Heat pump (air-to-water) Modbus interface · Modbus register map
Panasonic CZ-NSMB A2W Modbus PCB for Aquarea air-to-water heat pumps Modbus register map
Updated 19 November 2026
The CZ-NSMB is Panasonic's own Modbus RTU slave board that plugs into the CN-CNT connector of an Aquarea air-to-water unit. All points are holding registers: on/off, operating mode, zone and tank setpoints, compensation curves, smart-grid settings, quiet and powerful modes, sterilisation and system reset requests, plus readings of outdoor, water, tank and zone temperatures, error codes, energy use and generation, and unit configuration.
This page lists 153 Modbus registers for the Panasonic CZ-NSMB A2W Modbus PCB for Aquarea air-to-water heat pumps — 75 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Panasonic’s own free documentation (linked below) and checked against it.
- Manufacturer
- Panasonic
- Model
- CZ-NSMB A2W Modbus PCB for Aquarea air-to-water heat pumps
- Equipment type
- Heat pump (air-to-water) Modbus interface
- Registers
- 153 (75 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8N2
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- CZ-NSMB, A2W Modbus PCB, WH-CME8, WH-CME8L, WH-WXG20ME8, WH-WXG25ME8, WH-WXG30ME8, Aquarea M series Modbus, Big A2W Modbus
- Source document
- User Manual - A2W Modbus PCB - Model no. CZ-NSMB · M02412F0
Integration notes: Panasonic CZ-NSMB A2W Modbus PCB for Aquarea air-to-water heat pumps
Fit the PCB on the CN-CNT connector, set address and baud with SW1, then poll holding registers 0-52 for state and temperatures and write 0 (on/off), 4 (mode), 12/13 or 226-229 (zone setpoints) and 30/33 (tank).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Operation | UINT16 | On/off | Read/write |
| HR 4 | Mode | UINT16 | Operating mode | Read/write |
| HR 1 | Outdoor actual temperature | INT16 | Outdoor temperature | Read |
| HR 2 | Outlet water temperature | INT16 | Outlet water temperature | Read |
| HR 12 | Zone 1: (Water shift/room/pool) setpoint temperature | INT16 | Zone 1 setpoint | Read/write |
| HR 30 | Tank ON/OFF | UINT16 | Tank on/off | Read/write |
| HR 33 | Tank water set temperature | UINT16 | Tank setpoint | Read/write |
| HR 52 | Error code | UINT16 | Error code | Read |
| HR 70 | Current error status | UINT16 | Error status | Read |
Enable Modbus control & writes
No software enable: connect the supplied CN-CNT cable to the unit's main (or optional) PCB, connect CN2 to the RS-485 bus and set the slave address and baud rate on DIP SW1.
Byte order & addressing
- Serial format is 8N2 by default; 8N1 is also supported.
- Supported functions: 3, 4, 6 and 16; all points are holding registers.
- Mode codes 8-11 (Auto Heat, Auto Heat Tank, Auto Cool, Auto Cool Tank) are read-only states.
Network setup
- DIP SW1 sets slave address (default 1) and baud rate 9600 (default), 19200, 57600 or 115200.
- DIP SW2 P8 switches in the 120 ohm termination (default off).
- Up to 63 CZ-NSMB boards per bus; one heat pump per board.
- On Big A2W outdoor units the PCB sits in the C-BOX and the bus lands on terminals U1/U2.
Watch out for
- LED D3 flashing means the heat pump has not finished initialising; registers may not be valid yet.
- The remote controller and Modbus can be used at the same time.
