- Home
- Modbus register maps
- Yaskawa
- J1000 compact V/f drive (MEMOBUS/Modbus RTU)
Variable frequency drive · Modbus register map
Yaskawa J1000 compact V/f drive (MEMOBUS/Modbus RTU) Modbus register map
Updated 17 November 2026
The J1000 is Yaskawa's compact V/f drive; MEMOBUS/Modbus RTU needs the optional RS-422/485 interface. Commands are written to hex registers 0001H-000FH, status, fault and alarm words are read from 0020H upward, U monitors from 0040H, and parameters have their own hex addresses. This map covers the command block, all status/fault/alarm/CPF words, the main monitors, fault and alarm code tables, and the b1/H5 setup parameters.
This page lists 56 Modbus registers for the Yaskawa J1000 compact V/f drive (MEMOBUS/Modbus RTU) — 16 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Yaskawa’s own free documentation (linked below) and checked against it.
- Manufacturer
- Yaskawa
- Model
- J1000 compact V/f drive (MEMOBUS/Modbus RTU)
- Equipment type
- Variable frequency drive
- Registers
- 56 (16 writable)
- Transport
- Modbus RTU
- Default unit ID
- 31
- Default serial
- 9600 baud, 8N1
- Documented addressing
- hexadecimal, 0-based
- Also known as
- CIMR-JU, CIMR-JC, J1000 Compact V/f Control Drive
Integration notes: Yaskawa J1000 compact V/f drive (MEMOBUS/Modbus RTU)
Fit the RS-422/485 option, set H5-01..H5-03 and power-cycle, set b1-01 = 2 and b1-02 = 2, then write 0001H/0002H with function 10H and poll 0020H-002DH.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 1 | Operation signals and multi-function inputs | BITMAP16 | Run/stop and reset | Read/write |
| HR 2 | Frequency reference | UINT16 | Frequency reference | Read/write |
| HR 32 | Drive status 1 | BITMAP16 | Drive status 1 | Read |
| HR 33 | Fault contents 1 | BITMAP16 | Fault contents | Read |
| HR 36 | Output frequency | UINT16 | Output frequency | Read |
| HR 44 | Drive status 2 | BITMAP16 | Drive status 2 incl. comm timeout | Read |
| HR 66 | Output current (U1-03) | UINT16 | Output current (% rated) | Read |
| HR 128 | Current fault (U2-01) | UINT16 | Current fault code | Read |
Enable Modbus control & writes
H5-01 address (default 1Fh), H5-02 speed (default 3 = 9600), H5-03 parity (default none); cycle power. b1-01 = 2 and b1-02 = 2 hand reference and run to Modbus; H5-12 picks FWD/REV vs RUN/DIR bit meaning and H5-13 the frequency unit.
Communication loss & watchdog
H5-05 = 1 (default) raises CE when no data arrives for 2 s; H5-04 sets the reaction: 0 ramp, 1 coast, 2 fast-stop, 3 alarm only (default). 002CH bit F flags the timeout.
Byte order & addressing
- Registers are hex and 0-based.
- No 06H function: use 10H for single writes.
- Parameter changes take effect in RAM immediately; write 0 to 0900H to keep them over power loss. 0900H is write-only.
- Wait at least 10 ms between commands, 50 ms after a parameter write and 3-5 s after Enter.
Network setup
- MEMOBUS/Modbus needs the optional RS-422/485 interface for the J1000.
- Speeds 1200-38400 bps; parity none/even/odd; power-cycle after H5-01..H5-03 changes.
- H5-07 = 1 (RTS switched) for RS-485.
Watch out for
- With H5-01 = 0 the drive sends no Modbus responses.
