Thermostat / heating controller (district heating and HVAC) · Modbus register map
Danfoss ECL Comfort 210 / 296 / 310 heating controller (Modbus RTU / TCP) Modbus register map
Updated 17 November 2026
The ECL Comfort 210/296/310 is Danfoss's electronic heating controller for district heating substations, heating circuits and DHW, run by a plug-in application key. Every parameter has a parameter number (PNU), and the Modbus register is the PNU minus one. This map covers circuit modes and status, sensor temperatures, the main room and DHW setpoints, alarms, output status and override, the clock, communication settings and M-bus energy meter 1.
This page lists 131 Modbus registers for the Danfoss ECL Comfort 210 / 296 / 310 heating controller (Modbus RTU / TCP) — 40 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Danfoss’s own free documentation (linked below) and checked against it.
- Manufacturer
- Danfoss
- Model
- ECL Comfort 210 / 296 / 310 heating controller (Modbus RTU / TCP)
- Registers
- 131 (40 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- 1
- Default serial
- 38400 baud, 8E1
- TCP port
- 502
- Documented addressing
- 1-based (subtract 1 for the wire address)
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- Energy meter data from controller software 1.10; 8-state circuit status from 1.43
- Also known as
- ECL Comfort 210, ECL Comfort 296, ECL Comfort 310, ECL Comfort 210B, ECL Comfort 310B, 087H3020, 087H3024, 087H3030, 087H3034, 087H3040, 087H3044, 087H3050, 087H3054
Integration notes: Danfoss ECL Comfort 210 / 296 / 310 heating controller (Modbus RTU / TCP)
Read circuit status (PNU 4211, wire 4210), sensor temperatures (PNU 10201 and up, wire 10200 and up, value/100) and the comfort setpoint (PNU 11180, wire 11179, value/10) with function 03 or 04. Change the mode by writing PNU 4201 (wire 4200) and setpoints with function 06 only.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 10200 | Raw sensor S1 | INT16 | Sensor S1 (meaning depends on the application key) | Read |
| HR 10202 | Raw sensor S3 | INT16 | Sensor S3 (meaning depends on the application key) | Read |
| HR 4200 | Circuit 1 mode | UINT16 | Circuit 1 mode (write to change) | Read/write |
| HR 4210 | Circuit 1 status | UINT16 | Circuit 1 status | Read |
| HR 11179 | Circuit 1 comfort room setpoint | INT16 | Circuit 1 comfort room setpoint | Read/write |
| HR 1024 | Alarm field 1 (alarms 1-16) | BITMAP16 | Alarm bits 1-16 | Read |
| HR 6013 | Energy meter 1 accumulated energy | UINT32 ABCD | Energy meter 1 accumulated energy | Read |
Enable Modbus control & writes
No enable step: Modbus is always active. Set the Modbus address (PNU 38) and RS-485 baud rate (PNU 39). All three models have the USB service port and RS-485 Modbus RTU (galvanically isolated on the 296/310); Modbus/TCP is on the ECL 296/310 only.
Byte order & addressing
- Register = PNU - 1.
- Only FC03/FC04/FC06; no multi-register write.
- Address 254 is a service address for single-controller links (USB, TCP).
Network setup
- RS-485 default: address 1, 38400 baud, 8 data bits, Even parity, 1 stop bit.
- Bias is off by default (PNU 2049); Danfoss suggests biasing at the master.
- Modbus/TCP on port 502 (ECL 296/310).
Watch out for
- Baud and address changes take effect immediately, so you lose the link when you write them.
- Parameter availability and sensor meaning depend on the installed application key (e.g. A266.1); a non-existing PNU returns exception 2.
- Write the holiday mode after its start and end dates.
