VRF / split AC gateway · Modbus register map
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Panasonic application (Modbus) Modbus register map
Updated 19 November 2026
Intesis 700 Series gateway on Panasonic P-Link / S-Link (U1U2) systems serving Modbus RTU and TCP. Each indoor unit gets a 100-register block with control, temperatures, setpoint limits, error and occupancy values; outdoor units get pressure and demand-limit registers; low addresses hold occupancy setpoints and all-unit commands.
This page lists 58 Modbus registers for the Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Panasonic application (Modbus) — 39 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Intesis (HMS Networks)’s own free documentation (linked below) and checked against it.
- Manufacturer
- Intesis (HMS Networks)
- Model
- IN770AIR***O000 700 Series Air Gateway, Panasonic application (Modbus)
- Equipment type
- VRF / split AC gateway
- Registers
- 58 (39 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000
Integration notes: Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Panasonic application (Modbus)
Pick the Panasonic application and the Modbus interface in Intesis MAPS, discover or add the units, send the project, then read and write each unit's block.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 100 | IU on/off | UINT16 | On/off | Read/write |
| HR 101 | IU operation mode | UINT16 | Mode | Read/write |
| HR 102 | IU fan speed | UINT16 | Fan speed | Read/write |
| HR 104 | IU temperature setpoint | INT16 | Setpoint (x10) | Read/write |
| HR 105 | IU AC ambient temperature | INT16 | Room temperature (x10) | Read |
| HR 119 | IU unit error code | UINT16 | Error code | Read |
| HR 122 | IU communication error | UINT16 | Communication error | Read |
| HR 7025 | OU communication error | UINT16 | Outdoor unit communication error | Read |
Enable Modbus control & writes
The gateway must be configured with Intesis MAPS (Panasonic 770 project template, Modbus selected) and the project sent to it; the unit numbers used in the address formulas are the indoor / outdoor unit addresses.
Byte order & addressing
- Writes accept FC06 (single register) only.
- Trigger (T) registers act when 1 is written and are not meant to be read.
Network setup
- All Modbus settings (RTU or TCP, slave address, baud, parity) are made with the Intesis MAPS tool; the manual gives no factory serial settings.
- On first power-up DHCP is tried for 30 seconds, then the gateway falls back to 192.168.100.246.
- Modbus RTU uses the EIA-485 port (A+, B-); bias and 120 ohm termination are on DIP switch block SW A.
Watch out for
- The line number (1 or 2) moves the whole indoor and outdoor map by 10000.
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Panasonic application (Modbus) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0 | Occupancy cool setpoint | Tenths; -15..60 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1 | Occupancy heat setpoint | Tenths; -15..60 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 2 | Unoccupancy cool setpoint | Tenths; -15..60 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 3 | Unoccupancy heat setpoint | Tenths; -15..60 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 4 | Occupancy continuous check | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 5 | Unoccupancy deadband action | UINT16 | Read/write | 0 = Off; 1 = Current mode | ||||
| HR | 6 | On (all units) | UINT16 | Write | 1 = Execute | ||||
| HR | 7 | Off (all units) | UINT16 | Write | 1 = Execute | ||||
| HR | 8 | Mode Auto (all units) | UINT16 | Write | 1 = Execute | ||||
| HR | 9 | Mode Heat (all units) | UINT16 | Write | 1 = Execute | ||||
| HR | 10 | Mode Dry (all units) | UINT16 | Write | 1 = Execute | ||||
| HR | 11 | Mode Fan (all units) | UINT16 | Write | 1 = Execute | ||||
| HR | 12 | Mode Cool (all units) | UINT16 | Write | 1 = Execute | ||||
| HR | 13 | Fan speed Auto (all units) | UINT16 | Write | 1 = Execute | ||||
| HR | 14 | Fan speed Low (all units) | UINT16 | Write | 1 = Execute | ||||
| HR | 15 | Fan speed Med (all units) | UINT16 | Write | 1 = Execute | ||||
| HR | 16 | Fan speed High (all units) | UINT16 | Write | 1 = Execute | ||||
| HR | 17 | Vanes stop (all units) | UINT16 | Write | 1 = Execute | ||||