Yaskawa J1000 compact V/f drive (MEMOBUS/Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1doc 0001H | Operation signals and multi-function inputs | Bits 0/1 meaning set by H5-12. | BITMAP16 | Read/write | bit 0 = H5-12=0: forward run; H5-12=1: run; bit 1 = H5-12=0: reverse run; H5-12=1: reverse direction; bit 2 = External fault (EF0); bit 3 = Fault reset; bit 4 = Multi-function input 1; bit 5 = Multi-function input 2; bit 6 = Multi-function input 3; bit 7 = Multi-function input 4; bit 8 = Multi-function input 5 | |||
| HR | 2doc 0002H | Frequency reference | Units set by H5-13 (default 0.1 Hz). | UINT16 | Read/write | ||||
| HR | 9doc 0009H | Multi-function digital output setting | BITMAP16 | Read/write | bit 0 = Contact output MA-MB-MC | ||||
| HR | 15doc 000FH | Control selection setting | BITMAP16 | Read/write | bit 12 = Terminal S5 input enabled (broadcast) | ||||
| HR | 32doc 0020H | Drive status 1 | BITMAP16 | Read | bit 0 = During run; bit 1 = During reverse; bit 2 = Drive ready; bit 3 = Fault; bit 4 = Data setting error; bit 5 = Contact output MA/MB-MC; bit 14 = ComRef enabled; bit 15 = ComCtrl enabled | ||||
| HR | 33doc 0021H | Fault contents 1 | BITMAP16 | Read | bit 0 = Overcurrent (oC); bit 1 = Overvoltage (ov); bit 2 = Drive overload (oL2); bit 3 = Overheat 1 (oH1); bit 4 = Braking resistor overheat (rH); bit 7 = External fault EF0-EF5; bit 8 = Hardware fault CPF (incl. oFx); bit 9 = Motor overload (oL1) / overtorque 1 (oL3); bit 11 = Main circuit undervoltage (Uv); bit 12 = Undervoltage (Uv1) / soft charge fault (Uv3); bit 13 = Output (LF) or input (PF) phase loss; bit 14 = Modbus communication error (CE); bit 15 = Operator connection fault (oPr) | ||||
| HR | 34doc 0022H | Data link status | BITMAP16 | Read | bit 0 = Writing data or switching motors; bit 3 = Upper or lower limit error; bit 4 = Data conformity error; bit 5 = Writing to EEPROM | ||||
| HR | 35doc 0023H | Frequency reference | Units set by H5-13. | UINT16 | Read | ||||
| HR | 36doc 0024H | Output frequency | Units set by H5-13. | UINT16 | Read | ||||
| HR | 37doc 0025H | Output voltage reference | UINT16 | × 0.1 | V | Read | |||
| HR | 41doc 0029H | Fault contents 2 | BITMAP16 | Read | bit 2 = Input phase loss (PF); bit 3 = Output phase loss (LF); bit 4 = Braking resistor overheat (rH) | ||||
| HR | 42doc 002AH | Alarm contents 1 | BITMAP16 | Read | bit 2 = Run command input error (EF); bit 3 = Drive baseblock (bb); bit 4 = Overtorque detection 1 (oL3); bit 5 = Heatsink overheat (oH); bit 6 = Overvoltage (ov); bit 7 = Undervoltage (Uv); bit 9 = Modbus communication error (CE) | ||||
| HR | 43doc 002BH | Input terminal status | BITMAP16 | Read | bit 0 = S1 closed; bit 1 = S2 closed; bit 2 = S3 closed; bit 3 = S4 closed; bit 4 = S5 closed | ||||
| HR | 44doc 002CH | Drive status 2 | BITMAP16 | Read | bit 0 = During run; bit 1 = Zero speed; bit 2 = Speed agree; bit 3 = User speed agree; bit 4 = Frequency detection 1; bit 5 = Frequency detection 2; bit 6 = Drive ready; bit 7 = During undervoltage; bit 8 = During baseblock; bit 9 = Frequency reference from operator keypad; bit 10 = Run command from operator keypad; bit 11 = Overtorque; bit 14 = Fault; bit 15 = Communication timeout | ||||
| HR | 45doc 002DH | Output terminal status | BITMAP16 | Read | bit 0 = Contact output MA/MB-MC | ||||
| HR | 49doc 0031H | DC bus voltage | UINT16 | V | Read | ||||