Danfoss ECL Comfort 210 / 296 / 310 heating controller (Modbus RTU / TCP) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 1 | System command | Write 2 to reset the internal ECL log. | UINT16 | Write | 2 = Reset internal ECL log | |||
| HR | 7doc 8 | Software build number | UINT16 | Read | |||||
| HR | 18doc 19 | Code number | Product code; prefix 087H (e.g. 3040 = 087H3040). | UINT16 | Read | ||||
| HR | 33doc 34 | Hardware revision | High byte = letter (0x41 = A), low byte = number. | UINT16 | Read | ||||
| HR | 34doc 35 | Software version | High byte = major, low byte = minor (0x0101 = 1.01). | UINT16 | Read | ||||
| HR | 37doc 38 | Modbus address | 1-247; takes effect immediately. | UINT16 | Read/write | ||||
| HR | 38doc 39 | RS-485 baud rate | Takes effect immediately. | UINT16 | Read/write | 9 = 9600; 19 = 19200; 38 = 38400 | |||
| HR | 257doc 258 | IP address type | ECL 296/310 Ethernet. | UINT16 | Read/write | 0 = DHCP; 1 = Static IP | |||
| HR | 277doc 278 | IP address octet 1 | UINT16 | Read/write | |||||
| HR | 278doc 279 | IP address octet 2 | UINT16 | Read/write | |||||
| HR | 279doc 280 | IP address octet 3 | UINT16 | Read/write | |||||
| HR | 280doc 281 | IP address octet 4 | UINT16 | Read/write | |||||
| HR | 1023doc 1024 | Alarm field 2 (alarms 17-32) | Bitmask of alarms 17-32 (non-zero = an alarm in that range). | UINT16 | Read | ||||
| HR | 1024doc 1025 | Alarm field 1 (alarms 1-16) | Bit 0 = alarm number 1; meaning depends on the application. | BITMAP16 | Read | bit 0 = Alarm 1; bit 1 = Alarm 2; bit 2 = Alarm 3; bit 3 = Alarm 4; bit 4 = Alarm 5; bit 5 = Alarm 6; bit 6 = Alarm 7; bit 7 = Alarm 8; bit 8 = Alarm 9; bit 9 = Alarm 10; bit 10 = Alarm 11; bit 11 = Alarm 12; bit 12 = Alarm 13; bit 13 = Alarm 14; bit 14 = Alarm 15; bit 15 = Alarm 16 | |||
| HR | 1039doc 1040 | Alarm ID 1 status | Non-zero means alarm ID 1 is active. | UINT16 | Read | ||||
| HR | 1040doc 1041 | Alarm ID 2 status | Non-zero means alarm ID 2 is active. | UINT16 | Read | ||||
| HR | 1041doc 1042 | Alarm ID 3 status | Non-zero means alarm ID 3 is active. | UINT16 | Read | ||||
| HR | 1042doc 1043 | Alarm ID 4 status | Non-zero means alarm ID 4 is active. | UINT16 | Read | ||||
| HR | 1043doc 1044 | Alarm ID 5 status | Non-zero means alarm ID 5 is active. | UINT16 | Read | ||||
| HR | 1044doc 1045 | Alarm ID 6 status | Non-zero means alarm ID 6 is active. | UINT16 | Read | ||||
| HR | 1045doc 1046 | Alarm ID 7 status | Non-zero means alarm ID 7 is active. | UINT16 | Read | ||||
| HR | 1046doc 1047 | Alarm ID 8 status | Non-zero means alarm ID 8 is active. | UINT16 | Read | ||||
| HR | 1047doc 1048 | Alarm ID 9 status | Non-zero means alarm ID 9 is active. | UINT16 | Read | ||||
| HR | 1048doc 1049 | Alarm ID 10 status | Non-zero means alarm ID 10 is active. | UINT16 | Read | ||||
| HR | 1049doc 1050 | Alarm ID 11 status | Non-zero means alarm ID 11 is active. | UINT16 | Read | ||||
| HR | 1050doc 1051 | Alarm ID 12 status | Non-zero means alarm ID 12 is active. | UINT16 | Read | ||||
| HR | 1051doc 1052 | Alarm ID 13 status | Non-zero means alarm ID 13 is active. | UINT16 | Read | ||||
| HR | 1052doc 1053 | Alarm ID 14 status | Non-zero means alarm ID 14 is active. | UINT16 | Read | ||||
| HR | 1053doc 1054 | Alarm ID 15 status | Non-zero means alarm ID 15 is active. | UINT16 | Read | ||||
| HR | 1054doc 1055 | Alarm ID 16 status | Non-zero means alarm ID 16 is active. | UINT16 | Read | ||||
| HR | 1055doc 1056 | Alarm ID 17 status | Non-zero means alarm ID 17 is active. | UINT16 | Read | ||||
| HR | 1056doc 1057 | Alarm ID 18 status | Non-zero means alarm ID 18 is active. | UINT16 | Read | ||||
| HR | 1057doc 1058 | Alarm ID 19 status | Non-zero means alarm ID 19 is active. | UINT16 | Read | ||||