| HR | 18 | Vanes position 1 (all units) | UINT16 | Write | 1 = Execute | ||||
| HR | 19 | Vanes position 2 (all units) | UINT16 | Write | 1 = Execute | ||||
| HR | 20 | Vanes position 3 (all units) | UINT16 | Write | 1 = Execute | ||||
| HR | 21 | Vanes position 4 (all units) | UINT16 | Write | 1 = Execute | ||||
| HR | 22 | Vanes position 5 (all units) | UINT16 | Write | 1 = Execute | ||||
| HR | 23 | Vanes swing (all units) | UINT16 | Write | 1 = Execute | ||||
| HR | 100doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 0 | IU on/off | Line 1, indoor unit 1 shown; see notes. | UINT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 101doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 1 | IU operation mode | UINT16 | Read/write | 0 = Auto; 1 = Heat; 2 = Dry; 3 = Fan; 4 = Cool; 5 = AutoHeat; 6 = AutoCool | ||||
| HR | 102doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 2 | IU fan speed | UINT16 | Read/write | 0 = Auto; 1 = Low; 2 = Low+; 3 = Medium; 4 = Medium+; 5 = High | ||||
| HR | 103doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 3 | IU vane position | UINT16 | Read/write | 0 = Stop; 1 = Position 1; 2 = Position 2; 3 = Position 3; 4 = Position 4; 5 = Position 5; 10 = Swing | ||||
| HR | 104doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 4 | IU temperature setpoint | Tenths of °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 105doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 5 | IU AC ambient temperature | Tenths of °C. -35..92.5. | INT16 | × 0.1 | °C | Read | ||
| HR | 106doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 6 | IU wired remote controller sensor | UINT16 | Read/write | 0 = Body sensor; 1 = Remote control sensor | ||||
| HR | 107doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 7 | IU discharge setpoint cool | Tenths of °C. Printed range -10..10. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 108doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 8 | IU discharge setpoint heat | Tenths of °C. Printed range -10..10. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 109doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 9 | IU discharge current temperature | Tenths of °C. | INT16 | × 0.1 | °C | Read | ||
| HR | 110doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 10 | IU heat exchanger temperature | Tenths of °C. -1..26. | INT16 | × 0.1 | °C | Read | ||
| HR | 111doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 11 | IU heat setpoint upper limit | Tenths of °C. | INT16 | × 0.1 | °C | Read | ||
| HR | 112doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 12 | IU heat setpoint lower limit | Tenths of °C. | INT16 | × 0.1 | °C | Read | ||
| HR | 113doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 13 | IU cool setpoint upper limit | Tenths of °C. | INT16 | × 0.1 | °C | Read | ||
| HR | 114doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 14 | IU cool setpoint lower limit | Tenths of °C. | INT16 | × 0.1 | °C | Read | ||
| HR | 115doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 15 | IU dry setpoint upper limit | Tenths of °C. | INT16 | × 0.1 | °C | Read | ||
| HR | 116doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 16 | IU dry setpoint lower limit | Tenths of °C. | INT16 | × 0.1 | °C | Read | ||
| HR | 117doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 17 | IU auto setpoint upper limit | Tenths of °C. | INT16 | × 0.1 | °C | Read | ||
| HR | 118doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 18 | IU auto setpoint lower limit | Tenths of °C. | INT16 | × 0.1 | °C | Read | ||
| HR | 119doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 19 | IU unit error code | 0 = no error, 1..255 = error. | UINT16 | Read | 0 = No error | |||
| HR | 120doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 20 | IU filter alarm | UINT16 | Read | 0 = Normal; 1 = Alarm | ||||
| HR | 121doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 21 | IU filter alarm reset | UINT16 | Write | 1 = Reset | ||||
| HR | 122doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 22 | IU communication error | UINT16 | Read | 0 = No error; 1 = Error | ||||
| HR | 123doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 23 | IU allow on/off from RC | UINT16 | Read/write | 0 = Allow; 1 = Not allow | ||||
