- Home
- Modbus register maps
- Samsung
- CycloGic CL-MC03 Modbus interface module (Samsung DVM / CAC / RAC)
VRF / split AC gateway · Modbus register map
Samsung CycloGic CL-MC03 Modbus interface module (Samsung DVM / CAC / RAC) Modbus register map
Updated 17 November 2026
The CL-MC03 series is a CycloGic-made Modbus RTU interface that connects to the F1/F2 network of Samsung DVM, CAC, FJM or RAC indoor units and controls up to 64 of them. Each indoor unit has a 20-register block. This map covers the block for indoor unit 0: on/off, mode, set and room temperature, fan speed, louver swing and the duct-unit supply-air setpoints.
This page lists 10 Modbus registers for the Samsung CycloGic CL-MC03 Modbus interface module (Samsung DVM / CAC / RAC) — 5 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Samsung’s own free documentation (linked below) and checked against it.
- Manufacturer
- Samsung
- Model
- CycloGic CL-MC03 Modbus interface module (Samsung DVM / CAC / RAC)
- Equipment type
- VRF / split AC gateway
- Registers
- 10 (5 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 19200 baud, 8E1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- CL-MC0301C, CL-MC0308C, CL-MC0316C, CL-MC0332C, CL-MC0364C, CycloGic Modbus Interface Module
Integration notes: Samsung CycloGic CL-MC03 Modbus interface module (Samsung DVM / CAC / RAC)
Set DIP SW2 for the Samsung product type, set the Modbus address on the two rotary switches, then poll FC 03 from address 20*N for indoor unit N. Change the set temperature with FC 06 at 20*N + 4.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | IDU on/off status | UINT16 | Unit 0 on/off status | Read |
| HR 1 | IDU operation mode | UINT16 | Unit 0 operation mode | Read |
| HR 4 | Set temperature | UINT16 | Unit 0 set temperature | Read/write |
| HR 5 | Room temperature | UINT16 | Unit 0 room temperature | Read |
| HR 8 | IDU fan speed | UINT16 | Unit 0 fan speed | Read |
Enable Modbus control & writes
DIP SW2 OFF for DVM/CAC (AM/AC models), ON for RAC/FJM (AR/AJ models); DIP SW1 must stay ON (firmware download disabled) in normal use. The slave address is set with RSW1 (tens) and RSW2 (ones).
Byte order & addressing
- Modicon numbering, 20 registers per indoor unit.
- Temperatures are tenths of a degree.
Network setup
- 19200 bps, even parity, 1 stop bit; Modbus line up to 500 m.
- 12 V DC supply from the indoor unit V1/V2 terminals; F1/F2 to the Samsung network.
Watch out for
- DIP SW2 must match the Samsung product family: OFF for DVM/CAC, ON for RAC/FJM.
- The module's dry-contact input forces units on/off and its DO closes on an error.
Samsung CycloGic CL-MC03 Modbus interface module (Samsung DVM / CAC / RAC) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 40001 | IDU on/off status | Read value. Writes to this register use a packed on/off + mode format (see notes). | UINT16 | Read | 0 = Off; 1 = On | |||
| HR | 1doc 40002 | IDU operation mode | UINT16 | Read | 0 = Auto; 1 = Cooling; 2 = Dry (dehumidification); 3 = Fan; 4 = Heat; 11 = Auto cool; 12 = Auto dry; 13 = Auto fan; 14 = Auto heat | ||||
| HR | 4doc 40005 | Set temperature | Value / 10. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 5doc 40006 | Room temperature | Value / 10. | UINT16 | × 0.1 | °C | Read | ||
| HR | 8doc 40009 | IDU fan speed | Read value. Writes use a packed fan speed + louver format (see notes). | UINT16 | Read | 0 = Automatic; 1 = Low; 2 = Middle; 3 = High; 4 = Turbo | |||
| HR | 9doc 40010 | Deco panel louver swing | UINT16 | Read | 0 = Swing off; 1 = Swing on: upper and lower louver; 2 = Swing on: right and left louver; 3 = Swing on: upper/lower and right/left louver | ||||
| HR | 10doc 40011 | Supply air (discharge) temperature | Duct units only; value / 10. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 11doc 40012 | Supply air temperature control | UINT16 | Read/write | 0 = Disable; 1 = Enable | ||||
| HR | 12doc 40013 | Cooling supply air set temperature | Duct units only; value / 10. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 13doc 40014 | Heating supply air set temperature | Duct units only; value / 10. | UINT16 | × 0.1 | °C | Read/write |
Notes on this map
- Source host: an unaltered copy of the CycloGic manual on a product-catalogue site; we did not find a public copy on CycloGic's or Samsung's sites.