| HR | 1058doc 1059 | Alarm ID 20 status | Non-zero means alarm ID 20 is active. | UINT16 | Read | ||||
| HR | 1059doc 1060 | Alarm ID 21 status | Non-zero means alarm ID 21 is active. | UINT16 | Read | ||||
| HR | 1060doc 1061 | Alarm ID 22 status | Non-zero means alarm ID 22 is active. | UINT16 | Read | ||||
| HR | 1061doc 1062 | Alarm ID 23 status | Non-zero means alarm ID 23 is active. | UINT16 | Read | ||||
| HR | 1062doc 1063 | Alarm ID 24 status | Non-zero means alarm ID 24 is active. | UINT16 | Read | ||||
| HR | 1063doc 1064 | Alarm ID 25 status | Non-zero means alarm ID 25 is active. | UINT16 | Read | ||||
| HR | 1064doc 1065 | Alarm ID 26 status | Non-zero means alarm ID 26 is active. | UINT16 | Read | ||||
| HR | 1065doc 1066 | Alarm ID 27 status | Non-zero means alarm ID 27 is active. | UINT16 | Read | ||||
| HR | 1066doc 1067 | Alarm ID 28 status | Non-zero means alarm ID 28 is active. | UINT16 | Read | ||||
| HR | 1067doc 1068 | Alarm ID 29 status | Non-zero means alarm ID 29 is active. | UINT16 | Read | ||||
| HR | 1068doc 1069 | Alarm ID 30 status | Non-zero means alarm ID 30 is active. | UINT16 | Read | ||||
| HR | 1069doc 1070 | Alarm ID 31 status | Non-zero means alarm ID 31 is active. | UINT16 | Read | ||||
| HR | 1070doc 1071 | Alarm ID 32 status | Non-zero means alarm ID 32 is active. | UINT16 | Read | ||||
| HR | 2048doc 2049 | RS-485 bias | Bus biasing in the controller. | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | |||
| HR | 2059doc 2060 | Application prefix | Character code, 65 = A. | UINT16 | Read | ||||
| HR | 2060doc 2061 | Application type number | e.g. 214 for A214. | UINT16 | Read | ||||
| HR | 2061doc 2062 | Application sub number | UINT16 | Read | |||||
| HR | 2062doc 2063 | Application version | High byte = major, low byte = minor. | UINT16 | Read | ||||
| HR | 2096doc 2097 | Wink | Flash display backlight for this many seconds; 0 stops. | UINT16 | s | Read/write | |||
| HR | 2098doc 2099 | Production date | High byte = year minus 2000, low byte = week. | UINT16 | Read | ||||
| HR | 3999doc 4000 | Output status, triac 1 | Present value of the triac output. | UINT16 | Read | ||||
| HR | 4000doc 4001 | Output status, triac 2 | Present value of the triac output. | UINT16 | Read | ||||
| HR | 4001doc 4002 | Output status, triac 3 | Present value of the triac output. | UINT16 | Read | ||||
| HR | 4002doc 4003 | Output status, triac 4 | Present value of the triac output. | UINT16 | Read | ||||
| HR | 4003doc 4004 | Output status, triac 5 | Present value of the triac output. | UINT16 | Read | ||||
| HR | 4004doc 4005 | Output status, triac 6 | Present value of the triac output. | UINT16 | Read | ||||
| HR | 4005doc 4006 | Output status, relay 1 | Present value of the relay output. | UINT16 | Read | ||||
| HR | 4006doc 4007 | Output status, relay 2 | Present value of the relay output. | UINT16 | Read | ||||
| HR | 4007doc 4008 | Output status, relay 3 | Present value of the relay output. | UINT16 | Read | ||||
| HR | 4008doc 4009 | Output status, relay 4 | Present value of the relay output. | UINT16 | Read | ||||
| HR | 4009doc 4010 | Output status, relay 5 | Present value of the relay output. | UINT16 | Read | ||||
| HR | 4010doc 4011 | Output status, relay 6 | Present value of the relay output. | UINT16 | Read | ||||
| HR | 4015doc 4016 | Output status, ECA 32 AO 1 | Analog output of the ECA 32 module. | UINT16 | × 0.1 | % | Read | ||
| HR | 4016doc 4017 | Output status, ECA 32 AO 2 | Analog output of the ECA 32 module. | UINT16 | × 0.1 | % | Read | ||
| HR | 4017doc 4018 | Output status, ECA 32 AO 3 | Analog output of the ECA 32 module. | UINT16 | × 0.1 | % | Read | ||
| HR | 4019doc 4020 | Manual status, motorized valve 1 | Manual setting made on the display. | UINT16 | Read | 0 = AUTO; 1 = STOP; 2 = CLOSE; 3 = OPEN | |||
