  4. IN485DAI001A000 Daikin Altherma 3 air-to-water to Modbus RTU / BACnet MS/TP gateway

Heat pump gateway (VRF / split AC gateway) · Modbus register map

Intesis (HMS Networks) IN485DAI001A000 Daikin Altherma 3 air-to-water to Modbus RTU / BACnet MS/TP gateway Modbus register map

Updated 17 November 2026

Short answer

This Intesis gateway connects a Daikin Altherma 3 air-to-water heat pump to an RS-485 bus as a Modbus RTU server (or BACnet MS/TP device, chosen by DIP switch). All points are single 16-bit registers: on/off, heat/cool mode, zone, room and DHW setpoints with limits, water and outdoor temperatures, compressor and pump status and hours, flow, error codes and gateway diagnostics.

This page lists 70 Modbus registers for the Intesis (HMS Networks) IN485DAI001A000 Daikin Altherma 3 air-to-water to Modbus RTU / BACnet MS/TP gateway — 27 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Intesis (HMS Networks)’s own free documentation (linked below) and checked against it.

Manufacturer
Intesis (HMS Networks)
Model
IN485DAI001A000 Daikin Altherma 3 air-to-water to Modbus RTU / BACnet MS/TP gateway
Equipment type
Heat pump gateway (VRF / split AC gateway)
Registers
70 (27 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
2400 baud, 8N2
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
IN485DAI001A000, Daikin Altherma 3 Modbus, Intesis Altherma 3, HMS Daikin Altherma gateway
Source document
IN485DAI001A000 User Manual - Daikin Altherma 3 Air-to-water Heat Pumps to BACnet MS/TP and Modbus RTU · User Manual Version 1.0.2 · rev. 2025-07-18
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Intesis (HMS Networks) IN485DAI001A000 Daikin Altherma 3 air-to-water to Modbus RTU / BACnet MS/TP gateway

Integration in brief

Set SW1 position 5 ON for Modbus RTU, choose the baud on SW1 6-8 and the address on SW2 1-6, power-cycle, then read with function 03 or 04 (max 50 registers per request) and write one register at a time.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 140Zones on/offUINT16Zones on/offRead/write
HR 142Zones modeUINT16Heat/cool modeRead/write
HR 160Zone 1 temperature setpointINT16Zone 1 setpointRead/write
HR 270DHW on/offUINT16DHW on/offRead/write
HR 276DHW temperature setpointINT16DHW setpointRead/write
HR 304Outdoor ambient temperatureINT16Outdoor temperatureRead
HR 306Outlet water temperatureINT16Outlet water temperatureRead
HR 108Error codeUINT16Error codeRead

Enable Modbus control & writes

DIP switch SW1 position 5 ON selects Modbus RTU (default). All settings are DIP switches and only apply after a power cycle.

Byte order & addressing

Network setup

Watch out for

Intesis (HMS Networks) IN485DAI001A000 Daikin Altherma 3 air-to-water to Modbus RTU / BACnet MS/TP gateway Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