| HR | 124doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 24 | IU allow mode from RC | UINT16 | Read/write | 0 = Allow; 1 = Not allow | ||||
| HR | 125doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 25 | IU allow setpoint from RC | UINT16 | Read/write | 0 = Allow; 1 = Not allow | ||||
| HR | 126doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 26 | IU unit type | UINT16 | Read | 0 = Not defined; 1 = TBD; 2 = GHP; 3 = PAC; 4 = VRF | ||||
| HR | 127doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 27 | IU occupancy | UINT16 | Read/write | 1 = Occupied; 2 = Unoccupied; 3 = Disable | ||||
| HR | 128doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 28 | IU Modbus ambient temperature | Room temperature written from Modbus; tenths. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 129doc (IU address[1..64] × 100) + ((L - 1) × 10000) + 29 | IU AC real temperature setpoint | Tenths of °C. | INT16 | × 0.1 | °C | Read | ||
| HR | 7025doc (OU address[1..31] × 25) + ((L - 1) × 10000) + 7000) + 0 | OU communication error | Line 1, outdoor unit 1 shown. | UINT16 | Read | 0 = No error; 1 = Error | |||
| HR | 7026doc (OU address[1..31] × 25) + ((L - 1) × 10000) + 7000) + 1 | OU demand limit ratio | 0..200 %, 255 = no limit. | UINT16 | % | Read/write | 255 = No limit | ||
| HR | 7027doc (OU address[1..31] × 25) + ((L - 1) × 10000) + 7000) + 2 | OU high pressure sensor | bar x 10. | UINT16 | × 0.1 | bar | Read | ||
| HR | 7028doc (OU address[1..31] × 25) + ((L - 1) × 10000) + 7000) + 3 | OU low pressure sensor | bar x 10. | UINT16 | × 0.1 | bar | Read |
Notes on this map
- For indoor unit n add (n-1) x 100, for outdoor unit n add (n-1) x 25, and add 10000 for line 2.
- The all-unit temperature setpoint is printed at address 14, which is already the 'fan speed Low (all units)' address; it is left out.
- Compressor 1..3 operation time (outdoor +4..+6) are left out: a 0..16777215 h range does not fit the single register listed.
- One manual covers the three licence sizes of the same hardware: IN770AIRXXSO000 (4 indoor / 4 outdoor units), IN770AIR00SO000 (16 / 16) and IN770AIR00MO000 (64 indoor / 30 outdoor). The brand application is chosen in Intesis MAPS.
- The manual gives no data type for the registers; values whose printed range goes below zero are listed as INT16, the rest as UINT16.
- The consumption registers (yesterday / today / total, also per heat and cool) are left out: each takes two addresses, but the manual gives neither the word order nor a fixed unit (Wh or kWh is chosen in MAPS).
- Reads use FC03 or FC04; writes use FC06 only. 'T' (trigger) registers act when 1 is written.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Panasonic application (Modbus)
What Modbus registers does the Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Panasonic application (Modbus) have?
This map lists 58 registers: 58 holding registers. 39 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Panasonic application (Modbus) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Occupancy registers start at address 0, so printed addresses are wire addresses. Indoor unit n (1..64) on line L uses n x 100 + (L-1) x 10000 + offset; outdoor unit n (1..31) uses n x 25 + (L-1) x 10000 + 7000 + offset. This file lists line 1, indoor 1 (100..129) and outdoor 1 (7025..7028).
What are the minimum Modbus registers to integrate the Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Panasonic application (Modbus)?
Start with HR 100 IU on/off (On/off); HR 101 IU operation mode (Mode); HR 102 IU fan speed (Fan speed); HR 104 IU temperature setpoint (Setpoint (x10)); HR 105 IU AC ambient temperature (Room temperature (x10)); HR 119 IU unit error code (Error code); HR 122 IU communication error (Communication error); HR 7025 OU communication error (Outdoor unit communication error).
How do I enable Modbus control of the Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Panasonic application (Modbus)?
The gateway must be configured with Intesis MAPS (Panasonic 770 project template, Modbus selected) and the project sent to it; the unit numbers used in the address formulas are the indoor / outdoor unit addresses.
Where is the official Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Panasonic application (Modbus) Modbus documentation?