| HR | 61doc 003DH | Communications error log | Kept until fault reset. | BITMAP16 | Read | bit 0 = CRC error; bit 1 = Data length error; bit 3 = Parity error; bit 4 = Overrun error; bit 5 = Framing error; bit 6 = Timeout | |||
| HR | 64doc 40 | Frequency reference (U1-01) | Raw; display unit follows o1-03 (default 0.01 Hz). | UINT16 | Read | ||||
| HR | 65doc 41 | Output frequency (U1-02) | Raw; display unit follows o1-03 (default 0.01 Hz). | UINT16 | Read | ||||
| HR | 66doc 42 | Output current (U1-03) | Over Modbus 8192 = 100 % of drive rated current. | UINT16 | × 0.0122070312 | % | Read | ||
| HR | 69doc 45 | Output voltage reference (U1-06) | UINT16 | × 0.1 | V | Read | |||
| HR | 70doc 46 | DC bus voltage (U1-07) | UINT16 | V | Read | ||||
| HR | 73doc 49 | Input terminal status (U1-10) | BITMAP16 | Read | bit 0 = S1; bit 1 = S2; bit 2 = S3; bit 3 = S4; bit 4 = S5 | ||||
| HR | 74doc 4A | Output terminal status (U1-11) | BITMAP16 | Read | bit 0 = MA/MB-MC (fault) | ||||
| HR | 76doc 4C | Accumulated operation time (U4-01) | Modbus value is in 10 h units. | UINT16 | × 10 | h | Read | ||
| HR | 78doc 4E | Terminal A1 input level (U1-13) | 100 % = 10 V or 20 mA. | UINT16 | × 0.1 | % | Read | ||
| HR | 102doc 66 | Modbus error code (U1-19) | BITMAP16 | Read | bit 0 = CRC error; bit 1 = Data length error; bit 3 = Parity error; bit 4 = Overrun error; bit 5 = Framing error; bit 6 = Timed out | ||||
| HR | 124doc 7C | Capacitor maintenance (U4-05) | Percent of expected life. | UINT16 | % | Read | |||
| HR | 126doc 7E | Cooling fan maintenance (U4-04) | Percent of expected life. | UINT16 | % | Read | |||
| HR | 127doc 007FH | Alarm code | Active alarm (Table C.5). | UINT16 | Read | 1 = Uv undervoltage; 2 = ov overvoltage; 3 = oH heatsink overheat; 5 = oL3 overtorque 1; 7 = EF run command input error; 8 = bb baseblock; 9 = EF3 external fault S3; 10 = EF4 external fault S4; 11 = EF5 external fault S5; 20 = CE Modbus communication error; 23 = oL1 motor overload; 24 = oL2 drive overload; 32 = SE Modbus test mode fault; 57 = EF1 external fault S1; 58 = EF2 external fault S2 | |||
| HR | 128doc 80 | Current fault (U2-01) | UINT16 | Read | 2 = Uv1 undervoltage; 4 = Uv3 soft charge circuit fault; 7 = oC overcurrent; 8 = ov overvoltage; 10 = oH1 heatsink overheat; 11 = oL1 motor overload; 12 = oL2 drive overload; 13 = oL3 overtorque detection 1; 16 = rH braking resistor overheat; 17 = EF3 external fault S3; 18 = EF4 external fault S4; 19 = EF5 external fault S5; 27 = PF input phase loss; 28 = LF output phase loss; 30 = oPr operator connection; 31 = Err EEPROM write error; 33 = CE Modbus communication error; 39 = EF0 option external fault; 66 = EF1 external fault S1; 67 = EF2 external fault S2; 70 = CoF current offset fault; 131 = CPF02 A/D conversion error; 135 = CPF06 drive specification mismatch; 137 = CPF08 EEPROM serial communication fault; 140 = CPF11 RAM fault; 141 = CPF12 flash memory fault; 143 = CPF14 control circuit fault; 146 = CPF17 timing fault; 147 = CPF18 control circuit fault; 149 = CPF20 hardware fault at power up; 150 = CPF21 hardware fault at communication start; 151 = CPF22 A/D conversion fault; 152 = CPF23 PWM feedback fault; 153 = CPF24 drive capacity signal fault; 257 = oFA00 option compatibility error | ||||
