- L-STAT network thermostat / room operating unit (Modbus RTU)
Thermostat (room operating unit with sensors) · Modbus register map
LOYTEC L-STAT network thermostat / room operating unit (Modbus RTU) Modbus register map
Updated 17 November 2026
Wall-mounted room panel with LCD, touch buttons, temperature and humidity sensors (plus occupancy on the 801/802 and CO2 on the 802) that works as a Modbus RTU slave for a LOYTEC controller or any master. Everything is in holding registers: button and flag words, sensor readings, display values pushed by the master, set points with limits, offsets and configuration.
This page lists 28 Modbus registers for the LOYTEC L-STAT network thermostat / room operating unit (Modbus RTU) — 17 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from LOYTEC’s own free documentation (linked below) and checked against it.
- Manufacturer
- LOYTEC
- Model
- L-STAT network thermostat / room operating unit (Modbus RTU)
- Equipment type
- Thermostat (room operating unit with sensors)
- Registers
- 28 (17 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 57600 baud, 8N2
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- L-STAT, LSTAT-800, LSTAT-801, LSTAT-802, LSTAT-800-Gx-Lx, LSTAT-801-Gx-Lx, LSTAT-802-Gx-Lx
- Source document
- L-STAT User Manual · 88085811, version 3.2.8
Integration notes: LOYTEC L-STAT network thermostat / room operating unit (Modbus RTU)
Read the sensor block 48-54 with FC03 and the button/flag words 0-5; write display values (64+) and read back set points (384+) that the user adjusts. Clear latched flags by writing 1 to the bit.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 48 | sensor_value_0 internal temperature | INT16 | Room temperature | Read |
| HR 50 | sensor_value_2 relative humidity | UINT16 | Relative humidity | Read |
| HR 53 | sensor_value_5 amount CO2 | UINT16 | CO2 (802 only) | Read |
| HR 384 | set_point_0 | INT16 | Main set point | Read/write |
| HR 3 | change_flags_set_points | BITMAP16 | Which set points the user changed | Read/write |
| HR 1 | short_pressed | BITMAP16 | Button presses / occupancy | Read/write |
Enable Modbus control & writes
No enable step; the panel answers as a slave at address 1 out of the box. Change address/baud/parity in EDIT mode on the panel or in modbus_parameter (176), then reboot.
Byte order & addressing
- Only FC03 and FC06: no FC16 multi-register writes.
- Temperatures follow the Modbus unit flag (K, °C or °F) in config_flags, not the display unit.
- Latched press and change flags stay set until the master writes 1 to them.
Network setup
- Factory default: address 1, 57600 baud, no parity, 2 stop bits.
- Built-in 120 ohm terminator: switch it on only at the last device on the bus.
- Up to 16 L-STATs per LOYTEC controller; each needs a unique address.
Watch out for
- The device has no clock battery: the master must set system time after every reboot.
- Display range is -999..9999; larger values are shown shifted.
