Thermostat / heating controller (district heating and HVAC) · Modbus register map

Danfoss ECL Comfort 210 / 296 / 310 heating controller (Modbus RTU / TCP) Modbus register map

Updated 17 November 2026

Short answer

The ECL Comfort 210/296/310 is Danfoss's electronic heating controller for district heating substations, heating circuits and DHW, run by a plug-in application key. Every parameter has a parameter number (PNU), and the Modbus register is the PNU minus one. This map covers circuit modes and status, sensor temperatures, the main room and DHW setpoints, alarms, output status and override, the clock, communication settings and M-bus energy meter 1.

This page lists 131 Modbus registers for the Danfoss ECL Comfort 210 / 296 / 310 heating controller (Modbus RTU / TCP) — 40 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Danfoss’s own free documentation (linked below) and checked against it.

Manufacturer
Danfoss
Model
ECL Comfort 210 / 296 / 310 heating controller (Modbus RTU / TCP)
Equipment type
Thermostat / heating controller (district heating and HVAC)
Registers
131 (40 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
1
Default serial
38400 baud, 8E1
TCP port
502
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
ABCD high word first (big-endian)
Firmware
Energy meter data from controller software 1.10; 8-state circuit status from 1.43
Also known as
ECL Comfort 210, ECL Comfort 296, ECL Comfort 310, ECL Comfort 210B, ECL Comfort 310B, 087H3020, 087H3024, 087H3030, 087H3034, 087H3040, 087H3044, 087H3050, 087H3054
Source document
ECL Comfort 210 / 296 / 310, communication description · VI.LG.V5.02 (AQ074886472234en-010502) · rev. 2018-08
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Danfoss ECL Comfort 210 / 296 / 310 heating controller (Modbus RTU / TCP)

Integration in brief

Read circuit status (PNU 4211, wire 4210), sensor temperatures (PNU 10201 and up, wire 10200 and up, value/100) and the comfort setpoint (PNU 11180, wire 11179, value/10) with function 03 or 04. Change the mode by writing PNU 4201 (wire 4200) and setpoints with function 06 only.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 10200Raw sensor S1INT16Sensor S1 (meaning depends on the application key)Read
HR 10202Raw sensor S3INT16Sensor S3 (meaning depends on the application key)Read
HR 4200Circuit 1 modeUINT16Circuit 1 mode (write to change)Read/write
HR 4210Circuit 1 statusUINT16Circuit 1 statusRead
HR 11179Circuit 1 comfort room setpointINT16Circuit 1 comfort room setpointRead/write
HR 1024Alarm field 1 (alarms 1-16)BITMAP16Alarm bits 1-16Read
HR 6013Energy meter 1 accumulated energyUINT32 ABCDEnergy meter 1 accumulated energyRead

Enable Modbus control & writes

No enable step: Modbus is always active. Set the Modbus address (PNU 38) and RS-485 baud rate (PNU 39). All three models have the USB service port and RS-485 Modbus RTU (galvanically isolated on the 296/310); Modbus/TCP is on the ECL 296/310 only.

Byte order & addressing

Network setup

Watch out for

Danfoss ECL Comfort 210 / 296 / 310 heating controller (Modbus RTU / TCP) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