70 of 70 shown
Intesis (HMS Networks) IN485DAI001A000 Daikin Altherma 3 air-to-water to Modbus RTU / BACnet MS/TP gateway Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR108doc 108 (PLC 109)Error code0 = no error; any other value is the unit's error code.UINT16Read
HR109doc 109 (PLC 110)Error sub code0 = no error.UINT16Read
HR116doc 116 (PLC 117)Operating time counterNeeds compressor (369) or pump (371) register active; wraps at 65535.UINT16hRead/write
HR118doc 118 (PLC 119)Remote control lockUINT16Read/write0 = Unlocked (default); 1 = Locked - BMS control only
HR119doc 119 (PLC 120)Modbus control lockKeep at 0 for BMS control.UINT16Read/write0 = Unlocked (default); 1 = Locked - remote control only
HR140doc 140 (PLC 141)Zones on/offUINT16Read/write0 = Off; 1 = On
HR141doc 141 (PLC 142)Zones operationClimate demand present.UINT16Read0 = Not operating; 1 = Operating
HR142doc 142 (PLC 143)Zones modeUINT16Read/write0 = Heat; 1 = Cool
HR149doc 149 (PLC 150)Zone 1 control typeUINT16Read0 = Outlet water temperature; 1 = External ambient temperature; 2 = Room thermostat ambient temperature
HR150doc 150 (PLC 151)Zone 1 setpoint modeUINT16Read/write0 = Fixed; 1 = Weather dependent
HR151doc 151 (PLC 152)Zone 1 setpoint mode typeUINT16Read0 = Weather-dependent heating, fixed cooling; 1 = Weather-dependent heating and cooling
HR160doc 160 (PLC 161)Zone 1 temperature setpointINT16°CRead/write
HR161doc 161 (PLC 162)Zone 1 custom lower limit, heatINT16°CRead/write
HR162doc 162 (PLC 163)Zone 1 custom upper limit, heatINT16°CRead/write
HR163doc 163 (PLC 164)Zone 1 custom lower limit, coolINT16°CRead/write
HR164doc 164 (PLC 165)Zone 1 custom upper limit, coolINT16°CRead/write
HR165doc 165 (PLC 166)Zone 1 unit lower limit, heatINT16°CRead
HR166doc 166 (PLC 167)Zone 1 unit upper limit, heatINT16°CRead
HR167doc 167 (PLC 168)Zone 1 unit lower limit, coolINT16°CRead
HR168doc 168 (PLC 169)Zone 1 unit upper limit, coolINT16°CRead
HR169doc 169 (PLC 170)Zone 1 applied lower limit, heatINT16°CRead
HR170doc 170 (PLC 171)Zone 1 applied upper limit, heatINT16°CRead
HR171doc 171 (PLC 172)Zone 1 applied lower limit, coolINT16°CRead
HR172doc 172 (PLC 173)Zone 1 applied upper limit, coolINT16°CRead
HR190doc 190 (PLC 191)Zone 1 scheduled modeUINT16Read/write0 = Off; 1 = On
HR200doc 200 (PLC 201)Room 1 temperature setpointINT16°CRead/write
HR201doc 201 (PLC 202)Room 1 custom lower limit, heatINT16°CRead/write
HR202doc 202 (PLC 203)Room 1 custom upper limit, heatINT16°CRead/write
HR203doc 203 (PLC 204)Room 1 custom lower limit, coolINT16°CRead/write
HR204doc 204 (PLC 205)Room 1 custom upper limit, coolINT16°CRead/write
HR209doc 209 (PLC 210)Room 1 applied lower limit, heatINT16°CRead
HR210doc 210 (PLC 211)Room 1 applied upper limit, heatINT16°CRead
HR211doc 211 (PLC 212)Room 1 applied lower limit, coolINT16°CRead
HR212doc 212 (PLC 213)Room 1 applied upper limit, coolINT16°CRead
HR214doc 214 (PLC 215)Room 1 BMS ambient temperature referenceWrite a BMS-measured room temperature; a valid value enables virtual temperature.INT16°CRead/write
HR216doc 216 (PLC 217)Room 1 antifrost modeUINT16Read0 = Off; 1 = On
HR217doc 217 (PLC 218)Room 1 antifrost setpoint, heatINT16°CRead
HR270doc 270 (PLC 271)DHW on/offUINT16Read/write0 = Off; 1 = On
HR271doc 271 (PLC 272)DHW operationUINT16Read0 = Not operating; 1 = Operating
HR273doc 273 (PLC 274)DHW setpoint modeUINT16Read/write0 = Fixed; 1 = Weather dependent
HR276doc 276 (PLC 277)DHW temperature setpointINT16°CRead/write
HR277doc 277 (PLC 278)DHW custom lower limitINT16°CRead/write
HR278doc 278 (PLC 279)DHW custom upper limitINT16°CRead/write
HR279doc 279 (PLC 280)DHW tank lower limitINT16°CRead
HR280doc 280 (PLC 281)DHW tank upper limitINT16°CRead
HR281doc 281 (PLC 282)DHW applied lower limitINT16°CRead
HR282doc 282 (PLC 283)DHW applied upper limitINT16°CRead
HR285doc 285 (PLC 286)DHW tank temperatureFrom the tank thermistor.INT16°CRead
HR296doc 296 (PLC 297)DHW scheduled modeUINT16Read0 = Off; 1 = On
HR298doc 298 (PLC 299)DHW powerful operationSwitches the tank's electric booster heater.UINT16Read/write0 = Off; 1 = On
HR300doc 300 (PLC 301)DHW disinfection modeAnti-legionella cycle status.UINT16Read0 = Off; 1 = On
HR304doc 304 (PLC 305)Outdoor ambient temperatureINT16°CRead
HR305doc 305 (PLC 306)Refrigerant temperatureINT16°CRead
HR306doc 306 (PLC 307)Outlet water temperatureINT16°CRead
HR307doc 307 (PLC 308)Outlet water temperature (plate heat exchanger)INT16°CRead
HR308doc 308 (PLC 309)Inlet water temperatureINT16°CRead
HR361doc 361 (PLC 362)Quiet modeUINT16Read0 = Off; 1 = On
HR369doc 369 (PLC 370)Compressor operationUINT16Read0 = Off; 1 = On
HR370doc 370 (PLC 371)Compressor operating timeWrite 0 to reset; wraps at 65535.UINT16hRead/write
HR371doc 371 (PLC 372)Pump operationUINT16Read0 = Off; 1 = On
HR372doc 372 (PLC 373)Pump operating timeWrite 0 to reset; wraps at 65535.UINT16hRead/write
HR373doc 373 (PLC 374)Water flow rateUINT16l/hRead
HR374doc 374 (PLC 375)DHW water pressureUINT16PaRead
HR460doc 460 (PLC 461)Device identifierReads 0x2900 (10496).UINT16Read
HR461doc 461 (PLC 462)Firmware version, first two numbersFirst two numbers of the firmware version, in hexadecimal format.UINT16Read
HR462doc 462 (PLC 463)Firmware version, last two numbersLast two numbers of the firmware version, in hexadecimal format.UINT16Read
HR463doc 463 (PLC 464)Device resetWrite 1 to reboot the gateway.UINT16Read/write
HR464doc 464 (PLC 465)Baud rateUINT16Read1 = 2400 bps; 2 = 4800 bps; 3 = 9600 bps; 4 = 19200 bps; 5 = 38400 bps; 6 = 57600 bps; 7 = 76800 bps; 8 = 115200 bps
HR465doc 465 (PLC 466)Modbus slave address1-63, from DIP switch SW2.UINT16Read
HR466doc 466 (PLC 467)DIP switch valueDecimal value whose binary bits show SW1 and SW2 positions.UINT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Intesis (HMS Networks) IN485DAI001A000 Daikin Altherma 3 air-to-water to Modbus RTU / BACnet MS/TP gateway