The source is 700 Series Air Gateway - IN770AIR***O000, Panasonic to Modbus, KNX, BACnet, MQTT and Home Automation - User Manual (User Manual Version 1.1.7), revision 2025-12-09, published free by Intesis (HMS Networks) at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-in770panxxxo000.pdf.
More Intesis (HMS Networks) Modbus register maps
- Heat pump gateway (VRF / split AC gateway)
Intesis (HMS Networks) IN485DAI001A000 Daikin Altherma 3 air-to-water to Modbus RTU / BACnet MS/TP gateway
Intesis (HMS Networks) IN485DAI001A000 gateway for Daikin Altherma 3 air-to-water heat pumps, set to Modbus RTU, per user manual version 1.0.2 (2025-07-18).
Also known as: IN485DAI001A000, Daikin Altherma 3 Modbus, Intesis Altherma 3, HMS Daikin Altherma gateway - Heat pump gateway (VRF / split AC gateway)
Intesis (HMS Networks) IN485MIT001A000 Mitsubishi Electric Ecodan air-to-water to Modbus RTU / BACnet MS/TP gateway
Intesis (HMS Networks) IN485MIT001A000 gateway on the CN105 socket of Mitsubishi Electric Ecodan air-to-water heat pumps, set to Modbus RTU, per user manual version 1.0.3 (2025-12-02).
Also known as: IN485MIT001A000, Ecodan Modbus, Mitsubishi Ecodan Modbus RTU, Intesis Ecodan, HMS Ecodan gateway - VRF / split AC gateway
Intesis (HMS Networks) IN485SAM001R000 Samsung AC to Modbus RTU / BACnet MS/TP gateway
Samsung indoor units on the F3F4 remote-controller bus, gateway set to Modbus RTU (SW1-5 ON); user manual version 1.0.0.
Also known as: IN485SAM001R000, Intesis Samsung BACnet MS/TP Modbus - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Bosch application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Bosch application (XYE bus), Modbus RTU / TCP server, user manual version 1.0.13 (2025-12-09).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Midea application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Midea application (XYE bus), Modbus RTU / TCP server, user manual version 1.0.22 (2025-12-09).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Mitsubishi Electric City Multi application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Mitsubishi Electric City Multi application (M-NET centralised controllers (AE-200, EW-50, G-50 and others)), Modbus RTU / TCP server, user manual version 1.0.19 (2026-03-16).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSACA001I000 XYE-bus air conditioner to Modbus RTU interface (1 unit)
INMBSACA001I000, user manual v1.8 EN; one indoor unit at unit address 0 on its own XYE bus.
Also known as: INMBSACA001I000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSACA004I000 / 008I000 / 032I000 XYE-bus air conditioner to Modbus RTU interface (4 to 32 units)
INMBSACA004I000 / INMBSACA008I000 / INMBSACA032I000, user manual v1.8 EN; up to 4, 8 or 32 indoor units on one XYE bus.
Also known as: INMBSACA004I000, INMBSACA008I000, INMBSACA032I000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSDAI001I000 Daikin domestic AC to Modbus RTU gateway
Single Daikin domestic (S21-connector) indoor unit via INMBSDAI001I000, user manual v1.0.2.
Also known as: INMBSDAI001I000, Intesis Daikin domestic Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSDAI001R000 Daikin VRV / Sky Air to Modbus RTU gateway
One Daikin VRV or Sky Air indoor unit (or group) on the P1P2 bus via INMBSDAI001R000, user manual v1.0.1.
Also known as: INMBSDAI001R000, Intesis Daikin VRV Modbus - Lighting gateway (DALI-2 to Modbus)
Intesis (HMS Networks) INMBSDAL0640000 / INMBSDAL1280000 DALI-2 to Modbus RTU / TCP server
Intesis Modbus Server - DALI with one (0640000, RTU + TCP) or two (1280000, TCP only) DALI channels, Modbus Addresses parameter set to Fixed; user manual r1.2 (09/2021).