| HR | 4025doc 4026 | Manual status, relay 1 | Manual setting made on the display. | UINT16 | Read | 0 = AUTO; 1 = OFF; 2 = ON | |||
| HR | 4026doc 4027 | Manual status, relay 2 | Manual setting made on the display. | UINT16 | Read | 0 = AUTO; 1 = OFF; 2 = ON | |||
| HR | 4027doc 4028 | Manual status, relay 3 | Manual setting made on the display. | UINT16 | Read | 0 = AUTO; 1 = OFF; 2 = ON | |||
| HR | 4028doc 4029 | Manual status, relay 4 | Manual setting made on the display. | UINT16 | Read | 0 = AUTO; 1 = OFF; 2 = ON | |||
| HR | 4029doc 4030 | Manual status, relay 5 | Manual setting made on the display. | UINT16 | Read | 0 = AUTO; 1 = OFF; 2 = ON | |||
| HR | 4030doc 4031 | Manual status, relay 6 | Manual setting made on the display. | UINT16 | Read | 0 = AUTO; 1 = OFF; 2 = ON | |||
| HR | 4059doc 4060 | Override, motorized valve 1 (triac 1) | Output override for 3-point valve 1 when not in manual mode. | UINT16 | Read/write | 0 = AUTO; 1 = STOP; 2 = CLOSE; 3 = OPEN | |||
| HR | 4065doc 4066 | Override, relay 1 | Output override for relay 1 when not in manual mode. | UINT16 | Read/write | 0 = AUTO; 1 = OFF; 2 = ON | |||
| HR | 4066doc 4067 | Override, relay 2 | Output override for relay 2 when not in manual mode. | UINT16 | Read/write | 0 = AUTO; 1 = OFF; 2 = ON | |||
| HR | 4067doc 4068 | Override, relay 3 | Output override for relay 3 when not in manual mode. | UINT16 | Read/write | 0 = AUTO; 1 = OFF; 2 = ON | |||
| HR | 4068doc 4069 | Override, relay 4 | Output override for relay 4 when not in manual mode. | UINT16 | Read/write | 0 = AUTO; 1 = OFF; 2 = ON | |||
| HR | 4069doc 4070 | Override, relay 5 | Output override for relay 5 when not in manual mode. | UINT16 | Read/write | 0 = AUTO; 1 = OFF; 2 = ON | |||
| HR | 4070doc 4071 | Override, relay 6 | Output override for relay 6 when not in manual mode. | UINT16 | Read/write | 0 = AUTO; 1 = OFF; 2 = ON | |||
| HR | 4200doc 4201 | Circuit 1 mode | Operating mode; manual mode on one circuit applies to all. | UINT16 | Read/write | 0 = Manual operation; 1 = Scheduled operation; 2 = Constant comfort temperature; 3 = Constant setback temperature; 4 = Frost protection/standby; 5 = Active cooling (A232 only) | |||
| HR | 4201doc 4202 | Circuit 2 mode | Operating mode; manual mode on one circuit applies to all. | UINT16 | Read/write | 0 = Manual operation; 1 = Scheduled operation; 2 = Constant comfort temperature; 3 = Constant setback temperature; 4 = Frost protection/standby; 5 = Active cooling (A232 only) | |||
| HR | 4202doc 4203 | Circuit 3 mode | Operating mode; manual mode on one circuit applies to all. | UINT16 | Read/write | 0 = Manual operation; 1 = Scheduled operation; 2 = Constant comfort temperature; 3 = Constant setback temperature; 4 = Frost protection/standby; 5 = Active cooling (A232 only) | |||
| HR | 4203doc 4204 | Circuit 4 mode | Operating mode; manual mode on one circuit applies to all. | UINT16 | Read/write | 0 = Manual operation; 1 = Scheduled operation; 2 = Constant comfort temperature; 3 = Constant setback temperature; 4 = Frost protection/standby; 5 = Active cooling (A232 only) | |||
| HR | 4210doc 4211 | Circuit 1 status | Current operating status of the circuit. | UINT16 | Read | 0 = Setback; 1 = Pre-comfort; 2 = Comfort; 3 = Pre-setback; 4 = Holiday constant comfort temperature; 5 = Holiday 7-23h comfort temperature; 6 = Holiday constant setback temperature; 7 = Holiday frost protection/standby | |||
| HR | 4211doc 4212 | Circuit 2 status | Current operating status of the circuit. | UINT16 | Read | 0 = Setback; 1 = Pre-comfort; 2 = Comfort; 3 = Pre-setback; 4 = Holiday constant comfort temperature; 5 = Holiday 7-23h comfort temperature; 6 = Holiday constant setback temperature; 7 = Holiday frost protection/standby | |||
