- Home
- Modbus register maps
- Samsung
Manufacturer
Samsung Modbus register maps
Updated 17 November 2026
2 Samsung models, 44 registers in all, each re-typed from Samsung’s own free documentation and checked against it.
2 of 2 shown
- VRF / split AC gateway
Samsung CycloGic CL-MC03 Modbus interface module (Samsung DVM / CAC / RAC)
CycloGic CL-MC03*** series Modbus interface modules (1 to 64 indoor units) for Samsung DVM, CAC, FJM and RAC units, instruction manual Rev. 2 (Oct. 2017).
Also known as: CL-MC0301C, CL-MC0308C, CL-MC0316C, CL-MC0332C, CL-MC0364C, CycloGic Modbus Interface Module - VRF / split AC gateway
Samsung MIM-B19N Modbus interface module (DVM / EHS / indoor units)
Samsung MIM-B19N Modbus interface module on the R1/R2 bus of one outdoor system with up to 48 indoor units (installation manual DB68-07538A-00).
Also known as: MIM-B19N, Samsung Modbus interface module
Samsung: default communication settings
Factory defaults as the manufacturer documents them. Change one setting at a time on site and write down what you changed. Word order applies to 32-bit values; the addressing column says how the manufacturer prints register numbers (every map on this site also gives the 0-based wire address).
| Model | Transport | Unit ID | Serial | Word order | Documented addressing | Registers |
|---|---|---|---|---|---|---|
| CycloGic CL-MC03 Modbus interface module (Samsung DVM / CAC / RAC) | RTU | Not stated | 19200 baud, 8E1 | 16-bit only | Modicon | 10 |
| MIM-B19N Modbus interface module (DVM / EHS / indoor units) | RTU | Not stated | 9600 baud, 8E1 | 16-bit only | 0-based | 34 |