- MIM-B19N Modbus interface module (DVM / EHS / indoor units)
VRF / split AC gateway · Modbus register map
Samsung MIM-B19N Modbus interface module (DVM / EHS / indoor units) Modbus register map
Updated 17 November 2026
The MIM-B19N links one Samsung outdoor system (up to 4 modular outdoor units) and up to 48 indoor units, hydro units, AHU kits, ERVs, chillers or FCUs on the R1/R2 bus to a Modbus RTU master. Each indoor unit gets a fixed 50-register block. This map covers the module status registers and the indoor-unit block: on/off, mode, fan speed, setpoints, room and water temperatures, errors, ventilation and hot-water functions. Addresses are given for indoor unit 0.
This page lists 34 Modbus registers for the Samsung MIM-B19N Modbus interface module (DVM / EHS / indoor units) — 21 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Samsung’s own free documentation (linked below) and checked against it.
- Manufacturer
- Samsung
- Model
- MIM-B19N Modbus interface module (DVM / EHS / indoor units)
- Equipment type
- VRF / split AC gateway
- Registers
- 34 (21 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 9600 baud, 8E1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- MIM-B19N, Samsung Modbus interface module
Integration notes: Samsung MIM-B19N Modbus interface module (DVM / EHS / indoor units)
Set the module address with the DIP/rotary switches, connect RS-485 at 9600 8E1, wait until bits 0-2 of an indoor unit's communication status (50 + n*50) read 7, then read and write its 50-register block.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 50 | Communication status | BITMAP16 | Indoor unit 0 communication status | Read |
| HR 52 | Air conditioner on/off | UINT16 | Indoor unit 0 on/off | Read/write |
| HR 53 | Air conditioner mode | UINT16 | Indoor unit 0 mode | Read/write |
| HR 58 | Set temperature | INT16 | Indoor unit 0 set temperature | Read/write |
| IR 59 | Room temperature | INT16 | Indoor unit 0 room temperature | Read |
| IR 63 | Integrated indoor unit error code | UINT16 | Indoor unit 0 error code | Read |
| IR 0 | Modbus interface module error status | BITMAP16 | Module error status | Read |
Enable Modbus control & writes
Set the Modbus address (1-247) as the sum of the ON DIP switches plus the rotary switch value, connect R1/R2 to the outdoor unit, and give every indoor unit an address 0-47. Reset the module after changing indoor unit addresses or the central-control option.
Byte order & addressing
- Per-unit blocks: address = 50 + indoor address x 50 + offset.
- Temperatures are x10 integers.
- Holding values update only after the indoor unit reports a change.
Network setup
- Fixed serial format: 9600 bps, 8 data bits, even parity, 1 stop bit.
- RS-485 2-wire, up to 1000 m; DC 12 V supply.
Watch out for
- Leave at least 10 ms after each response before the next request.
- Repeated identical writes are sent to the unit each time; write only when a change is needed.
- After power-up all registers read 0 until tracking of the outdoor/indoor units completes.
Samsung MIM-B19N Modbus interface module (DVM / EHS / indoor units) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 0 | Modbus interface module error status | BITMAP16 | Read | bit 0 = Address error; bit 1 = Communication error on R1/R2; bit 2 = Tracking error | ||||
| IR | 1 | Integrated outdoor unit error code | 100-999 = error code. | UINT16 | Read | 0 = No error | |||
| IR | 2 | Outdoor defrost operation | 0 or 0xFF = defrost off; other values = defrost on. | UINT16 | Read | ||||
| IR | 50doc (50 + IU*50) + 0 | Communication status | Bits 0-2 all set (value 7) = unit tracked and ready for control. | BITMAP16 | Read | bit 0 = Exist; bit 1 = Type OK; bit 2 = Ready; bit 3 = Communication error | |||
| IR | 51doc (50 + IU*50) + 1 | Unit type | Low byte = model code (e.g. HE 110, ERV 100-102); high byte 10 = FCU. | UINT16 | Read | ||||
| IR | 56doc (50 + IU*50) + 6 | Filter-cleaning reminder | UINT16 | Read | 0 = Filter alarm not present; 1 = Filter alarm present | ||||
| IR | 59doc (50 + IU*50) + 9 | Room temperature | Celsius x10. Range -41 to 100 °C. | INT16 | × 0.1 | °C | Read | ||
| IR | 60doc (50 + IU*50) + 10 | Discharge temperature | Celsius x10. | INT16 | × 0.1 | °C | Read | ||