| HR | 129doc 81 | Previous fault (U2-02) | UINT16 | Read | 2 = Uv1 undervoltage; 4 = Uv3 soft charge circuit fault; 7 = oC overcurrent; 8 = ov overvoltage; 10 = oH1 heatsink overheat; 11 = oL1 motor overload; 12 = oL2 drive overload; 13 = oL3 overtorque detection 1; 16 = rH braking resistor overheat; 17 = EF3 external fault S3; 18 = EF4 external fault S4; 19 = EF5 external fault S5; 27 = PF input phase loss; 28 = LF output phase loss; 30 = oPr operator connection; 31 = Err EEPROM write error; 33 = CE Modbus communication error; 39 = EF0 option external fault; 66 = EF1 external fault S1; 67 = EF2 external fault S2; 70 = CoF current offset fault; 131 = CPF02 A/D conversion error; 135 = CPF06 drive specification mismatch; 137 = CPF08 EEPROM serial communication fault; 140 = CPF11 RAM fault; 141 = CPF12 flash memory fault; 143 = CPF14 control circuit fault; 146 = CPF17 timing fault; 147 = CPF18 control circuit fault; 149 = CPF20 hardware fault at power up; 150 = CPF21 hardware fault at communication start; 151 = CPF22 A/D conversion fault; 152 = CPF23 PWM feedback fault; 153 = CPF24 drive capacity signal fault; 257 = oFA00 option compatibility error | ||||
| HR | 152doc 0098H | Cumulative operation time (upper) | Hours / 10, e.g. 12345 h -> 1234. | UINT16 | × 10 | h | Read | ||
| HR | 153doc 0099H | Cumulative operation time (ones) | Last digit of hours, e.g. 12345 h -> 5. | UINT16 | h | Read | |||
| HR | 191doc 00BFH | oPE error number | UINT16 | Read | |||||
| HR | 192doc 00C0H | Fault contents 1 (detail) | BITMAP16 | Read | bit 1 = Uv1; bit 3 = Uv3; bit 6 = oC; bit 7 = ov; bit 9 = oH1; bit 10 = oL1; bit 11 = oL2; bit 12 = oL3; bit 15 = rH | ||||
| HR | 193doc 00C1H | Fault contents 2 (detail) | BITMAP16 | Read | bit 0 = EF3; bit 1 = EF4; bit 2 = EF5; bit 10 = PF; bit 13 = oPr; bit 14 = Err | ||||
| HR | 194doc 00C2H | Fault contents 3 (detail) | BITMAP16 | Read | bit 0 = CE; bit 6 = EF0 from RS-422/485 interface; bit 15 = Hardware fault (incl. oFx) | ||||
| HR | 196doc 00C4H | Fault contents 5 (detail) | BITMAP16 | Read | bit 1 = EF1; bit 2 = EF2; bit 5 = CoF current offset fault | ||||
| HR | 200doc 00C8H | Alarm contents 2 | BITMAP16 | Read | bit 0 = Uv; bit 1 = ov; bit 2 = oH; bit 4 = oL3; bit 6 = EF run command input error; bit 7 = bb; bit 8 = EF3; bit 9 = EF4; bit 10 = EF5 | ||||
| HR | 201doc 00C9H | Alarm contents 3 | BITMAP16 | Read | bit 2 = oPr; bit 3 = CE; bit 5 = CALL serial transmission error; bit 6 = oL1; bit 7 = oL2 | ||||
| HR | 203doc 00CBH | Alarm contents 5 | BITMAP16 | Read | bit 8 = EF1; bit 9 = EF2 | ||||
| HR | 208doc 00D0H | CPF contents 1 | BITMAP16 | Read | bit 2 = CPF02; bit 6 = CPF06; bit 8 = CPF08; bit 11 = CPF11; bit 12 = CPF12; bit 14 = CPF14 | ||||
| HR | 209doc 00D1H | CPF contents 2 | BITMAP16 | Read | bit 1 = CPF17; bit 2 = CPF18; bit 6 = CPF22; bit 7 = CPF23; bit 8 = CPF24 | ||||
| HR | 384doc 180 | b1-01 Frequency reference selection | UINT16 | Read/write | 0 = Digital operator; 1 = Terminal A1; 2 = MEMOBUS/Modbus (option); 3 = Potentiometer (option) | ||||
| HR | 385doc 181 | b1-02 Run command selection | UINT16 | Read/write | 0 = Digital operator; 1 = Digital input terminals; 2 = MEMOBUS/Modbus (option) | ||||
| HR | 1061doc 425 | H5-01 Drive slave address | 0-FFh, default 1Fh; 0 = no response. Power-cycle. | UINT16 | Read/write | ||||
| HR | 1062doc 426 | H5-02 Communication speed | Power-cycle after change. | UINT16 | Read/write | 0 = 1200; 1 = 2400; 2 = 4800; 3 = 9600; 4 = 19200; 5 = 38400 | |||
| HR | 1063doc 427 | H5-03 Parity | Power-cycle after change. | UINT16 | Read/write | 0 = None; 1 = Even; 2 = Odd | |||
