Mitsubishi Electric FR-A800 inverter (RS-485 terminals, Modbus RTU) Modbus register map
Updated 19 November 2026
Mitsubishi Electric's high-performance general-purpose inverter. Its RS-485 terminal block can speak Modbus RTU, exposing system variables (control word, operation mode, frequency command) at 40002-40015, a real-time monitor block from 40201, fault history at 40501, and parameters at 41000 + parameter number (Pr.1000 and up at 44000 + parameter number). This map covers control, status, the main monitors and the communication parameters.
This page lists 51 Modbus registers for the Mitsubishi Electric FR-A800 inverter (RS-485 terminals, Modbus RTU) — 21 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Mitsubishi Electric’s own free documentation (linked below) and checked against it.
- Manufacturer
- Mitsubishi Electric
- Model
- FR-A800 inverter (RS-485 terminals, Modbus RTU)
- Equipment type
- Variable frequency drive
- Registers
- 51 (21 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 9600 baud, 8E1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- FR-A820, FR-A840, FR-A842, FR-A846, FR-A800-GF, FR-A800 series
Integration notes: Mitsubishi Electric FR-A800 inverter (RS-485 terminals, Modbus RTU)
Set Pr.549 = 1, give the drive a station number in Pr.331 (the initial 0 means broadcast, so it never answers) and reset. Put the drive in NET mode by writing H0014 to 40010, write the frequency to 40014 (0.01 Hz) and the run bits to 40009, then poll 40009, 40201 and 40224.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 8 | Control input command / inverter status | BITMAP16 | Run/stop command and inverter status | Read/write |
| HR 9 | Operation mode / inverter setting | UINT16 | Operation mode (write H0014 for NET) | Read/write |
| HR 13 | Set frequency (RAM) | UINT16 | Frequency command (RAM) | Read/write |
| HR 200 | Output frequency | UINT16 | Output frequency | Read |
| HR 223 | Motor load factor | UINT16 | Motor load factor (% of rated current) | Read |
| HR 207 | Converter output voltage | UINT16 | DC bus voltage | Read |
| HR 500 | Fault record 1 | UINT16 | Latest fault code | Read/write |
Enable Modbus control & writes
Pr.549 = 1 selects Modbus RTU on the RS-485 terminals; set Pr.331 (1-247), Pr.332 speed and Pr.334 parity, then reset or power-cycle. Run and frequency commands are taken in NET operation mode (write H0014 to 40010, or use Pr.79/Pr.340 so the drive starts in NET mode). If a communication option is installed and Pr.550 = 9999, commands via the RS-485 terminals are ignored.
Communication loss & watchdog
Pr.539 sets the Modbus communication check interval (0.1-999.8 s, same behaviour as Pr.122); 9999 (initial) disables the check, 0 lets Modbus run but shuts the output off in NET mode.
Byte order & addressing
- Request address = register - 40001 (Pr.4 at 41004 is read at H03EB).
- Station 0 is broadcast: no reply, and some functions are disabled.
- Register 40009 means input command when written and inverter status when read.
Network setup
- Pr.331 initial value 0 is broadcast: set 1-247 first.
- Pr.332 initial 96 = 9600 bps; Pr.334 initial 2 = even parity, 1 stop bit; data length is fixed at 8 bits under Modbus.
- Modbus RTU cannot be used in PU operation mode.
Watch out for
- Current, power and energy monitors change resolution with drive size, so check the capacity before scaling them.
- Setting Pr.37/Pr.144 (or Pr.811) for rpm display also changes the frequency registers.
