Samsung MIM-B19N Modbus interface module (DVM / EHS / indoor units) Modbus register map

Updated 17 November 2026

Short answer

The MIM-B19N links one Samsung outdoor system (up to 4 modular outdoor units) and up to 48 indoor units, hydro units, AHU kits, ERVs, chillers or FCUs on the R1/R2 bus to a Modbus RTU master. Each indoor unit gets a fixed 50-register block. This map covers the module status registers and the indoor-unit block: on/off, mode, fan speed, setpoints, room and water temperatures, errors, ventilation and hot-water functions. Addresses are given for indoor unit 0.

This page lists 34 Modbus registers for the Samsung MIM-B19N Modbus interface module (DVM / EHS / indoor units) — 21 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Samsung’s own free documentation (linked below) and checked against it.

Manufacturer
Samsung
Model
MIM-B19N Modbus interface module (DVM / EHS / indoor units)
Equipment type
VRF / split AC gateway
Registers
34 (21 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
9600 baud, 8E1
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
MIM-B19N, Samsung Modbus interface module
Source document
Modbus Interface Module MIM-B19N Installation Manual · DB68-07538A-00 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Samsung MIM-B19N Modbus interface module (DVM / EHS / indoor units)

Integration in brief

Set the module address with the DIP/rotary switches, connect RS-485 at 9600 8E1, wait until bits 0-2 of an indoor unit's communication status (50 + n*50) read 7, then read and write its 50-register block.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 50Communication statusBITMAP16Indoor unit 0 communication statusRead
HR 52Air conditioner on/offUINT16Indoor unit 0 on/offRead/write
HR 53Air conditioner modeUINT16Indoor unit 0 modeRead/write
HR 58Set temperatureINT16Indoor unit 0 set temperatureRead/write
IR 59Room temperatureINT16Indoor unit 0 room temperatureRead
IR 63Integrated indoor unit error codeUINT16Indoor unit 0 error codeRead
IR 0Modbus interface module error statusBITMAP16Module error statusRead

Enable Modbus control & writes

Set the Modbus address (1-247) as the sum of the ON DIP switches plus the rotary switch value, connect R1/R2 to the outdoor unit, and give every indoor unit an address 0-47. Reset the module after changing indoor unit addresses or the central-control option.

Byte order & addressing

Network setup

Watch out for

Samsung MIM-B19N Modbus interface module (DVM / EHS / indoor units) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

