Heat pump gateway (VRF / split AC gateway) · Modbus register map
Intesis (HMS Networks) IN485DAI001A000 Daikin Altherma 3 air-to-water to Modbus RTU / BACnet MS/TP gateway Modbus register map
Updated 17 November 2026
This Intesis gateway connects a Daikin Altherma 3 air-to-water heat pump to an RS-485 bus as a Modbus RTU server (or BACnet MS/TP device, chosen by DIP switch). All points are single 16-bit registers: on/off, heat/cool mode, zone, room and DHW setpoints with limits, water and outdoor temperatures, compressor and pump status and hours, flow, error codes and gateway diagnostics.
This page lists 70 Modbus registers for the Intesis (HMS Networks) IN485DAI001A000 Daikin Altherma 3 air-to-water to Modbus RTU / BACnet MS/TP gateway — 27 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Intesis (HMS Networks)’s own free documentation (linked below) and checked against it.
- Manufacturer
- Intesis (HMS Networks)
- Model
- IN485DAI001A000 Daikin Altherma 3 air-to-water to Modbus RTU / BACnet MS/TP gateway
- Equipment type
- Heat pump gateway (VRF / split AC gateway)
- Registers
- 70 (27 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 2400 baud, 8N2
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- IN485DAI001A000, Daikin Altherma 3 Modbus, Intesis Altherma 3, HMS Daikin Altherma gateway
Integration notes: Intesis (HMS Networks) IN485DAI001A000 Daikin Altherma 3 air-to-water to Modbus RTU / BACnet MS/TP gateway
Set SW1 position 5 ON for Modbus RTU, choose the baud on SW1 6-8 and the address on SW2 1-6, power-cycle, then read with function 03 or 04 (max 50 registers per request) and write one register at a time.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 140 | Zones on/off | UINT16 | Zones on/off | Read/write |
| HR 142 | Zones mode | UINT16 | Heat/cool mode | Read/write |
| HR 160 | Zone 1 temperature setpoint | INT16 | Zone 1 setpoint | Read/write |
| HR 270 | DHW on/off | UINT16 | DHW on/off | Read/write |
| HR 276 | DHW temperature setpoint | INT16 | DHW setpoint | Read/write |
| HR 304 | Outdoor ambient temperature | INT16 | Outdoor temperature | Read |
| HR 306 | Outlet water temperature | INT16 | Outlet water temperature | Read |
| HR 108 | Error code | UINT16 | Error code | Read |
Enable Modbus control & writes
DIP switch SW1 position 5 ON selects Modbus RTU (default). All settings are DIP switches and only apply after a power cycle.
Byte order & addressing
- Function 16 is accepted but must write only one register per request.
- Registers read 0x8000 (-32768) until the unit has reported.
- Temperature scale and unit depend on SW2 positions 7 and 8.
Network setup
- Default 2400 bps, 8 data bits, no parity, 2 stop bits; 8-N-1 is detected automatically.
- Modbus address 1-63 on SW2 positions 1-6.
- SW3 position 1 ON adds the 120 ohm terminator; positions 2-3 ON add bus polarization.
Watch out for
- If the gateway ignores writes, check that Modbus control lock (119) is 0.
- Operating time (116) counts only when compressor or pump registers are active.