Panasonic CZ-NSMB A2W Modbus PCB for Aquarea air-to-water heat pumps Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0 | Operation | UINT16 | Read/write | 0 = Off; 1 = On (default) | ||||
| HR | 1 | Outdoor actual temperature | -127°C- 127°C | INT16 | °C | Read | |||
| HR | 2 | Outlet water temperature | -127°C-127°C | INT16 | °C | Read | |||
| HR | 3 | Inlet water temperature | -127°C-127°C | INT16 | °C | Read | |||
| HR | 4 | Mode | Codes 8-11 are read-only states. | UINT16 | Read/write | 1 = Heat; 2 = Heat tank; 3 = Tank; 4 = Cool Tank; 5 = Cool; 6 = Auto (default); 7 = Auto Tank; 8 = Auto Heat; 9 = Auto Heat Tank; 10 = Auto Cool; 11 = Auto Cool Tank | |||
| HR | 5 | Heat mode water temperature sensor | UINT16 | Read/write | 1 = Compensation curve; 2 = Direct | ||||
| HR | 6 | Cool mode water temperature sensor | UINT16 | Read/write | 1 = Compensation curve; 2 = Direct | ||||
| HR | 9 | Zone1-Zone2 ON/OFF | UINT16 | Read/write | 1 = On-Off; 2 = Off/On; 3 = On/On | ||||
| HR | 10 | Zone 1 sensors | UINT16 | Read/write | 1 = Water temperature; 2 = External; 3 = Internal; 4 = Thermistor | ||||
| HR | 11 | Zone 2 sensors | UINT16 | Read/write | 1 = Water temperature; 2 = External; 3 = Internal; 4 = Thermistor | ||||
| HR | 12 | Zone 1: (Water shift/room/pool) setpoint temperature | Zone 1 target (heat): water shift ±5, water 20-R36, room 10-30, pool 15-35 °C. | INT16 | °C | Read/write | |||
| HR | 13 | Zone 2: (Water shift/room/pool) setpoint temperature | Zone 2 target (heat): water shift ±5, water 20-R36, room 10-30, pool 15-35 °C. | INT16 | °C | Read/write | |||
| HR | 14 | Zone 1: Actual (water outlet/ room/pool) temperature | -127°C-127°C | INT16 | °C | Read | |||
| HR | 15 | Zone 2: Actual (water outlet/ room/pool) temperature | -127°C-127°C | INT16 | °C | Read | |||
| HR | 16 | Zone 1: Temperature conf mode | UINT16 | Read | 1 = Room; 2 = Compensation curve; 3 = Direct; 4 = Pool | ||||
| HR | 17 | Zone 2: Temperature conf mode | UINT16 | Read | 1 = Room; 2 = Compensation curve; 3 = Direct; 4 = Pool | ||||
| HR | 18 | Zone 1: Min. setpoint temperature | Lowest allowed zone 1 setpoint for the active sensor type (e.g. water shift -5 °C). | INT16 | °C | Read | |||
| HR | 19 | Zone 1: Max. setpoint temperature | Highest allowed zone 1 setpoint for the active sensor type (e.g. room 30 °C heat). | UINT16 | °C | Read | |||
| HR | 20 | Zone 2: Min. setpoint temperature | Lowest allowed zone 2 setpoint for the active sensor type (e.g. water shift -5 °C). | INT16 | °C | Read | |||
| HR | 21 | Zone 2: Max. setpoint temperature | Highest allowed zone 2 setpoint for the active sensor type (e.g. room 30 °C heat). | UINT16 | °C | Read | |||
| HR | 30 | Tank ON/OFF | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 32 | Tank actual temperature | -127°C-127°C | INT16 | °C | Read | |||
| HR | 33 | Tank water set temperature | 40°C - R36 value | UINT16 | °C | Read/write | |||
| HR | 34 | Tank heater | UINT16 | Read/write | 1 = Internal; 2 = External | ||||
| HR | 35 | Tank water min. setpoint temperature | 40°C (fixed) | UINT16 | °C | Read | |||
| HR | 36 | Tank water max. setpoint temperature | 55°C - 75°C | UINT16 | °C | Read | |||