LOYTEC L-STAT network thermostat / room operating unit (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 0 (0x0000) | present_state | Live button and occupancy state (updated in DISPLAY and DIRECT_ACCESS modes). | BITMAP16 | Read | bit 0 = Touch button TB0; bit 1 = Touch button TB1; bit 2 = Touch button TB2; bit 3 = Touch button TB3; bit 4 = Touch button TB4; bit 5 = Touch button TB5; bit 6 = Touch button TB6; bit 7 = Touch button TB7; bit 8 = External button EB0; bit 9 = External button EB1; bit 10 = External button EB2; bit 11 = External button EB3; bit 12 = Occu - occupancy detected (801/802 models) | |||
| HR | 1doc 1 (0x0001) | short_pressed | Latched short presses and flags; write 1 to a bit to clear it. | BITMAP16 | Read/write | bit 0 = Touch button TB0; bit 1 = Touch button TB1; bit 2 = Touch button TB2; bit 3 = Touch button TB3; bit 4 = Touch button TB4; bit 5 = Touch button TB5; bit 6 = Touch button TB6; bit 7 = Touch button TB7; bit 8 = External button EB0; bit 9 = External button EB1; bit 10 = External button EB2; bit 11 = External button EB3; bit 12 = Occu - occupancy detected; bit 13 = ENO - EnOcean frame received; bit 14 = NFC - NFC field detected; bit 15 = IRC - IR remote command received | |||
| HR | 2doc 2 (0x0002) | long_pressed | Latched long presses and status flags; write 1 to clear. | BITMAP16 | Read/write | bit 0 = Touch button TB0; bit 1 = Touch button TB1; bit 2 = Touch button TB2; bit 3 = Touch button TB3; bit 4 = Touch button TB4; bit 5 = Touch button TB5; bit 6 = Touch button TB6; bit 7 = Touch button TB7; bit 8 = External button EB0; bit 9 = External button EB1; bit 10 = External button EB2; bit 11 = External button EB3; bit 12 = SPC - a set point was changed locally; bit 13 = DOC - device setting or offset changed locally; bit 14 = ERR - internal error; bit 15 = FD - booted with factory defaults | |||
| HR | 3doc 3 (0x0003) | change_flags_set_points | Bit n set = set_point_n changed on the panel; write 1 to clear. | BITMAP16 | Read/write | bit 0 = set_point_0 changed; bit 1 = set_point_1 changed; bit 2 = set_point_2 changed; bit 3 = set_point_3 changed; bit 4 = set_point_4 changed; bit 5 = set_point_5 changed; bit 6 = set_point_6 changed; bit 7 = set_point_7 changed; bit 8 = set_point_8 changed; bit 9 = set_point_9 changed; bit 10 = set_point_10 changed; bit 11 = set_point_11 changed; bit 12 = set_point_12 changed; bit 13 = set_point_13 changed; bit 14 = set_point_14 changed; bit 15 = set_point_15 changed | |||
| HR | 4doc 4 (0x0004) | change_flags_device_settings | Device setting changed locally; write 1 to clear. | BITMAP16 | Read/write | bit 0 = modbus_parameter (176); bit 1 = pincode_system_administrator (177); bit 2 = pincode_end_user (178); bit 3 = lcd_color_red (179); bit 4 = lcd_color_green (180); bit 5 = lcd_color_blue (181); bit 6 = lcd_brightness_contrast (182); bit 7 = user_interface_settings (183); bit 8 = display_unit (192) | |||
| HR | 5doc 5 (0x0005) | change_flags_offset_values | Bit n set = offset_value_n changed; write 1 to clear. | BITMAP16 | Read/write | bit 0 = offset_value_0 changed; bit 1 = offset_value_1 changed; bit 2 = offset_value_2 changed; bit 3 = offset_value_3 changed; bit 4 = offset_value_4 changed; bit 5 = offset_value_5 changed; bit 6 = offset_value_6 changed; bit 7 = offset_value_7 changed; bit 8 = offset_value_8 changed | |||
| HR | 6doc 6 (0x0006) | manual_occupancy | 0 = unoccupied, any other value = occupied (external occupancy input). | UINT16 | Read/write | 0 = Unoccupied | |||
| HR | 32doc 32 (0x0020) | ir_remote_control_command | High byte button code, low byte remote id of the last IR command. | UINT16 | Read | ||||
| HR | 48doc 48 (0x0030) | sensor_value_0 internal temperature | Assumes the default Modbus unit system °C (config_flags MU = 1). | INT16 | × 0.1 | °C | Read | ||