Mitsubishi Electric FR-A800 inverter (RS-485 terminals, Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1doc 40002 | Inverter reset | Write any value to reset the inverter. | UINT16 | Write | ||||
| HR | 2doc 40003 | Parameter clear | Write H965A to clear parameters. | UINT16 | Write | ||||
| HR | 3doc 40004 | All parameter clear | Write H99AA to clear all parameters. | UINT16 | Write | ||||
| HR | 5doc 40006 | Parameter clear (keep comm settings) | Write H5A96; communication parameters are not cleared. | UINT16 | Write | ||||
| HR | 6doc 40007 | All parameter clear (keep comm settings) | Write HAA99; communication parameters are not cleared. | UINT16 | Write | ||||
| HR | 8doc 40009 | Control input command / inverter status | Write = control input command, read = inverter status. | BITMAP16 | Read/write | bit 0 = Write: stop command / Read: RUN (inverter running); bit 1 = Write: forward rotation command / Read: forward rotation output; bit 2 = Write: reverse rotation command / Read: reverse rotation output; bit 3 = Write: RH (high speed) / Read: SU (up to frequency); bit 4 = Write: RM (middle speed) / Read: OL (overload warning); bit 5 = Write: RL (low speed) / Read: IPF (instantaneous power failure / undervoltage); bit 6 = Write: JOG / Read: FU (frequency detection); bit 7 = Write: RT (second function) / Read: ABC1 (fault); bit 8 = Write: AU (terminal 4 input selection) / Read: ABC2; bit 9 = Write: CS (automatic restart / flying start selection) / Read: safety monitor output; bit 10 = Write: MRS (output stop) / Read: 0; bit 11 = Write: STP (start self-holding) / Read: 0; bit 12 = Write: RES (reset) / Read: 0; bit 15 = Read: fault occurrence | |||
| HR | 9doc 40010 | Operation mode / inverter setting | Read returns the current mode; write H0010 EXT, H0011 PU, H0014 NET. | UINT16 | Read/write | 0 = Read: EXT; 1 = Read: PU; 2 = Read: EXT JOG; 3 = Read: PU JOG; 4 = Read: NET; 5 = Read: PU + EXT; 16 = Write: EXT (H0010); 17 = Write: PU (H0011); 20 = Write: NET (H0014) | |||
| HR | 13doc 40014 | Set frequency (RAM) | Frequency command, not stored in EEPROM. | UINT16 | × 0.01 | Hz | Read/write | ||
| HR | 14doc 40015 | Set frequency (EEPROM) | Frequency command, also stored in EEPROM. | UINT16 | × 0.01 | Hz | Write | ||
| HR | 200doc 40201 | Output frequency | UINT16 | × 0.01 | Hz | Read | |||
| HR | 202doc 40203 | Output voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 204doc 40205 | Set frequency | UINT16 | × 0.01 | Hz | Read | |||
| HR | 205doc 40206 | Operation speed | Motor speed per Pr.37/Pr.144. | UINT16 | r/min | Read | |||
| HR | 207doc 40208 | Converter output voltage | DC bus voltage. | UINT16 | × 0.1 | V | Read | ||
| HR | 208doc 40209 | Regenerative brake duty | Brake duty set in Pr.70 (standard model). | UINT16 | × 0.1 | % | Read | ||
| HR | 209doc 40210 | Electronic thermal O/L relay load factor | Motor thermal accumulation, 100% = trip level. | UINT16 | × 0.1 | % | Read | ||
| HR | 211doc 40212 | Converter output voltage peak | DC bus peak since power-up. | UINT16 | × 0.1 | V | Read | ||
| HR | 214doc 40215 | Input terminal status | 1 = terminal on. | BITMAP16 | Read | bit 0 = STF; bit 1 = STR; bit 2 = AU; bit 3 = RT; bit 4 = RL; bit 5 = RM; bit 6 = RH; bit 7 = JOG; bit 8 = MRS; bit 9 = STP (STOP); bit 10 = RES; bit 11 = CS; bit 14 = S2; bit 15 = S1 | |||
| HR | 215doc 40216 | Output terminal status | 1 = terminal on. | BITMAP16 | Read | bit 0 = RUN; bit 1 = SU; bit 2 = IPF; bit 3 = OL; bit 4 = FU; bit 5 = ABC1; bit 6 = ABC2; bit 7 = So (SO) | |||
| HR | 216doc 40217 | Load meter | Torque current as % of Pr.56. | UINT16 | × 0.1 | % | Read | ||