131 of 131 shown
Danfoss ECL Comfort 210 / 296 / 310 heating controller (Modbus RTU / TCP) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 1System commandWrite 2 to reset the internal ECL log.UINT16Write2 = Reset internal ECL log
HR7doc 8Software build numberUINT16Read
HR18doc 19Code numberProduct code; prefix 087H (e.g. 3040 = 087H3040).UINT16Read
HR33doc 34Hardware revisionHigh byte = letter (0x41 = A), low byte = number.UINT16Read
HR34doc 35Software versionHigh byte = major, low byte = minor (0x0101 = 1.01).UINT16Read
HR37doc 38Modbus address1-247; takes effect immediately.UINT16Read/write
HR38doc 39RS-485 baud rateTakes effect immediately.UINT16Read/write9 = 9600; 19 = 19200; 38 = 38400
HR257doc 258IP address typeECL 296/310 Ethernet.UINT16Read/write0 = DHCP; 1 = Static IP
HR277doc 278IP address octet 1UINT16Read/write
HR278doc 279IP address octet 2UINT16Read/write
HR279doc 280IP address octet 3UINT16Read/write
HR280doc 281IP address octet 4UINT16Read/write
HR1023doc 1024Alarm field 2 (alarms 17-32)Bitmask of alarms 17-32 (non-zero = an alarm in that range).UINT16Read
HR1024doc 1025Alarm field 1 (alarms 1-16)Bit 0 = alarm number 1; meaning depends on the application.BITMAP16Readbit 0 = Alarm 1; bit 1 = Alarm 2; bit 2 = Alarm 3; bit 3 = Alarm 4; bit 4 = Alarm 5; bit 5 = Alarm 6; bit 6 = Alarm 7; bit 7 = Alarm 8; bit 8 = Alarm 9; bit 9 = Alarm 10; bit 10 = Alarm 11; bit 11 = Alarm 12; bit 12 = Alarm 13; bit 13 = Alarm 14; bit 14 = Alarm 15; bit 15 = Alarm 16
HR1039doc 1040Alarm ID 1 statusNon-zero means alarm ID 1 is active.UINT16Read
HR1040doc 1041Alarm ID 2 statusNon-zero means alarm ID 2 is active.UINT16Read
HR1041doc 1042Alarm ID 3 statusNon-zero means alarm ID 3 is active.UINT16Read
HR1042doc 1043Alarm ID 4 statusNon-zero means alarm ID 4 is active.UINT16Read
HR1043doc 1044Alarm ID 5 statusNon-zero means alarm ID 5 is active.UINT16Read
HR1044doc 1045Alarm ID 6 statusNon-zero means alarm ID 6 is active.UINT16Read
HR1045doc 1046Alarm ID 7 statusNon-zero means alarm ID 7 is active.UINT16Read
HR1046doc 1047Alarm ID 8 statusNon-zero means alarm ID 8 is active.UINT16Read
HR1047doc 1048Alarm ID 9 statusNon-zero means alarm ID 9 is active.UINT16Read
HR1048doc 1049Alarm ID 10 statusNon-zero means alarm ID 10 is active.UINT16Read
HR1049doc 1050Alarm ID 11 statusNon-zero means alarm ID 11 is active.UINT16Read
HR1050doc 1051Alarm ID 12 statusNon-zero means alarm ID 12 is active.UINT16Read
HR1051doc 1052Alarm ID 13 statusNon-zero means alarm ID 13 is active.UINT16Read
HR1052doc 1053Alarm ID 14 statusNon-zero means alarm ID 14 is active.UINT16Read
HR1053doc 1054Alarm ID 15 statusNon-zero means alarm ID 15 is active.UINT16Read
HR1054doc 1055Alarm ID 16 statusNon-zero means alarm ID 16 is active.UINT16Read
HR1055doc 1056Alarm ID 17 statusNon-zero means alarm ID 17 is active.UINT16Read
HR1056doc 1057Alarm ID 18 statusNon-zero means alarm ID 18 is active.UINT16Read
HR1057doc 1058Alarm ID 19 statusNon-zero means alarm ID 19 is active.UINT16Read
HR1058doc 1059Alarm ID 20 statusNon-zero means alarm ID 20 is active.UINT16Read
HR1059doc 1060Alarm ID 21 statusNon-zero means alarm ID 21 is active.UINT16Read
HR1060doc 1061Alarm ID 22 statusNon-zero means alarm ID 22 is active.UINT16Read
HR1061doc 1062Alarm ID 23 statusNon-zero means alarm ID 23 is active.UINT16Read
HR1062doc 1063Alarm ID 24 statusNon-zero means alarm ID 24 is active.UINT16Read
HR1063doc 1064Alarm ID 25 statusNon-zero means alarm ID 25 is active.UINT16Read
HR1064doc 1065Alarm ID 26 statusNon-zero means alarm ID 26 is active.UINT16Read
HR1065doc 1066Alarm ID 27 statusNon-zero means alarm ID 27 is active.UINT16Read
HR1066doc 1067Alarm ID 28 statusNon-zero means alarm ID 28 is active.UINT16Read
HR1067doc 1068Alarm ID 29 statusNon-zero means alarm ID 29 is active.UINT16Read
HR1068doc 1069Alarm ID 30 statusNon-zero means alarm ID 30 is active.UINT16Read
HR1069doc 1070Alarm ID 31 statusNon-zero means alarm ID 31 is active.UINT16Read
HR1070doc 1071Alarm ID 32 statusNon-zero means alarm ID 32 is active.UINT16Read
HR2048doc 2049RS-485 biasBus biasing in the controller.UINT16Read/write0 = Disabled; 1 = Enabled
HR2059doc 2060Application prefixCharacter code, 65 = A.UINT16Read
HR2060doc 2061Application type numbere.g. 214 for A214.UINT16Read
HR2061doc 2062Application sub numberUINT16Read
HR2062doc 2063Application versionHigh byte = major, low byte = minor.UINT16Read
HR2096doc 2097WinkFlash display backlight for this many seconds; 0 stops.UINT16sRead/write