Intesis (HMS Networks) IN485DAI001A000 Daikin Altherma 3 air-to-water to Modbus RTU / BACnet MS/TP gateway Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 108doc 108 (PLC 109) | Error code | 0 = no error; any other value is the unit's error code. | UINT16 | Read | ||||
| HR | 109doc 109 (PLC 110) | Error sub code | 0 = no error. | UINT16 | Read | ||||
| HR | 116doc 116 (PLC 117) | Operating time counter | Needs compressor (369) or pump (371) register active; wraps at 65535. | UINT16 | h | Read/write | |||
| HR | 118doc 118 (PLC 119) | Remote control lock | UINT16 | Read/write | 0 = Unlocked (default); 1 = Locked - BMS control only | ||||
| HR | 119doc 119 (PLC 120) | Modbus control lock | Keep at 0 for BMS control. | UINT16 | Read/write | 0 = Unlocked (default); 1 = Locked - remote control only | |||
| HR | 140doc 140 (PLC 141) | Zones on/off | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 141doc 141 (PLC 142) | Zones operation | Climate demand present. | UINT16 | Read | 0 = Not operating; 1 = Operating | |||
| HR | 142doc 142 (PLC 143) | Zones mode | UINT16 | Read/write | 0 = Heat; 1 = Cool | ||||
| HR | 149doc 149 (PLC 150) | Zone 1 control type | UINT16 | Read | 0 = Outlet water temperature; 1 = External ambient temperature; 2 = Room thermostat ambient temperature | ||||
| HR | 150doc 150 (PLC 151) | Zone 1 setpoint mode | UINT16 | Read/write | 0 = Fixed; 1 = Weather dependent | ||||
| HR | 151doc 151 (PLC 152) | Zone 1 setpoint mode type | UINT16 | Read | 0 = Weather-dependent heating, fixed cooling; 1 = Weather-dependent heating and cooling | ||||
| HR | 160doc 160 (PLC 161) | Zone 1 temperature setpoint | INT16 | °C | Read/write | ||||
| HR | 161doc 161 (PLC 162) | Zone 1 custom lower limit, heat | INT16 | °C | Read/write | ||||
| HR | 162doc 162 (PLC 163) | Zone 1 custom upper limit, heat | INT16 | °C | Read/write | ||||
| HR | 163doc 163 (PLC 164) | Zone 1 custom lower limit, cool | INT16 | °C | Read/write | ||||
| HR | 164doc 164 (PLC 165) | Zone 1 custom upper limit, cool | INT16 | °C | Read/write | ||||
| HR | 165doc 165 (PLC 166) | Zone 1 unit lower limit, heat | INT16 | °C | Read | ||||
| HR | 166doc 166 (PLC 167) | Zone 1 unit upper limit, heat | INT16 | °C | Read | ||||
| HR | 167doc 167 (PLC 168) | Zone 1 unit lower limit, cool | INT16 | °C | Read | ||||
| HR | 168doc 168 (PLC 169) | Zone 1 unit upper limit, cool | INT16 | °C | Read | ||||
| HR | 169doc 169 (PLC 170) | Zone 1 applied lower limit, heat | INT16 | °C | Read | ||||
| HR | 170doc 170 (PLC 171) | Zone 1 applied upper limit, heat | INT16 | °C | Read | ||||
| HR | 171doc 171 (PLC 172) | Zone 1 applied lower limit, cool | INT16 | °C | Read | ||||
| HR | 172doc 172 (PLC 173) | Zone 1 applied upper limit, cool | INT16 | °C | Read | ||||
| HR | 190doc 190 (PLC 191) | Zone 1 scheduled mode | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 200doc 200 (PLC 201) | Room 1 temperature setpoint | INT16 | °C | Read/write | ||||
| HR | 201doc 201 (PLC 202) | Room 1 custom lower limit, heat | INT16 | °C | Read/write | ||||
| HR | 202doc 202 (PLC 203) | Room 1 custom upper limit, heat | INT16 | °C | Read/write | ||||
| HR | 203doc 203 (PLC 204) | Room 1 custom lower limit, cool | INT16 | °C | Read/write | ||||
| HR | 204doc 204 (PLC 205) | Room 1 custom upper limit, cool | INT16 | °C | Read/write | ||||
| HR | 209doc 209 (PLC 210) | Room 1 applied lower limit, heat | INT16 | °C | Read | ||||
| HR | 210doc 210 (PLC 211) | Room 1 applied upper limit, heat | INT16 | °C | Read | ||||
| HR | 211doc 211 (PLC 212) | Room 1 applied lower limit, cool | INT16 | °C | Read | ||||
| HR | 212doc 212 (PLC 213) | Room 1 applied upper limit, cool | INT16 | °C | Read | ||||
| HR | 214doc 214 (PLC 215) | Room 1 BMS ambient temperature reference | Write a BMS-measured room temperature; a valid value enables virtual temperature. | INT16 | °C | Read/write | |||
