Invertek Drives Optidrive E3 IP20 (built-in Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

Invertek's compact general purpose variable frequency drive with Modbus RTU on the front RJ45 port. Registers 1-4 take the control word, frequency setpoint, PI setpoint and ramp time; registers 7-24 and 2001-2016 report status, output values, I/O and the trip code. Parameters P-04 to P-60 sit at register 128 + parameter number. This map covers the control and monitoring block plus the command-source parameter.

This page lists 29 Modbus registers for the Invertek Drives Optidrive E3 IP20 (built-in Modbus RTU) — 5 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Invertek Drives’s own free documentation (linked below) and checked against it.

Manufacturer
Invertek Drives
Model
Optidrive E3 IP20 (built-in Modbus RTU)
Equipment type
Variable frequency drive
Registers
29 (5 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
115200 baud, 8N1
Documented addressing
1-based (subtract 1 for the wire address)
Also known as
ODE-3, Optidrive E3, ODE-3 IP20, Optidrive ODE-3
Source document
Optidrive ODE-3 User Guide · 82-E3I20-IN V1.05
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Invertek Drives Optidrive E3 IP20 (built-in Modbus RTU)

Integration in brief

Set P-12 = 3 (or 4 to write ramp times in register 4), keep digital input 1 closed as the hardware enable, then write register 1 = 1 to run and register 2 with the frequency x10. Poll 2001 for status, 2002-2004 for speed, current and power, and 2016 for the trip code.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0Control wordBITMAP16Control word: run, reset, coast stopRead/write
HR 1Frequency setpointUINT16Frequency setpoint, 0.1 HzRead/write
HR 2000Status word 2BITMAP16Status word 2Read
HR 2001Motor output speedINT16Motor output speed, 0.1 HzRead
HR 2002Motor output currentUINT16Motor output current, 0.1 ARead
HR 2003Motor output powerUINT16Motor output power, 0.1 kWRead
HR 2015Trip codeUINT16Trip codeRead
HR 139P-12 Primary command sourceUINT16P-12 command sourceRead/write

Enable Modbus control & writes

Set P-12 = 3 (Modbus with internal ramps) or 4 (ramps from register 4). Set the drive address, baud rate and watchdog in P-36 indexes 1-3 (factory address 1, 115.2 kbps). An enable signal on digital input 1 is still required in Modbus mode. P-14 must hold the access code (P-37, factory 101) to reach parameters above P-14.

Communication loss & watchdog

P-36 index 3 sets the communication-loss time: 0 disables it, or 30, 100, 1000 or 3000 ms (factory 3000 ms with trip). A 't' suffix trips the drive (fault 50, Modbus comms loss); the other suffix coast-stops without tripping. P-63 decides whether any valid telegram (0, standard) or only telegrams for this node (1, advanced) reset the timer.

Byte order & addressing

Network setup

Watch out for

Invertek Drives Optidrive E3 IP20 (built-in Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