HR2098doc 2099Production dateHigh byte = year minus 2000, low byte = week.UINT16Read
HR3999doc 4000Output status, triac 1Present value of the triac output.UINT16Read
HR4000doc 4001Output status, triac 2Present value of the triac output.UINT16Read
HR4001doc 4002Output status, triac 3Present value of the triac output.UINT16Read
HR4002doc 4003Output status, triac 4Present value of the triac output.UINT16Read
HR4003doc 4004Output status, triac 5Present value of the triac output.UINT16Read
HR4004doc 4005Output status, triac 6Present value of the triac output.UINT16Read
HR4005doc 4006Output status, relay 1Present value of the relay output.UINT16Read
HR4006doc 4007Output status, relay 2Present value of the relay output.UINT16Read
HR4007doc 4008Output status, relay 3Present value of the relay output.UINT16Read
HR4008doc 4009Output status, relay 4Present value of the relay output.UINT16Read
HR4009doc 4010Output status, relay 5Present value of the relay output.UINT16Read
HR4010doc 4011Output status, relay 6Present value of the relay output.UINT16Read
HR4015doc 4016Output status, ECA 32 AO 1Analog output of the ECA 32 module.UINT16× 0.1%Read
HR4016doc 4017Output status, ECA 32 AO 2Analog output of the ECA 32 module.UINT16× 0.1%Read
HR4017doc 4018Output status, ECA 32 AO 3Analog output of the ECA 32 module.UINT16× 0.1%Read
HR4019doc 4020Manual status, motorized valve 1Manual setting made on the display.UINT16Read0 = AUTO; 1 = STOP; 2 = CLOSE; 3 = OPEN
HR4025doc 4026Manual status, relay 1Manual setting made on the display.UINT16Read0 = AUTO; 1 = OFF; 2 = ON
HR4026doc 4027Manual status, relay 2Manual setting made on the display.UINT16Read0 = AUTO; 1 = OFF; 2 = ON
HR4027doc 4028Manual status, relay 3Manual setting made on the display.UINT16Read0 = AUTO; 1 = OFF; 2 = ON
HR4028doc 4029Manual status, relay 4Manual setting made on the display.UINT16Read0 = AUTO; 1 = OFF; 2 = ON
HR4029doc 4030Manual status, relay 5Manual setting made on the display.UINT16Read0 = AUTO; 1 = OFF; 2 = ON
HR4030doc 4031Manual status, relay 6Manual setting made on the display.UINT16Read0 = AUTO; 1 = OFF; 2 = ON
HR4059doc 4060Override, motorized valve 1 (triac 1)Output override for 3-point valve 1 when not in manual mode.UINT16Read/write0 = AUTO; 1 = STOP; 2 = CLOSE; 3 = OPEN
HR4065doc 4066Override, relay 1Output override for relay 1 when not in manual mode.UINT16Read/write0 = AUTO; 1 = OFF; 2 = ON
HR4066doc 4067Override, relay 2Output override for relay 2 when not in manual mode.UINT16Read/write0 = AUTO; 1 = OFF; 2 = ON
HR4067doc 4068Override, relay 3Output override for relay 3 when not in manual mode.UINT16Read/write0 = AUTO; 1 = OFF; 2 = ON
HR4068doc 4069Override, relay 4Output override for relay 4 when not in manual mode.UINT16Read/write0 = AUTO; 1 = OFF; 2 = ON
HR4069doc 4070Override, relay 5Output override for relay 5 when not in manual mode.UINT16Read/write0 = AUTO; 1 = OFF; 2 = ON
HR4070doc 4071Override, relay 6Output override for relay 6 when not in manual mode.UINT16Read/write0 = AUTO; 1 = OFF; 2 = ON
HR4200doc 4201Circuit 1 modeOperating mode; manual mode on one circuit applies to all.UINT16Read/write0 = Manual operation; 1 = Scheduled operation; 2 = Constant comfort temperature; 3 = Constant setback temperature; 4 = Frost protection/standby; 5 = Active cooling (A232 only)
HR4201doc 4202Circuit 2 modeOperating mode; manual mode on one circuit applies to all.UINT16Read/write0 = Manual operation; 1 = Scheduled operation; 2 = Constant comfort temperature; 3 = Constant setback temperature; 4 = Frost protection/standby; 5 = Active cooling (A232 only)
HR4202doc 4203Circuit 3 modeOperating mode; manual mode on one circuit applies to all.UINT16Read/write0 = Manual operation; 1 = Scheduled operation; 2 = Constant comfort temperature; 3 = Constant setback temperature; 4 = Frost protection/standby; 5 = Active cooling (A232 only)
HR4203doc 4204Circuit 4 modeOperating mode; manual mode on one circuit applies to all.UINT16Read/write0 = Manual operation; 1 = Scheduled operation; 2 = Constant comfort temperature; 3 = Constant setback temperature; 4 = Frost protection/standby; 5 = Active cooling (A232 only)
HR4210doc 4211Circuit 1 statusCurrent operating status of the circuit.UINT16Read0 = Setback; 1 = Pre-comfort; 2 = Comfort; 3 = Pre-setback; 4 = Holiday constant comfort temperature; 5 = Holiday 7-23h comfort temperature; 6 = Holiday constant setback temperature; 7 = Holiday frost protection/standby