| HR | 1064doc 428 | H5-04 Stopping method after CE | UINT16 | Read/write | 0 = Ramp to stop; 1 = Coast to stop; 2 = Fast-stop; 3 = Alarm only | ||||
| HR | 1065doc 429 | H5-05 CE fault detection | CE after 2 s without data when enabled. | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | |||
| HR | 1066doc 42A | H5-06 Drive transmit wait time | 10-65 ms. | UINT16 | ms | Read/write | |||
| HR | 1067doc 42B | H5-07 RTS control | UINT16 | Read/write | 0 = Disabled (RTS always on); 1 = Enabled (RTS on when sending) | ||||
| HR | 1085doc 43D | H5-12 Run command method | UINT16 | Read/write | 0 = FWD/STOP, REV/STOP; 1 = RUN/STOP, FWD/REV | ||||
| HR | 1086doc 43E | H5-13 Frequency reference/monitor unit | Unit of 0002H, 0023H, 0024H. | UINT16 | Read/write | 0 = 0.1 Hz / 1; 1 = o1-03 based; 2 = 100 % / 30000; 3 = 0.1 % / 1 | |||
| HR | 2304doc 0900H | Enter command | Write 0 to save parameters to EEPROM (100,000 writes max). | UINT16 | Write |
Notes on this map
- U1-03 output current reads 8192 = 100 % of drive rated current over Modbus (parameter-table footnote), so it is mapped as percent.
- The 10H example writes 1770H (6000) for 60.00 Hz, while H5-13 default 0 is printed as 0.1 Hz/1; because of that conflict the frequency registers are left unscaled.
- Left out because the sign or unit is not stated: 0007H AM output setting, 0026H output current (no unit printed), 003FH/00B6H/00B8H frequency in 0.01 % (sign not stated), 0068H heatsink temperature, 00ABH rated current, U4-06/U4-07 and U4-13.
- Fault and alarm values are the hex codes of Tables C.4 and C.5 converted to decimal (e.g. 0021H CE = 33).
- Function codes 03H, 08H and 10H only; there is no single-register write (06H). Up to 16 registers per message.
- Broadcast (address 0) accepts 0001H (bit 0 run, bit 1 direction, bit 4 external fault, bit 5 fault reset, bit C S5) and 0002H (30000 = 100 %).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Yaskawa J1000 compact V/f drive (MEMOBUS/Modbus RTU)
What Modbus registers does the Yaskawa J1000 compact V/f drive (MEMOBUS/Modbus RTU) have?
This map lists 56 registers: 56 holding registers. 16 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Yaskawa J1000 compact V/f drive (MEMOBUS/Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register numbers are hex and sent unchanged: the 03H example reads from 00 20 (drive status) and the 10H example writes 0001H/0002H from 00 01 (0002H = 1770H = 6000 for 60.00 Hz). The parameter table lists addresses in hex without the H suffix (b1-01 = 180, H5-01 = 425, U1-01 = 40).
What are the minimum Modbus registers to integrate the Yaskawa J1000 compact V/f drive (MEMOBUS/Modbus RTU)?
Start with HR 1 Operation signals and multi-function inputs (Run/stop and reset); HR 2 Frequency reference (Frequency reference); HR 32 Drive status 1 (Drive status 1); HR 33 Fault contents 1 (Fault contents); HR 36 Output frequency (Output frequency); HR 44 Drive status 2 (Drive status 2 incl. comm timeout); HR 66 Output current (U1-03) (Output current (% rated)); HR 128 Current fault (U2-01) (Current fault code).
How do I enable Modbus control of the Yaskawa J1000 compact V/f drive (MEMOBUS/Modbus RTU)?
H5-01 address (default 1Fh), H5-02 speed (default 3 = 9600), H5-03 parity (default none); cycle power. b1-01 = 2 and b1-02 = 2 hand reference and run to Modbus; H5-12 picks FWD/REV vs RUN/DIR bit meaning and H5-13 the frequency unit.
What happens when the Yaskawa J1000 compact V/f drive (MEMOBUS/Modbus RTU) loses Modbus communication?
