  4. INMBSMID004I000 / 008I000 / 032I000 Midea AC to Modbus RTU interface (4 to 32 units)

VRF / split AC gateway · Modbus register map

Intesis (HMS Networks) INMBSMID004I000 / 008I000 / 032I000 Midea AC to Modbus RTU interface (4 to 32 units) Modbus register map

Updated 19 November 2026

Short answer

Modbus RTU slave on the XYE bus of Midea commercial and VRF indoor units. Each of up to 4, 8 or 32 index slots maps to an indoor unit address and has a 20-register block for on/off, mode, fan, vane, setpoint, room temperature, alarm, error and remote lock; registers 0..8 send commands to all units.

This page lists 21 Modbus registers for the Intesis (HMS Networks) INMBSMID004I000 / 008I000 / 032I000 Midea AC to Modbus RTU interface (4 to 32 units) — 14 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Intesis (HMS Networks)’s own free documentation (linked below) and checked against it.

Manufacturer
Intesis (HMS Networks)
Model
INMBSMID004I000 / 008I000 / 032I000 Midea AC to Modbus RTU interface (4 to 32 units)
Equipment type
VRF / split AC gateway
Registers
21 (14 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8N2
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
INMBSMID004I000, INMBSMID008I000, INMBSMID032I000, MD-AC-MBS-4, MD-AC-MBS-8, MD-AC-MBS-32
Source document
Intesis INMBSMID***I000 Modbus RTU (EIA-485) Interface for Midea air conditioners - User's Manual · User Manual v1.7 EN · rev. 2024-08
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Intesis (HMS Networks) INMBSMID004I000 / 008I000 / 032I000 Midea AC to Modbus RTU interface (4 to 32 units)

Integration in brief

Address the indoor units 0..63 in the AC system, write each unit's address into its slot (1000 + 20n + 9), then read and write the 20-register slot blocks.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 1009Indoor unit address assignmentUINT16Map slot 0 to an indoor unit addressRead/write
HR 1000AC unit on/offUINT16On/offRead/write
HR 1001AC unit modeUINT16ModeRead/write
HR 1002AC unit fan speedUINT16Fan speedRead/write
HR 1004AC unit temperature setpointUINT16SetpointRead/write
HR 1005AC unit temperature referenceUINT16Room temperatureRead
HR 1007AC error codeUINT16Error / communication errorRead

Enable Modbus control & writes

Write the AC-system address of each indoor unit into its slot's assignment register (1000 + 20n + 9); the slot index n is not the unit's address.

Byte order & addressing

Network setup

Watch out for

Intesis (HMS Networks) INMBSMID004I000 / 008I000 / 032I000 Midea AC to Modbus RTU interface (4 to 32 units) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

