- Versati heat pump water heater (wired-controller Modbus RTU, protocol V1.5)
Heat pump (air-to-water) · Modbus register map
Gree Versati heat pump water heater (wired-controller Modbus RTU, protocol V1.5) Modbus register map
Updated 19 November 2026
The Versati wired controller has a two-wire RS-485 BMS port that answers Modbus RTU, so up to 255 heat pumps can sit on one line. Holding registers (words) carry on/off, mode, water and room setpoints, temperature limits, power and current limits, unit status and compressor frequency; coils (bits) carry function switches (timers, quiet mode, weather compensation, disinfection, holiday) and indoor, outdoor and inverter fault and state flags.
This page lists 142 Modbus registers for the Gree Versati heat pump water heater (wired-controller Modbus RTU, protocol V1.5) — 63 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Gree’s own free documentation (linked below) and checked against it.
- Manufacturer
- Gree
- Model
- Versati heat pump water heater (wired-controller Modbus RTU, protocol V1.5)
- Equipment type
- Heat pump (air-to-water)
- Registers
- 142 (63 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 9600 baud, 8N1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- Versati III, R32 Versati, Versati heat pump water heater, Gree Versati Modbus V1.5
Integration notes: Gree Versati heat pump water heater (wired-controller Modbus RTU, protocol V1.5)
Wire the BMS port of the wired controller to RS-485, set a unique address, then read words 117-143 and coils 64-191 for status and faults, and write word 42 (0xAA/0x55), word 2 (mode) and the setpoint words.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 42 | On/Off | UINT16 | On/off | Read/write |
| HR 2 | Mode | UINT16 | Mode | Read/write |
| HR 10 | WOT-Heat | UINT16 | Heating water setpoint | Read/write |
| HR 13 | T-water tank | UINT16 | Tank setpoint | Read/write |
| HR 117 | Unit status | UINT16 | Unit status | Read |
| HR 143 | Running frequency | UINT16 | Compressor running frequency | Read |
| CO 80 | Compressor State | BIT | Compressor on | Read |
| CO 86 | Defrosting State | BIT | Defrosting | Read |
| CO 102 | System Recoverable Protection | BIT | System recoverable protection | Read |
Enable Modbus control & writes
On the wired controller press COMMISSION, then FUNCTION, page to 'Address', set the BMS address and press OK. The address must not be 0 or 126 and must match the address the BMS sends.
Byte order & addressing
- Read with function 0x03 and write with 0x10 (words); read with 0x01 and write with 0x0F (bits). Single-write functions 0x05/0x06 are not listed.
- At most 127 words per read.
- Broadcast (address 0) is accepted for writes only.
- BMS and Gree long-distance monitoring have equal control; the most recent command wins.
Network setup
- 9600 bit/s, 8 data bits, no parity, 1 stop bit.
- Controller BMS terminal: 1 = B, 2 = A (two-wire, twisted pair).
Watch out for
- Change the mode only while the unit is off; mode writes while running may be ignored.
- Hot-water related modes and functions are ignored when no water tank is configured, and cooling modes are ignored on heating-only units.
- After commanding disinfection, check word 135 for its state.