H5-05 = 1 (default) raises CE when no data arrives for 2 s; H5-04 sets the reaction: 0 ramp, 1 coast, 2 fast-stop, 3 alarm only (default). 002CH bit F flags the timeout.
Where is the official Yaskawa J1000 compact V/f drive (MEMOBUS/Modbus RTU) Modbus documentation?
The source is YASKAWA AC Drive J1000 Compact V/f Control Drive Technical Manual (SIEP C710606 31D), published free by Yaskawa at https://www.yaskawa.com/delegate/getAttachment?documentId=SIEPC71060631&cmd=documents&documentName=SIEPC71060631.pdf.
More Yaskawa Modbus register maps
- Variable frequency drive
Yaskawa A1000 AC drive (MEMOBUS/Modbus RTU)
Yaskawa A1000 drives (CIMR-AU; 200 V, 400 V and 600 V classes) using the built-in RS-422/485 MEMOBUS/Modbus terminals (TB5), per Technical Manual SIEP C710616 41H.
Also known as: CIMR-AU, CIMR-AUA, A1000 High Performance Vector Control Drive - Variable frequency drive (HVAC)
Yaskawa E7 HVAC drive (CIMR-E7U) - Modbus RTU
Yaskawa E7 (CIMR-E7U) HVAC fan and pump drives using the built-in RS-422/485 terminals with H5-08 = 0 (Memobus/Modbus), per Parameter Access Technical Manual TM.E7.11 (rev 3016).
Also known as: CIMR-E7U, E7U, E7 Drive - Variable frequency drive
Yaskawa F7 drive (CIMR-F7U, legacy) - Modbus RTU
Yaskawa F7 (CIMR-F7U) general-purpose drives using the built-in RS-422/485 terminals R+/R-/S+/S-, per user manual TM.F7.01 Appendix D, with parameter and monitor addresses from TM.F7.11.
Also known as: CIMR-F7U, F7U, F7 Drive - Variable frequency drive
Yaskawa FP605 enclosed bypass (MEMOBUS/Modbus RTU)
Yaskawa FP605 enclosed bypass packages using the bypass board RS-485 port (TB3) with H5-08 = 0 (MEMOBUS/Modbus); Technical Reference SIEPYAIF6B01C, section 10.6.
Also known as: FP605 Enclosed Bypass, FP605 bypass package - Variable frequency drive
Yaskawa FP605 industrial fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa FP605 drives using the built-in RS-485 port (MEMOBUS/Modbus RTU), per technical reference SIEPC7106171F.
Also known as: CIPR-FP6, FP605 drive, FP605 AC Drive for Industrial Fan and Pump Applications - Variable frequency drive
Yaskawa G7 drive (CIMR-G7U, legacy) - Modbus RTU
Yaskawa G7 (CIMR-G7U) drives using built-in Modbus RTU on terminals R+/R-/S+/S-, per the Modbus Communication Manual G7 TM.G7.11 (rev 07-01).
Also known as: CIMR-G7U, G7U, G7 Drive - Variable frequency drive
Yaskawa GA500 AC drive (MEMOBUS/Modbus RTU)
Yaskawa GA500 drives using the built-in RS-485 MEMOBUS/Modbus port (terminal TB4), per technical reference SIEPC71061752 revision C.
Also known as: CIPR-GA50U, GA500 Versatile Compact - Variable frequency drive
Yaskawa GA800 AC drive (MEMOBUS/Modbus RTU)
Yaskawa GA800 drives using the built-in RS-485 MEMOBUS/Modbus port, per technical reference SIEPC71061737 revision G.
Also known as: CIPR-GA80, GA800 Industrial AC Microdrive - Variable frequency drive
Yaskawa HV305 HVAC micro drive (MEMOBUS/Modbus RTU)
Yaskawa HV305 drives using the built-in RS-485 port with H5-08 = 0 (MEMOBUS/Modbus), per technical reference SIEPYAIHV3001B.
Also known as: HV35U, HV305 drive, HV305 Versatile Compact Drive - Variable frequency drive
Yaskawa HV600 HVAC fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa HV600 drives using the built-in RS-485 port with H5-08 = 0 (MEMOBUS/Modbus), per technical reference SIEPC71061732 revision F.
