Variable frequency drive · Modbus register map

AutomationDirect GS1 series AC drive Modbus register map

Updated 17 November 2026

Short answer

The GS1 is an AutomationDirect AC drive with a built-in RS-485 port running Modbus ASCII or RTU. Drive parameters P0.00-P9.xx map to holding registers (parameter group x 256 + number), and read-only status registers at 2100h report fault code, run state, frequencies, voltages and load. This map covers the status block and the P9 serial control parameters used to run the drive over Modbus.

This page lists 22 Modbus registers for the AutomationDirect GS1 series AC drive — 11 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from AutomationDirect’s own free documentation (linked below) and checked against it.

Manufacturer
AutomationDirect
Model
GS1 series AC drive
Equipment type
Variable frequency drive
Registers
22 (11 writable)
Transport
Modbus RTU, Modbus ASCII
Default unit ID
1
Default serial
9600 baud
Documented addressing
hexadecimal, 0-based
32-bit word order
CDAB low word first (word-swapped)
Also known as
GS1-10P2, GS1-10P5, GS1-20P2, GS1-20P5, GS1-21P0, GS1-22P0
Source document
GS1 Series AC Drives User Manual - Chapter 5: Communications · GS1-M 3rd Ed., Rev.B (chapter 5)
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: AutomationDirect GS1 series AC drive

Integration in brief

Set P9.02 to an RTU mode, P3.00 to serial operation and P4.00 = 5 for serial frequency source, then write speed (P9.26, x10) and run (P9.27). Monitor Status Monitor 1/2 and output frequency at 2100h-2103h.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 2330P9.26 Serial Comm Speed ReferenceUINT16Speed referenceRead/write
HR 2331P9.27 Serial Comm RUN CommandUINT16Run/stopRead/write
HR 2332P9.28 Serial Comm Direction CommandUINT16DirectionRead/write
HR 8448Status Monitor 1UINT16Fault codeRead
HR 8449Status Monitor 2BITMAP16Run state bitsRead
HR 8451Output Frequency HUINT16Output frequencyRead

Enable Modbus control & writes

Set P3.00 (source of operation) to 3 or 4 and P4.00 (source of frequency) to 5 for serial control, as referenced in Status Monitor 2; set P9.00-P9.02 for address, baud and protocol from the keypad.

Communication loss & watchdog

P9.04 enables communication time-out detection, P9.05 sets the time (0.1-60.0 s) and P9.03 selects the reaction (keep running, ramp stop, coast stop).

Byte order & addressing

Network setup

Watch out for

AutomationDirect GS1 series AC drive Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