| HR | 4212doc 4213 | Circuit 3 status | Current operating status of the circuit. | UINT16 | Read | 0 = Setback; 1 = Pre-comfort; 2 = Comfort; 3 = Pre-setback; 4 = Holiday constant comfort temperature; 5 = Holiday 7-23h comfort temperature; 6 = Holiday constant setback temperature; 7 = Holiday frost protection/standby | |||
| HR | 4213doc 4214 | Circuit 4 status | Current operating status of the circuit. | UINT16 | Read | 0 = Setback; 1 = Pre-comfort; 2 = Comfort; 3 = Pre-setback; 4 = Holiday constant comfort temperature; 5 = Holiday 7-23h comfort temperature; 6 = Holiday constant setback temperature; 7 = Holiday frost protection/standby | |||
| HR | 5996doc 5997 | M-bus baud rate | UINT16 | Read/write | 0 = 300; 1 = 600; 2 = 1200; 3 = 2400 | ||||
| HR | 5997doc 5998 | M-bus command | Start a meter scan or re-initialize. | UINT16 | Read/write | 0 = None; 1 = Init; 2 = Scan for energy meter | |||
| HR | 5998doc 5999 | M-bus state | UINT16 | Read | 0 = Reset; 1 = Init; 2 = Scanning; 3 = Idle | ||||
| HR | 5999doc 6000 | Energy meter 1 M-bus address | M-bus primary address 0-254 (251-254 special; 254 only with one meter) or 255. | UINT16 | Read/write | ||||
| HR | 6000doc 6001 | Energy meter 1 type | Data set read from the meter; changing it resets values. | UINT16 | Read/write | 0 = Generic small data set, small units; 1 = Generic small data set, large units; 2 = Generic large data set, small units; 3 = Generic large data set, large units; 4 = Volume and energy only | |||
| HR | 6001doc 6002 | Energy meter 1 scan time | Poll interval. | UINT16 | s | Read/write | |||
| HR | 6002doc 6003 | Energy meter 1 ID / serial | UINT32 | ABCD | Read | ||||
| HR | 6005doc 6006 | Energy meter 1 flow temperature | Types 0-3. | INT16 | × 0.01 | °C | Read | ||
| HR | 6006doc 6007 | Energy meter 1 return temperature | Types 0-3. | INT16 | × 0.01 | °C | Read | ||
| HR | 6007doc 6008 | Energy meter 1 flow | Types 0-3. | UINT32 | ABCD | × 0.1 | l/h | Read | |
| HR | 6009doc 6010 | Energy meter 1 power | Types 0-3. | UINT32 | ABCD | × 0.1 | kW | Read | |
| HR | 6011doc 6012 | Energy meter 1 accumulated volume | Types 0-3. | UINT32 | ABCD | × 0.1 | m³ | Read | |
| HR | 6013doc 6014 | Energy meter 1 accumulated energy | kWh for types 0 and 2; 0.1 MWh units for types 1 and 3. | UINT32 | ABCD | × 0.1 | kWh | Read | |
| HR | 10197doc 10198 | Automatic summer time | EU summer-time rules. | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | |||
| HR | 10200doc 10201 | Raw sensor S1 | Temperature at sensor input S1. | INT16 | × 0.01 | °C | Read | ||
| HR | 10201doc 10202 | Raw sensor S2 | Temperature at sensor input S2. | INT16 | × 0.01 | °C | Read | ||
| HR | 10202doc 10203 | Raw sensor S3 | Temperature at sensor input S3. | INT16 | × 0.01 | °C | Read | ||
| HR | 10203doc 10204 | Raw sensor S4 | Temperature at sensor input S4. | INT16 | × 0.01 | °C | Read | ||
| HR | 10204doc 10205 | Raw sensor S5 | Temperature at sensor input S5. | INT16 | × 0.01 | °C | Read | ||
| HR | 10205doc 10206 | Raw sensor S6 | Temperature at sensor input S6. | INT16 | × 0.01 | °C | Read | ||
| HR | 10206doc 10207 | Raw sensor S7 | Temperature at sensor input S7. | INT16 | × 0.01 | °C | Read | ||
| HR | 10207doc 10208 | Raw sensor S8 | Temperature at sensor input S8. | INT16 | × 0.01 | °C | Read | ||
| HR | 10208doc 10209 | Raw sensor S9 | Temperature at sensor input S9. | INT16 | × 0.01 | °C | Read | ||
| HR | 10209doc 10210 | Raw sensor S10 | Temperature at sensor input S10. | INT16 | × 0.01 | °C | Read | ||
| HR | 10210doc 10211 | Raw sensor S11 | Temperature at sensor input S11. | INT16 | × 0.01 | °C | Read | ||
| HR | 10211doc 10212 | Raw sensor S12 | Temperature at sensor input S12. | INT16 | × 0.01 | °C | Read | ||
