Variable frequency drive · Modbus register map
Danfoss VLT Compressor Drive CDS 803 (Modbus RTU) Modbus register map
Updated 19 November 2026
Danfoss's drive for variable-speed refrigeration and air-conditioning compressors. Its RS-485 port runs Modbus RTU: the FC-profile control and status words are coils 1-16 and 33-48, and every parameter is a holding register at ten times its parameter number. This map covers the control/status coils, compressor readouts, fault and warning words, and the communication and timeout parameters.
This page lists 79 Modbus registers for the Danfoss VLT Compressor Drive CDS 803 (Modbus RTU) — 33 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Danfoss’s own free documentation (linked below) and checked against it.
- Manufacturer
- Danfoss
- Model
- VLT Compressor Drive CDS 803 (Modbus RTU)
- Equipment type
- Variable frequency drive
- Registers
- 79 (33 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 8E1
- Documented addressing
- derived from parameter numbers
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- Design guide software 1.20; programming guide software 2.0
- Also known as
- CDS803, CDS-803, VLT Compressor Drive CDS 803
Integration notes: Danfoss VLT Compressor Drive CDS 803 (Modbus RTU)
Set 8-30 = [2] Modbus RTU plus 8-31 address, 8-32 baud and 8-33 parity, keep 8-02 = FC port, then drive the compressor with the control-word coils (coil 11 data valid, coil 7 start) and read 16-13 frequency, 16-14 current, 16-10 power and 16-90 alarm word.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| CO 6 | CTW bit 6: Ramp stop / start | BIT | CTW bit 6: ramp stop / start | Read/write |
| CO 10 | CTW bit 10: Data valid | BIT | CTW bit 10: data valid | Read/write |
| CO 43 | STW bit 11: Running | BIT | STW: running | Read |
| HR 16129 | 16-13 Frequency | UINT32 ABCD | 16-13 Frequency, 0.1 Hz | Read |
| HR 16139 | 16-14 Motor current | UINT16 | 16-14 Motor current, 0.01 A | Read |
| HR 16099 | 16-10 Power [kW] | UINT32 ABCD | 16-10 Power, 0.001 kW | Read |
| HR 16899 | 16-90 Alarm Word | UINT32 ABCD | 16-90 Alarm word | Read |
Enable Modbus control & writes
8-30 Protocol = [2] Modbus RTU, 8-31 Address (1-247), 8-32 Baud Rate, 8-33 Parity/Stop Bits. 8-01 Control Site chooses digital inputs and/or control word; 8-02 Control Source must be FC Port; 8-50..8-56 decide how bus bits combine with digital inputs (most default to Logic OR).
Communication loss & watchdog
8-03 Control Timeout Time (0.1-200 s, default 20 s) and 8-04 Control Timeout Function (default Off; Freeze output, Stop, Jogging, Max. speed, Stop and trip, N2 override release) act when the control word is not updated in time.
Byte order & addressing
- Parameter register = parameter number x 10, request address = that minus 1.
- 32-bit values are high word first (ABCD).
- CTW bit 10 (coil 11) must be 1 or the control word is ignored.
- Coil 65 chooses whether parameter writes also go to EEPROM.
Network setup
- Defaults: address 1, even parity with 1 stop bit; the protocol default is FC, so 8-30 must be changed to Modbus RTU.
- The guides say the default baud rate depends on the protocol chosen in 8-30 and do not print the Modbus default, so set 8-32 explicitly (2400-115200).
Watch out for
- Changing 8-30 Protocol may change the baud rate (8-32); re-check it after switching to Modbus.