| HR | 45 | Tank mode energy consumption | R0 - 65.534 W | UINT16 | W | Read | |||
| HR | 46 | Heat mode energy consumption | 0 - 65.534 W | UINT16 | W | Read | |||
| HR | 47 | (Cool mode/Heat recovery mode) energy consumption | 0 - 65.534 W | UINT16 | W | Read | |||
| HR | 49 | Type of Modbus Gateway | UINT16 | Read | 1 = Standard gateway; 2 = Checker gateway | ||||
| HR | 50 | Version of Modbus gateway | Gateway firmware version as hex (example 0x0100). | UINT16 | Read | ||||
| HR | 52 | Error code | 0 = no error; 1XX = Hxx, 2XX = Fxx, 3XX = Uxx (112 = H12). | UINT16 | Read | ||||
| HR | 64 | Deice status | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 70 | Current error status | UINT16 | Read | 0 = No error; 1 = Error | ||||
| HR | 81 | Tank connection | UINT16 | Read/write | 0 = No; 1 = Yes | ||||
| HR | 82 | Number zones | UINT16 | Read/write | 1 = Zone; 2 = Zones | ||||
| HR | 83 | Zone 1 setup | UINT16 | Read/write | 1 = Room; 2 = Pool | ||||
| HR | 84 | Zone 2 setup | UINT16 | Read/write | 1 = Room; 2 = Pool | ||||
| HR | 85 | Direction | UINT16 | Read | 1 = Room; 2 = Tank | ||||
| HR | 86 | Outdoor type | UINT16 | Read | 1 = STD; 2 = TCAP; 3 = HWT | ||||
| HR | 105 | Heat-Cool meter | If K series onwards. | UINT16 | Read | 0 = No; 1 = Yes | |||
| HR | 106 | Tank meter | If K series onwards. | UINT16 | Read | 0 = No; 1 = Yes | |||
| HR | 107 | Electricity meter HP | If K series onwards. | UINT16 | Read | 0 = No; 1 = Yes | |||
| HR | 111 | SG ready: Control pattern | If K series onwards. | UINT16 | Read | 1 = Normal; 2 = HP stop; 3 = Capacity 1; 4 = Capacity 2 | |||
| HR | 112 | Water pressure | If K series onwards. Range: 0 bar - 5080 mbar | UINT16 | mbar | Read | |||
| HR | 113 | Water inlet 2 temperature | If L series onwards. Range: -127°C - 127°C | INT16 | °C | Read | |||
| HR | 116 | RC-1: Room thermostat internal sensor temperature (integer part) | -127°C-127°C | INT16 | °C | Read | |||
| HR | 117 | Model series selection | UINT16 | Read | 1 = H-Series; 2 = J-Series; 3 = K-Series; 4 = L-Series; 5 = M-Series | ||||
| HR | 118 | RC-2: Room thermostat internal sensor temperature (integer part) | -127°C-127°C | INT16 | °C | Read | |||
| HR | 150 | External SW | UINT16 | Read/write | 0 = No; 1 = Yes | ||||
| HR | 151 | Heat-Cool SW | UINT16 | Read/write | 0 = Disable; 1 = Enable | ||||
| HR | 152 | External compressor SW | H/J/K/L: 0 no, 1 yes. M series: 0 no, 1 heat source, 2 heater. | UINT16 | Read/write | ||||
| HR | 153 | Solar connection | UINT16 | Read/write | 0 = No; 1 = Yes & Buffer Tank; 2 = Yes & DHW Tank | ||||
| HR | 154 | SG ready | H/J/K/L: 0 no, 1 yes. M series: 0 no, 1 capacity, 2 power consumption. | UINT16 | Read/write | ||||
| HR | 155 | rt Buffer tank | 0 °C - 10 °C | UINT16 | °C | Read/write | |||
| HR | 156 | SG ready: DHW capacity up (1-0) | 50% - 150% Resolution: ±5% | UINT16 | % | Read/write | |||
| HR | 157 | SG ready: Heat capacity up (1-0) | 50% - 150% Resolution: ±5% | UINT16 | % | Read/write | |||
| HR | 158 | Compensation curve - Heat - Zone 1 - Max. temperature | 20°C - R36 value | UINT16 | °C | Read/write | |||
| HR | 159 | Compensation curve - Heat - Zone 1 - Min. temperature | 20°C - R36 value | UINT16 | °C | Read/write | |||