| HR | 216doc 216 (PLC 217) | Room 1 antifrost mode | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 217doc 217 (PLC 218) | Room 1 antifrost setpoint, heat | INT16 | °C | Read | ||||
| HR | 270doc 270 (PLC 271) | DHW on/off | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 271doc 271 (PLC 272) | DHW operation | UINT16 | Read | 0 = Not operating; 1 = Operating | ||||
| HR | 273doc 273 (PLC 274) | DHW setpoint mode | UINT16 | Read/write | 0 = Fixed; 1 = Weather dependent | ||||
| HR | 276doc 276 (PLC 277) | DHW temperature setpoint | INT16 | °C | Read/write | ||||
| HR | 277doc 277 (PLC 278) | DHW custom lower limit | INT16 | °C | Read/write | ||||
| HR | 278doc 278 (PLC 279) | DHW custom upper limit | INT16 | °C | Read/write | ||||
| HR | 279doc 279 (PLC 280) | DHW tank lower limit | INT16 | °C | Read | ||||
| HR | 280doc 280 (PLC 281) | DHW tank upper limit | INT16 | °C | Read | ||||
| HR | 281doc 281 (PLC 282) | DHW applied lower limit | INT16 | °C | Read | ||||
| HR | 282doc 282 (PLC 283) | DHW applied upper limit | INT16 | °C | Read | ||||
| HR | 285doc 285 (PLC 286) | DHW tank temperature | From the tank thermistor. | INT16 | °C | Read | |||
| HR | 296doc 296 (PLC 297) | DHW scheduled mode | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 298doc 298 (PLC 299) | DHW powerful operation | Switches the tank's electric booster heater. | UINT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 300doc 300 (PLC 301) | DHW disinfection mode | Anti-legionella cycle status. | UINT16 | Read | 0 = Off; 1 = On | |||
| HR | 304doc 304 (PLC 305) | Outdoor ambient temperature | INT16 | °C | Read | ||||
| HR | 305doc 305 (PLC 306) | Refrigerant temperature | INT16 | °C | Read | ||||
| HR | 306doc 306 (PLC 307) | Outlet water temperature | INT16 | °C | Read | ||||
| HR | 307doc 307 (PLC 308) | Outlet water temperature (plate heat exchanger) | INT16 | °C | Read | ||||
| HR | 308doc 308 (PLC 309) | Inlet water temperature | INT16 | °C | Read | ||||
| HR | 361doc 361 (PLC 362) | Quiet mode | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 369doc 369 (PLC 370) | Compressor operation | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 370doc 370 (PLC 371) | Compressor operating time | Write 0 to reset; wraps at 65535. | UINT16 | h | Read/write | |||
| HR | 371doc 371 (PLC 372) | Pump operation | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 372doc 372 (PLC 373) | Pump operating time | Write 0 to reset; wraps at 65535. | UINT16 | h | Read/write | |||
| HR | 373doc 373 (PLC 374) | Water flow rate | UINT16 | l/h | Read | ||||
| HR | 374doc 374 (PLC 375) | DHW water pressure | UINT16 | Pa | Read | ||||
| HR | 460doc 460 (PLC 461) | Device identifier | Reads 0x2900 (10496). | UINT16 | Read | ||||
| HR | 461doc 461 (PLC 462) | Firmware version, first two numbers | First two numbers of the firmware version, in hexadecimal format. | UINT16 | Read | ||||
| HR | 462doc 462 (PLC 463) | Firmware version, last two numbers | Last two numbers of the firmware version, in hexadecimal format. | UINT16 | Read | ||||
| HR | 463doc 463 (PLC 464) | Device reset | Write 1 to reboot the gateway. | UINT16 | Read/write | ||||
| HR | 464doc 464 (PLC 465) | Baud rate | UINT16 | Read | 1 = 2400 bps; 2 = 4800 bps; 3 = 9600 bps; 4 = 19200 bps; 5 = 38400 bps; 6 = 57600 bps; 7 = 76800 bps; 8 = 115200 bps | ||||
| HR | 465doc 465 (PLC 466) | Modbus slave address | 1-63, from DIP switch SW2. | UINT16 | Read | ||||
| HR | 466doc 466 (PLC 467) | DIP switch value | Decimal value whose binary bits show SW1 and SW2 positions. | UINT16 | Read |
Notes on this map
- Temperatures follow DIP switch SW2: position 7 OFF = whole degrees (x1, default), ON = tenths (x10, 19.2 = 192); position 8 OFF = °C (default), ON = °F. Units and scale here are for the defaults; use scale 0.1 if you set x10.