Danfoss VLT Compressor Drive CDS 803 (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 1 | CTW bit 0: Preset reference LSB | 0/1 = reference select bit 0 | BIT | Read/write | ||||
| CO | 1doc 2 | CTW bit 1: Preset reference MSB | 0/1 = reference select bit 1 | BIT | Read/write | ||||
| CO | 2doc 3 | CTW bit 2: DC brake | 0 = DC brake, 1 = no DC brake | BIT | Read/write | ||||
| CO | 3doc 4 | CTW bit 3: Coast stop | 0 = coast stop, 1 = no coast stop | BIT | Read/write | ||||
| CO | 4doc 5 | CTW bit 4: Quick stop | 0 = quick stop, 1 = no quick stop | BIT | Read/write | ||||
| CO | 5doc 6 | CTW bit 5: Freeze frequency | 0 = freeze output frequency, 1 = no freeze | BIT | Read/write | ||||
| CO | 6doc 7 | CTW bit 6: Ramp stop / start | 0 = ramp stop, 1 = start | BIT | Read/write | ||||
| CO | 7doc 8 | CTW bit 7: Reset | 1 = reset (rising edge) | BIT | Read/write | ||||
| CO | 8doc 9 | CTW bit 8: Jog | 1 = jog | BIT | Read/write | ||||
| CO | 9doc 10 | CTW bit 9: Ramp 1 / ramp 2 | 0 = ramp 1, 1 = ramp 2 | BIT | Read/write | ||||
| CO | 10doc 11 | CTW bit 10: Data valid | 0 = control word ignored, 1 = data valid | BIT | Read/write | ||||
| CO | 11doc 12 | CTW bit 11: Relay 1 | 1 = relay 1 on | BIT | Read/write | ||||
| CO | 12doc 13 | CTW bit 12: Relay 2 | 1 = relay 2 on | BIT | Read/write | ||||
| CO | 13doc 14 | CTW bit 13: Set-up LSB | Set-up select | BIT | Read/write | ||||
| CO | 15doc 16 | CTW bit 15: Reversing | 1 = reversing | BIT | Read/write | ||||
| CO | 32doc 33 | STW bit 0: Control ready | 1 = control ready | BIT | Read | ||||
| CO | 33doc 34 | STW bit 1: Drive ready | 1 = frequency converter ready | BIT | Read | ||||
| CO | 34doc 35 | STW bit 2: Coast stop / safety closed | 0 = coast stop, 1 = safety closed | BIT | Read | ||||
| CO | 35doc 36 | STW bit 3: Alarm | 1 = alarm | BIT | Read | ||||
| CO | 39doc 40 | STW bit 7: Warning | 1 = warning | BIT | Read | ||||
| CO | 40doc 41 | STW bit 8: At reference | 1 = at reference | BIT | Read | ||||
| CO | 41doc 42 | STW bit 9: Hand / auto mode | 0 = hand mode, 1 = auto mode | BIT | Read | ||||
| CO | 42doc 43 | STW bit 10: In frequency range | 1 = in frequency range | BIT | Read | ||||
| CO | 43doc 44 | STW bit 11: Running | 0 = stopped, 1 = running | BIT | Read | ||||
| CO | 45doc 46 | STW bit 13: Voltage warning | 1 = voltage warning | BIT | Read | ||||
| CO | 46doc 47 | STW bit 14: Current limit | 1 = in current limit | BIT | Read | ||||
| CO | 47doc 48 | STW bit 15: Thermal warning | 1 = thermal warning | BIT | Read | ||||
| CO | 64doc 65 | Parameter write control | 0 = parameter writes go to RAM only, 1 = RAM and EEPROM. | BIT | Read/write | 0 = RAM only; 1 = RAM and EEPROM | |||
| HR | 6doc 7 | Last fault code | Fault code from the parameter database. | UINT16 | Read | ||||
| HR | 7doc 8 | Last error register | Address of the register where the last error occurred. | UINT16 | Read | ||||
| HR | 8doc 9 | Index pointer | Sub-index for array parameters. | UINT16 | Read/write | ||||
| HR | 3019doc 3020 | 3-02 Minimum Reference | In the reference/feedback unit. | INT32 | ABCD | × 0.001 | Read/write | ||
| HR | 3029doc 3030 | 3-03 Maximum Reference | In the reference/feedback unit. | INT32 | ABCD | × 0.001 | Read/write | ||
