Danfoss VLT Compressor Drive CDS 803 (Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

Danfoss's drive for variable-speed refrigeration and air-conditioning compressors. Its RS-485 port runs Modbus RTU: the FC-profile control and status words are coils 1-16 and 33-48, and every parameter is a holding register at ten times its parameter number. This map covers the control/status coils, compressor readouts, fault and warning words, and the communication and timeout parameters.

This page lists 79 Modbus registers for the Danfoss VLT Compressor Drive CDS 803 (Modbus RTU) — 33 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Danfoss’s own free documentation (linked below) and checked against it.

Manufacturer
Danfoss
Model
VLT Compressor Drive CDS 803 (Modbus RTU)
Equipment type
Variable frequency drive
Registers
79 (33 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
8E1
Documented addressing
derived from parameter numbers
32-bit word order
ABCD high word first (big-endian)
Firmware
Design guide software 1.20; programming guide software 2.0
Also known as
CDS803, CDS-803, VLT Compressor Drive CDS 803
Source document
VLT Compressor Drive CDS 803 Design Guide (chapter 7 RS485 Installation and Set-up) · MG18N202 · rev. 2015-12
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Danfoss VLT Compressor Drive CDS 803 (Modbus RTU)

Integration in brief

Set 8-30 = [2] Modbus RTU plus 8-31 address, 8-32 baud and 8-33 parity, keep 8-02 = FC port, then drive the compressor with the control-word coils (coil 11 data valid, coil 7 start) and read 16-13 frequency, 16-14 current, 16-10 power and 16-90 alarm word.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
CO 6CTW bit 6: Ramp stop / startBITCTW bit 6: ramp stop / startRead/write
CO 10CTW bit 10: Data validBITCTW bit 10: data validRead/write
CO 43STW bit 11: RunningBITSTW: runningRead
HR 1612916-13 FrequencyUINT32 ABCD16-13 Frequency, 0.1 HzRead
HR 1613916-14 Motor currentUINT1616-14 Motor current, 0.01 ARead
HR 1609916-10 Power [kW]UINT32 ABCD16-10 Power, 0.001 kWRead
HR 1689916-90 Alarm WordUINT32 ABCD16-90 Alarm wordRead

Enable Modbus control & writes

8-30 Protocol = [2] Modbus RTU, 8-31 Address (1-247), 8-32 Baud Rate, 8-33 Parity/Stop Bits. 8-01 Control Site chooses digital inputs and/or control word; 8-02 Control Source must be FC Port; 8-50..8-56 decide how bus bits combine with digital inputs (most default to Logic OR).

Communication loss & watchdog

8-03 Control Timeout Time (0.1-200 s, default 20 s) and 8-04 Control Timeout Function (default Off; Freeze output, Stop, Jogging, Max. speed, Stop and trip, N2 override release) act when the control word is not updated in time.

Byte order & addressing

Network setup

Watch out for

Danfoss VLT Compressor Drive CDS 803 (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