- Every register starts at 0x8000 (-32768) until the gateway has data, so temperatures are typed signed 16-bit.
- An invalid write resets a temperature register to its initial value; other registers keep their old value.
- Room 1 unit-limit registers (205-208) are left out to keep the map short; they report the Altherma's absolute room setpoint limits.
- The manual's baud-rate table prints 38500 bps for value 5; the physical-layer section lists 38400, which is used here.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Intesis (HMS Networks) IN485DAI001A000 Daikin Altherma 3 air-to-water to Modbus RTU / BACnet MS/TP gateway
What Modbus registers does the Intesis (HMS Networks) IN485DAI001A000 Daikin Altherma 3 air-to-water to Modbus RTU / BACnet MS/TP gateway have?
This map lists 70 registers: 70 holding registers. 27 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Intesis (HMS Networks) IN485DAI001A000 Daikin Altherma 3 air-to-water to Modbus RTU / BACnet MS/TP gateway Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual lists every register with a 'Modbus address (base 0)' and a 'PLC address (base 1)'. This map uses the base-0 value on the wire; Zones on/off is address 140 (PLC 141).
What are the minimum Modbus registers to integrate the Intesis (HMS Networks) IN485DAI001A000 Daikin Altherma 3 air-to-water to Modbus RTU / BACnet MS/TP gateway?
Start with HR 140 Zones on/off (Zones on/off); HR 142 Zones mode (Heat/cool mode); HR 160 Zone 1 temperature setpoint (Zone 1 setpoint); HR 270 DHW on/off (DHW on/off); HR 276 DHW temperature setpoint (DHW setpoint); HR 304 Outdoor ambient temperature (Outdoor temperature); HR 306 Outlet water temperature (Outlet water temperature); HR 108 Error code (Error code).
How do I enable Modbus control of the Intesis (HMS Networks) IN485DAI001A000 Daikin Altherma 3 air-to-water to Modbus RTU / BACnet MS/TP gateway?
DIP switch SW1 position 5 ON selects Modbus RTU (default). All settings are DIP switches and only apply after a power cycle.
Where is the official Intesis (HMS Networks) IN485DAI001A000 Daikin Altherma 3 air-to-water to Modbus RTU / BACnet MS/TP gateway Modbus documentation?
The source is IN485DAI001A000 User Manual - Daikin Altherma 3 Air-to-water Heat Pumps to BACnet MS/TP and Modbus RTU (User Manual Version 1.0.2), revision 2025-07-18, published free by Intesis (HMS Networks) at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-in485dai001a000.pdf.
More Intesis (HMS Networks) Modbus register maps
- Heat pump gateway (VRF / split AC gateway)
Intesis (HMS Networks) IN485MIT001A000 Mitsubishi Electric Ecodan air-to-water to Modbus RTU / BACnet MS/TP gateway
Intesis (HMS Networks) IN485MIT001A000 gateway on the CN105 socket of Mitsubishi Electric Ecodan air-to-water heat pumps, set to Modbus RTU, per user manual version 1.0.3 (2025-12-02).