| HR | 3409doc 3410 | 3-41 Ramp 1 Ramp Up Time | UINT32 | ABCD | × 0.01 | s | Read/write | ||
| HR | 3419doc 3420 | 3-42 Ramp 1 Ramp Down Time | UINT32 | ABCD | × 0.01 | s | Read/write | ||
| HR | 4119doc 4120 | 4-12 Motor Speed Low Limit [Hz] | UINT16 | × 0.1 | Hz | Read/write | |||
| HR | 4139doc 4140 | 4-14 Motor Speed High Limit [Hz] | UINT16 | × 0.1 | Hz | Read/write | |||
| HR | 4189doc 4190 | 4-19 Max Output Frequency | UINT16 | × 0.1 | Hz | Read/write | |||
| HR | 8009doc 8010 | 8-01 Control Site | Uint8 in one register; default digital and control word. | UINT16 | Read/write | ||||
| HR | 8019doc 8020 | 8-02 Control Source | Uint8 in one register; default FC port. | UINT16 | Read/write | ||||
| HR | 8029doc 8030 | 8-03 Control Timeout Time | 0.1-200 s, default 20 s. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 8039doc 8040 | 8-04 Control Timeout Function | UINT16 | Read/write | 0 = Off; 1 = Freeze output; 2 = Stop; 3 = Jogging; 4 = Max. speed; 5 = Stop and trip; 20 = N2 override release | ||||
| HR | 8299doc 8300 | 8-30 Protocol | UINT16 | Read/write | 0 = FC; 2 = Modbus RTU | ||||
| HR | 8309doc 8310 | 8-31 Address | 1-247 for Modbus; default 1. | UINT16 | Read/write | ||||
| HR | 8319doc 8320 | 8-32 Baud Rate | UINT16 | Read/write | 0 = 2400; 1 = 4800; 2 = 9600; 3 = 19200; 4 = 38400; 5 = 57600; 6 = 76800; 7 = 115200 | ||||
| HR | 8329doc 8330 | 8-33 Parity / Stop Bits | UINT16 | Read/write | 0 = Even parity, 1 stop bit; 1 = Odd parity, 1 stop bit; 2 = No parity, 1 stop bit; 3 = No parity, 2 stop bits | ||||
| HR | 8349doc 8350 | 8-35 Minimum Response Delay | UINT16 | × 0.001 | s | Read/write | |||
| HR | 14999doc 15000 | 15-00 Operating hours | UINT32 | ABCD | h | Read | |||
| HR | 15009doc 15010 | 15-01 Running Hours | UINT32 | ABCD | h | Read | |||
| HR | 15029doc 15030 | 15-03 Power Up's | UINT32 | ABCD | Read | ||||
| HR | 15039doc 15040 | 15-04 Over Temp's | UINT16 | Read | |||||
| HR | 15049doc 15050 | 15-05 Over Volt's | UINT16 | Read | |||||
| HR | 15299doc 15300 | 15-30 Alarm Log: Error Code | Array (index via register 9); uint8 in one register. | UINT16 | Read | ||||
| HR | 15999doc 16000 | 16-00 Control Word | UINT16 | Read | |||||
| HR | 16009doc 16010 | 16-01 Reference [Unit] | INT32 | ABCD | × 0.001 | Read | |||
| HR | 16019doc 16020 | 16-02 Reference [%] | INT16 | × 0.1 | % | Read | |||
| HR | 16029doc 16030 | 16-03 Status Word | UINT16 | Read | |||||
| HR | 16049doc 16050 | 16-05 Main Actual Value [%] | INT16 | × 0.01 | % | Read | |||
| HR | 16099doc 16100 | 16-10 Power [kW] | UINT32 | ABCD | × 0.001 | kW | Read | ||
| HR | 16119doc 16120 | 16-12 Motor Voltage | UINT32 | ABCD | × 0.1 | V | Read | ||
| HR | 16129doc 16130 | 16-13 Frequency | UINT32 | ABCD | × 0.1 | Hz | Read | ||
| HR | 16139doc 16140 | 16-14 Motor current | UINT16 | × 0.01 | A | Read | |||
| HR | 16149doc 16150 | 16-15 Frequency [%] | UINT16 | × 0.1 | % | Read | |||
| HR | 16159doc 16160 | 16-16 Torque [Nm] | INT32 | ABCD | × 0.1 | Nm | Read | ||
| HR | 16179doc 16180 | 16-18 Motor Thermal | Uint8 in one register. | UINT16 | % | Read | |||
| HR | 16219doc 16220 | 16-22 Torque [%] | INT16 | % | Read | ||||
| HR | 16299doc 16300 | 16-30 DC Link Voltage | UINT32 | ABCD | V | Read | |||
| HR | 16349doc 16350 | 16-35 Inverter Thermal | Uint8 in one register. | UINT16 | % | Read | |||
