Thermostat (room operating unit with sensors) · Modbus register map

LOYTEC L-STAT network thermostat / room operating unit (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

Wall-mounted room panel with LCD, touch buttons, temperature and humidity sensors (plus occupancy on the 801/802 and CO2 on the 802) that works as a Modbus RTU slave for a LOYTEC controller or any master. Everything is in holding registers: button and flag words, sensor readings, display values pushed by the master, set points with limits, offsets and configuration.

This page lists 28 Modbus registers for the LOYTEC L-STAT network thermostat / room operating unit (Modbus RTU) — 17 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from LOYTEC’s own free documentation (linked below) and checked against it.

Manufacturer
LOYTEC
Model
L-STAT network thermostat / room operating unit (Modbus RTU)
Equipment type
Thermostat (room operating unit with sensors)
Registers
28 (17 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
57600 baud, 8N2
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
L-STAT, LSTAT-800, LSTAT-801, LSTAT-802, LSTAT-800-Gx-Lx, LSTAT-801-Gx-Lx, LSTAT-802-Gx-Lx
Source document
L-STAT User Manual · 88085811, version 3.2.8
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: LOYTEC L-STAT network thermostat / room operating unit (Modbus RTU)

Integration in brief

Read the sensor block 48-54 with FC03 and the button/flag words 0-5; write display values (64+) and read back set points (384+) that the user adjusts. Clear latched flags by writing 1 to the bit.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 48sensor_value_0 internal temperatureINT16Room temperatureRead
HR 50sensor_value_2 relative humidityUINT16Relative humidityRead
HR 53sensor_value_5 amount CO2UINT16CO2 (802 only)Read
HR 384set_point_0INT16Main set pointRead/write
HR 3change_flags_set_pointsBITMAP16Which set points the user changedRead/write
HR 1short_pressedBITMAP16Button presses / occupancyRead/write

Enable Modbus control & writes

No enable step; the panel answers as a slave at address 1 out of the box. Change address/baud/parity in EDIT mode on the panel or in modbus_parameter (176), then reboot.

Byte order & addressing

Network setup

Watch out for

LOYTEC L-STAT network thermostat / room operating unit (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