Also known as: IN485MIT001A000, Ecodan Modbus, Mitsubishi Ecodan Modbus RTU, Intesis Ecodan, HMS Ecodan gateway - VRF / split AC gateway
Intesis (HMS Networks) IN485SAM001R000 Samsung AC to Modbus RTU / BACnet MS/TP gateway
Samsung indoor units on the F3F4 remote-controller bus, gateway set to Modbus RTU (SW1-5 ON); user manual version 1.0.0.
Also known as: IN485SAM001R000, Intesis Samsung BACnet MS/TP Modbus - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Bosch application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Bosch application (XYE bus), Modbus RTU / TCP server, user manual version 1.0.13 (2025-12-09).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Midea application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Midea application (XYE bus), Modbus RTU / TCP server, user manual version 1.0.22 (2025-12-09).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Mitsubishi Electric City Multi application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Mitsubishi Electric City Multi application (M-NET centralised controllers (AE-200, EW-50, G-50 and others)), Modbus RTU / TCP server, user manual version 1.0.19 (2026-03-16).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Panasonic application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Panasonic application (U1U2 P-Link / S-Link), Modbus RTU / TCP server, user manual version 1.1.7 (2025-12-09).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSACA001I000 XYE-bus air conditioner to Modbus RTU interface (1 unit)
INMBSACA001I000, user manual v1.8 EN; one indoor unit at unit address 0 on its own XYE bus.
Also known as: INMBSACA001I000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSACA004I000 / 008I000 / 032I000 XYE-bus air conditioner to Modbus RTU interface (4 to 32 units)
INMBSACA004I000 / INMBSACA008I000 / INMBSACA032I000, user manual v1.8 EN; up to 4, 8 or 32 indoor units on one XYE bus.
Also known as: INMBSACA004I000, INMBSACA008I000, INMBSACA032I000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSDAI001I000 Daikin domestic AC to Modbus RTU gateway
Single Daikin domestic (S21-connector) indoor unit via INMBSDAI001I000, user manual v1.0.2.
Also known as: INMBSDAI001I000, Intesis Daikin domestic Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSDAI001R000 Daikin VRV / Sky Air to Modbus RTU gateway
One Daikin VRV or Sky Air indoor unit (or group) on the P1P2 bus via INMBSDAI001R000, user manual v1.0.1.
Also known as: INMBSDAI001R000, Intesis Daikin VRV Modbus - Lighting gateway (DALI-2 to Modbus)
Intesis (HMS Networks) INMBSDAL0640000 / INMBSDAL1280000 DALI-2 to Modbus RTU / TCP server
Intesis Modbus Server - DALI with one (0640000, RTU + TCP) or two (1280000, TCP only) DALI channels, Modbus Addresses parameter set to Fixed; user manual r1.2 (09/2021).
Also known as: INMBSDAL0640000, INMBSDAL1280000, Intesis Modbus Server - DALI, Intesis DALI-2 Modbus gateway - VRF / split AC gateway
Intesis (HMS Networks) INMBSFGL001I000 Fujitsu domestic AC to Modbus RTU gateway
One Fujitsu domestic (RAC) or compatible VRF indoor unit, connected to the CN65/CN12/CN6 socket on the indoor board via INMBSFGL001I000, user manual v1.5 (01/2024).
Also known as: INMBSFGL001I000, FJ-AC-MBS-1, Intesis Fujitsu domestic Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSFGL001R000 Fujitsu AC to Modbus RTU gateway
One Fujitsu indoor unit, or a group of up to 16 controlled together as one, on the 3-wire BWR remote-controller bus via INMBSFGL001R000, user manual v2.4 (02/2025).