34 of 34 shown
Samsung MIM-B19N Modbus interface module (DVM / EHS / indoor units) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR0Modbus interface module error statusBITMAP16Readbit 0 = Address error; bit 1 = Communication error on R1/R2; bit 2 = Tracking error
IR1Integrated outdoor unit error code100-999 = error code.UINT16Read0 = No error
IR2Outdoor defrost operation0 or 0xFF = defrost off; other values = defrost on.UINT16Read
IR50doc (50 + IU*50) + 0Communication statusBits 0-2 all set (value 7) = unit tracked and ready for control.BITMAP16Readbit 0 = Exist; bit 1 = Type OK; bit 2 = Ready; bit 3 = Communication error
IR51doc (50 + IU*50) + 1Unit typeLow byte = model code (e.g. HE 110, ERV 100-102); high byte 10 = FCU.UINT16Read
IR56doc (50 + IU*50) + 6Filter-cleaning reminderUINT16Read0 = Filter alarm not present; 1 = Filter alarm present
IR59doc (50 + IU*50) + 9Room temperatureCelsius x10. Range -41 to 100 °C.INT16× 0.1°CRead
IR60doc (50 + IU*50) + 10Discharge temperatureCelsius x10.INT16× 0.1°CRead
IR63doc (50 + IU*50) + 13Integrated indoor unit error code100-999 = error code.UINT16Read0 = No error
IR65doc (50 + IU*50) + 15Water-in temperatureCelsius x10.INT16× 0.1°CRead
IR66doc (50 + IU*50) + 16Water-out TemperatureCelsius x10.INT16× 0.1°CRead
IR67doc (50 + IU*50) + 17MCC water-out temperatureCelsius x10.INT16× 0.1°CRead
IR75doc (50 + IU*50) + 25Hot water temperatureCelsius x10.INT16× 0.1°CRead
HR3Buzzer on/offUINT16Write0 = Turns the buzzer on; 1 = Turns the buzzer off
HR52doc (50 + IU*50) + 2Air conditioner on/offUINT16Read/write0 = Off; 1 = On
HR53doc (50 + IU*50) + 3Air conditioner modeUINT16Read/write0 = Auto; 1 = Cool; 2 = Dry; 3 = Fan; 4 = Heat; 21 = Cool Storage; 24 = Heat Storage
HR54doc (50 + IU*50) + 4Indoor fan speedUINT16Read/write0 = Auto; 1 = Low; 2 = Middle; 3 = High
HR55doc (50 + IU*50) + 5Use of vertical air flow directionUINT16Read/write0 = Off; 1 = On
HR57doc (50 + IU*50) + 7Canceling the filter-cleaning reminderUINT16Write0 = No Clear Filter Alarm; 1 = Clear Filter Alarm
HR58doc (50 + IU*50) + 8Set temperatureCelsius x10.INT16× 0.1°CRead/write
HR61doc (50 + IU*50) + 11Cooling discharge set temperatureCelsius x10. Range 8 to 18 °C.INT16× 0.1°CRead/write
HR62doc (50 + IU*50) + 12Heating discharge set temperatureCelsius x10. Range 30 to 43 °C.INT16× 0.1°CRead/write
HR64doc (50 + IU*50) + 14Restrictions on the remote controlRead 0 = none, other = restricted; write 0x0000 to release, 0x6363 to restrict.UINT16Read/write
HR68doc (50 + IU*50) + 18Water-out set temperatureCelsius x10; allowed range depends on unit type.INT16× 0.1°CRead/write
HR69doc (50 + IU*50) + 19Ventilation on/offUINT16Read/write0 = Off; 1 = On
HR70doc (50 + IU*50) + 20Ventilation modeUINT16Read/write0 = Bypass; 1 = HeatEx; 2 = Auto; 6 = Sleep
HR71doc (50 + IU*50) + 21Ventilation fan speedUINT16Read/write0 = AUTO; 2 = Low; 3 = High; 4 = Turbo
HR72doc (50 + IU*50) + 22Hot water operation on/offUINT16Read/write0 = HotWater Off; 1 = HotWater On
HR73doc (50 + IU*50) + 23Hot water modeUINT16Read/write0 = Eco; 1 = Standard; 2 = Power; 3 = Force (for the EHS only)
HR74doc (50 + IU*50) + 24Hot water set temperatureCelsius x10; allowed range depends on unit type.INT16× 0.1°CRead/write
HR78doc (50 + IU*50) + 28Quiet controlUINT16Read/write0 = Slience Off; 1 = Slience On
HR79doc (50 + IU*50) + 29Away functionUINT16Read/write0 = Outing Off; 1 = Outing On
HR80doc (50 + IU*50) + 30Wind-Free functionUINT16Read/write0 = None; 9 = WindFree
HR81doc (50 + IU*50) + 31360 air flow directionOther values = individual control.UINT16Read/write15 = Swing; 64 = Wide; 85 = Mid; 106 = Spot

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Samsung MIM-B19N Modbus interface module (DVM / EHS / indoor units)

What Modbus registers does the Samsung MIM-B19N Modbus interface module (DVM / EHS / indoor units) have?

This map lists 34 registers: 13 input registers, 21 holding registers. 21 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Samsung MIM-B19N Modbus interface module (DVM / EHS / indoor units) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The table prints both a 1-based register number and the Modbus PDU address; the PDU address is used. Indoor unit n (0-47) occupies PDU addresses 50 + n*50 + k. This map lists indoor unit 0 (addresses 50-81); add 50 per unit, e.g. indoor unit 3 on/off = 50 + 150 + 2 = 202.

What are the minimum Modbus registers to integrate the Samsung MIM-B19N Modbus interface module (DVM / EHS / indoor units)?

Start with IR 50 Communication status (Indoor unit 0 communication status); HR 52 Air conditioner on/off (Indoor unit 0 on/off); HR 53 Air conditioner mode (Indoor unit 0 mode); HR 58 Set temperature (Indoor unit 0 set temperature); IR 59 Room temperature (Indoor unit 0 room temperature); IR 63 Integrated indoor unit error code (Indoor unit 0 error code); IR 0 Modbus interface module error status (Module error status).

How do I enable Modbus control of the Samsung MIM-B19N Modbus interface module (DVM / EHS / indoor units)?

Set the Modbus address (1-247) as the sum of the ON DIP switches plus the rotary switch value, connect R1/R2 to the outdoor unit, and give every indoor unit an address 0-47. Reset the module after changing indoor unit addresses or the central-control option.

Where is the official Samsung MIM-B19N Modbus interface module (DVM / EHS / indoor units) Modbus documentation?

The source is Modbus Interface Module MIM-B19N Installation Manual (DB68-07538A-00). Samsung doesn't publish it on its own website, so this map was re-typed from a free copy at https://midsummerwholesale.co.uk/pdfs/mim-b19n-manual.pdf. It may be an older revision, so check it against the live unit.