| HR | 160 | Compensation curve - Heat - Zone 1 - Outdoor air min. Temperature | -20°C - 15°C | INT16 | °C | Read/write | |||
| HR | 161 | Compensation curve - Heat - Zone 1 - Outdoor air max. Temperature | -20°C - 15°C | INT16 | °C | Read/write | |||
| HR | 162 | Compensation curve - Heat - Zone 2 - Max. temperature | 20°C - R36 value | UINT16 | °C | Read/write | |||
| HR | 163 | Compensation curve - Heat - Zone 2 - Min. temperature | 20°C - R36 value | UINT16 | °C | Read/write | |||
| HR | 164 | Compensation curve - Heat - Zone 2 - Outdoor air min. Temperature | -20°C - 15°C | INT16 | °C | Read/write | |||
| HR | 165 | Compensation curve - Heat - Zone 2 - Outdoor air max. Temperature | -20°C - 15°C | INT16 | °C | Read/write | |||
| HR | 166 | Compensation curve - Cool - Zone 1 - Max. temperature | 5°C - 20°C | UINT16 | °C | Read/write | |||
| HR | 167 | Compensation curve - Cool - Zone 1 - Min. temperature | 5°C - 20°C | UINT16 | °C | Read/write | |||
| HR | 168 | Compensation curve - Cool - Zone 1 - Outdoor air min. Temperature | 15°C - 30°C | UINT16 | °C | Read/write | |||
| HR | 169 | Compensation curve - Cool - Zone 1 - Outdoor air max. Temperature | 15°C - 30°C | UINT16 | °C | Read/write | |||
| HR | 170 | Compensation curve - Cool - Zone 2 - Max. temperature | 5°C - 20°C | UINT16 | °C | Read/write | |||
| HR | 171 | Compensation curve - Cool - Zone 2 - Min. temperature | 5°C - 20°C | UINT16 | °C | Read/write | |||
| HR | 172 | Compensation curve - Cool - Zone 2 - Outdoor air min. Temperature | 15°C - 30°C | UINT16 | °C | Read/write | |||
| HR | 173 | Compensation curve - Cool - Zone 2 - Outdoor air max. Temperature | 15°C - 30°C | UINT16 | °C | Read/write | |||
| HR | 174 | Solar (actual) | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 175 | 2-way valve direction (actual) | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 176 | Zone1: Water temperature | -127°C - 127°C | INT16 | °C | Read | |||
| HR | 177 | Zone2: Water temperature | -127°C - 127°C | INT16 | °C | Read | |||
| HR | 178 | Zone 1 temperature (target) | -127°C - 127°C | INT16 | °C | Read | |||
| HR | 179 | Zone 2 temperature (target) | -127°C - 127°C | INT16 | °C | Read | |||
| HR | 180 | Buffer tank: Water temperature | -127°C - 127°C | INT16 | °C | Read | |||
| HR | 181 | Solar: Water temperature | -127°C - 127°C | INT16 | °C | Read | |||
| HR | 182 | Pool: Water temperature | -127°C - 127°C | INT16 | °C | Read | |||
| HR | 184doc 184/185 | Compressor total ON time | 32-bit: first register MSB, second LSB (as printed). | UINT32 | ABCD | h | Read | ||
| HR | 187 | Tank mode energy generation | 0 - 65.534 W | UINT16 | W | Read | |||
| HR | 188 | Heat mode energy generation | 0 - 65.534 W | UINT16 | W | Read | |||
| HR | 189 | (Cool mode/Heat recovery mode) energy generation | 0 - 65.534 W | UINT16 | W | Read | |||
| HR | 197 | Powerful (request) | UINT16 | Read/write | 1 = OFF; 2 = ON 30 mins; 3 = ON 60 mins; 4 = ON 90 mins | ||||
| HR | 198 | Quiet (request) | UINT16 | Read/write | 1 = OFF; 2 = Level 1; 3 = Level 2; 4 = Level 3 | ||||
| HR | 199 | Quiet timer | UINT16 | Read/write | 1 = Cancel; 2 = Set | ||||