Also known as: INMBSFGL001R000, Intesis Fujitsu Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSFGL016O000 Fujitsu VRF to Modbus RTU / TCP gateway (up to 16 indoor units)
Intesis Modbus Server - Fujitsu VRF, order code INMBSFGL016O000 (legacy FJ-AC-MBS-16), user manual r1.0 (02/2020); up to 16 indoor units configured in MAPS.
Also known as: INMBSFGL016O000, FJ-AC-MBS-16, Intesis Modbus Server Fujitsu VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIS001R000 Hisense AC to Modbus RTU gateway
Hisense commercial-line indoor units on the AB remote-controller bus, user manual v1.6 (01/2024).
Also known as: INMBSHIS001R000, HS-RC-MBS-1, Intesis Hisense Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIS016O000 Hisense VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)
Intesis Modbus Server - Hisense VRF, order codes INMBSHIS016O000 / INMBSHIS064O000 (legacy HS-AC-MBS-16 / HS-AC-MBS-64), user manual User Manual r1.0 EN.
Also known as: INMBSHIS016O000, INMBSHIS064O000, HS-AC-MBS-16, HS-AC-MBS-64, Intesis Modbus Server Hisense VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIT001R000 Hitachi AC to Modbus RTU gateway
Intesis (HMS Networks) INMBSHIT001R000 interface on the AB bus of one Hitachi commercial-line indoor unit (or group), per user manual v1.6 (01/2024).
Also known as: INMBSHIT001R000, Hitachi Modbus gateway, Intesis Hitachi - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIT016O000 Hitachi VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)
Intesis Modbus Server - Hitachi VRF, order codes INMBSHIT016O000 / INMBSHIT064O000 (legacy HI-AC-MBS-16 / HI-AC-MBS-64), user manual User Manual r1.2 EN.
Also known as: INMBSHIT016O000, INMBSHIT064O000, HI-AC-MBS-16, HI-AC-MBS-64, Intesis Modbus Server Hitachi VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSLGE001R000 LG AC to Modbus RTU gateway
One LG indoor unit on the BYR (wired remote) bus via INMBSLGE001R000 (legacy code LG-RC-MBS-1), user manual v1.9 (01/2024).
Also known as: INMBSLGE001R000, LG-RC-MBS-1, Intesis LG Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSLGE016O000 LG VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)
Intesis Modbus - LG VRF, order codes INMBSLGE016O000 / INMBSLGE064O000 (legacy LG-AC-MBS-16 / -64), user manual r1.0 (04/2020); LG PI485 bus.
Also known as: INMBSLGE016O000, INMBSLGE064O000, LG-AC-MBS-16, LG-AC-MBS-64, Intesis Modbus LG VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSMHI001R000 Mitsubishi Heavy Industries AC to Modbus RTU gateway
Mitsubishi Heavy Industries indoor units (one, or up to 16 controlled together as one) on the XY remote-controller bus, user manual r6.4 (01/2024).
Also known as: INMBSMHI001R000, MH-RC-MBS-1, Intesis Mitsubishi Heavy Industries Modbus, Intesis MHI Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSMHI128O000 / INMBSMHI048O000 Mitsubishi Heavy Industries Superlink to Modbus gateway
Intesis Modbus Server - Mitsubishi Heavy Industries AC, order codes INMBSMHI128O000 (128 units, Superlink-II) and INMBSMHI048O000 (48 units, Superlink-I or II), user's manual r1.0 (05/2012).
Also known as: INMBSMHI128O000, INMBSMHI048O000, MH-AC-MBS-128, MH-AC-MBS-48, Intesis Modbus Server MHI Superlink - VRF / split AC gateway
Intesis (HMS Networks) INMBSMID001I000 Midea AC to Modbus RTU gateway
One Midea commercial / VRF indoor unit on the XYE bus, user manual v1.11.
Also known as: INMBSMID001I000, Intesis Midea Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSMID004I000 / 008I000 / 032I000 Midea AC to Modbus RTU interface (4 to 32 units)
INMBSMID004I000 / INMBSMID008I000 / INMBSMID032I000 / MD-AC-MBS-4 / MD-AC-MBS-8 / MD-AC-MBS-32, user manual v1.7 EN; up to 4, 8 or 32 indoor units on one XYE bus.