| IR | 63doc (50 + IU*50) + 13 | Integrated indoor unit error code | 100-999 = error code. | UINT16 | Read | 0 = No error | |||
| IR | 65doc (50 + IU*50) + 15 | Water-in temperature | Celsius x10. | INT16 | × 0.1 | °C | Read | ||
| IR | 66doc (50 + IU*50) + 16 | Water-out Temperature | Celsius x10. | INT16 | × 0.1 | °C | Read | ||
| IR | 67doc (50 + IU*50) + 17 | MCC water-out temperature | Celsius x10. | INT16 | × 0.1 | °C | Read | ||
| IR | 75doc (50 + IU*50) + 25 | Hot water temperature | Celsius x10. | INT16 | × 0.1 | °C | Read | ||
| HR | 3 | Buzzer on/off | UINT16 | Write | 0 = Turns the buzzer on; 1 = Turns the buzzer off | ||||
| HR | 52doc (50 + IU*50) + 2 | Air conditioner on/off | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 53doc (50 + IU*50) + 3 | Air conditioner mode | UINT16 | Read/write | 0 = Auto; 1 = Cool; 2 = Dry; 3 = Fan; 4 = Heat; 21 = Cool Storage; 24 = Heat Storage | ||||
| HR | 54doc (50 + IU*50) + 4 | Indoor fan speed | UINT16 | Read/write | 0 = Auto; 1 = Low; 2 = Middle; 3 = High | ||||
| HR | 55doc (50 + IU*50) + 5 | Use of vertical air flow direction | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 57doc (50 + IU*50) + 7 | Canceling the filter-cleaning reminder | UINT16 | Write | 0 = No Clear Filter Alarm; 1 = Clear Filter Alarm | ||||
| HR | 58doc (50 + IU*50) + 8 | Set temperature | Celsius x10. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 61doc (50 + IU*50) + 11 | Cooling discharge set temperature | Celsius x10. Range 8 to 18 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 62doc (50 + IU*50) + 12 | Heating discharge set temperature | Celsius x10. Range 30 to 43 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 64doc (50 + IU*50) + 14 | Restrictions on the remote control | Read 0 = none, other = restricted; write 0x0000 to release, 0x6363 to restrict. | UINT16 | Read/write | ||||
| HR | 68doc (50 + IU*50) + 18 | Water-out set temperature | Celsius x10; allowed range depends on unit type. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 69doc (50 + IU*50) + 19 | Ventilation on/off | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 70doc (50 + IU*50) + 20 | Ventilation mode | UINT16 | Read/write | 0 = Bypass; 1 = HeatEx; 2 = Auto; 6 = Sleep | ||||
| HR | 71doc (50 + IU*50) + 21 | Ventilation fan speed | UINT16 | Read/write | 0 = AUTO; 2 = Low; 3 = High; 4 = Turbo | ||||
| HR | 72doc (50 + IU*50) + 22 | Hot water operation on/off | UINT16 | Read/write | 0 = HotWater Off; 1 = HotWater On | ||||
| HR | 73doc (50 + IU*50) + 23 | Hot water mode | UINT16 | Read/write | 0 = Eco; 1 = Standard; 2 = Power; 3 = Force (for the EHS only) | ||||
| HR | 74doc (50 + IU*50) + 24 | Hot water set temperature | Celsius x10; allowed range depends on unit type. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 78doc (50 + IU*50) + 28 | Quiet control | UINT16 | Read/write | 0 = Slience Off; 1 = Slience On | ||||
| HR | 79doc (50 + IU*50) + 29 | Away function | UINT16 | Read/write | 0 = Outing Off; 1 = Outing On | ||||
| HR | 80doc (50 + IU*50) + 30 | Wind-Free function | UINT16 | Read/write | 0 = None; 9 = WindFree | ||||
| HR | 81doc (50 + IU*50) + 31 | 360 air flow direction | Other values = individual control. | UINT16 | Read/write | 15 = Swing; 64 = Wide; 85 = Mid; 106 = Spot |
Notes on this map
- Source host: the unaltered Samsung manual hosted by a UK distributor; we did not find a public Samsung copy.
- All values are single 16-bit registers, big-endian. Temperatures are Celsius x10; the manual's ranges go down to -41 °C, so they are listed as signed.
- The manual marks each point R, W or R/W per unit type (indoor, HE/HT/EHS, AHU kit, ERV, ERV+, chiller, FCU, FCU kit). Read-only points are listed as input registers (FC 04) and writable points as holding registers (FC 03/06/16); the module supports both read functions but the manual does not say which table each read-only point lives in, so try FC 03 if FC 04 is refused.
- Access shown is the widest across unit types; a point marked '-' for a unit type does not apply to it (e.g. water temperatures only for HE/HT/EHS and chillers, ventilation only for ERV).
- Left out: the MCC chiller error-information registers (+26/+27, packed bytes) and the reserved ranges.