What Modbus registers does the Intesis (HMS Networks) IN485DAI001A000 Daikin Altherma 3 air-to-water to Modbus RTU / BACnet MS/TP gateway have?

This map lists 70 registers: 70 holding registers. 27 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Intesis (HMS Networks) IN485DAI001A000 Daikin Altherma 3 air-to-water to Modbus RTU / BACnet MS/TP gateway Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual lists every register with a 'Modbus address (base 0)' and a 'PLC address (base 1)'. This map uses the base-0 value on the wire; Zones on/off is address 140 (PLC 141).

What are the minimum Modbus registers to integrate the Intesis (HMS Networks) IN485DAI001A000 Daikin Altherma 3 air-to-water to Modbus RTU / BACnet MS/TP gateway?

Start with HR 140 Zones on/off (Zones on/off); HR 142 Zones mode (Heat/cool mode); HR 160 Zone 1 temperature setpoint (Zone 1 setpoint); HR 270 DHW on/off (DHW on/off); HR 276 DHW temperature setpoint (DHW setpoint); HR 304 Outdoor ambient temperature (Outdoor temperature); HR 306 Outlet water temperature (Outlet water temperature); HR 108 Error code (Error code).

How do I enable Modbus control of the Intesis (HMS Networks) IN485DAI001A000 Daikin Altherma 3 air-to-water to Modbus RTU / BACnet MS/TP gateway?

DIP switch SW1 position 5 ON selects Modbus RTU (default). All settings are DIP switches and only apply after a power cycle.

Where is the official Intesis (HMS Networks) IN485DAI001A000 Daikin Altherma 3 air-to-water to Modbus RTU / BACnet MS/TP gateway Modbus documentation?

The source is IN485DAI001A000 User Manual - Daikin Altherma 3 Air-to-water Heat Pumps to BACnet MS/TP and Modbus RTU (User Manual Version 1.0.2), revision 2025-07-18, published free by Intesis (HMS Networks) at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-in485dai001a000.pdf.

More Intesis (HMS Networks) Modbus register maps

Other ac & vrf gateways register maps

All ac & vrf gateways Modbus register maps →

Source: IN485DAI001A000 User Manual - Daikin Altherma 3 Air-to-water Heat Pumps to BACnet MS/TP and Modbus RTU · User Manual Version 1.0.2 · rev. 2025-07-18. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.