AutomationDirect Modbus register maps
Updated 17 November 2026
5 AutomationDirect models, 131 registers in all, each re-typed from AutomationDirect’s own free documentation and checked against it.
- Variable frequency drive
AutomationDirect DURApulse GS10 AC drive
GS10 drives (built-in RS-485 port) per the GS10 user manual, 1st edition rev. C, chapter 5.
Also known as: DURApulse GS10, GS10 micro drive - Variable frequency drive
AutomationDirect DURApulse GS20 / GS20X AC drive
GS20 and GS20X drives (built-in RS-485 port) per the GS20 & GS20X user manual, 1st edition rev. F, chapter 5.
Also known as: GS20X, DURApulse GS20, GS21-11P0 - Variable frequency drive
AutomationDirect DURApulse GS3 AC drive
All GS3 drives; status addresses and P9.xx serial-communication parameters from chapter 5 of the user manual.
Also known as: DURApulse GS3, GS3-21P0, GS3-22P0, GS3-23P0, GS3-25P0, GS3-27P5, GS3-2010, GS3-2015, GS3-2020, GS3-2025 - Variable frequency drive
AutomationDirect GS1 series AC drive
All GS1 drives; status addresses and P9.xx serial-communication parameters from chapter 5 of the user manual.
Also known as: GS1-10P2, GS1-10P5, GS1-20P2, GS1-20P5, GS1-21P0, GS1-22P0 - Variable frequency drive
AutomationDirect GS2 series AC drive
All GS2 drives; status addresses and P9.xx serial-communication parameters from chapter 5 of the user manual.
Also known as: GS2-10P2, GS2-10P5, GS2-11P0, GS2-20P5, GS2-21P0, GS2-22P0, GS2-23P0, GS2-25P0, GS2-27P5, GS2-41P0, GS2-42P0, GS2-43P0, GS2-45P0, GS2-47P5
AutomationDirect: default communication settings
Factory defaults as the manufacturer documents them. Change one setting at a time on site and write down what you changed. Word order applies to 32-bit values; the addressing column says how the manufacturer prints register numbers (every map on this site also gives the 0-based wire address).
| Model | Transport | Unit ID | Serial | Word order | Documented addressing | Registers |
|---|---|---|---|---|---|---|
| DURApulse GS10 AC drive | RTU/ASCII | 1 | 38400 baud, 8N2 | 16-bit only | hex 0-based | 33 |
| DURApulse GS20 / GS20X AC drive | RTU/ASCII | 1 | 9600 baud | 16-bit only | hex 0-based | 34 |
| DURApulse GS3 AC drive | RTU/ASCII | Not stated | - | CDAB | hex 0-based | 21 |
| GS1 series AC drive | RTU/ASCII | 1 | 9600 baud | CDAB | hex 0-based | 22 |
| GS2 series AC drive | RTU/ASCII | 1 | 9600 baud | CDAB | hex 0-based | 21 |