Gree Versati heat pump water heater (wired-controller Modbus RTU, protocol V1.5) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 8doc Bit 8 | Weekly Timer | BIT | Read/write | 0 = Close; 1 = Open | ||||
| CO | 9doc Bit 9 | Clock Timer | BIT | Read/write | 0 = Close; 1 = Open | ||||
| CO | 10doc Bit 10 | Temp Timer | BIT | Read/write | 0 = Close; 1 = Open | ||||
| CO | 11doc Bit 11 | Gate-Ctrl. | BIT | Read/write | 0 = Close; 1 = Open | ||||
| CO | 16doc Bit 16 | Solar heater | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 17doc Bit 17 | Ctrl.state | BIT | Read/write | 0 = T-water out; 1 = T-room | ||||
| CO | 18doc Bit 18 | Fast Hot Water | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 19doc Bit 19 | Cool+Hot Water Priority | BIT | Read/write | 0 = Cool; 1 = Hot water | ||||
| CO | 20doc Bit 20 | Heat+Hot Water Priority | BIT | Read/write | 0 = Heat; 1 = Hot water | ||||
| CO | 21doc Bit 21 | Quite Mode | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 22doc Bit 22 | Weather depend | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 23doc Bit 23 | Disinfection | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 24doc Bit 24 | Floor Debug | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 25doc Bit 25 | Floor Debug start/stop | BIT | Read/write | 0 = Stop; 1 = Start | ||||
| CO | 26doc Bit 26 | Emergen. mode | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 27doc Bit 27 | Other thermal | BIT | Read/write | 0 = Without; 1 = With | ||||
| CO | 29doc Bit 29 | Water Tank | BIT | Read/write | 0 = Without; 1 = With | ||||
| CO | 31doc Bit 31 | Solar setting | BIT | Read/write | 0 = Without; 1 = With | ||||
| CO | 33doc Bit 33 | Remote sensor | BIT | Read/write | 0 = Without; 1 = With | ||||
| CO | 34doc Bit 34 | Holiday Mode | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 35doc Bit 35 | Refri. recovery | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 36doc Bit 36 | Manual defrost | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 37doc Bit 37 | Cool 2-Way valve | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 38doc Bit 38 | Heat 2-Way valve | BIT | Read | 0 = Off; 1 = On | ||||
| CO | 64doc Bit 64 | Communication Error between the Wired Controller and IDU | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 65doc Bit 65 | Communication Error between the Wired Controler and ODU | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 66doc Bit 66 | Communication Error between the Wired Controller and Drive | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 67doc Bit 67 | HP-Antifree | BIT | Read | 0 = Off; 1 = On | ||||
| CO | 80doc Bit 80 | Compressor State | BIT | Read | 0 = Off; 1 = On | ||||
| CO | 81doc Bit 81 | ODU Fan State | BIT | Read | 0 = Off; 1 = On | ||||
| CO | 83doc Bit 83 | 4-way Valve State | BIT | Read | 0 = Off; 1 = On | ||||
| CO | 84doc Bit 84 | Compressor Crankcase Heater State | BIT | Read | 0 = Off; 1 = On | ||||
| CO | 85doc Bit 85 | Underpan Heater State | BIT | Read | 0 = Off; 1 = On | ||||
| CO | 86doc Bit 86 | Defrosting State | BIT | Read | 0 = End; 1 = Defrosting | ||||
| CO | 87doc Bit 87 | Oil Return State | BIT | Read | 0 = No oil return; 1 = In oil return | ||||
| CO | 88doc Bit 88 | Ambient Temp Sensor Error | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 89doc Bit 89 | Defrost Temp Sensor Error | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 90doc Bit 90 | Discharge Temp Sensor Error | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 91doc Bit 91 | Suction Temp Sensor Error | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 92doc Bit 92 | ODU Fan Error | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 93doc Bit 93 | High-Pressure Sensor Error | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 94doc Bit 94 | High Pressure Protection | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 95doc Bit 95 | Low Pressure Protection | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 96doc Bit 96 | High Discharge Protection | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 97doc Bit 97 | Capacity DIP Setting Error | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 98doc Bit 98 | Communication Error between IDU and ODU | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 102doc Bit 102 | System Recoverable Protection | BIT | Read | 0 = NO; 1 = Yes | ||||