Also known as: INMBSMID004I000, INMBSMID008I000, INMBSMID032I000, MD-AC-MBS-4, MD-AC-MBS-8, MD-AC-MBS-32 - VRF / split AC gateway
Intesis (HMS Networks) INMBSMIT001I000 Mitsubishi Electric AC to Modbus RTU gateway
One Mitsubishi Electric Domestic, Mr. Slim or City Multi indoor unit via INMBSMIT001I000, user manual r2.8 (11/2024).
Also known as: INMBSMIT001I000, Intesis Mitsubishi Electric Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSMIT050C000 / INMBSMIT100C000 Mitsubishi Electric City Multi centralised controller to Modbus gateway
Intesis Modbus Server - Mitsubishi Electric CC, order codes INMBSMIT050C000 / INMBSMIT100C000 (legacy ME-AC-MBS-50 / -100), user manual r1.4 (05/2021); talks to City Multi centralised controllers (G-50A, GB-50A, AG-150A, EB-50, EW-50, AE-200 and newer) through their XML interface over Ethernet.
Also known as: INMBSMIT050C000, INMBSMIT100C000, ME-AC-MBS-50, ME-AC-MBS-100, Intesis Modbus Server Mitsubishi Electric CC - Heat pump gateway (VRF / split AC gateway)
Intesis (HMS Networks) INMBSPAN001A100 Panasonic Aquarea H/J/K/L/M air-to-water to Modbus RTU gateway
Intesis (HMS Networks) INMBSPAN001A100 gateway connected to Panasonic Aquarea H, J, K, L and M series air-to-water heat pumps, per user manual version 1.0.2 (2026-02-04).
Also known as: INMBSPAN001A100, Aquarea Modbus, Panasonic Aquarea Modbus RTU, Intesis Aquarea, INMBSPAN001A000 (legacy order code) - VRF / split AC gateway
Intesis (HMS Networks) INMBSPAN001I100 Panasonic Etherea (domestic) AC to Modbus RTU gateway
Panasonic Etherea-line domestic split units, user's manual r1.5 (09/2025). Some registers only on 2013 (PKE series) and later models.
Also known as: INMBSPAN001I100, Intesis Panasonic Etherea Modbus, Intesis Panasonic domestic Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSPAN001R000 Panasonic AC to Modbus RTU gateway
Panasonic / Sanyo ECOi and PACi indoor units (one, or up to 16 controlled together as one) on the R1R2 remote-controller bus, user manual v2.8 (09/2025).
Also known as: INMBSPAN001R000, PA-RC2-MBS-1, Intesis Panasonic Modbus, Intesis Sanyo Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSPAN016O000 / 064O000 / 128O000 Panasonic VRF (P-Link) to Modbus gateway
Intesis Modbus Server - Panasonic, order codes INMBSPAN016O000 / 064O000 / 128O000 (legacy PA-AC-MBS-16 / -64 / -128), user manual r1.1 (11/2020); Panasonic P-Link systems.
Also known as: INMBSPAN016O000, INMBSPAN064O000, INMBSPAN128O000, PA-AC-MBS-16, PA-AC-MBS-64, PA-AC-MBS-128, Intesis Modbus Server Panasonic VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSSAM001R000 Samsung AC to Modbus RTU gateway
Samsung commercial indoor units on the F3F4/V1V2 remote-controller bus, user's manual v1.5 (01/2024).
Also known as: INMBSSAM001R000, Intesis Samsung Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSSAM001R100 Samsung NASA AC to Modbus RTU gateway
Samsung NASA-protocol commercial indoor units on the remote-controller bus, user's manual r1.4 (01/2024).