79 of 79 shown
Danfoss VLT Compressor Drive CDS 803 (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0doc 1CTW bit 0: Preset reference LSB0/1 = reference select bit 0BITRead/write
CO1doc 2CTW bit 1: Preset reference MSB0/1 = reference select bit 1BITRead/write
CO2doc 3CTW bit 2: DC brake0 = DC brake, 1 = no DC brakeBITRead/write
CO3doc 4CTW bit 3: Coast stop0 = coast stop, 1 = no coast stopBITRead/write
CO4doc 5CTW bit 4: Quick stop0 = quick stop, 1 = no quick stopBITRead/write
CO5doc 6CTW bit 5: Freeze frequency0 = freeze output frequency, 1 = no freezeBITRead/write
CO6doc 7CTW bit 6: Ramp stop / start0 = ramp stop, 1 = startBITRead/write
CO7doc 8CTW bit 7: Reset1 = reset (rising edge)BITRead/write
CO8doc 9CTW bit 8: Jog1 = jogBITRead/write
CO9doc 10CTW bit 9: Ramp 1 / ramp 20 = ramp 1, 1 = ramp 2BITRead/write
CO10doc 11CTW bit 10: Data valid0 = control word ignored, 1 = data validBITRead/write
CO11doc 12CTW bit 11: Relay 11 = relay 1 onBITRead/write
CO12doc 13CTW bit 12: Relay 21 = relay 2 onBITRead/write
CO13doc 14CTW bit 13: Set-up LSBSet-up selectBITRead/write
CO15doc 16CTW bit 15: Reversing1 = reversingBITRead/write
CO32doc 33STW bit 0: Control ready1 = control readyBITRead
CO33doc 34STW bit 1: Drive ready1 = frequency converter readyBITRead
CO34doc 35STW bit 2: Coast stop / safety closed0 = coast stop, 1 = safety closedBITRead
CO35doc 36STW bit 3: Alarm1 = alarmBITRead
CO39doc 40STW bit 7: Warning1 = warningBITRead
CO40doc 41STW bit 8: At reference1 = at referenceBITRead
CO41doc 42STW bit 9: Hand / auto mode0 = hand mode, 1 = auto modeBITRead
CO42doc 43STW bit 10: In frequency range1 = in frequency rangeBITRead
CO43doc 44STW bit 11: Running0 = stopped, 1 = runningBITRead
CO45doc 46STW bit 13: Voltage warning1 = voltage warningBITRead
CO46doc 47STW bit 14: Current limit1 = in current limitBITRead
CO47doc 48STW bit 15: Thermal warning1 = thermal warningBITRead
CO64doc 65Parameter write control0 = parameter writes go to RAM only, 1 = RAM and EEPROM.BITRead/write0 = RAM only; 1 = RAM and EEPROM
HR6doc 7Last fault codeFault code from the parameter database.UINT16Read
HR7doc 8Last error registerAddress of the register where the last error occurred.UINT16Read
HR8doc 9Index pointerSub-index for array parameters.UINT16Read/write
HR3019doc 30203-02 Minimum ReferenceIn the reference/feedback unit.INT32ABCD× 0.001Read/write
HR3029doc 30303-03 Maximum ReferenceIn the reference/feedback unit.INT32ABCD× 0.001Read/write
HR3409doc 34103-41 Ramp 1 Ramp Up TimeUINT32ABCD× 0.01sRead/write
HR3419doc 34203-42 Ramp 1 Ramp Down TimeUINT32ABCD× 0.01sRead/write
HR4119doc 41204-12 Motor Speed Low Limit [Hz]UINT16× 0.1HzRead/write
HR4139doc 41404-14 Motor Speed High Limit [Hz]UINT16× 0.1HzRead/write
HR4189doc 41904-19 Max Output FrequencyUINT16× 0.1HzRead/write
HR8009doc 80108-01 Control SiteUint8 in one register; default digital and control word.UINT16Read/write
HR8019doc 80208-02 Control SourceUint8 in one register; default FC port.UINT16Read/write
HR8029doc 80308-03 Control Timeout Time0.1-200 s, default 20 s.UINT16× 0.1sRead/write
HR8039doc 80408-04 Control Timeout FunctionUINT16Read/write0 = Off; 1 = Freeze output; 2 = Stop; 3 = Jogging; 4 = Max. speed; 5 = Stop and trip; 20 = N2 override release
HR8299doc 83008-30 ProtocolUINT16Read/write0 = FC; 2 = Modbus RTU
HR8309doc 83108-31 Address1-247 for Modbus; default 1.UINT16Read/write
HR8319doc 83208-32 Baud RateUINT16Read/write0 = 2400; 1 = 4800; 2 = 9600; 3 = 19200; 4 = 38400; 5 = 57600; 6 = 76800; 7 = 115200
HR8329doc 83308-33 Parity / Stop BitsUINT16Read/write0 = Even parity, 1 stop bit; 1 = Odd parity, 1 stop bit; 2 = No parity, 1 stop bit; 3 = No parity, 2 stop bits
HR8349doc 83508-35 Minimum Response DelayUINT16× 0.001sRead/write
HR14999doc 1500015-00 Operating hoursUINT32ABCDhRead
HR15009doc 1501015-01 Running HoursUINT32ABCDhRead
HR15029doc 1503015-03 Power Up'sUINT32ABCDRead
HR15039doc 1504015-04 Over Temp'sUINT16Read
HR15049doc 1505015-05 Over Volt'sUINT16Read
HR15299doc 1530015-30 Alarm Log: Error CodeArray (index via register 9); uint8 in one register.UINT16Read
HR15999doc 1600016-00 Control WordUINT16Read
HR16009doc 1601016-01 Reference [Unit]INT32ABCD× 0.001Read
HR16019doc 1602016-02 Reference [%]INT16× 0.1%Read
HR16029doc 1603016-03 Status WordUINT16Read
HR16049doc 1605016-05 Main Actual Value [%]INT16× 0.01%Read
HR16099doc 1610016-10 Power [kW]UINT32ABCD× 0.001kWRead
HR16119doc 1612016-12 Motor VoltageUINT32ABCD× 0.1VRead
HR16129doc 1613016-13 FrequencyUINT32ABCD× 0.1HzRead
HR16139doc 1614016-14 Motor currentUINT16× 0.01ARead
HR16149doc 1615016-15 Frequency [%]UINT16× 0.1%Read
HR16159doc 1616016-16 Torque [Nm]INT32ABCD× 0.1NmRead
HR16179doc 1618016-18 Motor ThermalUint8 in one register.UINT16%Read
HR16219doc 1622016-22 Torque [%]INT16%Read
HR16299doc 1630016-30 DC Link VoltageUINT32ABCDVRead
HR16349doc 1635016-35 Inverter ThermalUint8 in one register.UINT16%Read
HR16359doc 1636016-36 Inv. Nom. CurrentUINT16× 0.01ARead
HR16369doc 1637016-37 Inv. Max. CurrentUINT16× 0.01ARead
HR16499doc 1650016-50 External ReferenceINT16× 0.1%Read
HR16519doc 1652016-52 Feedback [Unit]INT32ABCD× 0.001Read
HR16599doc 1660016-60 Digital InputUINT16Read
HR16859doc 1686016-86 FC Port REF 1INT16Read
HR16899doc 1690016-90 Alarm WordUINT32ABCDRead
HR16909doc 1691016-91 Alarm Word 2UINT32ABCDRead
HR16919doc 1692016-92 Warning WordUINT32ABCDRead
HR16929doc 1693016-93 Warning Word 2UINT32ABCDRead
HR16939doc 1694016-94 Ext. Status WordUINT32ABCDRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Danfoss VLT Compressor Drive CDS 803 (Modbus RTU)