HR4211doc 4212Circuit 2 statusCurrent operating status of the circuit.UINT16Read0 = Setback; 1 = Pre-comfort; 2 = Comfort; 3 = Pre-setback; 4 = Holiday constant comfort temperature; 5 = Holiday 7-23h comfort temperature; 6 = Holiday constant setback temperature; 7 = Holiday frost protection/standby
HR4212doc 4213Circuit 3 statusCurrent operating status of the circuit.UINT16Read0 = Setback; 1 = Pre-comfort; 2 = Comfort; 3 = Pre-setback; 4 = Holiday constant comfort temperature; 5 = Holiday 7-23h comfort temperature; 6 = Holiday constant setback temperature; 7 = Holiday frost protection/standby
HR4213doc 4214Circuit 4 statusCurrent operating status of the circuit.UINT16Read0 = Setback; 1 = Pre-comfort; 2 = Comfort; 3 = Pre-setback; 4 = Holiday constant comfort temperature; 5 = Holiday 7-23h comfort temperature; 6 = Holiday constant setback temperature; 7 = Holiday frost protection/standby
HR5996doc 5997M-bus baud rateUINT16Read/write0 = 300; 1 = 600; 2 = 1200; 3 = 2400
HR5997doc 5998M-bus commandStart a meter scan or re-initialize.UINT16Read/write0 = None; 1 = Init; 2 = Scan for energy meter
HR5998doc 5999M-bus stateUINT16Read0 = Reset; 1 = Init; 2 = Scanning; 3 = Idle
HR5999doc 6000Energy meter 1 M-bus addressM-bus primary address 0-254 (251-254 special; 254 only with one meter) or 255.UINT16Read/write
HR6000doc 6001Energy meter 1 typeData set read from the meter; changing it resets values.UINT16Read/write0 = Generic small data set, small units; 1 = Generic small data set, large units; 2 = Generic large data set, small units; 3 = Generic large data set, large units; 4 = Volume and energy only
HR6001doc 6002Energy meter 1 scan timePoll interval.UINT16sRead/write
HR6002doc 6003Energy meter 1 ID / serialUINT32ABCDRead
HR6005doc 6006Energy meter 1 flow temperatureTypes 0-3.INT16× 0.01°CRead
HR6006doc 6007Energy meter 1 return temperatureTypes 0-3.INT16× 0.01°CRead
HR6007doc 6008Energy meter 1 flowTypes 0-3.UINT32ABCD× 0.1l/hRead
HR6009doc 6010Energy meter 1 powerTypes 0-3.UINT32ABCD× 0.1kWRead
HR6011doc 6012Energy meter 1 accumulated volumeTypes 0-3.UINT32ABCD× 0.1m³Read
HR6013doc 6014Energy meter 1 accumulated energykWh for types 0 and 2; 0.1 MWh units for types 1 and 3.UINT32ABCD× 0.1kWhRead
HR10197doc 10198Automatic summer timeEU summer-time rules.UINT16Read/write0 = Disabled; 1 = Enabled
HR10200doc 10201Raw sensor S1Temperature at sensor input S1.INT16× 0.01°CRead
HR10201doc 10202Raw sensor S2Temperature at sensor input S2.INT16× 0.01°CRead
HR10202doc 10203Raw sensor S3Temperature at sensor input S3.INT16× 0.01°CRead
HR10203doc 10204Raw sensor S4Temperature at sensor input S4.INT16× 0.01°CRead
HR10204doc 10205Raw sensor S5Temperature at sensor input S5.INT16× 0.01°CRead
HR10205doc 10206Raw sensor S6Temperature at sensor input S6.INT16× 0.01°CRead
HR10206doc 10207Raw sensor S7Temperature at sensor input S7.INT16× 0.01°CRead
HR10207doc 10208Raw sensor S8Temperature at sensor input S8.INT16× 0.01°CRead
HR10208doc 10209Raw sensor S9Temperature at sensor input S9.INT16× 0.01°CRead
HR10209doc 10210Raw sensor S10Temperature at sensor input S10.INT16× 0.01°CRead
HR10210doc 10211Raw sensor S11Temperature at sensor input S11.INT16× 0.01°CRead
HR10211doc 10212Raw sensor S12Temperature at sensor input S12.INT16× 0.01°CRead
HR10212doc 10213ECA 30 room A, room temperatureRoom temperature from an ECA 30/31 set as HMI A; reads 19200 if none is fitted.INT16× 0.01°CRead
HR11174doc 11175Circuit 1 heat curve slopeSlope of the heat curve; writable in some applications.UINT16× 0.1Read
HR11179doc 11180Circuit 1 comfort room setpointINT16× 0.1°CRead/write
HR11180doc 11181Circuit 1 saving room setpointINT16× 0.1°CRead/write
HR11189doc 11190Circuit 1 comfort DHW setpointUsed when circuit 1 is a DHW circuit.INT16× 0.1°CRead/write
HR11190doc 11191Circuit 1 saving DHW setpointUsed when circuit 1 is a DHW circuit.INT16× 0.1°CRead/write
HR12179doc 12180Circuit 2 comfort room setpointCircuit 2 = circuit 1 PNU + 1000.INT16× 0.1°CRead/write
HR12180doc 12181Circuit 2 saving room setpointINT16× 0.1°CRead/write
HR12189doc 12190Circuit 2 comfort DHW setpointDHW setpoint when circuit 2 is DHW (e.g. A266.1).INT16× 0.1°CRead/write
HR12190doc 12191Circuit 2 saving DHW setpointINT16× 0.1°CRead/write
HR64044doc 64045Clock hour0-23.UINT16Read/write
HR64045doc 64046Clock minute0-59; seconds reset to 0 on write.UINT16Read/write
HR64046doc 64047Date day1-31.UINT16Read/write
HR64047doc 64048Date month1-12.UINT16Read/write
HR64048doc 64049Date year2009-2099.UINT16Read/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Danfoss ECL Comfort 210 / 296 / 310 heating controller (Modbus RTU / TCP)