Also known as: INMBSDAL0640000, INMBSDAL1280000, Intesis Modbus Server - DALI, Intesis DALI-2 Modbus gateway - VRF / split AC gateway
Intesis (HMS Networks) INMBSFGL001I000 Fujitsu domestic AC to Modbus RTU gateway
One Fujitsu domestic (RAC) or compatible VRF indoor unit, connected to the CN65/CN12/CN6 socket on the indoor board via INMBSFGL001I000, user manual v1.5 (01/2024).
Also known as: INMBSFGL001I000, FJ-AC-MBS-1, Intesis Fujitsu domestic Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSFGL001R000 Fujitsu AC to Modbus RTU gateway
One Fujitsu indoor unit, or a group of up to 16 controlled together as one, on the 3-wire BWR remote-controller bus via INMBSFGL001R000, user manual v2.4 (02/2025).
Also known as: INMBSFGL001R000, Intesis Fujitsu Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSFGL016O000 Fujitsu VRF to Modbus RTU / TCP gateway (up to 16 indoor units)
Intesis Modbus Server - Fujitsu VRF, order code INMBSFGL016O000 (legacy FJ-AC-MBS-16), user manual r1.0 (02/2020); up to 16 indoor units configured in MAPS.
Also known as: INMBSFGL016O000, FJ-AC-MBS-16, Intesis Modbus Server Fujitsu VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIS001R000 Hisense AC to Modbus RTU gateway
Hisense commercial-line indoor units on the AB remote-controller bus, user manual v1.6 (01/2024).
Also known as: INMBSHIS001R000, HS-RC-MBS-1, Intesis Hisense Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIS016O000 Hisense VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)
Intesis Modbus Server - Hisense VRF, order codes INMBSHIS016O000 / INMBSHIS064O000 (legacy HS-AC-MBS-16 / HS-AC-MBS-64), user manual User Manual r1.0 EN.
Also known as: INMBSHIS016O000, INMBSHIS064O000, HS-AC-MBS-16, HS-AC-MBS-64, Intesis Modbus Server Hisense VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIT001R000 Hitachi AC to Modbus RTU gateway
Intesis (HMS Networks) INMBSHIT001R000 interface on the AB bus of one Hitachi commercial-line indoor unit (or group), per user manual v1.6 (01/2024).
Also known as: INMBSHIT001R000, Hitachi Modbus gateway, Intesis Hitachi - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIT016O000 Hitachi VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)
Intesis Modbus Server - Hitachi VRF, order codes INMBSHIT016O000 / INMBSHIT064O000 (legacy HI-AC-MBS-16 / HI-AC-MBS-64), user manual User Manual r1.2 EN.
Also known as: INMBSHIT016O000, INMBSHIT064O000, HI-AC-MBS-16, HI-AC-MBS-64, Intesis Modbus Server Hitachi VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSLGE001R000 LG AC to Modbus RTU gateway
One LG indoor unit on the BYR (wired remote) bus via INMBSLGE001R000 (legacy code LG-RC-MBS-1), user manual v1.9 (01/2024).
Also known as: INMBSLGE001R000, LG-RC-MBS-1, Intesis LG Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSLGE016O000 LG VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)
Intesis Modbus - LG VRF, order codes INMBSLGE016O000 / INMBSLGE064O000 (legacy LG-AC-MBS-16 / -64), user manual r1.0 (04/2020); LG PI485 bus.
Also known as: INMBSLGE016O000, INMBSLGE064O000, LG-AC-MBS-16, LG-AC-MBS-64, Intesis Modbus LG VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSMHI001R000 Mitsubishi Heavy Industries AC to Modbus RTU gateway
Mitsubishi Heavy Industries indoor units (one, or up to 16 controlled together as one) on the XY remote-controller bus, user manual r6.4 (01/2024).
Also known as: INMBSMHI001R000, MH-RC-MBS-1, Intesis Mitsubishi Heavy Industries Modbus, Intesis MHI Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSMHI128O000 / INMBSMHI048O000 Mitsubishi Heavy Industries Superlink to Modbus gateway
Intesis Modbus Server - Mitsubishi Heavy Industries AC, order codes INMBSMHI128O000 (128 units, Superlink-II) and INMBSMHI048O000 (48 units, Superlink-I or II), user's manual r1.0 (05/2012).
