Variable frequency drive · Modbus register map
Invertek Drives Optidrive E3 IP20 (built-in Modbus RTU) Modbus register map
Updated 17 November 2026
Invertek's compact general purpose variable frequency drive with Modbus RTU on the front RJ45 port. Registers 1-4 take the control word, frequency setpoint, PI setpoint and ramp time; registers 7-24 and 2001-2016 report status, output values, I/O and the trip code. Parameters P-04 to P-60 sit at register 128 + parameter number. This map covers the control and monitoring block plus the command-source parameter.
This page lists 29 Modbus registers for the Invertek Drives Optidrive E3 IP20 (built-in Modbus RTU) — 5 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Invertek Drives’s own free documentation (linked below) and checked against it.
- Manufacturer
- Invertek Drives
- Model
- Optidrive E3 IP20 (built-in Modbus RTU)
- Equipment type
- Variable frequency drive
- Registers
- 29 (5 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 115200 baud, 8N1
- Documented addressing
- 1-based (subtract 1 for the wire address)
- Also known as
- ODE-3, Optidrive E3, ODE-3 IP20, Optidrive ODE-3
- Source document
- Optidrive ODE-3 User Guide · 82-E3I20-IN V1.05
Integration notes: Invertek Drives Optidrive E3 IP20 (built-in Modbus RTU)
Set P-12 = 3 (or 4 to write ramp times in register 4), keep digital input 1 closed as the hardware enable, then write register 1 = 1 to run and register 2 with the frequency x10. Poll 2001 for status, 2002-2004 for speed, current and power, and 2016 for the trip code.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Control word | BITMAP16 | Control word: run, reset, coast stop | Read/write |
| HR 1 | Frequency setpoint | UINT16 | Frequency setpoint, 0.1 Hz | Read/write |
| HR 2000 | Status word 2 | BITMAP16 | Status word 2 | Read |
| HR 2001 | Motor output speed | INT16 | Motor output speed, 0.1 Hz | Read |
| HR 2002 | Motor output current | UINT16 | Motor output current, 0.1 A | Read |
| HR 2003 | Motor output power | UINT16 | Motor output power, 0.1 kW | Read |
| HR 2015 | Trip code | UINT16 | Trip code | Read |
| HR 139 | P-12 Primary command source | UINT16 | P-12 command source | Read/write |
Enable Modbus control & writes
Set P-12 = 3 (Modbus with internal ramps) or 4 (ramps from register 4). Set the drive address, baud rate and watchdog in P-36 indexes 1-3 (factory address 1, 115.2 kbps). An enable signal on digital input 1 is still required in Modbus mode. P-14 must hold the access code (P-37, factory 101) to reach parameters above P-14.
Communication loss & watchdog
P-36 index 3 sets the communication-loss time: 0 disables it, or 30, 100, 1000 or 3000 ms (factory 3000 ms with trip). A 't' suffix trips the drive (fault 50, Modbus comms loss); the other suffix coast-stops without tripping. P-63 decides whether any valid telegram (0, standard) or only telegrams for this node (1, advanced) reset the timer.
Byte order & addressing
- Register numbers are 1-based: subtract 1 for the wire address.
- Only 8-N-1 framing is listed; the factory baud rate is 115200.
- Parameter registers are 128 + parameter number, not the parameter number itself.
Network setup
- Wire RS485- to RJ45 pin 7, RS485+ to pin 8 and 0 V common to pin 3; pins 4/5 are the PC/keypad port.
- Use twisted pair for RS485+/-, connect 0 V common across all devices, and terminate the shield at the controller only.
- The RJ45 port is not Ethernet: do not plug it into a network switch.
Watch out for
- With the factory P-63 = 0, telegrams for other nodes also keep the watchdog alive.
- After an over current or overload trip (codes 3, 4, 15) a reset is refused until the built-in delay has elapsed.