| HR | 10212doc 10213 | ECA 30 room A, room temperature | Room temperature from an ECA 30/31 set as HMI A; reads 19200 if none is fitted. | INT16 | × 0.01 | °C | Read | ||
| HR | 11174doc 11175 | Circuit 1 heat curve slope | Slope of the heat curve; writable in some applications. | UINT16 | × 0.1 | Read | |||
| HR | 11179doc 11180 | Circuit 1 comfort room setpoint | INT16 | × 0.1 | °C | Read/write | |||
| HR | 11180doc 11181 | Circuit 1 saving room setpoint | INT16 | × 0.1 | °C | Read/write | |||
| HR | 11189doc 11190 | Circuit 1 comfort DHW setpoint | Used when circuit 1 is a DHW circuit. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 11190doc 11191 | Circuit 1 saving DHW setpoint | Used when circuit 1 is a DHW circuit. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 12179doc 12180 | Circuit 2 comfort room setpoint | Circuit 2 = circuit 1 PNU + 1000. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 12180doc 12181 | Circuit 2 saving room setpoint | INT16 | × 0.1 | °C | Read/write | |||
| HR | 12189doc 12190 | Circuit 2 comfort DHW setpoint | DHW setpoint when circuit 2 is DHW (e.g. A266.1). | INT16 | × 0.1 | °C | Read/write | ||
| HR | 12190doc 12191 | Circuit 2 saving DHW setpoint | INT16 | × 0.1 | °C | Read/write | |||
| HR | 64044doc 64045 | Clock hour | 0-23. | UINT16 | Read/write | ||||
| HR | 64045doc 64046 | Clock minute | 0-59; seconds reset to 0 on write. | UINT16 | Read/write | ||||
| HR | 64046doc 64047 | Date day | 1-31. | UINT16 | Read/write | ||||
| HR | 64047doc 64048 | Date month | 1-12. | UINT16 | Read/write | ||||
| HR | 64048doc 64049 | Date year | 2009-2099. | UINT16 | Read/write |
Notes on this map
- All values are 16-bit integers that must be scaled per parameter. The guide warns that scales in its PNU list are guidelines and can change with the application; check the application key instructions for the parameters you write.
- The guide does not say whether integers are signed. Temperatures (sensors, setpoints) are listed as INT16 because outdoor temperatures go below zero; codes and counts as UINT16.
- Sensor S2 example: raw 0x0860 = 2144 = 21.44 °C (scale 100). Setpoint example: 200 = 20.0 °C (scale 10).
- Application parameters live at 11xxx (circuit 1), 12xxx (circuit 2), 13xxx (circuit 3); add 1000 per circuit. Only circuits 1 and 2 setpoints are listed.
- M-bus energy meter values use two PNUs with the high word in the first one (serial example 0x00A7, 0xFEE3 = 11009763), so 32-bit values are ABCD. Meters 2-5 start at PNU 6050, 6100, 6150, 6200 with the same offsets. Energy meter type 4 uses a different layout and is not listed.
- Only function codes 03 and 04 (read) and 06 (write single) are supported; function 16 is not, so write one register at a time. Up to 123 PNUs can be read in one request.
- Output bitmask PNUs 3998 (high word) and 3999 (low word) are left out because the guide's bit table does not say which bits sit in which word; use the per-output status PNUs 4000-4018 instead.
- Manual output states can only be set on the display or ECA 30/31, not over Modbus. Override only applies when the controller is not in manual mode.
- Holiday programs (10700-10839), weekly schedules (3110-3975), heat-curve points and the anti-bacteria settings are documented in the guide but left out to keep the map short.
- The operating status reads 0 (setback) whenever the circuit mode is above 3.
- Modbus/TCP connections are closed by the controller after about 75 seconds without traffic.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Danfoss ECL Comfort 210 / 296 / 310 heating controller (Modbus RTU / TCP)
What Modbus registers does the Danfoss ECL Comfort 210 / 296 / 310 heating controller (Modbus RTU / TCP) have?