Also known as: INMBSMHI128O000, INMBSMHI048O000, MH-AC-MBS-128, MH-AC-MBS-48, Intesis Modbus Server MHI Superlink - VRF / split AC gateway
Intesis (HMS Networks) INMBSMID001I000 Midea AC to Modbus RTU gateway
One Midea commercial / VRF indoor unit on the XYE bus, user manual v1.11.
Also known as: INMBSMID001I000, Intesis Midea Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSMID004I000 / 008I000 / 032I000 Midea AC to Modbus RTU interface (4 to 32 units)
INMBSMID004I000 / INMBSMID008I000 / INMBSMID032I000 / MD-AC-MBS-4 / MD-AC-MBS-8 / MD-AC-MBS-32, user manual v1.7 EN; up to 4, 8 or 32 indoor units on one XYE bus.
Also known as: INMBSMID004I000, INMBSMID008I000, INMBSMID032I000, MD-AC-MBS-4, MD-AC-MBS-8, MD-AC-MBS-32 - VRF / split AC gateway
Intesis (HMS Networks) INMBSMIT001I000 Mitsubishi Electric AC to Modbus RTU gateway
One Mitsubishi Electric Domestic, Mr. Slim or City Multi indoor unit via INMBSMIT001I000, user manual r2.8 (11/2024).
Also known as: INMBSMIT001I000, Intesis Mitsubishi Electric Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSMIT050C000 / INMBSMIT100C000 Mitsubishi Electric City Multi centralised controller to Modbus gateway
Intesis Modbus Server - Mitsubishi Electric CC, order codes INMBSMIT050C000 / INMBSMIT100C000 (legacy ME-AC-MBS-50 / -100), user manual r1.4 (05/2021); talks to City Multi centralised controllers (G-50A, GB-50A, AG-150A, EB-50, EW-50, AE-200 and newer) through their XML interface over Ethernet.
Also known as: INMBSMIT050C000, INMBSMIT100C000, ME-AC-MBS-50, ME-AC-MBS-100, Intesis Modbus Server Mitsubishi Electric CC - Heat pump gateway (VRF / split AC gateway)
Intesis (HMS Networks) INMBSPAN001A100 Panasonic Aquarea H/J/K/L/M air-to-water to Modbus RTU gateway
Intesis (HMS Networks) INMBSPAN001A100 gateway connected to Panasonic Aquarea H, J, K, L and M series air-to-water heat pumps, per user manual version 1.0.2 (2026-02-04).
Also known as: INMBSPAN001A100, Aquarea Modbus, Panasonic Aquarea Modbus RTU, Intesis Aquarea, INMBSPAN001A000 (legacy order code) - VRF / split AC gateway
Intesis (HMS Networks) INMBSPAN001I100 Panasonic Etherea (domestic) AC to Modbus RTU gateway
Panasonic Etherea-line domestic split units, user's manual r1.5 (09/2025). Some registers only on 2013 (PKE series) and later models.
Also known as: INMBSPAN001I100, Intesis Panasonic Etherea Modbus, Intesis Panasonic domestic Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSPAN001R000 Panasonic AC to Modbus RTU gateway
Panasonic / Sanyo ECOi and PACi indoor units (one, or up to 16 controlled together as one) on the R1R2 remote-controller bus, user manual v2.8 (09/2025).
Also known as: INMBSPAN001R000, PA-RC2-MBS-1, Intesis Panasonic Modbus, Intesis Sanyo Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSPAN016O000 / 064O000 / 128O000 Panasonic VRF (P-Link) to Modbus gateway
Intesis Modbus Server - Panasonic, order codes INMBSPAN016O000 / 064O000 / 128O000 (legacy PA-AC-MBS-16 / -64 / -128), user manual r1.1 (11/2020); Panasonic P-Link systems.
Also known as: INMBSPAN016O000, INMBSPAN064O000, INMBSPAN128O000, PA-AC-MBS-16, PA-AC-MBS-64, PA-AC-MBS-128, Intesis Modbus Server Panasonic VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSSAM001R000 Samsung AC to Modbus RTU gateway
Samsung commercial indoor units on the F3F4/V1V2 remote-controller bus, user's manual v1.5 (01/2024).