| HR | 200 | System reset (request) | UINT16 | Write | 0 = No request; 1 = Request | ||||
| HR | 202 | Sterilisation (request) | UINT16 | Write | 0 = No request; 1 = Request | ||||
| HR | 208 | Optional PCB connection | UINT16 | Read/write | 0 = No; 1 = Yes | ||||
| HR | 212 | Buffer tank connection | UINT16 | Read/write | 0 = No; 1 = Yes | ||||
| HR | 213 | Heater capacity | Codes not printed; options 3/6/9 kW, or 6/12/18 kW or 1-3 heaters on Big-A2W. | UINT16 | Read/write | ||||
| HR | 217 | Bivalent heat mode | UINT16 | Read/write | 0 = No; 1 = Yes | ||||
| HR | 218 | Bivalent DHW mode | UINT16 | Read/write | 0 = No; 1 = Yes | ||||
| HR | 219 | Demand control | UINT16 | Read/write | 0 = No; 1 = Yes | ||||
| HR | 222 | Defrost signal | If J series onwards. | UINT16 | Read/write | 0 = No; 1 = Yes | |||
| HR | 226 | Zone 1: (Water shift/water/ room/pool) set temperature for Heat mode | Zone 1 heat target: water shift ±5, water 20-R36, room 10-30, pool 15-35 °C. | INT16 | °C | Read/write | |||
| HR | 227 | Zone 1: (Water shift/water/ room) set temperature for Cool mode | Zone 1 cool target: water shift -5 to 5, water 5-20, room 18-35 °C. | INT16 | °C | Read/write | |||
| HR | 228 | Zone 2: (Water shift/water/ room/pool) set temperature for Heat mode | Zone 2 heat target: water shift ±5, water 20-R36, room 10-30, pool 15-35 °C. | INT16 | °C | Read/write | |||
| HR | 229 | Zone 2: (Water shift/water/ room) set temperature for Cool mode | Zone 2 cool target: water shift -5 to 5, water 5-20, room 18-35 °C. | INT16 | °C | Read/write | |||
| HR | 235 | Current Lv | 0 - 20 Lv | UINT16 | Read/write | ||||
| HR | 248 | SG ready: DHW capacity up (2-0) | 50 - 150 % Resolution: ±5% | UINT16 | % | Read/write | |||
| HR | 249 | SG ready: Heat capacity up (2-1) | 50 - 150 % Resolution: ±5% | UINT16 | % | Read/write | |||
| HR | 256 | Tank: Floor operation time (maximum) | 0 - 600 min Resolution: ±30min | UINT16 | min | Read/write | |||
| HR | 257 | Tank: Heat up time (maximum) | 5 - 240 min Resolution: ±5 min | UINT16 | min | Read/write | |||
| HR | 258 | Tank: Re-heat temperature | -12°C - -2°C | INT16 | °C | Read/write | |||
| HR | 259 | Tank: Sterilisation boiling temperature | 55°C - 75°C | UINT16 | °C | Read/write | |||
| HR | 260 | Tank: Sterilisation operation time (maximum) | 5 - 60 min Resolution: ± 5min | UINT16 | min | Read/write | |||
| HR | 261 | SG ready: Cool capacity up (1-2) | If J series onwards. Range: -15°C - 0°C | INT16 | °C | Read/write | |||
| HR | 262 | SG ready: Cool capacity up (2-2) | If J series onwards. Range: -15°C - 0°C | INT16 | °C | Read/write | |||
| HR | 267 | External SW | UINT16 | Read | 1 = Close; 2 = Open | ||||
| HR | 268 | Heat-Cool SW | UINT16 | Read | 1 = Heat; 2 = Cool | ||||
| HR | 269 | Powerful (actual) | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 270 | Quiet (actual) | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 271 | Heat mode water set temperature range | UINT16 | Read | 1 = Range 1; 2 = Range 2; 3 = Range 3 | ||||