Also known as: CIPR-HV60, HV600 HVAC drive - Variable frequency drive (HVAC bypass package)
Yaskawa HV600 Narrow and Enclosed Bypass (MEMOBUS/Modbus RTU)
Yaskawa HV600 Narrow and Enclosed Bypass packages using the bypass board RS-485 port (TB3) with H5-08 = 0 (Modbus); Technical Reference SIEPYAIH6B01F, section 10.6.
Also known as: HV600 Bypass, HV600 Enclosed Bypass, HV600 Narrow Bypass - Variable frequency drive (pump)
Yaskawa iQpump drive (P7U-based, legacy) - Modbus RTU
Legacy Yaskawa iQpump drives built on the P7U platform (CIMR-P7U...), per user manual TM.iQp.01, using the built-in RS-422/485 terminals R+/R-/S+/S-.
Also known as: iQpump, CIMR-P7U iQpump, iQpump Drive - Variable frequency drive
Yaskawa iQpump Micro compact pump drive (MEMOBUS/Modbus RTU)
Yaskawa iQpump Micro drives using the built-in RS-485/422 MEMOBUS/Modbus terminals, per user manual TOEP YAIQPM 03B.
Also known as: CIMR-PW (iQpump Micro), iQpump Micro AC Drive, iQpump Micro Compact Intelligent Pump Controller - Variable frequency drive
Yaskawa iQpump1000 intelligent pump drive (MEMOBUS/Modbus RTU)
Yaskawa iQpump1000 drives (CIMR-PW) using the built-in RS-485/422 MEMOBUS/Modbus terminals, per user manual TOEPYAIP1W01G.
Also known as: CIMR-PW, CIMR-PWA, iQpump1000 AC Drive - Variable frequency drive
Yaskawa iQpump605 intelligent pump controller (MEMOBUS/Modbus RTU)
Yaskawa iQpump605 drives using the built-in RS-485 port (MEMOBUS/Modbus RTU), per user manual SIEPYAIWM6502D.
Also known as: WM65W, iQpump605 drive, iQpump605 Intelligent Pump Controller - Variable frequency drive (HVAC bypass package)
Yaskawa P1000 Bypass for industrial fans and pumps (MEMOBUS/Modbus RTU)
P1000 Bypass bypass controller RS-485 port with Z3-01 = 0 (Modbus); Technical Manual SIEP YAIP1B 01D, appendix D.
Also known as: P1000 Bypass, P1B - Variable frequency drive
Yaskawa P1000 industrial fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa P1000 drives using the built-in RS-485/422 MEMOBUS/Modbus port (terminals R+, R-, S+, S-), per technical manual SIEP YAIP1U 01C.
Also known as: CIMR-PU, P1000 Industrial Fan and Pump Drive - Variable frequency drive (fan / pump)
Yaskawa P7 fan/pump drive (CIMR-P7U, legacy) - Modbus RTU
Yaskawa P7 (CIMR-P7U) fan and pump drives using the built-in RS-422/485 terminals R+/R-/S+/S-, per user manual TM.P7.01 Appendix D.
Also known as: CIMR-P7U, P7U, P7 Drive - Variable frequency drive (fan / pump bypass package)
Yaskawa P7B drive/bypass (legacy) - Modbus RTU
Yaskawa P7B drive/bypass packages (P7 drive CIMR-P7U inside a bypass enclosure, option V native Modbus) using the drive's RS-422/485 terminals, per technical manual TM.P7B.01 Appendix D.
Also known as: P7B, P7 Bypass - Variable frequency drive
Yaskawa U1000 Industrial MATRIX drive (MEMOBUS/Modbus RTU)
Yaskawa U1000 matrix drives using the built-in RS-422/485 MEMOBUS/Modbus port (terminals R+, R-, S+, S-), per technical manual SIEP C710636 04E.
Also known as: CIMR-UU, U1000 Industrial MATRIX Drive - Variable frequency drive
Yaskawa V1000 AC drive (MEMOBUS/Modbus RTU)
Yaskawa V1000 drives (CIMR-VU; 200 V single/three-phase and 400 V three-phase, 0.1-18.5 kW) using the built-in RS-422/485 MEMOBUS/Modbus terminals, per Technical Manual SIEP C710606 18F.