| HR | 16359doc 16360 | 16-36 Inv. Nom. Current | UINT16 | × 0.01 | A | Read | |||
| HR | 16369doc 16370 | 16-37 Inv. Max. Current | UINT16 | × 0.01 | A | Read | |||
| HR | 16499doc 16500 | 16-50 External Reference | INT16 | × 0.1 | % | Read | |||
| HR | 16519doc 16520 | 16-52 Feedback [Unit] | INT32 | ABCD | × 0.001 | Read | |||
| HR | 16599doc 16600 | 16-60 Digital Input | UINT16 | Read | |||||
| HR | 16859doc 16860 | 16-86 FC Port REF 1 | INT16 | Read | |||||
| HR | 16899doc 16900 | 16-90 Alarm Word | UINT32 | ABCD | Read | ||||
| HR | 16909doc 16910 | 16-91 Alarm Word 2 | UINT32 | ABCD | Read | ||||
| HR | 16919doc 16920 | 16-92 Warning Word | UINT32 | ABCD | Read | ||||
| HR | 16929doc 16930 | 16-93 Warning Word 2 | UINT32 | ABCD | Read | ||||
| HR | 16939doc 16940 | 16-94 Ext. Status Word | UINT32 | ABCD | Read |
Notes on this map
- Parameter data (conversion index, data type) come from VLT Compressor Drive CDS 803 Programming Guide MG18P202, https://files.danfoss.com/download/Drives/MG18P202.pdf. Scale = 10^conversion index; the hour counters carry index 74 (factor 3600, i.e. hours expressed in seconds), so one count is one hour.
- 32-bit values are high word first: the design guide reads 3-03 at registers 3030/3031 and gets 0016 E360 hex = 1500000 (1500.000 with conversion index -3).
- 8-bit parameters (Uint8) are read and written as one 16-bit register. 16-34 Heatsink Temp (Int8) is left out because the sign extension in the 16-bit register is not stated.
- Coils 17-32 (speed reference) and 49-64 (output frequency / feedback) carry 16-bit words bit by bit; they are not listed. REF/MAV use 4000 hex = 100 % of the reference range (two's complement for negative).
- Alarm, warning and extended status words (16-90..16-94) are listed as raw UINT32; bit meanings are in the programming guide.
- The two guides cover different software versions (1.20 and 2.0); check 15-43 Software Version on site.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Danfoss VLT Compressor Drive CDS 803 (Modbus RTU)
What Modbus registers does the Danfoss VLT Compressor Drive CDS 803 (Modbus RTU) have?
This map lists 79 registers: 28 coils, 51 holding registers. 33 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Danfoss VLT Compressor Drive CDS 803 (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers derived from parameter numbers. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The design guide states coil 1 is sent as 0000 and holding register 40001 as 0000. A parameter's register is 10 x its parameter number (3-03 -> 3030), sent minus 1: the guide's example reads 3-03 at start address 0x0BD5 (3029). Coils are 1-based too (coil 65 is sent as 64).
What byte order does the Danfoss VLT Compressor Drive CDS 803 (Modbus RTU) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Danfoss VLT Compressor Drive CDS 803 (Modbus RTU)?
Start with CO 6 CTW bit 6: Ramp stop / start (CTW bit 6: ramp stop / start); CO 10 CTW bit 10: Data valid (CTW bit 10: data valid); CO 43 STW bit 11: Running (STW: running); HR 16129 16-13 Frequency (16-13 Frequency, 0.1 Hz); HR 16139 16-14 Motor current (16-14 Motor current, 0.01 A); HR 16099 16-10 Power [kW] (16-10 Power, 0.001 kW); HR 16899 16-90 Alarm Word (16-90 Alarm word).