28 of 28 shown
LOYTEC L-STAT network thermostat / room operating unit (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 0 (0x0000)present_stateLive button and occupancy state (updated in DISPLAY and DIRECT_ACCESS modes).BITMAP16Readbit 0 = Touch button TB0; bit 1 = Touch button TB1; bit 2 = Touch button TB2; bit 3 = Touch button TB3; bit 4 = Touch button TB4; bit 5 = Touch button TB5; bit 6 = Touch button TB6; bit 7 = Touch button TB7; bit 8 = External button EB0; bit 9 = External button EB1; bit 10 = External button EB2; bit 11 = External button EB3; bit 12 = Occu - occupancy detected (801/802 models)
HR1doc 1 (0x0001)short_pressedLatched short presses and flags; write 1 to a bit to clear it.BITMAP16Read/writebit 0 = Touch button TB0; bit 1 = Touch button TB1; bit 2 = Touch button TB2; bit 3 = Touch button TB3; bit 4 = Touch button TB4; bit 5 = Touch button TB5; bit 6 = Touch button TB6; bit 7 = Touch button TB7; bit 8 = External button EB0; bit 9 = External button EB1; bit 10 = External button EB2; bit 11 = External button EB3; bit 12 = Occu - occupancy detected; bit 13 = ENO - EnOcean frame received; bit 14 = NFC - NFC field detected; bit 15 = IRC - IR remote command received
HR2doc 2 (0x0002)long_pressedLatched long presses and status flags; write 1 to clear.BITMAP16Read/writebit 0 = Touch button TB0; bit 1 = Touch button TB1; bit 2 = Touch button TB2; bit 3 = Touch button TB3; bit 4 = Touch button TB4; bit 5 = Touch button TB5; bit 6 = Touch button TB6; bit 7 = Touch button TB7; bit 8 = External button EB0; bit 9 = External button EB1; bit 10 = External button EB2; bit 11 = External button EB3; bit 12 = SPC - a set point was changed locally; bit 13 = DOC - device setting or offset changed locally; bit 14 = ERR - internal error; bit 15 = FD - booted with factory defaults
HR3doc 3 (0x0003)change_flags_set_pointsBit n set = set_point_n changed on the panel; write 1 to clear.BITMAP16Read/writebit 0 = set_point_0 changed; bit 1 = set_point_1 changed; bit 2 = set_point_2 changed; bit 3 = set_point_3 changed; bit 4 = set_point_4 changed; bit 5 = set_point_5 changed; bit 6 = set_point_6 changed; bit 7 = set_point_7 changed; bit 8 = set_point_8 changed; bit 9 = set_point_9 changed; bit 10 = set_point_10 changed; bit 11 = set_point_11 changed; bit 12 = set_point_12 changed; bit 13 = set_point_13 changed; bit 14 = set_point_14 changed; bit 15 = set_point_15 changed
HR4doc 4 (0x0004)change_flags_device_settingsDevice setting changed locally; write 1 to clear.BITMAP16Read/writebit 0 = modbus_parameter (176); bit 1 = pincode_system_administrator (177); bit 2 = pincode_end_user (178); bit 3 = lcd_color_red (179); bit 4 = lcd_color_green (180); bit 5 = lcd_color_blue (181); bit 6 = lcd_brightness_contrast (182); bit 7 = user_interface_settings (183); bit 8 = display_unit (192)
HR5doc 5 (0x0005)change_flags_offset_valuesBit n set = offset_value_n changed; write 1 to clear.BITMAP16Read/writebit 0 = offset_value_0 changed; bit 1 = offset_value_1 changed; bit 2 = offset_value_2 changed; bit 3 = offset_value_3 changed; bit 4 = offset_value_4 changed; bit 5 = offset_value_5 changed; bit 6 = offset_value_6 changed; bit 7 = offset_value_7 changed; bit 8 = offset_value_8 changed
HR6doc 6 (0x0006)manual_occupancy0 = unoccupied, any other value = occupied (external occupancy input).UINT16Read/write0 = Unoccupied
HR32doc 32 (0x0020)ir_remote_control_commandHigh byte button code, low byte remote id of the last IR command.UINT16Read
HR48doc 48 (0x0030)sensor_value_0 internal temperatureAssumes the default Modbus unit system °C (config_flags MU = 1).INT16× 0.1°CRead
HR49doc 49 (0x0031)sensor_value_1 external temperatureSensor wired to EB3 and GND; default MU = °C assumed.INT16× 0.1°CRead
HR50doc 50 (0x0032)sensor_value_2 relative humidityRaw x 5 x 10^-3.UINT16× 0.005%RHRead
HR51doc 51 (0x0033)sensor_value_3 dew pointDefault MU = °C assumed.INT16× 0.1°CRead
HR53doc 53 (0x0035)sensor_value_5 amount CO2LSTAT-802 models only.UINT16ppmRead
HR54doc 54 (0x0036)sensor_value_6 L-STAT supply voltageUINT16× 0.1VRead
HR64doc 64 (0x0040)display_value_0Value written by the master for display; scaling per its configuration (256+).INT16Read/write
HR65doc 65 (0x0041)display_value_1As display_value_0.INT16Read/write
HR66doc 66 (0x0042)display_value_2As display_value_0.INT16Read/write
HR67doc 67 (0x0043)display_value_3As display_value_0.INT16Read/write
HR176doc 176 (0x00B0)modbus_parameterBits 13-12 parity, 11-8 baud code, 7-0 slave address. Takes effect after reboot.UINT16Read/write
HR192doc 192 (0x00C0)config_flagsBits 9-8 MU Modbus unit (0 K, 1 °C, 2 °F); 11-10 display unit; bit 0 reboot.UINT16Read/write
HR384doc 384 (0x0180)set_point_0Signed; scaling follows the unit set in set point config (320+). Default 220.INT16Read/write
HR385doc 385 (0x0181)set_point_1Signed; scaling follows its set point configuration.INT16Read/write
HR386doc 386 (0x0182)set_point_2Signed; scaling follows its set point configuration.INT16Read/write
HR387doc 387 (0x0183)set_point_3Signed; scaling follows its set point configuration.INT16Read/write
HR480doc 480 (0x01E0)offset_value_0Offset added to its sensor value; same scaling as that sensor.INT16Read/write
HR560doc 560-569 (0x0230-0x0239)product_code_stringModel / product code text.STRING[20]Read
HR576doc 576-585 (0x0240-0x0249)serial_number_stringSTRING[20]Read
HR592doc 592-595 (0x0250-0x0253)firmware_version_stringSTRING[8]Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the LOYTEC L-STAT network thermostat / room operating unit (Modbus RTU)

What Modbus registers does the LOYTEC L-STAT network thermostat / room operating unit (Modbus RTU) have?

This map lists 28 registers: 28 holding registers. 17 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the LOYTEC L-STAT network thermostat / room operating unit (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each register is printed with its decimal address and hex equivalent (e.g. 48 / 0x0030). The table starts at register address 0 (present_state, 0x0000), which only exists in 0-based protocol addressing, so these are the wire addresses. 'documented' keeps both forms.

What are the minimum Modbus registers to integrate the LOYTEC L-STAT network thermostat / room operating unit (Modbus RTU)?

Start with HR 48 sensor_value_0 internal temperature (Room temperature); HR 50 sensor_value_2 relative humidity (Relative humidity); HR 53 sensor_value_5 amount CO2 (CO2 (802 only)); HR 384 set_point_0 (Main set point); HR 3 change_flags_set_points (Which set points the user changed); HR 1 short_pressed (Button presses / occupancy).

How do I enable Modbus control of the LOYTEC L-STAT network thermostat / room operating unit (Modbus RTU)?

No enable step; the panel answers as a slave at address 1 out of the box. Change address/baud/parity in EDIT mode on the panel or in modbus_parameter (176), then reboot.

Where is the official LOYTEC L-STAT network thermostat / room operating unit (Modbus RTU) Modbus documentation?

The source is L-STAT User Manual (88085811, version 3.2.8), published free by LOYTEC at https://www.loytec.com/component/docman/doc_download/2159-l-stat-user-manual-3-2-4.

Other hvac equipment register maps

All hvac equipment Modbus register maps →

Source: L-STAT User Manual · 88085811, version 3.2.8. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.