| CO | 103doc Bit 103 | System Irrecoverable Protection | BIT | Read | 0 = No; 1 = Yes | ||||
| CO | 108doc Bit 108 | Flow Switch Protection | BIT | Read | 0 = Normal; 1 = protected | ||||
| CO | 109doc Bit 109 | 4-way valve | BIT | Read | 0 = No; 1 = Yes | ||||
| CO | 128doc Bit 128 | DC Bus Low-voltage or Voltage Drop | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 129doc Bit 129 | DC Bus Over-voltage | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 130doc Bit 130 | AC Current Protection (Input Side) | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 131doc Bit 131 | IPM Error | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 132doc Bit 132 | PFC Error | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 133doc Bit 133 | Startup Error | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 134doc Bit 134 | Phase Loss | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 135doc Bit 135 | Drive Module Resetting | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 136doc Bit 136 | Compressor Overcurrent | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 137doc Bit 137 | Over-speed | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 138doc Bit 138 | Charging Circuit Error or Current Sensor Error | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 139doc Bit 139 | Desynchronizing | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 140doc Bit 140 | Compressor Stalling | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 141doc Bit 141 | Drive Communication Error | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 142doc Bit 142 | Radiator or IPM or PFC Over-temperature | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 143doc Bit 143 | Defective Radiator or IPM or PFC | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 146doc Bit 146 | Charging Circuit Error | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 147doc Bit 147 | AC Input Voltage Error | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 148doc Bit 148 | Drive Board Temp Sensor Error | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 149doc Bit 149 | AC Contactor Protection or Input Cross-zero Error | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 150doc Bit 150 | Temp Drift Protection | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 151doc Bit 151 | Sensor Connection Protection (Connection to Phase U or V failed) | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 152doc Bit 152 | Condenser Leaving Water Temp Sensor Error | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 153doc Bit 153 | E-heater Leaving Water Temp Sensor Error | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 154doc Bit 154 | Refrigerant Liquid Temp Sensor Error | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 155doc Bit 155 | Condenser Entering Water Temp Sensor Error | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 156doc Bit 156 | Water Tank Temp Sensor Error | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 158doc Bit 158 | Refrigerant Vapor Line Temp Sensor Error | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 160doc Bit 160 | Remote Room Temp Sensor Error | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 169doc Bit 169 | Other Heat Source State | BIT | Read | 0 = Off; 1 = On | ||||
| CO | 170doc Bit 170 | Flow Switch State | BIT | Read | 0 = Close; 1 = Open | ||||
| CO | 171doc Bit 171 | IDU E-heater 1 State | BIT | Read | 0 = Off; 1 = On | ||||
| CO | 172doc Bit 172 | IDU E-heater 2 State | BIT | Read | 0 = Off; 1 = On | ||||
| CO | 173doc Bit 173 | Water Tank Heater State | BIT | Read | 0 = Off; 1 = On | ||||
| CO | 175doc Bit 175 | IDU Water Pump State | BIT | Read | 0 = Off; 1 = On | ||||
| CO | 176doc Bit 176 | Circulating 2-way Valve State | BIT | Read | 0 = Off; 1 = On | ||||
| CO | 179doc Bit 179 | Gate-Ctrl | BIT | Read | 0 = Card out; 1 = Card in | ||||
| CO | 185doc Bit 185 | E-heater 1 Welding Protection | BIT | Read | 0 = Normal; 1 = protected | ||||
