the Bonfiglioli Agile frequency inverter (Modbus RTU/ASCII) loses Modbus communication?

1505 Modbus watchdog timer in seconds (factory 0 = off). If no correct exchange occurs within that time the inverter trips with a fault.

Where is the official Bonfiglioli Agile frequency inverter (Modbus RTU/ASCII) Modbus documentation?

The source is Modbus Communication manual - Frequency inverter 230V / 400V Agile (VEC 691 R1), revision 2011-02, published free by Bonfiglioli at https://www.bonfiglioli.com/_default_upload_bucket/AGL_Modbus_EN_VEC691R1.pdf.

More Bonfiglioli Modbus register maps

Other variable frequency drives register maps

All variable frequency drives Modbus register maps →

Source: Modbus Communication manual - Frequency inverter 230V / 400V Agile · VEC 691 R1 · rev. 2011-02. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.