Invertek Drives Optidrive E3 IP20 (built-in Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 1 | Control word | Run enable, decel ramp select, fault reset, coast stop, relay/DO control. | BITMAP16 | Read/write | bit 0 = 1 = run enable, 0 = stop; bit 1 = 0 = decel ramp 1 (P-04), 1 = decel ramp 2 (P-24); bit 2 = 1 = fault reset; bit 3 = 1 = coast stop request; bit 8 = Relay control: 0 = open, 1 = close; bit 9 = DO control: 1 = off, 0 = on | |||
| HR | 1doc 2 | Frequency setpoint | 0-5000 = 0.0-500.0 Hz. | UINT16 | × 0.1 | Hz | Read/write | ||
| HR | 2doc 3 | PI setpoint / analog output control | 0-4096 = 0-100.0 %. | UINT16 | Read/write | ||||
| HR | 3doc 4 | Ramp time | 0-60000; used when P-12 = 4. | UINT16 | × 0.01 | s | Read/write | ||
| HR | 6doc 7 | Output motor frequency | 0-20000. | UINT16 | × 0.1 | Hz | Read | ||
| HR | 7doc 8 | Output motor current | UINT16 | × 0.1 | A | Read | |||
| HR | 10doc 11 | Digital input status | Lowest bit = input 1. | BITMAP16 | Read | bit 0 = DI1; bit 1 = DI2; bit 2 = DI3; bit 3 = DI4 | |||
| HR | 19doc 20 | Analog input 1 value (P00-01) | Percent of full scale. | UINT16 | × 0.1 | % | Read | ||
| HR | 20doc 21 | Analog input 2 value (P00-02) | Percent of full scale. | UINT16 | × 0.1 | % | Read | ||
| HR | 21doc 22 | Speed reference value (P00-03) | Active setpoint frequency. | UINT16 | × 0.1 | Hz | Read | ||
| HR | 22doc 23 | DC bus voltage (P00-08) | UINT16 | V | Read | ||||
| HR | 23doc 24 | Drive temperature (P00-09) | Heatsink temperature. | UINT16 | °C | Read | |||
| HR | 139doc 140 (P-12) | P-12 Primary command source | Set 3 or 4 for Modbus control; register = 128 + 12. | UINT16 | Read/write | 0 = Terminal control; 1 = Keypad, forward only; 2 = Keypad, forward/reverse; 3 = Modbus, internal ramps; 4 = Modbus, ramps written over Modbus (register 4); 5 = PI control; 6 = PI control + AI1 summation; 7 = CAN, internal ramps; 8 = CAN, ramps over CAN; 9 = Slave mode | |||
| HR | 2000doc 2001 | Status word 2 | BITMAP16 | Read | bit 0 = Ready (no trip, no mains loss, hardware enabled); bit 1 = Running; bit 2 = Tripped; bit 3 = Standby; bit 4 = Fire mode active; bit 6 = At speed (setpoint reached); bit 7 = Below minimum speed (P-02); bit 8 = Overload (current > P-08); bit 9 = Mains loss; bit 10 = Heatsink > 85 °C; bit 11 = Control board > 80 °C; bit 12 = Switching frequency foldback active; bit 13 = Reverse rotation (negative speed); bit 15 = Toggles on every read | ||||
| HR | 2001doc 2002 | Motor output speed | Hz with one decimal; negative in reverse (see 2001 bit 13). | INT16 | × 0.1 | Hz | Read | ||
| HR | 2002doc 2003 | Motor output current | UINT16 | × 0.1 | A | Read | |||
| HR | 2003doc 2004 | Motor output power | UINT16 | × 0.1 | kW | Read | |||
| HR | 2004doc 2005 | IO status word | BITMAP16 | Read | bit 0 = DI1 closed; bit 1 = DI2 closed; bit 2 = DI3 (AI-2) closed; bit 3 = DI4 (AI-1) closed; bit 6 = IP66 FWD switch closed; bit 7 = IP66 REV switch closed; bit 8 = Digital output active / analog output > 0; bit 9 = Relay closed; bit 12 = AI1 4-20 mA signal lost; bit 13 = AI2 4-20 mA signal lost; bit 15 = IP66 pot input > 50 % | ||||
| HR | 2005doc 2006 | Motor output torque | 0.0 to +/-200.0 %. | INT16 | × 0.1 | % | Read | ||
| HR | 2006doc 2007 | DC bus voltage (P00-08) | UINT16 | V | Read | ||||
| HR | 2007doc 2008 | Heatsink temperature (P00-09) | UINT16 | °C | Read | ||||
| HR | 2008doc 2009 | Analog input 1 (P00-01) | Raw 0-4096 (12 bit). | UINT16 | Read | ||||
| HR | 2009doc 2010 | Analog input 2 (P00-02) | Raw 0-4096 (12 bit). | UINT16 | Read | ||||
| HR | 2010doc 2011 | Analog output | 0.0-100.0 %. | UINT16 | × 0.1 | % | Read | ||
| HR | 2011doc 2012 | PI output (P00-05) | 0.0-100.0 %. | UINT16 | × 0.1 | % | Read | ||
| HR | 2012doc 2013 | Internal temperature (P00-20) | UINT16 | °C | Read | ||||
| HR | 2013doc 2014 | Motor output voltage (P00-07) | 0-500 V. | UINT16 | V | Read | |||
| HR | 2014doc 2015 | IP66 pot input value | Raw 0-4096 (12 bit). | UINT16 | Read | ||||
