Easy Modbus
  1. Home
  2. Modbus register maps
  3. Intesis (HMS Networks)
  4. IN770AIR***O000 700 Series Air Gateway, Panasonic application (Modbus)

VRF / split AC gateway · Modbus register map

Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Panasonic application (Modbus) Modbus register map

Updated 19 November 2026

Short answer

Intesis 700 Series gateway on Panasonic P-Link / S-Link (U1U2) systems serving Modbus RTU and TCP. Each indoor unit gets a 100-register block with control, temperatures, setpoint limits, error and occupancy values; outdoor units get pressure and demand-limit registers; low addresses hold occupancy setpoints and all-unit commands.

This page lists 58 Modbus registers for the Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Panasonic application (Modbus) — 39 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Intesis (HMS Networks)’s own free documentation (linked below) and checked against it.

Manufacturer
Intesis (HMS Networks)
Model
IN770AIR***O000 700 Series Air Gateway, Panasonic application (Modbus)
Equipment type
VRF / split AC gateway
Registers
58 (39 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000
Source document
700 Series Air Gateway - IN770AIR***O000, Panasonic to Modbus, KNX, BACnet, MQTT and Home Automation - User Manual · User Manual Version 1.1.7 · rev. 2025-12-09
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Panasonic application (Modbus)

Integration in brief

Pick the Panasonic application and the Modbus interface in Intesis MAPS, discover or add the units, send the project, then read and write each unit's block.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 100IU on/offUINT16On/offRead/write
HR 101IU operation modeUINT16ModeRead/write
HR 102IU fan speedUINT16Fan speedRead/write
HR 104IU temperature setpointINT16Setpoint (x10)Read/write
HR 105IU AC ambient temperatureINT16Room temperature (x10)Read
HR 119IU unit error codeUINT16Error codeRead
HR 122IU communication errorUINT16Communication errorRead
HR 7025OU communication errorUINT16Outdoor unit communication errorRead

Enable Modbus control & writes

The gateway must be configured with Intesis MAPS (Panasonic 770 project template, Modbus selected) and the project sent to it; the unit numbers used in the address formulas are the indoor / outdoor unit addresses.

Byte order & addressing

Network setup

Watch out for

Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Panasonic application (Modbus) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