This map lists 131 registers: 131 holding registers. 40 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Danfoss ECL Comfort 210 / 296 / 310 heating controller (Modbus RTU / TCP) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide lists parameter numbers (PNU) and states the register address is PNU-1; its frame example reads comfort setpoint PNU 11180 at 0x2BAB (11179). So request PNU minus 1 on the wire.
What byte order does the Danfoss ECL Comfort 210 / 296 / 310 heating controller (Modbus RTU / TCP) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Danfoss ECL Comfort 210 / 296 / 310 heating controller (Modbus RTU / TCP)?
Start with HR 10200 Raw sensor S1 (Sensor S1 (meaning depends on the application key)); HR 10202 Raw sensor S3 (Sensor S3 (meaning depends on the application key)); HR 4200 Circuit 1 mode (Circuit 1 mode (write to change)); HR 4210 Circuit 1 status (Circuit 1 status); HR 11179 Circuit 1 comfort room setpoint (Circuit 1 comfort room setpoint); HR 1024 Alarm field 1 (alarms 1-16) (Alarm bits 1-16); HR 6013 Energy meter 1 accumulated energy (Energy meter 1 accumulated energy).
How do I enable Modbus control of the Danfoss ECL Comfort 210 / 296 / 310 heating controller (Modbus RTU / TCP)?
No enable step: Modbus is always active. Set the Modbus address (PNU 38) and RS-485 baud rate (PNU 39). All three models have the USB service port and RS-485 Modbus RTU (galvanically isolated on the 296/310); Modbus/TCP is on the ECL 296/310 only.
Where is the official Danfoss ECL Comfort 210 / 296 / 310 heating controller (Modbus RTU / TCP) Modbus documentation?
The source is ECL Comfort 210 / 296 / 310, communication description (VI.LG.V5.02 (AQ074886472234en-010502)), revision 2018-08, published free by Danfoss at https://assets.danfoss.com/documents/63852/AQ074886472234en-010502.pdf.
More Danfoss Modbus register maps
- Sensor (refrigerant / toxic gas detector)
Danfoss Gas Detection Units GD Basic / Premium / Heavy Duty (Modbus RTU)
Danfoss GD Basic, Premium and Heavy Duty gas detection units on their own RS-485 Modbus port (Part 2 of the guide). The gas detection controller's X-bus map in Part 1 is not included.
Also known as: GDA, GDC, GDHC, GDHF, GDH, GD Basic, GD Premium, GD Heavy Duty - Variable frequency drive
Danfoss iC2-Micro frequency converter (Modbus RTU)
Danfoss iC2-Micro frequency converters using the built-in RS-485 port with P 10.1.1 Protocol = [2] Modbus RTU and the FC control profile; Application Guide AB413939445838en-000401.
Also known as: iC2-Micro, iC2 Micro, Danfoss iC2 - Sensor / controller (CO2 condensing unit gateway)
Danfoss Optyma iCO2 gateway (OP-MPAM015 / OP-MPAM005)
Danfoss Optyma iCO2 CO2 condensing units (4.6 kW MT and 20 kW MT / 10 kW LT) through their Modbus gateway, software 1.0x.
Also known as: OP-MPAM015, OP-MPAM005, Optyma iCO2 4.6 kW MT, Optyma iCO2 20 kW MT / 10 kW LT - Variable frequency drive
Danfoss VLT AQUA Drive FC 202 (Modbus RTU)
VLT AQUA Drive FC 202 using the built-in RS-485 (FC) port with 8-30 Protocol = Modbus RTU and the FC control profile; parameter data checked against the software 5.4X programming guide.
Also known as: VLT AQUA Drive, FC202, FC-202, AQUA Drive FC 202 - Variable frequency drive
Danfoss VLT AutomationDrive FC 301/302 (Modbus RTU)
VLT AutomationDrive FC 301 and FC 302 (0.25-75 kW design guide; same scheme across sizes) using the built-in RS-485 (FC) port with 8-30 Protocol = Modbus RTU and the FC control profile; parameter data checked against the software 9.5x / 48.96 programming guide.
Also known as: VLT AutomationDrive, FC 301, FC301, FC302, FC-302, FC-301, FC 300 - Variable frequency drive
Danfoss VLT AutomationDrive FC 360 (Modbus RTU)
VLT AutomationDrive FC 360 on its built-in RS-485 port with 8-30 Protocol = Modbus RTU and the FC control profile.