| HR | 2015doc 2016 | Trip code | Fault code per the guide's fault table; 0 = no fault. | UINT16 | Read | 0 = No fault; 1 = Brake channel over current; 2 = Brake resistor overload; 3 = Output over current; 4 = Motor thermal overload (I2t); 6 = DC bus over voltage; 7 = DC bus under voltage; 8 = Heatsink over temperature; 9 = Under temperature; 10 = Factory default parameters loaded; 11 = External trip; 12 = Optibus comms loss; 13 = DC bus ripple too high; 14 = Input phase loss; 15 = Output over current (short circuit); 16 = Faulty heatsink thermistor; 17 = Internal memory fault (IO); 18 = 4-20 mA signal lost; 19 = Internal memory fault (DSP); 21 = Motor PTC thermistor trip; 22 = Cooling fan fault (IP66 only); 23 = Drive internal temperature too high; 26 = Output fault; 41 = Autotune fault; 50 = Modbus comms loss; 51 = CAN comms loss |
Notes on this map
- Left out: register 6 (drive status / error code) because the guide contradicts itself on which byte holds the error code (the table says low byte, the bit table puts status in bits 0-7 and the trip code in the high byte). Use register 2001 (status) and 2016 (trip code) instead.
- Parameter registers P-04 to P-60 (128 + parameter number) are left out apart from P-12: the guide says some use internal scaling without stating it. P-36 (address, baud, watchdog) has three sub-indexes and no stated register layout.
- The guide does not state signedness for most registers. Values with a 0-n range are typed UINT16; torque (+/-200 %) and motor output speed (status bit 13 = negative speed) are typed INT16.
- Function code 16 (write multiple) is accepted for registers 1-4 only; 03 and 06 work on all registers.
- The E3 IP66 Indoor guide (82-E3MAN-IN V2.00) lists only registers 1-24 with slightly different register-6 wording; this map follows the IP20 guide.
- Register 3 scaling is given only as 0-4096 = 0-100.0 %, so it is kept raw.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Invertek Drives Optidrive E3 IP20 (built-in Modbus RTU)
What Modbus registers does the Invertek Drives Optidrive E3 IP20 (built-in Modbus RTU) have?
This map lists 29 registers: 29 holding registers. 5 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Invertek Drives Optidrive E3 IP20 (built-in Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide numbers registers from 1 and tells zero-based masters to subtract 1, so register 1 (control word) is wire address 0 and register 2001 is address 2000. Parameter registers are 128 + parameter number (P-12 = register 140 = address 139).
What are the minimum Modbus registers to integrate the Invertek Drives Optidrive E3 IP20 (built-in Modbus RTU)?
Start with HR 0 Control word (Control word: run, reset, coast stop); HR 1 Frequency setpoint (Frequency setpoint, 0.1 Hz); HR 2000 Status word 2 (Status word 2); HR 2001 Motor output speed (Motor output speed, 0.1 Hz); HR 2002 Motor output current (Motor output current, 0.1 A); HR 2003 Motor output power (Motor output power, 0.1 kW); HR 2015 Trip code (Trip code); HR 139 P-12 Primary command source (P-12 command source).
How do I enable Modbus control of the Invertek Drives Optidrive E3 IP20 (built-in Modbus RTU)?
Set P-12 = 3 (Modbus with internal ramps) or 4 (ramps from register 4). Set the drive address, baud rate and watchdog in P-36 indexes 1-3 (factory address 1, 115.2 kbps). An enable signal on digital input 1 is still required in Modbus mode. P-14 must hold the access code (P-37, factory 101) to reach parameters above P-14.
What happens when the Invertek Drives Optidrive E3 IP20 (built-in Modbus RTU) loses Modbus communication?
P-36 index 3 sets the communication-loss time: 0 disables it, or 30, 100, 1000 or 3000 ms (factory 3000 ms with trip). A 't' suffix trips the drive (fault 50, Modbus comms loss); the other suffix coast-stops without tripping. P-63 decides whether any valid telegram (0, standard) or only telegrams for this node (1, advanced) reset the timer.
Where is the official Invertek Drives Optidrive E3 IP20 (built-in Modbus RTU) Modbus documentation?