What Modbus registers does the Danfoss VLT Compressor Drive CDS 803 (Modbus RTU) have?

This map lists 79 registers: 28 coils, 51 holding registers. 33 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Danfoss VLT Compressor Drive CDS 803 (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers derived from parameter numbers. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The design guide states coil 1 is sent as 0000 and holding register 40001 as 0000. A parameter's register is 10 x its parameter number (3-03 -> 3030), sent minus 1: the guide's example reads 3-03 at start address 0x0BD5 (3029). Coils are 1-based too (coil 65 is sent as 64).

What byte order does the Danfoss VLT Compressor Drive CDS 803 (Modbus RTU) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Danfoss VLT Compressor Drive CDS 803 (Modbus RTU)?

Start with CO 6 CTW bit 6: Ramp stop / start (CTW bit 6: ramp stop / start); CO 10 CTW bit 10: Data valid (CTW bit 10: data valid); CO 43 STW bit 11: Running (STW: running); HR 16129 16-13 Frequency (16-13 Frequency, 0.1 Hz); HR 16139 16-14 Motor current (16-14 Motor current, 0.01 A); HR 16099 16-10 Power [kW] (16-10 Power, 0.001 kW); HR 16899 16-90 Alarm Word (16-90 Alarm word).

How do I enable Modbus control of the Danfoss VLT Compressor Drive CDS 803 (Modbus RTU)?

8-30 Protocol = [2] Modbus RTU, 8-31 Address (1-247), 8-32 Baud Rate, 8-33 Parity/Stop Bits. 8-01 Control Site chooses digital inputs and/or control word; 8-02 Control Source must be FC Port; 8-50..8-56 decide how bus bits combine with digital inputs (most default to Logic OR).

What happens when the Danfoss VLT Compressor Drive CDS 803 (Modbus RTU) loses Modbus communication?

8-03 Control Timeout Time (0.1-200 s, default 20 s) and 8-04 Control Timeout Function (default Off; Freeze output, Stop, Jogging, Max. speed, Stop and trip, N2 override release) act when the control word is not updated in time.

Where is the official Danfoss VLT Compressor Drive CDS 803 (Modbus RTU) Modbus documentation?

The source is VLT Compressor Drive CDS 803 Design Guide (chapter 7 RS485 Installation and Set-up) (MG18N202), revision 2015-12, published free by Danfoss at https://files.danfoss.com/download/Drives/MG18N202.pdf.

More Danfoss Modbus register maps

Other variable frequency drives register maps

All variable frequency drives Modbus register maps →

Source: VLT Compressor Drive CDS 803 Design Guide (chapter 7 RS485 Installation and Set-up) · MG18N202 · rev. 2015-12. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.