| HR | 219doc 40220 | Cumulative energization time | Wraps at 65535 h. | UINT16 | h | Read | |||
| HR | 222doc 40223 | Actual operation time | Wraps at 65535 h; reset with Pr.171. | UINT16 | h | Read | |||
| HR | 223doc 40224 | Motor load factor | Output current as % of inverter rated current. | UINT16 | × 0.1 | % | Read | ||
| HR | 236doc 40237 | Heat sink temperature | Monitor range 0-130 °C. | UINT16 | °C | Read | |||
| HR | 251doc 40252 | PID set point | UINT16 | × 0.1 | % | Read | |||
| HR | 252doc 40253 | PID measured value | UINT16 | × 0.1 | % | Read | |||
| HR | 260doc 40261 | Motor thermal load factor | E.THM trips at 100%. | UINT16 | × 0.1 | % | Read | ||
| HR | 261doc 40262 | Inverter thermal load factor | E.THT trips at 100%. | UINT16 | × 0.1 | % | Read | ||
| HR | 266doc 40267 | PID measured value 2 | Shown whenever PID is enabled. | UINT16 | × 0.1 | % | Read | ||
| HR | 291doc 40292 | Second PID set point | UINT16 | × 0.1 | % | Read | |||
| HR | 292doc 40293 | Second PID measured value | UINT16 | × 0.1 | % | Read | |||
| HR | 500doc 40501 | Fault record 1 | Low byte = error code. Write any value to 40501 to clear history. | UINT16 | Read/write | ||||
| HR | 501doc 40502 | Fault record 2 | Low byte = error code. | UINT16 | Read | ||||
| HR | 502doc 40503 | Fault record 3 | Low byte = error code. | UINT16 | Read | ||||
| HR | 503doc 40504 | Fault record 4 | Low byte = error code. | UINT16 | Read | ||||
| HR | 504doc 40505 | Fault record 5 | Low byte = error code. | UINT16 | Read | ||||
| HR | 505doc 40506 | Fault record 6 | Low byte = error code. | UINT16 | Read | ||||
| HR | 506doc 40507 | Fault record 7 | Low byte = error code. | UINT16 | Read | ||||
| HR | 507doc 40508 | Fault record 8 | Low byte = error code. | UINT16 | Read | ||||
| HR | 1000doc 41001 | Pr.1 Maximum frequency | UINT16 | × 0.01 | Hz | Read/write | |||
| HR | 1001doc 41002 | Pr.2 Minimum frequency | UINT16 | × 0.01 | Hz | Read/write | |||
| HR | 1003doc 41004 | Pr.4 Multi-speed setting (high speed) | UINT16 | × 0.01 | Hz | Read/write | |||
| HR | 1004doc 41005 | Pr.5 Multi-speed setting (middle speed) | UINT16 | × 0.01 | Hz | Read/write | |||
| HR | 1005doc 41006 | Pr.6 Multi-speed setting (low speed) | UINT16 | × 0.01 | Hz | Read/write | |||
| HR | 1078doc 41079 | Pr.79 Operation mode selection | UINT16 | Read/write | 0 = External/PU switchover (External at power-on); 1 = Fixed PU operation; 2 = Fixed External operation (NET switchable); 3 = External/PU combined mode 1; 4 = External/PU combined mode 2; 6 = Switchover during operation; 7 = External operation (PU interlock) | ||||
| HR | 1330doc 41331 | Pr.331 RS-485 communication station number | 0 = broadcast; 1-247 under Modbus RTU. | UINT16 | Read/write | ||||
| HR | 1331doc 41332 | Pr.332 RS-485 communication speed | Setting x 100 = bps (96 = 9600). | UINT16 | Read/write | ||||
| HR | 1333doc 41334 | Pr.334 RS-485 communication parity check selection | Under Modbus RTU this also sets the stop bits. | UINT16 | Read/write | 0 = No parity (stop bits per Pr.333); 1 = Odd parity, 1 stop bit; 2 = Even parity, 1 stop bit | |||
| HR | 1342doc 41343 | Pr.343 Communication error count | Modbus RTU error count. | UINT16 | Read | ||||
| HR | 1538doc 41539 | Pr.539 MODBUS RTU communication check time interval | 0 = Modbus allowed but output shut off in NET mode; 9999 = no check. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 1548doc 41549 | Pr.549 Protocol selection | UINT16 | Read/write | 0 = Mitsubishi inverter protocol (computer link); 1 = MODBUS RTU |
Notes on this map
- All registers are single 16-bit words. The manual notes that a 32-bit parameter or monitor whose value exceeds HFFFF reads back as HFFFF.