58 of 58 shown
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Panasonic application (Modbus) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0Occupancy cool setpointTenths; -15..60 °C.INT16× 0.1°CRead/write
HR1Occupancy heat setpointTenths; -15..60 °C.INT16× 0.1°CRead/write
HR2Unoccupancy cool setpointTenths; -15..60 °C.INT16× 0.1°CRead/write
HR3Unoccupancy heat setpointTenths; -15..60 °C.INT16× 0.1°CRead/write
HR4Occupancy continuous checkUINT16Read/write0 = Disabled; 1 = Enabled
HR5Unoccupancy deadband actionUINT16Read/write0 = Off; 1 = Current mode
HR6On (all units)UINT16Write1 = Execute
HR7Off (all units)UINT16Write1 = Execute
HR8Mode Auto (all units)UINT16Write1 = Execute
HR9Mode Heat (all units)UINT16Write1 = Execute
HR10Mode Dry (all units)UINT16Write1 = Execute
HR11Mode Fan (all units)UINT16Write1 = Execute
HR12Mode Cool (all units)UINT16Write1 = Execute
HR13Fan speed Auto (all units)UINT16Write1 = Execute
HR14Fan speed Low (all units)UINT16Write1 = Execute
HR15Fan speed Med (all units)UINT16Write1 = Execute
HR16Fan speed High (all units)UINT16Write1 = Execute
HR17Vanes stop (all units)UINT16Write1 = Execute
HR18Vanes position 1 (all units)UINT16Write1 = Execute
HR19Vanes position 2 (all units)UINT16Write1 = Execute
HR20Vanes position 3 (all units)UINT16Write1 = Execute
HR21Vanes position 4 (all units)UINT16Write1 = Execute
HR22Vanes position 5 (all units)UINT16Write1 = Execute
HR23Vanes swing (all units)UINT16Write1 = Execute
HR100doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 0IU on/offLine 1, indoor unit 1 shown; see notes.UINT16Read/write0 = Off; 1 = On
HR101doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 1IU operation modeUINT16Read/write0 = Auto; 1 = Heat; 2 = Dry; 3 = Fan; 4 = Cool; 5 = AutoHeat; 6 = AutoCool
HR102doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 2IU fan speedUINT16Read/write0 = Auto; 1 = Low; 2 = Low+; 3 = Medium; 4 = Medium+; 5 = High
HR103doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 3IU vane positionUINT16Read/write0 = Stop; 1 = Position 1; 2 = Position 2; 3 = Position 3; 4 = Position 4; 5 = Position 5; 10 = Swing
HR104doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 4IU temperature setpointTenths of °C.INT16× 0.1°CRead/write
HR105doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 5IU AC ambient temperatureTenths of °C. -35..92.5.INT16× 0.1°CRead
HR106doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 6IU wired remote controller sensorUINT16Read/write0 = Body sensor; 1 = Remote control sensor
HR107doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 7IU discharge setpoint coolTenths of °C. Printed range -10..10.INT16× 0.1°CRead/write
HR108doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 8IU discharge setpoint heatTenths of °C. Printed range -10..10.INT16× 0.1°CRead/write
HR109doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 9IU discharge current temperatureTenths of °C.INT16× 0.1°CRead
HR110doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 10IU heat exchanger temperatureTenths of °C. -1..26.INT16× 0.1°CRead
HR111doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 11IU heat setpoint upper limitTenths of °C.INT16× 0.1°CRead
HR112doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 12IU heat setpoint lower limitTenths of °C.INT16× 0.1°CRead
HR113doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 13IU cool setpoint upper limitTenths of °C.INT16× 0.1°CRead
HR114doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 14IU cool setpoint lower limitTenths of °C.INT16× 0.1°CRead
HR115doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 15IU dry setpoint upper limitTenths of °C.INT16× 0.1°CRead
HR116doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 16IU dry setpoint lower limitTenths of °C.INT16× 0.1°CRead
HR117doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 17IU auto setpoint upper limitTenths of °C.INT16× 0.1°CRead
HR118doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 18IU auto setpoint lower limitTenths of °C.INT16× 0.1°CRead
HR119doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 19IU unit error code0 = no error, 1..255 = error.UINT16Read0 = No error
HR120doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 20IU filter alarmUINT16Read0 = Normal; 1 = Alarm
HR121doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 21IU filter alarm resetUINT16Write1 = Reset
HR122doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 22IU communication errorUINT16Read0 = No error; 1 = Error
HR123doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 23IU allow on/off from RCUINT16Read/write0 = Allow; 1 = Not allow
HR124doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 24IU allow mode from RCUINT16Read/write0 = Allow; 1 = Not allow
HR125doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 25IU allow setpoint from RCUINT16Read/write0 = Allow; 1 = Not allow
HR126doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 26IU unit typeUINT16Read0 = Not defined; 1 = TBD; 2 = GHP; 3 = PAC; 4 = VRF
HR127doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 27IU occupancyUINT16Read/write1 = Occupied; 2 = Unoccupied; 3 = Disable
HR128doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 28IU Modbus ambient temperatureRoom temperature written from Modbus; tenths.INT16× 0.1°CRead/write
HR129doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 29IU AC real temperature setpointTenths of °C.INT16× 0.1°CRead
HR7025doc (OU address[1..31] × 25) + ((L - 1) × 10000) + 7000) + 0OU communication errorLine 1, outdoor unit 1 shown.UINT16Read0 = No error; 1 = Error
HR7026doc (OU address[1..31] × 25) + ((L - 1) × 10000) + 7000) + 1OU demand limit ratio0..200 %, 255 = no limit.UINT16%Read/write255 = No limit
HR7027doc (OU address[1..31] × 25) + ((L - 1) × 10000) + 7000) + 2OU high pressure sensorbar x 10.UINT16× 0.1barRead
HR7028doc (OU address[1..31] × 25) + ((L - 1) × 10000) + 7000) + 3OU low pressure sensorbar x 10.UINT16× 0.1barRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Panasonic application (Modbus)

What Modbus registers does the Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Panasonic application (Modbus) have?

This map lists 58 registers: 58 holding registers. 39 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Panasonic application (Modbus) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Occupancy registers start at address 0, so printed addresses are wire addresses. Indoor unit n (1..64) on line L uses n x 100 + (L-1) x 10000 + offset; outdoor unit n (1..31) uses n x 25 + (L-1) x 10000 + 7000 + offset. This file lists line 1, indoor 1 (100..129) and outdoor 1 (7025..7028).

What are the minimum Modbus registers to integrate the Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Panasonic application (Modbus)?

Start with HR 100 IU on/off (On/off); HR 101 IU operation mode (Mode); HR 102 IU fan speed (Fan speed); HR 104 IU temperature setpoint (Setpoint (x10)); HR 105 IU AC ambient temperature (Room temperature (x10)); HR 119 IU unit error code (Error code); HR 122 IU communication error (Communication error); HR 7025 OU communication error (Outdoor unit communication error).

How do I enable Modbus control of the Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Panasonic application (Modbus)?

The gateway must be configured with Intesis MAPS (Panasonic 770 project template, Modbus selected) and the project sent to it; the unit numbers used in the address formulas are the indoor / outdoor unit addresses.

Where is the official Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Panasonic application (Modbus) Modbus documentation?

The source is 700 Series Air Gateway - IN770AIR***O000, Panasonic to Modbus, KNX, BACnet, MQTT and Home Automation - User Manual (User Manual Version 1.1.7), revision 2025-12-09, published free by Intesis (HMS Networks) at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-in770panxxxo000.pdf.