22 of 22 shown
AutomationDirect GS1 series AC drive Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR2304doc 0900h (42305)P9.00 Communication AddressDrive address 1-254.UINT16Read/write
HR2305doc 0901h (42306)P9.01 Transmission SpeedUINT16Read/write0 = 4800; 1 = 9600; 2 = 19200
HR2306doc 0902h (42307)P9.02 Communication ProtocolFactory default 0 is Modbus ASCII.UINT16Read/write0 = ASCII 7N2; 1 = ASCII 7E1; 2 = ASCII 7O1; 3 = RTU 8N2; 4 = RTU 8E1; 5 = RTU 8O1
HR2307doc 0903h (42308)P9.03 Transmission Fault TreatmentUINT16Read/write0 = Display fault, keep running; 1 = Display fault, ramp to stop; 2 = Display fault, coast to stop; 3 = No fault, keep running
HR2308doc 0904h (42309)P9.04 Time Out DetectionUINT16Read/write0 = Disable; 1 = Enable
HR2330doc 091Ah (42331)P9.26 Serial Comm Speed Reference0.0-400.0 Hz with implied decimal (600 = 60.0 Hz).UINT16× 0.1HzRead/write
HR2331doc 091Bh (42332)P9.27 Serial Comm RUN CommandUINT16Read/write0 = Stop; 1 = Run
HR2332doc 091Ch (42333)P9.28 Serial Comm Direction CommandUINT16Read/write0 = Forward; 1 = Reverse
HR2333doc 091Dh (42334)P9.29 Serial Comm External FaultUINT16Read/write0 = No fault; 1 = External fault
HR2334doc 091Eh (42335)P9.30 Serial Comm Fault ResetUINT16Read/write0 = No action; 1 = Fault reset
HR2335doc 091Fh (42336)P9.31 Serial Comm JOG CommandUINT16Read/write0 = Stop; 1 = Jog
HR8448doc 2100h (48449)Status Monitor 1Present fault code.UINT16Read0 = No fault; 1 = Over-current (oc); 2 = Over-voltage (ov); 3 = Overheat (oH); 4 = Overload (oL); 5 = Overload 1 (oL1); 6 = Overload 2 (oL2); 7 = External fault (EF); 8 = CPU failure 1 (cF1); 9 = CPU failure 2 (cF2); 10 = CPU failure 3 (cF3); 11 = Hardware protection failure (HPF); 12 = Over-current during accel (ocA); 13 = Over-current during decel (ocd); 14 = Over-current at steady state (ocn); 16 = Low voltage (Lv); 18 = External base-block (bb); 19 = Auto adjust accel/decel failure (cFA); 20 = Software protection code (codE)
HR8449doc 2101h (48450)Status Monitor 2Bits 0-1 run state (0 stop..3 run); bits 3-4 direction (0 FWD..3 REV).BITMAP16Readbit 2 = JOG active; bit 5 = Frequency source = serial comm (P4.00 = 5); bit 6 = Frequency source = AI terminal; bit 7 = Operation source = serial comm (P3.00 = 3 or 4); bit 8 = Parameters locked (P9.07 = 1)
HR8450doc 2102h (48451)Frequency Command FFrequency setpoint (XXX.X).UINT16× 0.1HzRead
HR8451doc 2103h (48452)Output Frequency HOutput frequency (XXX.X).UINT16× 0.1HzRead
HR8452doc 2104h (48453)Output Current AOutput current (XXX.X).UINT16× 0.1ARead
HR8453doc 2105h (48454)DC Bus Voltage d(XXX.X)UINT16× 0.1VRead
HR8454doc 2106h (48455)Output Voltage URMS line-to-line output voltage (XXX.X).UINT16× 0.1VRead
HR8455doc 2107h (48456)Motor RPMEstimated motor speed.UINT16rpmRead
HR8456doc 2108h (48457)Scale FrequencyOutput frequency x P8.01; low word at 2108h, high word at 2109h.UINT32CDABRead
HR8459doc 210Bh (48460)% LoadOutput current / drive rated current x 100.UINT16%Read
HR8464doc 2110h (48465)Firmware VersionUINT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the AutomationDirect GS1 series AC drive

What Modbus registers does the AutomationDirect GS1 series AC drive have?

This map lists 22 registers: 22 holding registers. 11 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the AutomationDirect GS1 series AC drive Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual lists each register in hex and as a Modicon number: hex 0000h = 40001, 2100h = 48449. The hex value is the wire address. CLICK PLCs need a six-digit form (402331 instead of 42331).

What byte order does the AutomationDirect GS1 series AC drive use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the AutomationDirect GS1 series AC drive?

Start with HR 2330 P9.26 Serial Comm Speed Reference (Speed reference); HR 2331 P9.27 Serial Comm RUN Command (Run/stop); HR 2332 P9.28 Serial Comm Direction Command (Direction); HR 8448 Status Monitor 1 (Fault code); HR 8449 Status Monitor 2 (Run state bits); HR 8451 Output Frequency H (Output frequency).

How do I enable Modbus control of the AutomationDirect GS1 series AC drive?

Set P3.00 (source of operation) to 3 or 4 and P4.00 (source of frequency) to 5 for serial control, as referenced in Status Monitor 2; set P9.00-P9.02 for address, baud and protocol from the keypad.

What happens when the AutomationDirect GS1 series AC drive loses Modbus communication?

P9.04 enables communication time-out detection, P9.05 sets the time (0.1-60.0 s) and P9.03 selects the reaction (keep running, ramp stop, coast stop).

Where is the official AutomationDirect GS1 series AC drive Modbus documentation?

The source is GS1 Series AC Drives User Manual - Chapter 5: Communications (GS1-M 3rd Ed., Rev.B (chapter 5)), published free by AutomationDirect at https://cdn.automationdirect.com/static/manuals/gs1m/ch5.pdf.