Also known as: INMBSSAM001R100, Intesis Samsung NASA Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSSAM016O000 Samsung NASA (R1/R2) VRF to Modbus gateway (4 to 64 units)
Intesis Modbus Server - Samsung NASA, order codes INMBSSAM004O000 / 008O000 / 016O000 / 064O000 (legacy SM-ACN-MBS-4/8/16/64), user manual r1.4 (12/2020); Samsung NASA R1/R2 bus.
Also known as: INMBSSAM004O000, INMBSSAM008O000, INMBSSAM016O000, INMBSSAM064O000, SM-ACN-MBS-4, SM-ACN-MBS-8, SM-ACN-MBS-16, SM-ACN-MBS-64 - VRF / split AC gateway
Intesis (HMS Networks) INMBSTOS001R000 Toshiba AC to Modbus RTU gateway
Toshiba Digital Inverter (RAV) and VRF indoor units on the AB remote bus via INMBSTOS001R0xx, user manual r2.9 (01/2024).
Also known as: INMBSTOS001R000, INMBSTOS001R0xx, Intesis Toshiba Modbus
Other ac & vrf gateways register maps
- Air handler DX kit (VRF / split AC gateway built in)
LG PAHCMR000 AHU Communication Kit (Multi V DX kit, Modbus to DDC)
LG PAHCMR000 AHU Communication Kit (R32 and R410A Multi V / single split outdoor units with a PRLK EEV kit), installation manual IM_AHU_Comm_Kit_PAHCMR000_R32_06_26.
Also known as: PAHCMR000, LG AHU Communication Kit R32, LG AHU comm kit Modbus - VRF / split AC gateway (retail controller)
Mitsubishi Electric Procon MelcoRETAIL MINI controller for Air-To-Air split units
Procon MelcoRETAIL MINI on the CN105/CN92 connector of Mitsubishi Electric M, S and P series Air-To-Air indoor units, installation manual v1.0.6, firmware 1.0.3.
Also known as: MelcoRETAIL MINI, Procon MelcoRETAIL MINI - VRF / split AC gateway (built-in indoor-unit Modbus)
Sinclair UNI SPLIT DC inverter indoor units (integrated Modbus RTU)
Sinclair All DC Inverter UNI SPLIT indoor units with the built-in Modbus RTU interface, per the UNI SPLIT Modbus user's manual.
Also known as: Sinclair UNI SPLIT, UNI SPLIT Modbus, All DC Inverter UNI SPLIT - Split AC unit (VRF / split AC gateway built in)
Aermec LPG series DC inverter air conditioners (built-in Modbus)
Aermec LPG series DC inverter units whose indoor-unit controller has the built-in Modbus RTU interface; ModBus Protocol LPG series 5385759_02 (EN 25.05).
Also known as: LPG - Sensor / controller (CO2 condensing unit gateway)
Danfoss Optyma iCO2 gateway (OP-MPAM015 / OP-MPAM005)
Danfoss Optyma iCO2 CO2 condensing units (4.6 kW MT and 20 kW MT / 10 kW LT) through their Modbus gateway, software 1.0x.
Also known as: OP-MPAM015, OP-MPAM005, Optyma iCO2 4.6 kW MT, Optyma iCO2 20 kW MT / 10 kW LT - VRF / split AC gateway
Mitsubishi Electric MelcoBEMS MINI (A1M) gateway for Air-To-Air split units
Procon MelcoBEMS MINI (A1M) on the CN105/CN92 connector of a Mitsubishi Electric Air-To-Air indoor unit, installation manual v1.1.11 (firmware 3.0.28 for revision 2-4 hardware, 3.1.1 for revision 5).
Also known as: MelcoBEMS MINI (A1M), A1M, Procon A1M, MelcoBEMS MINI
All ac & vrf gateways Modbus register maps →
Source: IN485DAI001A000 User Manual - Daikin Altherma 3 Air-to-water Heat Pumps to BACnet MS/TP and Modbus RTU · User Manual Version 1.0.2 · rev. 2025-07-18. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.