How do I enable Modbus control of the Danfoss VLT Compressor Drive CDS 803 (Modbus RTU)?
8-30 Protocol = [2] Modbus RTU, 8-31 Address (1-247), 8-32 Baud Rate, 8-33 Parity/Stop Bits. 8-01 Control Site chooses digital inputs and/or control word; 8-02 Control Source must be FC Port; 8-50..8-56 decide how bus bits combine with digital inputs (most default to Logic OR).
What happens when the Danfoss VLT Compressor Drive CDS 803 (Modbus RTU) loses Modbus communication?
8-03 Control Timeout Time (0.1-200 s, default 20 s) and 8-04 Control Timeout Function (default Off; Freeze output, Stop, Jogging, Max. speed, Stop and trip, N2 override release) act when the control word is not updated in time.
Where is the official Danfoss VLT Compressor Drive CDS 803 (Modbus RTU) Modbus documentation?
The source is VLT Compressor Drive CDS 803 Design Guide (chapter 7 RS485 Installation and Set-up) (MG18N202), revision 2015-12, published free by Danfoss at https://files.danfoss.com/download/Drives/MG18N202.pdf.
More Danfoss Modbus register maps
- Thermostat / heating controller (district heating and HVAC)
Danfoss ECL Comfort 210 / 296 / 310 heating controller (Modbus RTU / TCP)
ECL Comfort 210, 296 and 310 controllers (and B versions) with any application key; many parameters depend on the loaded application.
Also known as: ECL Comfort 210, ECL Comfort 296, ECL Comfort 310, ECL Comfort 210B, ECL Comfort 310B, 087H3020, 087H3024, 087H3030, 087H3034, 087H3040, 087H3044, 087H3050, 087H3054 - Sensor (refrigerant / toxic gas detector)
Danfoss Gas Detection Units GD Basic / Premium / Heavy Duty (Modbus RTU)
Danfoss GD Basic, Premium and Heavy Duty gas detection units on their own RS-485 Modbus port (Part 2 of the guide). The gas detection controller's X-bus map in Part 1 is not included.
Also known as: GDA, GDC, GDHC, GDHF, GDH, GD Basic, GD Premium, GD Heavy Duty - Variable frequency drive
Danfoss iC2-Micro frequency converter (Modbus RTU)
Danfoss iC2-Micro frequency converters using the built-in RS-485 port with P 10.1.1 Protocol = [2] Modbus RTU and the FC control profile; Application Guide AB413939445838en-000401.
Also known as: iC2-Micro, iC2 Micro, Danfoss iC2 - Sensor / controller (CO2 condensing unit gateway)
Danfoss Optyma iCO2 gateway (OP-MPAM015 / OP-MPAM005)
Danfoss Optyma iCO2 CO2 condensing units (4.6 kW MT and 20 kW MT / 10 kW LT) through their Modbus gateway, software 1.0x.
Also known as: OP-MPAM015, OP-MPAM005, Optyma iCO2 4.6 kW MT, Optyma iCO2 20 kW MT / 10 kW LT - Variable frequency drive
Danfoss VLT AQUA Drive FC 202 (Modbus RTU)
VLT AQUA Drive FC 202 using the built-in RS-485 (FC) port with 8-30 Protocol = Modbus RTU and the FC control profile; parameter data checked against the software 5.4X programming guide.
Also known as: VLT AQUA Drive, FC202, FC-202, AQUA Drive FC 202 - Variable frequency drive
Danfoss VLT AutomationDrive FC 301/302 (Modbus RTU)
VLT AutomationDrive FC 301 and FC 302 (0.25-75 kW design guide; same scheme across sizes) using the built-in RS-485 (FC) port with 8-30 Protocol = Modbus RTU and the FC control profile; parameter data checked against the software 9.5x / 48.96 programming guide.