Also known as: INMBSSAM001R000, Intesis Samsung Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSSAM001R100 Samsung NASA AC to Modbus RTU gateway
Samsung NASA-protocol commercial indoor units on the remote-controller bus, user's manual r1.4 (01/2024).
Also known as: INMBSSAM001R100, Intesis Samsung NASA Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSSAM016O000 Samsung NASA (R1/R2) VRF to Modbus gateway (4 to 64 units)
Intesis Modbus Server - Samsung NASA, order codes INMBSSAM004O000 / 008O000 / 016O000 / 064O000 (legacy SM-ACN-MBS-4/8/16/64), user manual r1.4 (12/2020); Samsung NASA R1/R2 bus.
Also known as: INMBSSAM004O000, INMBSSAM008O000, INMBSSAM016O000, INMBSSAM064O000, SM-ACN-MBS-4, SM-ACN-MBS-8, SM-ACN-MBS-16, SM-ACN-MBS-64 - VRF / split AC gateway
Intesis (HMS Networks) INMBSTOS001R000 Toshiba AC to Modbus RTU gateway
Toshiba Digital Inverter (RAV) and VRF indoor units on the AB remote bus via INMBSTOS001R0xx, user manual r2.9 (01/2024).
Also known as: INMBSTOS001R000, INMBSTOS001R0xx, Intesis Toshiba Modbus
Other ac & vrf gateways register maps
- Air handler DX interface (VRF / split AC gateway)
Mitsubishi Electric PAC-IF013B-E / PAC-SIF013B-E air handling unit interface (Modbus RTU)
PAC-IF013B-E and PAC-SIF013B-E interface controllers linking a Mitsubishi Electric outdoor unit to an AHU coil, Modbus manual dated September 2015 (RG79F084H01).
Also known as: PAC-IF013B-E, PAC-SIF013B-E, PAC-(S)IF013B-E - Air handler (rack-mounted room cooling unit, split DX)
Schneider Electric Uniflair Rack Mounted Room Cooling ACRMD4K
Schneider Electric Uniflair Rack Mounted Room Cooling units ACRMD4Kxxx (indoor rack unit with matching outdoor unit), register map part number 990-91589.
Also known as: ACRMD4K, ACRMD4Kxxx, Uniflair rack mounted room cooling, 990-91589 - Split AC unit (VRF / split AC gateway built in)
Aermec LCG series DC inverter air conditioners (built-in Modbus)
Aermec LCG series DC inverter units whose indoor-unit controller has the built-in Modbus RTU interface; Modbus Protocol user manual LCG 5385758_02 (24.01).
Also known as: LCG - VRF / split AC gateway
Daikin EKMBPP1 / EKMBPP1A Modbus adapter (Sky Air / VRV P1P2)
EKMBPP1 and EKMBPP1A adapters on the P1P2 bus of Sky Air / VRV indoor units (up to 16), installation manual 4P720139-1C (2024.11).
Also known as: EKMBPP1, EKMBPP1A - Air handler DX kit (VRF / split AC gateway built in)
LG PAHCMS000 AHU Communication Kit, discharge-air control (Multi V DX kit, Modbus to DDC)
LG PAHCMS000 AHU Communication Kit for discharge (supply) air control with up to four LG outdoor units, installation manual IM_AHU_Comm_Kit_PAHCMS000_11_23.
Also known as: PAHCMS000, LG AHU Communication Kit discharge air, LG AHU comm kit PAHCMS000 Modbus - VRF / split AC gateway
Realtime Control Systems RTD-NET Modbus interface for Daikin VRV / Sky Air
RTD-NET on the Daikin P1/P2 bus (VRV, Sky Air, VAM/VKM), up to 16 indoor units as one group; RTD-10 with the same firmware uses the same layout.
Also known as: RTD-NET, RTD-10, Daikin RTD-NET
All ac & vrf gateways Modbus register maps →
Source: 700 Series Air Gateway - IN770AIR***O000, Panasonic to Modbus, KNX, BACnet, MQTT and Home Automation - User Manual · User Manual Version 1.1.7 · rev. 2025-12-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.