The source is Optidrive ODE-3 User Guide (82-E3I20-IN V1.05), published free by Invertek Drives at https://admin.invertekdrives.com/assets/A09D2FA5-3BCD-4511-BA4D-A4878F2634AE/82-E3I20-IN_V1.05%20E3%20IP20%20User%20Guide%20V1.04%20ENGLISH.pdf.
More Invertek Drives Modbus register maps
- Variable frequency drive
Invertek Drives Optidrive Coolvert compressor drive (built-in Modbus RTU)
Invertek Optidrive Coolvert HVAC compressor drives on the terminal or RJ45 Modbus RTU port, per user guide version 2.01.
Also known as: Optidrive CoolVert, Coolvert - Variable frequency drive
Invertek Drives Optidrive Eco (built-in Modbus RTU)
Invertek Optidrive Eco drives using the built-in RJ45 RS-485 Modbus RTU port, per user guide 82-HEMAN-IN V3.13.
Also known as: ODV-3, Optidrive Eco HVAC, Optidrive Eco IP20, Optidrive Eco IP55, Optidrive Eco IP66 - Variable frequency drive
Invertek Drives Optidrive Elevator Core (built-in Modbus RTU)
Invertek Elevator Core lift drives on the RJ45 Modbus RTU port, per the online Elevator Core user guide (support.invertekdrives.com).
Also known as: Elevator Core, Optidrive Elevator Core - Variable frequency drive
Invertek Drives Optidrive P2 (built-in Modbus RTU)
Invertek Optidrive P2 drives (0.75-250 kW) using the built-in RJ45 RS-485 Modbus RTU port, per user guide 82-P2MAN-IN V3.10.
Also known as: ODP-2, Optidrive P2 IP20, Optidrive P2 IP55, Optidrive P2 IP66
Other variable frequency drives register maps
- Variable frequency drive
INVT Goodrive270 (GD270) fan and pump VFD
INVT Goodrive270 fan and pump drives using the built-in RS-485 Modbus RTU port, per the GD270 manual V1.4 (chapter 9).
Also known as: GD270, Goodrive270, GD270 fan and pump drive, GD270 HVAC drive - Variable frequency drive
Lenze MC Series drives MC1000 / MC3000 (Modbus RTU)
Lenze AC Tech MC1000 and MC3000 Series drives, software 213-083 rev 13 (parameter configurations 188-190); reference guide RG-MCMOD.
Also known as: MC1000, MC3000, MC Series, Lenze AC Tech MC, RG-MCMOD - Variable frequency drive
Mitsubishi Electric FR-A800 inverter (RS-485 terminals, Modbus RTU)
FR-A800 series inverters (FR-A820/A840/A842/A846, incl. -GF) using the built-in RS-485 terminals with Pr.549 = 1 (MODBUS RTU); Instruction Manual (Detailed) revision P.
Also known as: FR-A820, FR-A840, FR-A842, FR-A846, FR-A800-GF, FR-A800 series - Variable frequency drive
Schneider Electric Altivar Machine ATV340 (embedded Modbus serial / Modbus TCP)
ATV340 drives on the built-in Modbus serial port; Ethernet versions (ATV340...N4E) expose the same addresses on embedded Modbus TCP. Per Communication Parameters file NVE61728 V4.6.
Also known as: ATV340, Altivar 340, Altivar Machine ATV340, ATV340U, ATV340D, ATV340...N4E - Variable frequency drive
Siemens SINAMICS G120 / G120C (Modbus RTU)
SINAMICS G120 with an RS485 Control Unit (CU230P-2 HVAC/BT, CU240B-2, CU240E-2 / -2 F, CU250S-2), G120C USS/MB and G110M CU240M USS, firmware V4.7, per Fieldbuses function manual A5E34229197B AA. Not SINAMICS G120X, which has its own documentation.
Also known as: G120C USS/MB, CU230P-2 HVAC, CU230P-2 BT, CU240B-2, CU240E-2, CU240E-2 F, CU250S-2, G110M CU240M USS, G120P - Variable frequency drive (HVAC fan / pump)
TECO-Westinghouse F510 HVAC fan/pump inverter (Modbus RTU/ASCII)
TECO-Westinghouse F510 HVAC inverters using the built-in RS-485 port (CN6) in Modbus mode, per communication addendum DOCUMENT-TECO-F510-AC001 Ver01 (2015-03).
Also known as: TECO F510, F510 HVAC drive
All variable frequency drives Modbus register maps →
Source: Optidrive ODE-3 User Guide · 82-E3I20-IN V1.05. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.