- Left out because the increment depends on inverter capacity (0.01 unit up to FR-A820-03160(55K)/FR-A840-01800(55K), 0.1 unit above): output current 40202, output current peak 40211, input power 40213, output power 40214, motor excitation current 40218, cumulative energy 40225, motor output 40234 and the 32-bit cumulative energy halves 40279/40280. Motor load factor 40224 (% of rated current) gives a size-independent current reading.
- Left out because sign handling is unclear (footnote *1 says Modbus cannot carry a minus sign, footnote *20 says Pr.1018 enables signed monitors): motor torque 40207, torque 40236, PID deviation 40254, second PID deviation 40294, PID manipulated amounts, remote output values and control circuit temperature 40298. Output frequency 40201 and operation speed 40206 are kept as unsigned: they only become signed when Pr.1018 is set. Vector-control position/pulse monitors (40219-40231, 40271-40275) are also left out.
- Output frequency, set frequency and the frequency command use 0.01 Hz by default; with Pr.37 = 1-9998 or Pr.144 = 2-12/102-112 the increment becomes 1 (speed display), and Pr.811 also affects the 40014/40015 display. The 0.01 Hz unit for 40014/40015 comes from the same manual's computer-link set-frequency description (H0000-HFFFF in 0.01 Hz increments).
- Fault history registers hold the error code in the low byte (high byte H00); code meanings are in the manual's fault chapter.
- Parameters 0-999 sit at 41000 + Pr. number and 1000-1999 at 44000 + Pr. number. Calibration parameters C2-C45 have their own registers (41902-43935) and are not listed.
- Parameters with a 9999 (function off) setting, such as the communication check interval, are listed with their normal increment; the manual does not say how the 9999 setting itself is encoded on the wire, so read the parameter back after setting it from the panel.
- Pr.7/Pr.8 acceleration/deceleration times are left out: their increment changes with Pr.21.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Mitsubishi Electric FR-A800 inverter (RS-485 terminals, Modbus RTU)
What Modbus registers does the Mitsubishi Electric FR-A800 inverter (RS-485 terminals, Modbus RTU) have?
This map lists 51 registers: 51 holding registers. 21 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Mitsubishi Electric FR-A800 inverter (RS-485 terminals, Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints Modicon-style register numbers (40002, 41004). Its rule: starting address = register number - 40001, e.g. reading 41004 (Pr.4) sends start address H03EB (1003).
What are the minimum Modbus registers to integrate the Mitsubishi Electric FR-A800 inverter (RS-485 terminals, Modbus RTU)?
Start with HR 8 Control input command / inverter status (Run/stop command and inverter status); HR 9 Operation mode / inverter setting (Operation mode (write H0014 for NET)); HR 13 Set frequency (RAM) (Frequency command (RAM)); HR 200 Output frequency (Output frequency); HR 223 Motor load factor (Motor load factor (% of rated current)); HR 207 Converter output voltage (DC bus voltage); HR 500 Fault record 1 (Latest fault code).
How do I enable Modbus control of the Mitsubishi Electric FR-A800 inverter (RS-485 terminals, Modbus RTU)?
Pr.549 = 1 selects Modbus RTU on the RS-485 terminals; set Pr.331 (1-247), Pr.332 speed and Pr.334 parity, then reset or power-cycle. Run and frequency commands are taken in NET operation mode (write H0014 to 40010, or use Pr.79/Pr.340 so the drive starts in NET mode). If a communication option is installed and Pr.550 = 9999, commands via the RS-485 terminals are ignored.
What happens when the Mitsubishi Electric FR-A800 inverter (RS-485 terminals, Modbus RTU) loses Modbus communication?
Pr.539 sets the Modbus communication check interval (0.1-999.8 s, same behaviour as Pr.122); 9999 (initial) disables the check, 0 lets Modbus run but shuts the output off in NET mode.
Where is the official Mitsubishi Electric FR-A800 inverter (RS-485 terminals, Modbus RTU) Modbus documentation?
The source is FR-A800 Instruction Manual (Detailed) (IB(NA)-0600503ENG-P), revision 2026-04, published free by Mitsubishi Electric at https://dl.mitsubishielectric.com/dl/fa/document/manual/inv/ib0600503eng/ib0600503engp.pdf.