| HR | 273 | Room heater (actual) | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 274 | Tank heater (actual) | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 275 | Bivalent (actual) | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 276 | Last error number (x1) | One digit (0-9) of the last error number; 10 = no error. | UINT16 | Read | 10 = No error | |||
| HR | 277 | Last error number (x2) | One digit (0-9) of the last error number; 10 = no error. | UINT16 | Read | 10 = No error | |||
| HR | 278 | Last error number (x3) | One digit (0-9) of the last error number; 10 = no error. | UINT16 | Read | 10 = No error | |||
| HR | 280 | Last error character | UINT16 | Read | 0 = No error; 1 = U; 2 = H; 3 = F | ||||
| HR | 289 | Sterilization status (actual) | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 305 | Indoor unit model reference | Read as hex: e.g. EEPROM A53D8170C reads 0x8170. | UINT16 | Read | ||||
| HR | 314 | Outdoor Unit Model Reference | Read as hex: e.g. EEPROM A53D8191C reads 0x8191. | UINT16 | Read | ||||
| HR | 351 | Capacity rank | 0 - 30 kW | UINT16 | kW | Read | |||
| HR | 352 | Electricity meter HP | UINT16 | Read | 1 = No error; 2 = Error | ||||
| HR | 353 | Heat-Cool meter | UINT16 | Read | 1 = No error; 2 = Error | ||||
| HR | 354 | Tank meter | UINT16 | Read | 1 = No error; 2 = Error | ||||
| HR | 358 | Modbus Meter Gateway | UINT16 | Read | 1 = No error; 2 = Error; 3 = Comm. not yet establish | ||||
| HR | 360 | Heat mode energy consumption | If K series onwards. Range: 0 - 65.534 W | UINT16 | W | Read | |||
| HR | 361 | (Cool mode/Heat recovery mode) energy consumption | If K series onwards. Range: 0 - 65.534 W | UINT16 | W | Read | |||
| HR | 362 | Tank mode energy consumption | If K series onwards. Range: 0 - 65.534 W | UINT16 | W | Read | |||
| HR | 363 | Heat mode energy generation | If K series onwards. Range: 0 - 65.534 W | UINT16 | W | Read | |||
| HR | 364 | (Cool mode/Heat recovery mode) energy generation | If K series onwards. Range: 0 - 65.534 W | UINT16 | W | Read | |||
| HR | 365 | Tank mode energy generation | If K Series onwards. Range: 0 - 65.534 W | UINT16 | W | Read | |||
| HR | 378 | Consumption reset | Write 1337 to clear the consumption counters; 0 = no request. | UINT16 | Write | ||||
| HR | 417 | SG ready: Power consumption [1-0]: DHW | If M series. Range: 500 W to 10000 W Resolution: ±100 W | UINT16 | W | Read/write | |||
| HR | 418 | SG ready: Power consumption [1-1]: Heat | If M series. Range: 500 W to 10000 W Resolution: ±100 W | UINT16 | W | Read/write | |||
| HR | 419 | SG ready: Power consumption [1-2]: Cool | If M series. Range: 500 W to 10000 W Resolution: ±100 W | UINT16 | W | Read/write | |||
| HR | 420 | SG ready: Power consumption [2-0]: DHW | If M series. Range: 500 W to 10000 W Resolution: ±100 W | UINT16 | W | Read/write | |||
| HR | 421 | SG ready: Power consumption [2-1]: Heat | If M series. Range: 500 W to 10000 W Resolution: ±100 W | UINT16 | W | Read/write | |||
| HR | 422 | SG ready: Power consumption [2-2]: Cool | If M series. Range: 500 W to 10000 W Resolution: ±100 W | UINT16 | W | Read/write | |||
| HR | 423 | SG ready: HPU stop consumption | If M series. Range: 500 W to 10000 W Resolution: ±100 W | UINT16 | W | Read/write | |||
| HR | 426 | Anti-stick mode | If M series. | UINT16 | Read | 0 = Disable; 1 = Enable | |||