| CO | 186doc Bit 186 | E-heater 2 Welding Protection | BIT | Read | 0 = Normal; 1 = protected | ||||
| CO | 187doc Bit 187 | Water Heater Welding Protection | BIT | Read | 0 = Normal; 1 = protected | ||||
| CO | 188doc Bit 188 | Water Flow Protection | BIT | Read | 0 = No; 1 = Yes | ||||
| CO | 190doc Bit 190 | IDU Recoverable Protection | BIT | Read | 0 = No; 1 = Yes | ||||
| CO | 191doc Bit 191 | IDU Irrecoverable Protection | BIT | Read | 0 = No; 1 = Yes | ||||
| HR | 2doc Word 2 | Mode | UINT16 | Read/write | 1 = Heat; 2 = Hot water; 3 = Cool+Heat water; 4 = Heat +Hot water; 5 = Cool | ||||
| HR | 3doc Word 3 | Optional E-Heater | UINT16 | Read/write | 1 = 1 set; 2 = 2 sets; 3 = Off | ||||
| HR | 4doc Word 4 | Disinfection Temp | Range 40-70°C, Default: 70°C | UINT16 | °C | Read/write | |||
| HR | 5doc Word 5 | Floor Debug Segments | Range 1-10 sections Default : 1 section | UINT16 | Read/write | ||||
| HR | 6doc Word 6 | Floor Debug Period 1 temp | Range 25-35°C, Default: 25°C | UINT16 | °C | Read/write | |||
| HR | 7doc Word 7 | Delta T of segment | Range 2-10°C, Default: 5°C | UINT16 | °C | Read/write | |||
| HR | 8doc Word 8 | Segment time | Range 12-72Hours, Default: 0 Hour | UINT16 | h | Read/write | |||
| HR | 9doc Word 9 | WOT-Cool | Range 7-25°C Default: 18°C | UINT16 | °C | Read/write | |||
| HR | 10doc Word 10 | WOT-Heat | Range 20-60°C [High-temp] / 20-55°C[low-temp] Default: 45°C[High-temp]/45°C[Low-temp] | UINT16 | °C | Read/write | |||
| HR | 11doc Word 11 | RT-Cool | Range 18-30°C, Default: 24°C | UINT16 | °C | Read/write | |||
| HR | 12doc Word 12 | RT-Heat | Range 18-30°C, Default:20°C | UINT16 | °C | Read/write | |||
| HR | 13doc Word 13 | T-water tank | Range 40-80°C, Default: 50°C | UINT16 | °C | Read/write | |||
| HR | 16doc Word 16 | T-HP max | Range 40-55°C, Default: 50°C | UINT16 | °C | Read/write | |||
| HR | 17doc Word 17 | Upper AT-Heat | Range 10-37°C, Default:25°C | UINT16 | °C | Read/write | |||
| HR | 19doc Word 19 | Upper RT-Heat | Range 22-30°C, Default: 24°C | UINT16 | °C | Read/write | |||
| HR | 20doc Word 20 | Lower RT-Heat | Range 18-21°C, Default: 18°C | UINT16 | °C | Read/write | |||
| HR | 21doc Word 21 | Upper WT-Heat | Range 46-60°C[High-temp]/ 46-55°C[Low-temp] Default: 55°C[High-temp]/55°C[Low-temp] | UINT16 | °C | Read/write | |||
| HR | 22doc Word 22 | Lower WT-Heat | Range 20-45°C Default: 40°C | UINT16 | °C | Read/write | |||
| HR | 23doc Word 23 | Upper AT-Cool | Range 26-48°C, Default :40°C | UINT16 | °C | Read/write | |||
| HR | 24doc Word 24 | Lower AT-Cool | Range 10-25°C, Default :25°C | UINT16 | °C | Read/write | |||
| HR | 25doc Word 25 | Upper RT-Cool | Range 24-30°C, Default : 27°C | UINT16 | °C | Read/write | |||
| HR | 26doc Word 26 | Lower RT-Cool | Range 18-23°C, Default : 22°C | UINT16 | °C | Read/write | |||
| HR | 27doc Word 27 | Upper WT-Cool | Range 15-25°C[with FCU] Default : 15°C | UINT16 | °C | Read/write | |||
| HR | 28doc Word 28 | Lower WT-Cool | Range 7-14°C Default : 7°C | UINT16 | °C | Read/write | |||
| HR | 29doc Word 29 | Delta T-Cool | Range 2-10°C, Default :5°C | UINT16 | °C | Read/write | |||
| HR | 30doc Word 30 | Delta T-Heat | Range 2-10°C, Default :10°C | UINT16 | °C | Read/write | |||
| HR | 31doc Word 31 | Delta T-hot water | Range 2-8°C, Default :5°C | UINT16 | °C | Read/write | |||
| HR | 32doc Word 32 | Delta T-Room temp | Range 1-5°C, Default :2°C | UINT16 | °C | Read/write | |||
| HR | 33doc Word 33 | Cool run time | Range 1-10min Default :3min | UINT16 | min | Read/write | |||
| HR | 34doc Word 34 | Heat run time | Range 1-10min Default :5min | UINT16 | min | Read/write | |||
| HR | 35doc Word 35 | Other thermal logic | Range 1-3 Default :1 | UINT16 | Read/write | ||||
| HR | 36doc Word 36 | Tank heater | Range 1-2 Default :1 | UINT16 | Read/write | ||||
| HR | 37doc Word 37 | Optional E-Heater logic | Range 1-2 Default :1 | UINT16 | Read/write | ||||
| HR | 38doc Word 38 | Current limit value | Range 0-50A Default :16A | UINT16 | A | Read/write | |||
| HR | 39doc Word 39 | Thermostat | UINT16 | Read/write | 0 = Without; 1 = Air; 2 = Air+hot water | ||||