More Mitsubishi Electric Modbus register maps
- Variable frequency drive
Mitsubishi Electric FR-A700 inverter (RS-485 terminals, Modbus RTU)
FR-A700 series inverters (FR-A720-0.4K to 90K, FR-A740-0.4K to 500K) using the RS-485 terminals with Pr.549 = 1 (Modbus-RTU); Instruction Manual (Applied) revision E.
Also known as: FR-A720, FR-A740, FR-A700 series - Variable frequency drive
Mitsubishi Electric FR-D700 compact inverter (PU connector, Modbus RTU)
FR-D700 series (FR-D720/D740/D720S/D710W) using the PU connector with Pr.549 = 1; Instruction Manual (Applied) revision H.
Also known as: FR-D720, FR-D740, FR-D720S, FR-D710W - Variable frequency drive
Mitsubishi Electric FR-E700 compact inverter (PU connector, Modbus RTU)
FR-E700 series (FR-E720/E740/E720S/E710W, incl. SC safety-stop models) using the PU connector with Pr.549 = 1; Instruction Manual (Applied) revision G.
Also known as: FR-E720, FR-E740, FR-E720S, FR-E710W, FR-E700-SC - Variable frequency drive
Mitsubishi Electric FR-F800 fan and pump inverter (RS-485 terminals, Modbus RTU)
FR-F800 series inverters (FR-F820/F840/F842/F846) using the built-in RS-485 terminals with Pr.549 = 1 (MODBUS RTU); Instruction Manual (Detailed) revision G.
Also known as: FR-F820, FR-F840, FR-F842, FR-F846, FR-F800 series - VRF / split AC gateway
Mitsubishi Electric MelcoBEMS MINI (A1M) gateway for Air-To-Air split units
Procon MelcoBEMS MINI (A1M) on the CN105/CN92 connector of a Mitsubishi Electric Air-To-Air indoor unit, installation manual v1.1.11 (firmware 3.0.28 for revision 2-4 hardware, 3.1.1 for revision 5).
Also known as: MelcoBEMS MINI (A1M), A1M, Procon A1M, MelcoBEMS MINI - Air handler (heat recovery ventilation unit)
Mitsubishi Electric MelcoBEMS MINI (A1M+ / A1M) gateway for Lossnay heat recovery ventilators (LGH and VL series)
Procon MelcoBEMS MINI A1M+ (manual v1.0.3, firmware 4.1.1) on Lossnay LGH-15..200RVX-E1, LGH-150..250RVXT-E1 and VL-250..500CZPVU-R/L-E; the older A1M (manual v1.1.11) prints the identical Lossnay table.
Also known as: A1M+ Lossnay, MelcoBEMS MINI Lossnay, Procon A1M+, Procon A1M, A1M, Lossnay LGH-RVX Modbus, LGH-15RVX-E1, LGH-200RVX-E1, LGH-150RVXT-E1, LGH-250RVXT-E1, VL-250CZPVU-R-E, VL-500CZPVU-L-E, Lossnay VL Vertical - VRF / split AC gateway
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Air-To-Air split units (M, S and P series)
MelcoBEMS MINI (A1M+) on the CN105 connector of a Mitsubishi Electric Air-To-Air indoor unit (M series MSZ/MFZ/MLZ, S series SEZ/SLZ, P series per Appendix A), installation manual v1.0.3, firmware 4.1.1.
Also known as: A1M+, MelcoBEMS MINI, Procon A1M+, MelcoBEMS MINI A1M PLUS, A1M+ ATA - Chiller / heat pump gateway (VRF / split AC gateway)
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for CAHV / CRHV / QAHV heat pumps and EAHV / EACV e-series chillers
Procon MelcoBEMS MINI (A1M+) firmware 4.1.0 on Mitsubishi Electric CAHV and CRHV heat pumps, QAHV CO2 heat pumps and EAHV / EACV e-series chillers (master and slave units); holding-register table only.
Also known as: A1M+, MelcoBEMS MINI, Procon A1M+, CAHV, CRHV, QAHV, EAHV, EACV, e-series chiller - Heat pump (VRF / split AC gateway)
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Ecodan FTC4/FTC5/FTC6 air-to-water systems
Procon MelcoBEMS MINI (A1M+) firmware 4.1.0 connected to an Ecodan FTC4, FTC5 or FTC6 air-to-water controller; holding-register table only.