Also known as: CIMR-VU, V1000 Compact Vector Control Drive - Variable frequency drive
Yaskawa V7 / V74X compact drive (legacy) - Modbus RTU
Yaskawa V7 (CIMR-V7AM) and V74X (CIMR-V7CU) compact drives with built-in Modbus RTU (keypad RJ-45 or R+/R-/S+/S- terminals), per TM.V7.11 Rev 07-01.
Also known as: CIMR-V7AM, CIMR-V7CU, V74X - Variable frequency drive (HVAC bypass package)
Yaskawa Z1000 Bypass for HVAC fans and pumps (MEMOBUS/Modbus RTU)
Z1000 Bypass bypass controller RS-485 port with Z3-01 = 0 (Modbus); Technical Manual SIEP YAIZ1B 01F, appendix D.
Also known as: Z1000 Bypass, Z1B1 - Variable frequency drive (HVAC fan / pump)
Yaskawa Z1000 HVAC fan/pump drive (MEMOBUS/Modbus RTU)
Yaskawa Z1000 HVAC drives (CIMR-ZU) using the built-in RS-485 terminals with H5-08 = 0, per Programming Manual SIEP YAIZ1U 03C (the copy covers the 600 V class models 5A0007-5A0242).
Also known as: CIMR-ZU, Z1000 AC Drive for HVAC Fan and Pump - Variable frequency drive
Yaskawa Z1000U HVAC matrix drive (MEMOBUS/Modbus RTU)
Yaskawa Z1000U HVAC matrix drives using the built-in serial terminals with H5-08 = 0 (MEMOBUS/Modbus), per programming manual SIEP C710636 10D.
Also known as: Z1000U HVAC MATRIX Drive, Z1000U Matrix
Other variable frequency drives register maps
- Variable frequency drive
ABB ACQ580 water and wastewater drive (embedded Modbus RTU)
ACQ580 drives running the ACQ580 pump control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000035867 Rev H.
Also known as: ACQ580-01, ACQ580-04, ACQ580-07, ACQ580-31, ACQ580-34, ACQ580 pump control program - Variable frequency drive
ABB ACS580 general purpose drive (embedded Modbus RTU)
ACS580 drives running the ACS580 standard control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default).
Also known as: ACS580-01, ACS580-04, ACS580-07, ACS580 standard control program - Variable frequency drive
AutomationDirect DURApulse GS3 AC drive
All GS3 drives; status addresses and P9.xx serial-communication parameters from chapter 5 of the user manual.
Also known as: DURApulse GS3, GS3-21P0, GS3-22P0, GS3-23P0, GS3-25P0, GS3-27P5, GS3-2010, GS3-2015, GS3-2020, GS3-2025 - Variable frequency drive
Danfoss VLT AutomationDrive FC 301/302 (Modbus RTU)
VLT AutomationDrive FC 301 and FC 302 (0.25-75 kW design guide; same scheme across sizes) using the built-in RS-485 (FC) port with 8-30 Protocol = Modbus RTU and the FC control profile; parameter data checked against the software 9.5x / 48.96 programming guide.
Also known as: VLT AutomationDrive, FC 301, FC301, FC302, FC-302, FC-301, FC 300 - Variable frequency drive
Danfoss VACON VACON 100 family (built-in Modbus RTU / Modbus TCP)
VACON 100 INDUSTRIAL, FLOW, HVAC and 100 X drives using the built-in RS-485 Modbus RTU or Ethernet Modbus TCP/UDP (manual DPD00156D); application IDs per the VACON 100 INDUSTRIAL application guide DPD00927L (FW0072V037).
Also known as: VACON 100 INDUSTRIAL, VACON 100 FLOW, VACON 100 HVAC, VACON 100 X, VACON0100 - Variable frequency drive (HVAC / pump)
Fuji Electric FRENIC-HVAC / FRENIC-AQUA inverters (RS-485 Modbus RTU)
Fuji Electric FRENIC-HVAC (AR) and FRENIC-AQUA (AQ) inverters on the RS-485 port in Modbus RTU mode (y10 = 0); RS-485 Communication User's Manual 24A7-E-0021b.
Also known as: FRENIC-HVAC, FRENIC-AQUA, FRN-AR, FRN-AQ
All variable frequency drives Modbus register maps →
Source: YASKAWA AC Drive J1000 Compact V/f Control Drive Technical Manual · SIEP C710606 31D. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.