| HR | 40doc Word 40 | Force mode | UINT16 | Read/write | 1 = Force-cool; 2 = Force-heat; 3 = Off | ||||
| HR | 41doc Word 41 | Air removal | UINT16 | Read/write | 1 = Air; 2 = Water tank; 3 = Off | ||||
| HR | 42doc Word 42 | On/Off | UINT16 | Read/write | 85 = Off (0x55); 170 = On (0xAA) | ||||
| HR | 43doc Word 43 | Power limit | Range 0-10 Kw Default :3 Kw | UINT16 | × 0.1 | kW | Read/write | ||
| HR | 44doc Word 44 | Error reset | UINT16 | Read/write | 0 = Does not clear fault; 1 = Clear fault | ||||
| HR | 117doc Word 117 | Unit status | UINT16 | Read | 1 = Cool; 2 = Heat; 6 = Hot water; 8 = Off | ||||
| HR | 132doc Word 132 | Thermostat | UINT16 | Read | 1 = Cool; 2 = Heat; 3 = Off | ||||
| HR | 133doc Word 133 | T-floor debug | Calculated value. | UINT16 | °C | Read | |||
| HR | 134doc Word 134 | Debug time | Calculated value. | UINT16 | h | Read | |||
| HR | 135doc Word 135 | Disinfection | UINT16 | Read | 0 = Off; 1 = Running; 2 = Done; 3 = Failed | ||||
| HR | 136doc Word 136 | Error Time for Floor Debug | Calculated value. | UINT16 | s | Read | |||
| HR | 137doc Word 137 | T-weather depend | Calculated value. | UINT16 | °C | Read | |||
| HR | 142doc Word 142 | Setting frequency | Range 0-100 Hz Default:0 | UINT16 | Hz | Read | |||
| HR | 143doc Word 143 | Running frequency | Range 0-100 Hz Default: 0 | UINT16 | Hz | Read |
Notes on this map
- Gree does not appear to host this protocol publicly; the link is an unaltered copy of Gree's document in the Ukrainian distributor Kiev Climate's manual library, filed there under Versati III as 'R32_Versati Modbus V1.5'. Page headers inside still read 'V1.1' while the cover says V1.5.
- Every word is printed as an unsigned integer with transmission value = actual value. Words whose printed range goes below 0 °C are left out because the document gives no rule for coding negative values: settings 14 (T-Eheater), 15 (T-Other switch on) and 18 (Lower AT-Heat), and all sensor readings 118-131 (outdoor, discharge, defrost, suction, economizer, discharge pressure, water out/in, optional water sensor, tank, remote room, gas pipe and liquid pipe temperatures).
- Reserved words and bits are left out, as are bits 99, 100, 177, 178 and 184, which are named but have no access type printed.
- Word 42 uses 0xAA for on and 0x55 for off, not 1/0. Word 43 is sent as kW x 10.
- Several limits differ between high-temperature and low-temperature units (words 10 and 21); the description quotes both ranges.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Gree Versati heat pump water heater (wired-controller Modbus RTU, protocol V1.5)
What Modbus registers does the Gree Versati heat pump water heater (wired-controller Modbus RTU, protocol V1.5) have?
This map lists 142 registers: 93 coils, 49 holding registers. 63 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Gree Versati heat pump water heater (wired-controller Modbus RTU, protocol V1.5) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are words numbered from 0 and coils are bits numbered from 0 (Bit 0 = Byte0.0). Word n is holding register n and Bit n is coil n on the wire; the protocol's example frames agree (read from word 1 sends 00 01, read from coil 5 sends 00 05).
What are the minimum Modbus registers to integrate the Gree Versati heat pump water heater (wired-controller Modbus RTU, protocol V1.5)?
Start with HR 42 On/Off (On/off); HR 2 Mode (Mode); HR 10 WOT-Heat (Heating water setpoint); HR 13 T-water tank (Tank setpoint); HR 117 Unit status (Unit status); HR 143 Running frequency (Compressor running frequency); CO 80 Compressor State (Compressor on); CO 86 Defrosting State (Defrosting); CO 102 System Recoverable Protection (System recoverable protection).
How do I enable Modbus control of the Gree Versati heat pump water heater (wired-controller Modbus RTU, protocol V1.5)?
On the wired controller press COMMISSION, then FUNCTION, page to 'Address', set the BMS address and press OK. The address must not be 0 or 126 and must match the address the BMS sends.
Where is the official Gree Versati heat pump water heater (wired-controller Modbus RTU, protocol V1.5) Modbus documentation?