| HR | 49doc 49 (0x0031) | sensor_value_1 external temperature | Sensor wired to EB3 and GND; default MU = °C assumed. | INT16 | × 0.1 | °C | Read | ||
| HR | 50doc 50 (0x0032) | sensor_value_2 relative humidity | Raw x 5 x 10^-3. | UINT16 | × 0.005 | %RH | Read | ||
| HR | 51doc 51 (0x0033) | sensor_value_3 dew point | Default MU = °C assumed. | INT16 | × 0.1 | °C | Read | ||
| HR | 53doc 53 (0x0035) | sensor_value_5 amount CO2 | LSTAT-802 models only. | UINT16 | ppm | Read | |||
| HR | 54doc 54 (0x0036) | sensor_value_6 L-STAT supply voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 64doc 64 (0x0040) | display_value_0 | Value written by the master for display; scaling per its configuration (256+). | INT16 | Read/write | ||||
| HR | 65doc 65 (0x0041) | display_value_1 | As display_value_0. | INT16 | Read/write | ||||
| HR | 66doc 66 (0x0042) | display_value_2 | As display_value_0. | INT16 | Read/write | ||||
| HR | 67doc 67 (0x0043) | display_value_3 | As display_value_0. | INT16 | Read/write | ||||
| HR | 176doc 176 (0x00B0) | modbus_parameter | Bits 13-12 parity, 11-8 baud code, 7-0 slave address. Takes effect after reboot. | UINT16 | Read/write | ||||
| HR | 192doc 192 (0x00C0) | config_flags | Bits 9-8 MU Modbus unit (0 K, 1 °C, 2 °F); 11-10 display unit; bit 0 reboot. | UINT16 | Read/write | ||||
| HR | 384doc 384 (0x0180) | set_point_0 | Signed; scaling follows the unit set in set point config (320+). Default 220. | INT16 | Read/write | ||||
| HR | 385doc 385 (0x0181) | set_point_1 | Signed; scaling follows its set point configuration. | INT16 | Read/write | ||||
| HR | 386doc 386 (0x0182) | set_point_2 | Signed; scaling follows its set point configuration. | INT16 | Read/write | ||||
| HR | 387doc 387 (0x0183) | set_point_3 | Signed; scaling follows its set point configuration. | INT16 | Read/write | ||||
| HR | 480doc 480 (0x01E0) | offset_value_0 | Offset added to its sensor value; same scaling as that sensor. | INT16 | Read/write | ||||
| HR | 560doc 560-569 (0x0230-0x0239) | product_code_string | Model / product code text. | STRING[20] | Read | ||||
| HR | 576doc 576-585 (0x0240-0x0249) | serial_number_string | STRING[20] | Read | |||||
| HR | 592doc 592-595 (0x0250-0x0253) | firmware_version_string | STRING[8] | Read |
Notes on this map
- The download link is named 3.2.4 but the document inside is printed as version 3.2.8.
- Only function codes 03 (read holding registers) and 06 (write single register) are supported, so multi-register values and strings must be read with FC03 and written one register at a time.
- Sensor scaling comes from the manual's value-scaling table: temperatures x0.1 in the configured Modbus unit system (factory default °C; K uses a -2740 offset, °F also x0.1), humidity raw x 0.005 %RH, CO2 1 ppm, voltage x0.1 V.
- Set points, set point min/max, display values and offsets are listed raw (scale 1) because their scale depends on the unit chosen in each value's configuration register (addresses 256-351); apply the manual's scaling table for that unit (e.g. °C x0.1, l/s x0.1, inWC x0.001).
- Only set_point_0..3, display_value_0..3 and offset_value_0 are listed; the full blocks are set_point 384-399, max 416-431, min 448-463, display values 64-79, offsets 480-488.
- Left out: system_time (112-113), Modbus statistics (128+) and firmware/bootloader dates, because the manual does not say which of the two 16-bit halves is the high word; CPU temperature/voltage (55-56), whose scaling is not given.
- Configuration and device-setting registers are stored in flash with limited write cycles; do not write them cyclically.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the LOYTEC L-STAT network thermostat / room operating unit (Modbus RTU)
What Modbus registers does the LOYTEC L-STAT network thermostat / room operating unit (Modbus RTU) have?