| HR | 427 | DHW circulation | If M series. | UINT16 | Read | 0 = Off; 1 = On | |||
| HR | 428 | Power consumption: Minimum range | If M series. | UINT16 | Read | 1 = 0.5 kW; 2 = 1.0 kW; 3 = 1.5 kW; 4 = 2.0 kW; 5 = 2.5 kW; 6 = 3.0 kW; 7 = 3.5 kW; 8 = 4.0 kW; 9 = 5.0 kW; 10 = 6.0 kW; 11 = 7.0 kW; 12 = 8.0 kW; 13 = 9.0 kW; 14 = 10.0 kW | |||
| HR | 429 | Power consumption: Maximum range | If M series. | UINT16 | Read | 1 = 0.5 kW; 2 = 1.0 kW; 3 = 1.5 kW; 4 = 2.0 kW; 5 = 2.5 kW; 6 = 3.0 kW; 7 = 3.5 kW; 8 = 4.0 kW; 9 = 5.0 kW; 10 = 6.0 kW; 11 = 7.0 kW; 12 = 8.0 kW; 13 = 9.0 kW; 14 = 10.0 kW | |||
| HR | 432 | Electrical anode (actual) | If M series. | UINT16 | Read | 0 = Off; 1 = On | |||
| HR | 437 | Big-A2W Heater Capacity | If Big-A2W. | UINT16 | Read/write | 0 = <18 kW; 1 = >18 kW | |||
| HR | 438 | Big-A2W | If M series. | UINT16 | Read | 0 = No; 1 = Yes |
Notes on this map
- The manual gives no data type per register. Values whose printed range goes below zero (temperatures, water-shift setpoints, curve outdoor limits, tank re-heat and cool capacity shifts) are listed as INT16; all others as UINT16.
- Temperatures are whole degrees Celsius by default. DIP SW2 P1 ON switches all temperature registers to tenths (x10) and P2 ON to Fahrenheit; the scale of 1 here matches the default.
- 32-bit totals at 120/121-130/131 and 366/367-372/373 are left out: the manual marks them only '(MSB)' or not at all and never says which register holds the high word. 184/185 (compressor hours) is printed as [MSB/LSB] and is listed as UINT32 with the high word first.
- Many registers apply only to some series ('If K series onwards', 'If M series'); the condition is quoted in the description. 213 and 437 apply to Big A2W variants.
- Error code 52 encodes the remote-controller code: 1XX = Hxx, 2XX = Fxx, 3XX = Uxx (e.g. 214 = F14), per the manual's error-code section (the register table itself prints 1XXX/2XXX/3XXX).
- Write 1337 to 378 to clear the consumption counters.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Panasonic CZ-NSMB A2W Modbus PCB for Aquarea air-to-water heat pumps
What Modbus registers does the Panasonic CZ-NSMB A2W Modbus PCB for Aquarea air-to-water heat pumps have?
This map lists 153 registers: 153 holding registers. 75 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Panasonic CZ-NSMB A2W Modbus PCB for Aquarea air-to-water heat pumps Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are listed by protocol address starting at 0 (address 0 = Operation on/off), so the printed address goes on the wire unchanged.
What byte order does the Panasonic CZ-NSMB A2W Modbus PCB for Aquarea air-to-water heat pumps use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Panasonic CZ-NSMB A2W Modbus PCB for Aquarea air-to-water heat pumps?
Start with HR 0 Operation (On/off); HR 4 Mode (Operating mode); HR 1 Outdoor actual temperature (Outdoor temperature); HR 2 Outlet water temperature (Outlet water temperature); HR 12 Zone 1: (Water shift/room/pool) setpoint temperature (Zone 1 setpoint); HR 30 Tank ON/OFF (Tank on/off); HR 33 Tank water set temperature (Tank setpoint); HR 52 Error code (Error code); HR 70 Current error status (Error status).