21 of 21 shown
Intesis (HMS Networks) INMBSMID004I000 / 008I000 / 032I000 Midea AC to Modbus RTU interface (4 to 32 units) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0All units on/offUINT16Write0 = Off; 1 = On
HR1All units modeUINT16Write0 = Auto; 1 = Heat; 2 = Dry; 3 = Fan; 4 = Cool
HR2All units fan speedUINT16Write0 = Auto; 1 = SP1; 2 = SP2; 3 = SP3
HR3All units vane positionUINT16Write0 = Auto/Stop; 10 = Swing
HR4All units temperature setpoint17..30 °C (63..86 °F). SW4 x1 °C assumed (x10: 0.1, or °F).UINT16°CWrite
HR8All units remote lockBlocks wired remotes on the MD-RC bus. Non-volatile.UINT16Write0 = Off; 1 = On
HR1000doc (1000 + 20*n + 0)AC unit on/offIndex n = 0 shown; see notes.UINT16Read/write0 = Off; 1 = On
HR1001doc (1000 + 20*n + 1)AC unit modeAvailable modes depend on the unit.UINT16Read/write0 = Auto; 1 = Heat; 2 = Dry; 3 = Fan; 4 = Cool
HR1002doc (1000 + 20*n + 2)AC unit fan speedUINT16Read/write0 = Auto; 1 = SP1; 2 = SP2; 3 = SP3
HR1003doc (1000 + 20*n + 3)AC unit up/down vane positionUINT16Read/write0 = Off; 10 = Swing
HR1004doc (1000 + 20*n + 4)AC unit temperature setpoint17..30 °C (63..86 °F). SW4 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead/write
HR1005doc (1000 + 20*n + 5)AC unit temperature referenceSW4 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead
HR1006doc (1000 + 20*n + 6)AC alarm statusUINT16Read0 = No alarm; 1 = Alarm
HR1007doc (1000 + 20*n + 7)AC error code0 = no error, 65535 = interface-to-unit communication error, other = unit code.UINT16Read0 = No error active; 65535 = Interface to AC unit communication error
HR1008doc (1000 + 20*n + 8)Remote lockNon-volatile.UINT16Read/write0 = Off; 1 = On
HR1009doc (1000 + 20*n + 9)Indoor unit address assignmentMidea address (0..63) of the unit handled by index n.UINT16Read/write
HR2000Device IDReads 0x2200.UINT16Read
HR2031CapacityMax indoor units of this model.UINT16Read4 = 4 indoor units; 8 = 8 indoor units; 32 = 32 indoor units
HR2041Modbus slave address1..63.UINT16Read
HR2050Software versionUINT16Read
HR2099Reset / reboot deviceUINT16Write1 = Reset

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Intesis (HMS Networks) INMBSMID004I000 / 008I000 / 032I000 Midea AC to Modbus RTU interface (4 to 32 units)

What Modbus registers does the Intesis (HMS Networks) INMBSMID004I000 / 008I000 / 032I000 Midea AC to Modbus RTU interface (4 to 32 units) have?

This map lists 21 registers: 21 holding registers. 14 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Intesis (HMS Networks) INMBSMID004I000 / 008I000 / 032I000 Midea AC to Modbus RTU interface (4 to 32 units) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Tables give a 'protocol address' and a 'PLC address' (protocol + 1); the protocol address is the wire address. Index n (0..31) uses protocol address 1000 + 20 x n + offset. This file lists n = 0 (1000..1009).

What are the minimum Modbus registers to integrate the Intesis (HMS Networks) INMBSMID004I000 / 008I000 / 032I000 Midea AC to Modbus RTU interface (4 to 32 units)?

Start with HR 1009 Indoor unit address assignment (Map slot 0 to an indoor unit address); HR 1000 AC unit on/off (On/off); HR 1001 AC unit mode (Mode); HR 1002 AC unit fan speed (Fan speed); HR 1004 AC unit temperature setpoint (Setpoint); HR 1005 AC unit temperature reference (Room temperature); HR 1007 AC error code (Error / communication error).

How do I enable Modbus control of the Intesis (HMS Networks) INMBSMID004I000 / 008I000 / 032I000 Midea AC to Modbus RTU interface (4 to 32 units)?

Write the AC-system address of each indoor unit into its slot's assignment register (1000 + 20n + 9); the slot index n is not the unit's address.

Where is the official Intesis (HMS Networks) INMBSMID004I000 / 008I000 / 032I000 Midea AC to Modbus RTU interface (4 to 32 units) Modbus documentation?

The source is Intesis INMBSMID***I000 Modbus RTU (EIA-485) Interface for Midea air conditioners - User's Manual (User Manual v1.7 EN), revision 2024-08, published free by Intesis (HMS Networks) at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-inmbsmidxxxi000.pdf.

More Intesis (HMS Networks) Modbus register maps

Other ac & vrf gateways register maps

All ac & vrf gateways Modbus register maps →

Source: Intesis INMBSMID***I000 Modbus RTU (EIA-485) Interface for Midea air conditioners - User's Manual · User Manual v1.7 EN · rev. 2024-08. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.