Manufacturer
Gree Modbus register maps
Updated 19 November 2026
4 Gree models, 441 registers in all, each re-typed from Gree’s own free documentation and checked against it.
- Split AC unit (VRF / split AC gateway built in)
Gree Export residential split air conditioners (built-in Modbus on indoor unit / wired controller)
Gree export residential air conditioners whose indoor-unit controller or wired controller has the integrated Modbus RTU interface; protocol PDF dated 2023-05.
Also known as: Gree residential split Modbus, Gree wall split Modbus, Gree wired controller Modbus - VRF / split AC gateway
Gree Modbus Gateway (Mini) ME30-24/E6(M) for GMV multi VRF systems
Gree Modbus Gateway (Mini) on CAN-bus multi VRF systems (GMV5, GMV5 C/E/HR/MAX/MINI/SLIM, GMV Water, energy-recovery ventilation); Communication Protocol V2.0, multi VRF part only.
Also known as: ME30-24/E6(M), Modbus Gateway(Mini), GMV5 Modbus gateway - Split AC unit (VRF / split AC gateway built in)
Gree U-Match all-DC-inverter duct / cassette / floor-ceiling units (built-in Modbus)
Gree U-Match fourth-generation all-DC-inverter light-commercial units whose controller has the integrated Modbus RTU interface; Chinese-English protocol dated 2018-03-07.
Also known as: U-Match, Gree U-Match 4th generation DC inverter, U-Match BMS Modbus - Heat pump (air-to-water)
Gree Versati heat pump water heater (wired-controller Modbus RTU, protocol V1.5)
Gree Versati air-to-water heat pumps through the BMS port of the wired controller, per 'Modbus Protocol (V1.5) for the Versati Heat Pump Water Heater'. The document itself does not name a generation or refrigerant; the distributor files it as the R32 Versati III protocol.
Also known as: Versati III, R32 Versati, Versati heat pump water heater, Gree Versati Modbus V1.5
Gree: default communication settings
Factory defaults as the manufacturer documents them. Change one setting at a time on site and write down what you changed. Word order applies to 32-bit values; the addressing column says how the manufacturer prints register numbers (every map on this site also gives the 0-based wire address).
| Model | Transport | Unit ID | Serial | Word order | Documented addressing | Registers |
|---|---|---|---|---|---|---|
| Export residential split air conditioners (built-in Modbus on indoor unit / wired controller) | RTU | Not stated | 9600 baud, 8N1 | 16-bit only | 0-based | 113 |
| Modbus Gateway (Mini) ME30-24/E6(M) for GMV multi VRF systems | RTU | Not stated | 9600 baud, 8N1 | 16-bit only | 0-based | 65 |
| U-Match all-DC-inverter duct / cassette / floor-ceiling units (built-in Modbus) | RTU | Not stated | 9600 baud, 8N1 | 16-bit only | 0-based | 121 |
| Versati heat pump water heater (wired-controller Modbus RTU, protocol V1.5) | RTU | Not stated | 9600 baud, 8N1 | 16-bit only | 0-based | 142 |