How do I enable Modbus control of the Panasonic CZ-NSMB A2W Modbus PCB for Aquarea air-to-water heat pumps?
No software enable: connect the supplied CN-CNT cable to the unit's main (or optional) PCB, connect CN2 to the RS-485 bus and set the slave address and baud rate on DIP SW1.
Where is the official Panasonic CZ-NSMB A2W Modbus PCB for Aquarea air-to-water heat pumps Modbus documentation?
The source is User Manual - A2W Modbus PCB - Model no. CZ-NSMB (M02412F0), published free by Panasonic at https://www.library.aircon.panasonic.eu/GB_en/doc/xujWwPz*Ev0=/.
More Panasonic Modbus register maps
- Energy meter
Panasonic KW7M Eco-POWER METER
Panasonic KW7M (AKW7111 / AKW7111B) with Modbus RTU selected, user manual ARCT1F434E-6.
Also known as: AKW7111, AKW7111B - Energy meter
Panasonic KW8M Eco-POWER METER
Panasonic KW8M AKW8111 and AKW8111H (logging/demand version) with Modbus RTU selected, manual ARCT1F440E-8.
Also known as: AKW8111, AKW8111H - Energy meter (multi-circuit power monitor)
Panasonic KW9M Eco-POWER METER
Panasonic KW9M (AKW91110) with the Modbus RTU protocol selected, user manual WUME-KW9M-10.
Also known as: AKW91110
Other pumps register maps
- Pump (multistage pressure-boosting pump)
Wilo Helix2.0-VE / Medana CH3-LE with CIF module Modbus RTU
Wilo Helix2.0-VE pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.
Also known as: Wilo-Helix2.0-VE, Medana CH3-LE, Wilo-Medana CH3-LE - Pump controller (switchgear)
Wilo Wilo-Control EC-WP switchgear (ModBus RTU)
Wilo-Control EC-WP for one or two fixed-speed pumps, hardware HW2, software SW102x (instructions Ed.01/2024-08, 2552567).
Also known as: Control EC-WP, Wilo Control EC WP, EC-WP - Heat pump
Daikin DCOM-LT/MB Modbus interface for Daikin Altherma LT heat pumps
Daikin Altherma low-temperature (LT) air-to-water heat pumps fitted with the DCOM-LT/MB (model number 534-001) P1P2-to-Modbus RTU interface, standard operating mode, per reference manual 534-252-A3.
Also known as: DCOM-LT-MB, 534-001, Altherma LT Modbus interface - Heat pump (air-to-water)
Gree Versati heat pump water heater (wired-controller Modbus RTU, protocol V1.5)
Gree Versati air-to-water heat pumps through the BMS port of the wired controller, per 'Modbus Protocol (V1.5) for the Versati Heat Pump Water Heater'. The document itself does not name a generation or refrigerant; the distributor files it as the R32 Versati III protocol.
Also known as: Versati III, R32 Versati, Versati heat pump water heater, Gree Versati Modbus V1.5 - Heat pump (air-to-water)
LG THERMA V R32 Monobloc air-to-water heat pump (built-in Modbus RTU)
LG THERMA V R32 Monobloc air-to-water heat pumps covered by installation manual MFL68026615 Rev.02 (North American models ZHBW041GA0 / ZHBW048GA0 / ZHBW055GA0), using the indoor PCB's own Modbus RTU slave port.
Also known as: ZHBW041GA0, ZHBW048GA0, ZHBW055GA0, KPHTC411M, KPHTC481M, KPHTC551M, THERMA V, MFL68026615 - Heat pump / ventilation unit controller (air handler)
Nilan CTS602 controller with HMI350T panel (Modbus version 23)
Nilan ventilation, heat-recovery and compact heat pump units with the CTS602 board and HMI350T user panel, Modbus protocol version 23 (software 3.6.58/3.6.59).
Also known as: CTS 602, CTS602 HMI350T, CTS602 w. HMI350T
All pumps Modbus register maps →
Source: User Manual - A2W Modbus PCB - Model no. CZ-NSMB · M02412F0. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.