VRF / split AC gateway · Modbus register map

Samsung CycloGic CL-MC03 Modbus interface module (Samsung DVM / CAC / RAC) Modbus register map

Updated 17 November 2026

Short answer

The CL-MC03 series is a CycloGic-made Modbus RTU interface that connects to the F1/F2 network of Samsung DVM, CAC, FJM or RAC indoor units and controls up to 64 of them. Each indoor unit has a 20-register block. This map covers the block for indoor unit 0: on/off, mode, set and room temperature, fan speed, louver swing and the duct-unit supply-air setpoints.

This page lists 10 Modbus registers for the Samsung CycloGic CL-MC03 Modbus interface module (Samsung DVM / CAC / RAC) — 5 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Samsung’s own free documentation (linked below) and checked against it.

Manufacturer
Samsung
Model
CycloGic CL-MC03 Modbus interface module (Samsung DVM / CAC / RAC)
Equipment type
VRF / split AC gateway
Registers
10 (5 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
19200 baud, 8E1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
CL-MC0301C, CL-MC0308C, CL-MC0316C, CL-MC0332C, CL-MC0364C, CycloGic Modbus Interface Module
Source document
CL-MC03*** Series Modbus Interface Module Instruction Manual · Document Rev. 2 · rev. 2017-10 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Samsung CycloGic CL-MC03 Modbus interface module (Samsung DVM / CAC / RAC)

Integration in brief

Set DIP SW2 for the Samsung product type, set the Modbus address on the two rotary switches, then poll FC 03 from address 20*N for indoor unit N. Change the set temperature with FC 06 at 20*N + 4.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0IDU on/off statusUINT16Unit 0 on/off statusRead
HR 1IDU operation modeUINT16Unit 0 operation modeRead
HR 4Set temperatureUINT16Unit 0 set temperatureRead/write
HR 5Room temperatureUINT16Unit 0 room temperatureRead
HR 8IDU fan speedUINT16Unit 0 fan speedRead

Enable Modbus control & writes

DIP SW2 OFF for DVM/CAC (AM/AC models), ON for RAC/FJM (AR/AJ models); DIP SW1 must stay ON (firmware download disabled) in normal use. The slave address is set with RSW1 (tens) and RSW2 (ones).

Byte order & addressing

Network setup

Watch out for

Samsung CycloGic CL-MC03 Modbus interface module (Samsung DVM / CAC / RAC) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

10 of 10 shown
Samsung CycloGic CL-MC03 Modbus interface module (Samsung DVM / CAC / RAC) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 40001IDU on/off statusRead value. Writes to this register use a packed on/off + mode format (see notes).UINT16Read0 = Off; 1 = On
HR1doc 40002IDU operation modeUINT16Read0 = Auto; 1 = Cooling; 2 = Dry (dehumidification); 3 = Fan; 4 = Heat; 11 = Auto cool; 12 = Auto dry; 13 = Auto fan; 14 = Auto heat
HR4doc 40005Set temperatureValue / 10.UINT16× 0.1°CRead/write
HR5doc 40006Room temperatureValue / 10.UINT16× 0.1°CRead
HR8doc 40009IDU fan speedRead value. Writes use a packed fan speed + louver format (see notes).UINT16Read0 = Automatic; 1 = Low; 2 = Middle; 3 = High; 4 = Turbo
HR9doc 40010Deco panel louver swingUINT16Read0 = Swing off; 1 = Swing on: upper and lower louver; 2 = Swing on: right and left louver; 3 = Swing on: upper/lower and right/left louver
HR10doc 40011Supply air (discharge) temperatureDuct units only; value / 10.UINT16× 0.1°CRead/write
HR11doc 40012Supply air temperature controlUINT16Read/write0 = Disable; 1 = Enable
HR12doc 40013Cooling supply air set temperatureDuct units only; value / 10.UINT16× 0.1°CRead/write
HR13doc 40014Heating supply air set temperatureDuct units only; value / 10.UINT16× 0.1°CRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Samsung CycloGic CL-MC03 Modbus interface module (Samsung DVM / CAC / RAC)

What Modbus registers does the Samsung CycloGic CL-MC03 Modbus interface module (Samsung DVM / CAC / RAC) have?

This map lists 10 registers: 10 holding registers. 5 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Samsung CycloGic CL-MC03 Modbus interface module (Samsung DVM / CAC / RAC) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual uses Modicon numbers: 40001-40014 for indoor unit 00, plus 20 per indoor unit (unit 01 = 40021, unit 63 = 41261). Subtract 40001 for the wire address: unit N, register 4000k is address 20*N + k - 1.

What are the minimum Modbus registers to integrate the Samsung CycloGic CL-MC03 Modbus interface module (Samsung DVM / CAC / RAC)?

Start with HR 0 IDU on/off status (Unit 0 on/off status); HR 1 IDU operation mode (Unit 0 operation mode); HR 4 Set temperature (Unit 0 set temperature); HR 5 Room temperature (Unit 0 room temperature); HR 8 IDU fan speed (Unit 0 fan speed).

How do I enable Modbus control of the Samsung CycloGic CL-MC03 Modbus interface module (Samsung DVM / CAC / RAC)?

DIP SW2 OFF for DVM/CAC (AM/AC models), ON for RAC/FJM (AR/AJ models); DIP SW1 must stay ON (firmware download disabled) in normal use. The slave address is set with RSW1 (tens) and RSW2 (ones).

Where is the official Samsung CycloGic CL-MC03 Modbus interface module (Samsung DVM / CAC / RAC) Modbus documentation?

The source is CL-MC03*** Series Modbus Interface Module Instruction Manual (Document Rev. 2), revision 2017-10. Samsung doesn't publish it on its own website, so this map was re-typed from a free copy at https://cdn.komachine.com/media/product-catalog/Manual-CYCLOGIC-Modbus_Interface_Module.pdf. It may be an older revision, so check it against the live unit.

More Samsung Modbus register maps

Other ac & vrf gateways register maps

All ac & vrf gateways Modbus register maps →

Source: CL-MC03*** Series Modbus Interface Module Instruction Manual · Document Rev. 2 · rev. 2017-10 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.