29 of 29 shown
Invertek Drives Optidrive E3 IP20 (built-in Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 1Control wordRun enable, decel ramp select, fault reset, coast stop, relay/DO control.BITMAP16Read/writebit 0 = 1 = run enable, 0 = stop; bit 1 = 0 = decel ramp 1 (P-04), 1 = decel ramp 2 (P-24); bit 2 = 1 = fault reset; bit 3 = 1 = coast stop request; bit 8 = Relay control: 0 = open, 1 = close; bit 9 = DO control: 1 = off, 0 = on
HR1doc 2Frequency setpoint0-5000 = 0.0-500.0 Hz.UINT16× 0.1HzRead/write
HR2doc 3PI setpoint / analog output control0-4096 = 0-100.0 %.UINT16Read/write
HR3doc 4Ramp time0-60000; used when P-12 = 4.UINT16× 0.01sRead/write
HR6doc 7Output motor frequency0-20000.UINT16× 0.1HzRead
HR7doc 8Output motor currentUINT16× 0.1ARead
HR10doc 11Digital input statusLowest bit = input 1.BITMAP16Readbit 0 = DI1; bit 1 = DI2; bit 2 = DI3; bit 3 = DI4
HR19doc 20Analog input 1 value (P00-01)Percent of full scale.UINT16× 0.1%Read
HR20doc 21Analog input 2 value (P00-02)Percent of full scale.UINT16× 0.1%Read
HR21doc 22Speed reference value (P00-03)Active setpoint frequency.UINT16× 0.1HzRead
HR22doc 23DC bus voltage (P00-08)UINT16VRead
HR23doc 24Drive temperature (P00-09)Heatsink temperature.UINT16°CRead
HR139doc 140 (P-12)P-12 Primary command sourceSet 3 or 4 for Modbus control; register = 128 + 12.UINT16Read/write0 = Terminal control; 1 = Keypad, forward only; 2 = Keypad, forward/reverse; 3 = Modbus, internal ramps; 4 = Modbus, ramps written over Modbus (register 4); 5 = PI control; 6 = PI control + AI1 summation; 7 = CAN, internal ramps; 8 = CAN, ramps over CAN; 9 = Slave mode
HR2000doc 2001Status word 2BITMAP16Readbit 0 = Ready (no trip, no mains loss, hardware enabled); bit 1 = Running; bit 2 = Tripped; bit 3 = Standby; bit 4 = Fire mode active; bit 6 = At speed (setpoint reached); bit 7 = Below minimum speed (P-02); bit 8 = Overload (current > P-08); bit 9 = Mains loss; bit 10 = Heatsink > 85 °C; bit 11 = Control board > 80 °C; bit 12 = Switching frequency foldback active; bit 13 = Reverse rotation (negative speed); bit 15 = Toggles on every read
HR2001doc 2002Motor output speedHz with one decimal; negative in reverse (see 2001 bit 13).INT16× 0.1HzRead
HR2002doc 2003Motor output currentUINT16× 0.1ARead
HR2003doc 2004Motor output powerUINT16× 0.1kWRead
HR2004doc 2005IO status wordBITMAP16Readbit 0 = DI1 closed; bit 1 = DI2 closed; bit 2 = DI3 (AI-2) closed; bit 3 = DI4 (AI-1) closed; bit 6 = IP66 FWD switch closed; bit 7 = IP66 REV switch closed; bit 8 = Digital output active / analog output > 0; bit 9 = Relay closed; bit 12 = AI1 4-20 mA signal lost; bit 13 = AI2 4-20 mA signal lost; bit 15 = IP66 pot input > 50 %
HR2005doc 2006Motor output torque0.0 to +/-200.0 %.INT16× 0.1%Read
HR2006doc 2007DC bus voltage (P00-08)UINT16VRead
HR2007doc 2008Heatsink temperature (P00-09)UINT16°CRead
HR2008doc 2009Analog input 1 (P00-01)Raw 0-4096 (12 bit).UINT16Read
HR2009doc 2010Analog input 2 (P00-02)Raw 0-4096 (12 bit).UINT16Read
HR2010doc 2011Analog output0.0-100.0 %.UINT16× 0.1%Read
HR2011doc 2012PI output (P00-05)0.0-100.0 %.UINT16× 0.1%Read
HR2012doc 2013Internal temperature (P00-20)UINT16°CRead
HR2013doc 2014Motor output voltage (P00-07)0-500 V.UINT16VRead
HR2014doc 2015IP66 pot input valueRaw 0-4096 (12 bit).UINT16Read
HR2015doc 2016Trip codeFault code per the guide's fault table; 0 = no fault.UINT16Read0 = No fault; 1 = Brake channel over current; 2 = Brake resistor overload; 3 = Output over current; 4 = Motor thermal overload (I2t); 6 = DC bus over voltage; 7 = DC bus under voltage; 8 = Heatsink over temperature; 9 = Under temperature; 10 = Factory default parameters loaded; 11 = External trip; 12 = Optibus comms loss; 13 = DC bus ripple too high; 14 = Input phase loss; 15 = Output over current (short circuit); 16 = Faulty heatsink thermistor; 17 = Internal memory fault (IO); 18 = 4-20 mA signal lost; 19 = Internal memory fault (DSP); 21 = Motor PTC thermistor trip; 22 = Cooling fan fault (IP66 only); 23 = Drive internal temperature too high; 26 = Output fault; 41 = Autotune fault; 50 = Modbus comms loss; 51 = CAN comms loss

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Invertek Drives Optidrive E3 IP20 (built-in Modbus RTU)

What Modbus registers does the Invertek Drives Optidrive E3 IP20 (built-in Modbus RTU) have?

This map lists 29 registers: 29 holding registers. 5 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Invertek Drives Optidrive E3 IP20 (built-in Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide numbers registers from 1 and tells zero-based masters to subtract 1, so register 1 (control word) is wire address 0 and register 2001 is address 2000. Parameter registers are 128 + parameter number (P-12 = register 140 = address 139).

What are the minimum Modbus registers to integrate the Invertek Drives Optidrive E3 IP20 (built-in Modbus RTU)?

Start with HR 0 Control word (Control word: run, reset, coast stop); HR 1 Frequency setpoint (Frequency setpoint, 0.1 Hz); HR 2000 Status word 2 (Status word 2); HR 2001 Motor output speed (Motor output speed, 0.1 Hz); HR 2002 Motor output current (Motor output current, 0.1 A); HR 2003 Motor output power (Motor output power, 0.1 kW); HR 2015 Trip code (Trip code); HR 139 P-12 Primary command source (P-12 command source).

How do I enable Modbus control of the Invertek Drives Optidrive E3 IP20 (built-in Modbus RTU)?

Set P-12 = 3 (Modbus with internal ramps) or 4 (ramps from register 4). Set the drive address, baud rate and watchdog in P-36 indexes 1-3 (factory address 1, 115.2 kbps). An enable signal on digital input 1 is still required in Modbus mode. P-14 must hold the access code (P-37, factory 101) to reach parameters above P-14.

What happens when the Invertek Drives Optidrive E3 IP20 (built-in Modbus RTU) loses Modbus communication?

P-36 index 3 sets the communication-loss time: 0 disables it, or 30, 100, 1000 or 3000 ms (factory 3000 ms with trip). A 't' suffix trips the drive (fault 50, Modbus comms loss); the other suffix coast-stops without tripping. P-63 decides whether any valid telegram (0, standard) or only telegrams for this node (1, advanced) reset the timer.

Where is the official Invertek Drives Optidrive E3 IP20 (built-in Modbus RTU) Modbus documentation?

The source is Optidrive ODE-3 User Guide (82-E3I20-IN V1.05), published free by Invertek Drives at https://admin.invertekdrives.com/assets/A09D2FA5-3BCD-4511-BA4D-A4878F2634AE/82-E3I20-IN_V1.05%20E3%20IP20%20User%20Guide%20V1.04%20ENGLISH.pdf.

More Invertek Drives Modbus register maps

Other variable frequency drives register maps

All variable frequency drives Modbus register maps →

Source: Optidrive ODE-3 User Guide · 82-E3I20-IN V1.05. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.