Also known as: A1M+, MelcoBEMS MINI, Procon A1M+, Ecodan FTC4, Ecodan FTC5, Ecodan FTC6 - Air handler DX interface (VRF / split AC gateway)
Mitsubishi Electric PAC-IF013B-E / PAC-SIF013B-E air handling unit interface (Modbus RTU)
PAC-IF013B-E and PAC-SIF013B-E interface controllers linking a Mitsubishi Electric outdoor unit to an AHU coil, Modbus manual dated September 2015 (RG79F084H01).
Also known as: PAC-IF013B-E, PAC-SIF013B-E, PAC-(S)IF013B-E - VRF / split AC gateway (retail controller)
Mitsubishi Electric Procon MelcoRETAIL MINI controller for Air-To-Air split units
Procon MelcoRETAIL MINI on the CN105/CN92 connector of Mitsubishi Electric M, S and P series Air-To-Air indoor units, installation manual v1.0.6, firmware 1.0.3.
Also known as: MelcoRETAIL MINI, Procon MelcoRETAIL MINI - Air handler (computer room air conditioner)
Mitsubishi Electric s-MEXT-G00 computer room air conditioner (ME28 relC)
Mitsubishi Electric (Hydronics & IT Cooling) s-MEXT-G00 006-044 close-control units with ME28-relC software and the Modbus serial board.
Also known as: s-MEXT, s-MEXT-G00 006-044, s-MEXT G00, ME28 relC
Other variable frequency drives register maps
- Variable frequency drive
Schneider Electric Altivar Machine ATV340 (embedded Modbus serial / Modbus TCP)
ATV340 drives on the built-in Modbus serial port; Ethernet versions (ATV340...N4E) expose the same addresses on embedded Modbus TCP. Per Communication Parameters file NVE61728 V4.6.
Also known as: ATV340, Altivar 340, Altivar Machine ATV340, ATV340U, ATV340D, ATV340...N4E - Variable frequency drive
Siemens SINAMICS G120 / G120C (Modbus RTU)
SINAMICS G120 with an RS485 Control Unit (CU230P-2 HVAC/BT, CU240B-2, CU240E-2 / -2 F, CU250S-2), G120C USS/MB and G110M CU240M USS, firmware V4.7, per Fieldbuses function manual A5E34229197B AA. Not SINAMICS G120X, which has its own documentation.
Also known as: G120C USS/MB, CU230P-2 HVAC, CU230P-2 BT, CU240B-2, CU240E-2, CU240E-2 F, CU250S-2, G110M CU240M USS, G120P - Variable frequency drive (HVAC fan / pump)
TECO-Westinghouse F510 HVAC fan/pump inverter (Modbus RTU/ASCII)
TECO-Westinghouse F510 HVAC inverters using the built-in RS-485 port (CN6) in Modbus mode, per communication addendum DOCUMENT-TECO-F510-AC001 Ver01 (2015-03).
Also known as: TECO F510, F510 HVAC drive - Variable frequency drive
Yaskawa A1000 AC drive (MEMOBUS/Modbus RTU)
Yaskawa A1000 drives (CIMR-AU; 200 V, 400 V and 600 V classes) using the built-in RS-422/485 MEMOBUS/Modbus terminals (TB5), per Technical Manual SIEP C710616 41H.
Also known as: CIMR-AU, CIMR-AUA, A1000 High Performance Vector Control Drive - Variable frequency drive
Yaskawa GA800 AC drive (MEMOBUS/Modbus RTU)
Yaskawa GA800 drives using the built-in RS-485 MEMOBUS/Modbus port, per technical reference SIEPC71061737 revision G.
Also known as: CIPR-GA80, GA800 Industrial AC Microdrive - Variable frequency drive
Yaskawa iQpump605 intelligent pump controller (MEMOBUS/Modbus RTU)
Yaskawa iQpump605 drives using the built-in RS-485 port (MEMOBUS/Modbus RTU), per user manual SIEPYAIWM6502D.
Also known as: WM65W, iQpump605 drive, iQpump605 Intelligent Pump Controller
All variable frequency drives Modbus register maps →
Source: FR-A800 Instruction Manual (Detailed) · IB(NA)-0600503ENG-P · rev. 2026-04. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.