The source is Modbus Protocol (V1.5) for the Versati Heat Pump Water Heater (V1.5). Gree doesn't publish it on its own website, so this map was re-typed from a free copy at https://man.kievclimate.com/man/Gree/Versati/Versati%20III/R32_Versati%20Modbus%20V1.5.pdf. It may be an older revision, so check it against the live unit.
More Gree Modbus register maps
- Split AC unit (VRF / split AC gateway built in)
Gree Export residential split air conditioners (built-in Modbus on indoor unit / wired controller)
Gree export residential air conditioners whose indoor-unit controller or wired controller has the integrated Modbus RTU interface; protocol PDF dated 2023-05.
Also known as: Gree residential split Modbus, Gree wall split Modbus, Gree wired controller Modbus - VRF / split AC gateway
Gree Modbus Gateway (Mini) ME30-24/E6(M) for GMV multi VRF systems
Gree Modbus Gateway (Mini) on CAN-bus multi VRF systems (GMV5, GMV5 C/E/HR/MAX/MINI/SLIM, GMV Water, energy-recovery ventilation); Communication Protocol V2.0, multi VRF part only.
Also known as: ME30-24/E6(M), Modbus Gateway(Mini), GMV5 Modbus gateway - Split AC unit (VRF / split AC gateway built in)
Gree U-Match all-DC-inverter duct / cassette / floor-ceiling units (built-in Modbus)
Gree U-Match fourth-generation all-DC-inverter light-commercial units whose controller has the integrated Modbus RTU interface; Chinese-English protocol dated 2018-03-07.
Also known as: U-Match, Gree U-Match 4th generation DC inverter, U-Match BMS Modbus
Other pumps register maps
- Heat pump (air-to-water)
LG THERMA V R32 Monobloc air-to-water heat pump (built-in Modbus RTU)
LG THERMA V R32 Monobloc air-to-water heat pumps covered by installation manual MFL68026615 Rev.02 (North American models ZHBW041GA0 / ZHBW048GA0 / ZHBW055GA0), using the indoor PCB's own Modbus RTU slave port.
Also known as: ZHBW041GA0, ZHBW048GA0, ZHBW055GA0, KPHTC411M, KPHTC481M, KPHTC551M, THERMA V, MFL68026615 - Heat pump / ventilation unit controller (air handler)
Nilan CTS602 controller with HMI350T panel (Modbus version 23)
Nilan ventilation, heat-recovery and compact heat pump units with the CTS602 board and HMI350T user panel, Modbus protocol version 23 (software 3.6.58/3.6.59).
Also known as: CTS 602, CTS602 HMI350T, CTS602 w. HMI350T - Pump (refrigerant pumping unit for Liebert XD rack cooling)
Vertiv Liebert XDP pumping unit for XD systems with iCOM v4 (IntelliSlot Modbus)
Liebert XDP pumping units on the iCOM v4 controller with a Liebert IntelliSlot Modbus card.
Also known as: Liebert XDP, XDP, Liebert XD pumping unit - Pump (smart circulator)
Wilo Stratos MAXO with CIF module Modbus RTU
Wilo-Stratos MAXO single and twin-head circulators fitted with the plug-in CIF module Modbus RTU (article 2190368, UL 2237080), module firmware 1.00-99.99; some registers need a newer module version as noted.
Also known as: Wilo-Stratos MAXO, Stratos MAXO-D, Stratos MAXO-Z, CIF-Module Modbus RTU, CIF Modbus RTU 2190368, CIF Modbus RTU UL 2237080 - Pump (reverse osmosis water treatment unit)
Condair RO-E reverse osmosis water treatment (Integrated Controller, Modbus RTU/TCP)
Condair RO-E / RO-E+ with the Integrated Controller, per addendum 2603326-G.
Also known as: Condair RO-E, RO-E+, Condair RO-E+ - Heat pump (water-source heat pump controller)
First Co. WSHP series DDC controller CB900 (water-source heat pump, Modbus RTU/TCP)
First Co. / AE-Air water-source heat pumps (WSV and related series) with the factory DDC controller CB900, without hot-gas reheat (IOM8083D02 rev. A).
Also known as: CB900, CB900-1, CB900-2, IOM8083D02, WSV series DDC, First Co. WSHP DDC controller, AE-Air WSHP DDC
All pumps Modbus register maps →
Source: Modbus Protocol (V1.5) for the Versati Heat Pump Water Heater · V1.5 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.