This map lists 28 registers: 28 holding registers. 17 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the LOYTEC L-STAT network thermostat / room operating unit (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each register is printed with its decimal address and hex equivalent (e.g. 48 / 0x0030). The table starts at register address 0 (present_state, 0x0000), which only exists in 0-based protocol addressing, so these are the wire addresses. 'documented' keeps both forms.
What are the minimum Modbus registers to integrate the LOYTEC L-STAT network thermostat / room operating unit (Modbus RTU)?
Start with HR 48 sensor_value_0 internal temperature (Room temperature); HR 50 sensor_value_2 relative humidity (Relative humidity); HR 53 sensor_value_5 amount CO2 (CO2 (802 only)); HR 384 set_point_0 (Main set point); HR 3 change_flags_set_points (Which set points the user changed); HR 1 short_pressed (Button presses / occupancy).
How do I enable Modbus control of the LOYTEC L-STAT network thermostat / room operating unit (Modbus RTU)?
No enable step; the panel answers as a slave at address 1 out of the box. Change address/baud/parity in EDIT mode on the panel or in modbus_parameter (176), then reboot.
Where is the official LOYTEC L-STAT network thermostat / room operating unit (Modbus RTU) Modbus documentation?
The source is L-STAT User Manual (88085811, version 3.2.8), published free by LOYTEC at https://www.loytec.com/component/docman/doc_download/2159-l-stat-user-manual-3-2-4.
Other hvac equipment register maps
- Thermostat / fan coil controller
Neptronic EFCB Series networkable fan coil controller (Modbus RTU)
Neptronic EFCB Series fan coil controllers (24, 120 and 240 Vac; 2 or 4 relays) with the Modbus communication module, guide EFCB-Modbus Guide-260626.
Also known as: EFCB10TU2, EFCB10TU4, EFCB11TU2, EFCB11TU4, EFCB12TU2, EFCB12TU4, EFCB fan coil controller - Air handler evaporative cooler (adiabatic cooling / humidification)
Neptronic SKVF evaporative cooler / humidifier (Modbus communication module)
Neptronic SKVF series evaporative coolers with the Modbus communication module, guide SKVF-Modbus Guide-211025.
Also known as: SKVF Evaporative Cooler, SKVF Series, Neptronic SKVF Modbus - Thermostat / room controller (chilled beam, fan coil water circuits)
Swegon CONDUCTOR W1 room controller (waterborne cooling/heating, Modbus RTU)
Swegon CONDUCTOR W1 room controller, software 1.38 and later (technical manual updated 2015-06-15).
Also known as: CONDUCTOR RE W1, Conductor W1, 942334001 - Air handler (residential heat recovery ventilation)
Vasco SAB RVU ventilation unit controller (D150 Compact, Energy Plus)
Vasco SAB RVU controller boards (models 0x52xx residential and 0x53xx Energy Plus) with protocol release 0x0006, manual 90.01.06.53.
Also known as: D150 Compact, Energy Plus ENY-P1, ENY-P2, ENY-P3, ENY-P4, ESP170V, ESP270, ESP360, ESP460 - Air handler (in-row data-centre cooling unit)
APC (Schneider Electric) InRow ACRD60x / ACRC60x cooling units (Modbus register map 990-5786)
APC / Schneider Electric InRow ACRD60x and ACRC60x in-row cooling units, register map part number 990-5786A.
Also known as: ACRD60x, ACRC60x, InRow ACRD60x, InRow ACRC60x, 990-5786 - Air handler humidifier (high-pressure room system)
Condair Vita high-pressure humidification system (Integrated Controller, Modbus RTU/TCP)
Condair Vita system with the Integrated Controller, per addendum 2603326-G.
Also known as: Condair Vita, Vita System Master
All hvac equipment Modbus register maps →
Source: L-STAT User Manual · 88085811, version 3.2.8. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.