Also known as: FC360, FC-360, VLT AutomationDrive FC 360 - Variable frequency drive
Danfoss VLT Compressor Drive CDS 803 (Modbus RTU)
VLT Compressor Drive CDS 803 (variable-speed compressor drive for HVAC/R) using the built-in RS-485 port with 8-30 Protocol = Modbus RTU; Modbus rules from Design Guide MG18N202 (software 1.20), parameter data from Programming Guide MG18P202 (software 2.0).
Also known as: CDS803, CDS-803, VLT Compressor Drive CDS 803 - Variable frequency drive (HVAC fans and pumps)
Danfoss VLT HVAC Basic Drive FC 101 (Modbus RTU)
VLT HVAC Basic Drive FC 101 on its built-in RS-485 port with 8-30 Protocol = Modbus RTU and the FC control profile.
Also known as: FC101, FC-101, VLT HVAC Basic Drive FC 101, VLT HVAC Basic - Variable frequency drive
Danfoss VLT HVAC Drive FC 102 (Modbus RTU)
VLT HVAC Drive FC 102 using the built-in RS-485 (FC) port with 8-30 Protocol = Modbus RTU and the FC control profile; parameter scaling checked against the software 7.61 programming guide.
Also known as: VLT HVAC Drive, FC102, FC-102 - Variable frequency drive
Danfoss VLT Micro Drive FC 51 (Modbus RTU)
VLT Micro Drive FC 51 on the built-in RS-485 port with 8-30 = Modbus, software 3.1x; registers per design guide MG02K402 and parameter data per programming guide MG02C702.
Also known as: FC 51, FC51, VLT Micro Drive, VLT Micro Drive FC 51 - Variable frequency drive
Danfoss VLT Midi Drive FC 280 (Modbus RTU)
VLT Midi Drive FC 280 on its built-in RS-485 port with 8-30 Protocol = Modbus RTU and the FC control profile.
Also known as: FC280, FC-280, VLT Midi Drive FC 280, VLT Midi Drive
Other hvac equipment register maps
- Air handler (heat recovery ventilation unit)
Jablotron FUTURA L / M / S heat recovery ventilation unit (Modbus TCP)
Futura L/M/S from firmware FUA.P.06.71, register list v5.0 (13.10.2025). Futura L+ uses different addresses and is not covered.
Also known as: Futura L, Futura M, Futura S, JABLOTRON FUTURA - Thermostat (room operating unit with sensors)
LOYTEC L-STAT network thermostat / room operating unit (Modbus RTU)
LSTAT-800/801/802 room operating units (all button layouts), user manual version 3.2.8 (document 88085811).
Also known as: L-STAT, LSTAT-800, LSTAT-801, LSTAT-802, LSTAT-800-Gx-Lx, LSTAT-801-Gx-Lx, LSTAT-802-Gx-Lx - Thermostat / fan coil controller
Neptronic EFCB Series networkable fan coil controller (Modbus RTU)
Neptronic EFCB Series fan coil controllers (24, 120 and 240 Vac; 2 or 4 relays) with the Modbus communication module, guide EFCB-Modbus Guide-260626.
Also known as: EFCB10TU2, EFCB10TU4, EFCB11TU2, EFCB11TU4, EFCB12TU2, EFCB12TU4, EFCB fan coil controller - Air handler evaporative cooler (adiabatic cooling / humidification)
Neptronic SKVF evaporative cooler / humidifier (Modbus communication module)
Neptronic SKVF series evaporative coolers with the Modbus communication module, guide SKVF-Modbus Guide-211025.
Also known as: SKVF Evaporative Cooler, SKVF Series, Neptronic SKVF Modbus - Thermostat / room controller (chilled beam, fan coil water circuits)
Swegon CONDUCTOR W1 room controller (waterborne cooling/heating, Modbus RTU)
Swegon CONDUCTOR W1 room controller, software 1.38 and later (technical manual updated 2015-06-15).
Also known as: CONDUCTOR RE W1, Conductor W1, 942334001 - Air handler (residential heat recovery ventilation)
Vasco SAB RVU ventilation unit controller (D150 Compact, Energy Plus)
Vasco SAB RVU controller boards (models 0x52xx residential and 0x53xx Energy Plus) with protocol release 0x0006, manual 90.01.06.53.
Also known as: D150 Compact, Energy Plus ENY-P1, ENY-P2, ENY-P3, ENY-P4, ESP170V, ESP270, ESP360, ESP460
All hvac equipment Modbus register maps →
Source: ECL Comfort 210 / 296 / 310, communication description · VI.LG.V5.02 (AQ074886472234en-010502) · rev. 2018-08. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.