Also known as: VLT AutomationDrive, FC 301, FC301, FC302, FC-302, FC-301, FC 300 - Variable frequency drive
Danfoss VLT AutomationDrive FC 360 (Modbus RTU)
VLT AutomationDrive FC 360 on its built-in RS-485 port with 8-30 Protocol = Modbus RTU and the FC control profile.
Also known as: FC360, FC-360, VLT AutomationDrive FC 360 - Variable frequency drive (HVAC fans and pumps)
Danfoss VLT HVAC Basic Drive FC 101 (Modbus RTU)
VLT HVAC Basic Drive FC 101 on its built-in RS-485 port with 8-30 Protocol = Modbus RTU and the FC control profile.
Also known as: FC101, FC-101, VLT HVAC Basic Drive FC 101, VLT HVAC Basic - Variable frequency drive
Danfoss VLT HVAC Drive FC 102 (Modbus RTU)
VLT HVAC Drive FC 102 using the built-in RS-485 (FC) port with 8-30 Protocol = Modbus RTU and the FC control profile; parameter scaling checked against the software 7.61 programming guide.
Also known as: VLT HVAC Drive, FC102, FC-102 - Variable frequency drive
Danfoss VLT Micro Drive FC 51 (Modbus RTU)
VLT Micro Drive FC 51 on the built-in RS-485 port with 8-30 = Modbus, software 3.1x; registers per design guide MG02K402 and parameter data per programming guide MG02C702.
Also known as: FC 51, FC51, VLT Micro Drive, VLT Micro Drive FC 51 - Variable frequency drive
Danfoss VLT Midi Drive FC 280 (Modbus RTU)
VLT Midi Drive FC 280 on its built-in RS-485 port with 8-30 Protocol = Modbus RTU and the FC control profile.
Also known as: FC280, FC-280, VLT Midi Drive FC 280, VLT Midi Drive
Other variable frequency drives register maps
- Variable frequency drive
Eaton PowerXL DA1 variable frequency drive (Modbus RTU)
Eaton PowerXL DA1 per the Modbus RTU communication manual MN040018EN, edition 12/22.
Also known as: DA1, PowerXL DA1, DA1-12, DA1-32, DA1-34, DA1-35 - Variable frequency drive
Hitachi SJ-P1 series inverter (Modbus RTU, firmware Ver. 2.00)
Hitachi SJ-P1 inverters on the built-in RS485 port in Modbus-RTU mode, register layout of firmware Ver. 2.00 (User's Guide NT251BX-2, Rev. 6).
Also known as: SJ-P1, P1-xxxxx-L, P1-xxxxx-H - Variable frequency drive
Invertek Drives Optidrive Eco (built-in Modbus RTU)
Invertek Optidrive Eco drives using the built-in RJ45 RS-485 Modbus RTU port, per user guide 82-HEMAN-IN V3.13.
Also known as: ODV-3, Optidrive Eco HVAC, Optidrive Eco IP20, Optidrive Eco IP55, Optidrive Eco IP66 - Variable frequency drive
INVT Goodrive300 (GD300) vector VFD
INVT Goodrive300 open-loop vector drives using the built-in RS-485 Modbus RTU port, per the GD300 VFD manual V3.6 (chapter 10).
Also known as: GD300, Goodrive300, GD300 vector VFD - Variable frequency drive
Lenze MCH Series HVAC drive (Modbus RTU)
Lenze AC Tech MCH Series drives, software 213-070 rev 00 (parameter configuration 148); reference guide RG-MHMOD.
Also known as: MCH, Lenze AC Tech MCH, RG-MHMOD - Variable frequency drive
Mitsubishi Electric FR-D700 compact inverter (PU connector, Modbus RTU)
FR-D700 series (FR-D720/D740/D720S/D710W) using the PU connector with Pr.549 = 1; Instruction Manual (Applied) revision H.
Also known as: FR-D720, FR-D740, FR-D720S, FR-D710W
All variable frequency drives Modbus register maps →
Source: VLT Compressor Drive CDS 803 Design Guide (chapter 7 RS485 Installation and Set-up) · MG18N202 · rev. 2015-12. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.