- Any write to a holding register is always forwarded to the indoor unit as a command, even if the value is unchanged.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Samsung MIM-B19N Modbus interface module (DVM / EHS / indoor units)
What Modbus registers does the Samsung MIM-B19N Modbus interface module (DVM / EHS / indoor units) have?
This map lists 34 registers: 13 input registers, 21 holding registers. 21 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Samsung MIM-B19N Modbus interface module (DVM / EHS / indoor units) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The table prints both a 1-based register number and the Modbus PDU address; the PDU address is used. Indoor unit n (0-47) occupies PDU addresses 50 + n*50 + k. This map lists indoor unit 0 (addresses 50-81); add 50 per unit, e.g. indoor unit 3 on/off = 50 + 150 + 2 = 202.
What are the minimum Modbus registers to integrate the Samsung MIM-B19N Modbus interface module (DVM / EHS / indoor units)?
Start with IR 50 Communication status (Indoor unit 0 communication status); HR 52 Air conditioner on/off (Indoor unit 0 on/off); HR 53 Air conditioner mode (Indoor unit 0 mode); HR 58 Set temperature (Indoor unit 0 set temperature); IR 59 Room temperature (Indoor unit 0 room temperature); IR 63 Integrated indoor unit error code (Indoor unit 0 error code); IR 0 Modbus interface module error status (Module error status).
How do I enable Modbus control of the Samsung MIM-B19N Modbus interface module (DVM / EHS / indoor units)?
Set the Modbus address (1-247) as the sum of the ON DIP switches plus the rotary switch value, connect R1/R2 to the outdoor unit, and give every indoor unit an address 0-47. Reset the module after changing indoor unit addresses or the central-control option.
Where is the official Samsung MIM-B19N Modbus interface module (DVM / EHS / indoor units) Modbus documentation?
The source is Modbus Interface Module MIM-B19N Installation Manual (DB68-07538A-00). Samsung doesn't publish it on its own website, so this map was re-typed from a free copy at https://midsummerwholesale.co.uk/pdfs/mim-b19n-manual.pdf. It may be an older revision, so check it against the live unit.
More Samsung Modbus register maps
Other ac & vrf gateways register maps
- Sensor (1-Wire temperature gateway)
Unipi Technology Unipi Extension xG18 1-Wire temperature gateway
Unipi Extension xG18 RS-485 module per the Unipi Extension xG18 Modbus map v1.1.
Also known as: Unipi Extension xG18, xG18 - VRF / split AC gateway
Daikin EKMBDXB Modbus Interface DIII
EKMBDXB7V1 Modbus RTU interface on the DIII-net of Daikin VRV, Sky Air, split (via KRP928), VAM/VKM ventilation, VRV hydrobox, air curtains, ERQ control box, heating and applied units; design guide 4P642495-1A (2022.02).
Also known as: EKMBDXB7V1, Modbus Interface DIII - Heat pump gateway (VRF / split AC gateway)
Intesis (HMS Networks) IN485DAI001A000 Daikin Altherma 3 air-to-water to Modbus RTU / BACnet MS/TP gateway
Intesis (HMS Networks) IN485DAI001A000 gateway for Daikin Altherma 3 air-to-water heat pumps, set to Modbus RTU, per user manual version 1.0.2 (2025-07-18).
Also known as: IN485DAI001A000, Daikin Altherma 3 Modbus, Intesis Altherma 3, HMS Daikin Altherma gateway - VRF / split AC gateway
Intesis (HMS Networks) INMBSACA001I000 XYE-bus air conditioner to Modbus RTU interface (1 unit)
INMBSACA001I000, user manual v1.8 EN; one indoor unit at unit address 0 on its own XYE bus.
Also known as: INMBSACA001I000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSFGL016O000 Fujitsu VRF to Modbus RTU / TCP gateway (up to 16 indoor units)
Intesis Modbus Server - Fujitsu VRF, order code INMBSFGL016O000 (legacy FJ-AC-MBS-16), user manual r1.0 (02/2020); up to 16 indoor units configured in MAPS.
Also known as: INMBSFGL016O000, FJ-AC-MBS-16, Intesis Modbus Server Fujitsu VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSMHI001R000 Mitsubishi Heavy Industries AC to Modbus RTU gateway
Mitsubishi Heavy Industries indoor units (one, or up to 16 controlled together as one) on the XY remote-controller bus, user manual r6.4 (01/2024).
Also known as: INMBSMHI001R000, MH-RC-MBS-1, Intesis Mitsubishi Heavy Industries Modbus, Intesis MHI Modbus
All ac & vrf gateways Modbus register maps →
Source: Modbus Interface Module MIM-B19N Installation Manual · DB68-07538A-00 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.