What Modbus registers does the Danfoss ECL Comfort 210 / 296 / 310 heating controller (Modbus RTU / TCP) have?

This map lists 131 registers: 131 holding registers. 40 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Danfoss ECL Comfort 210 / 296 / 310 heating controller (Modbus RTU / TCP) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide lists parameter numbers (PNU) and states the register address is PNU-1; its frame example reads comfort setpoint PNU 11180 at 0x2BAB (11179). So request PNU minus 1 on the wire.

What byte order does the Danfoss ECL Comfort 210 / 296 / 310 heating controller (Modbus RTU / TCP) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Danfoss ECL Comfort 210 / 296 / 310 heating controller (Modbus RTU / TCP)?

Start with HR 10200 Raw sensor S1 (Sensor S1 (meaning depends on the application key)); HR 10202 Raw sensor S3 (Sensor S3 (meaning depends on the application key)); HR 4200 Circuit 1 mode (Circuit 1 mode (write to change)); HR 4210 Circuit 1 status (Circuit 1 status); HR 11179 Circuit 1 comfort room setpoint (Circuit 1 comfort room setpoint); HR 1024 Alarm field 1 (alarms 1-16) (Alarm bits 1-16); HR 6013 Energy meter 1 accumulated energy (Energy meter 1 accumulated energy).

How do I enable Modbus control of the Danfoss ECL Comfort 210 / 296 / 310 heating controller (Modbus RTU / TCP)?

No enable step: Modbus is always active. Set the Modbus address (PNU 38) and RS-485 baud rate (PNU 39). All three models have the USB service port and RS-485 Modbus RTU (galvanically isolated on the 296/310); Modbus/TCP is on the ECL 296/310 only.

Where is the official Danfoss ECL Comfort 210 / 296 / 310 heating controller (Modbus RTU / TCP) Modbus documentation?

The source is ECL Comfort 210 / 296 / 310, communication description (VI.LG.V5.02 (AQ074886472234en-010502)), revision 2018-08, published free by Danfoss at https://assets.danfoss.com/documents/63852/AQ074886472234en-010502.pdf.

More Danfoss Modbus register maps

Other hvac equipment register maps

All hvac equipment Modbus register maps →

Source: ECL Comfort 210 / 296 / 310, communication description · VI.LG.V5.02 (AQ074886472234en-010502) · rev. 2018-08. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.