- Only FC 03 (read) and FC 06 (write single register) are supported; all values are 16-bit.
- Writes to 40001 and 40009 carry two one-byte fields (on/off + mode, fan speed + louver swing). The manual does not say which byte holds which field, so those writes are not mapped; the registers are listed for reading.
- Temperatures are value / 10; the manual does not state whether they are signed.
- Registers 40003-40004 and 40007-40008 are not described in the manual.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Samsung CycloGic CL-MC03 Modbus interface module (Samsung DVM / CAC / RAC)
What Modbus registers does the Samsung CycloGic CL-MC03 Modbus interface module (Samsung DVM / CAC / RAC) have?
This map lists 10 registers: 10 holding registers. 5 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Samsung CycloGic CL-MC03 Modbus interface module (Samsung DVM / CAC / RAC) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual uses Modicon numbers: 40001-40014 for indoor unit 00, plus 20 per indoor unit (unit 01 = 40021, unit 63 = 41261). Subtract 40001 for the wire address: unit N, register 4000k is address 20*N + k - 1.
What are the minimum Modbus registers to integrate the Samsung CycloGic CL-MC03 Modbus interface module (Samsung DVM / CAC / RAC)?
Start with HR 0 IDU on/off status (Unit 0 on/off status); HR 1 IDU operation mode (Unit 0 operation mode); HR 4 Set temperature (Unit 0 set temperature); HR 5 Room temperature (Unit 0 room temperature); HR 8 IDU fan speed (Unit 0 fan speed).
How do I enable Modbus control of the Samsung CycloGic CL-MC03 Modbus interface module (Samsung DVM / CAC / RAC)?
DIP SW2 OFF for DVM/CAC (AM/AC models), ON for RAC/FJM (AR/AJ models); DIP SW1 must stay ON (firmware download disabled) in normal use. The slave address is set with RSW1 (tens) and RSW2 (ones).
Where is the official Samsung CycloGic CL-MC03 Modbus interface module (Samsung DVM / CAC / RAC) Modbus documentation?
The source is CL-MC03*** Series Modbus Interface Module Instruction Manual (Document Rev. 2), revision 2017-10. Samsung doesn't publish it on its own website, so this map was re-typed from a free copy at https://cdn.komachine.com/media/product-catalog/Manual-CYCLOGIC-Modbus_Interface_Module.pdf. It may be an older revision, so check it against the live unit.
More Samsung Modbus register maps
Other ac & vrf gateways register maps
- Boiler gateway (OpenTherm to Modbus RTU)
Unipi Technology MM-OT101 Modbus / OpenTherm gateway
Unipi MM-OT101 DIN-rail gateway between Modbus RTU (RS-485) and OpenTherm/Plus boilers and thermostats, per its technical documentation.
Also known as: MM-OT101, MM-OT1010, Unipi OpenTherm gateway - VRF / split AC gateway
Daikin DTA116A51 D-NET / Modbus communication adaptor (VRV)
DTA116A51 adaptor with up to 16 VRV indoor units (D-NET 1-00 to 1-15), per functional specification CB13A033 first edition.
Also known as: DTA116A51, DIII-NET Modbus adaptor, D3NET Modbus adapter - Split AC unit (VRF / split AC gateway built in)
Gree U-Match all-DC-inverter duct / cassette / floor-ceiling units (built-in Modbus)
Gree U-Match fourth-generation all-DC-inverter light-commercial units whose controller has the integrated Modbus RTU interface; Chinese-English protocol dated 2018-03-07.
Also known as: U-Match, Gree U-Match 4th generation DC inverter, U-Match BMS Modbus - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Panasonic application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Panasonic application (U1U2 P-Link / S-Link), Modbus RTU / TCP server, user manual version 1.1.7 (2025-12-09).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSFGL001R000 Fujitsu AC to Modbus RTU gateway
One Fujitsu indoor unit, or a group of up to 16 controlled together as one, on the 3-wire BWR remote-controller bus via INMBSFGL001R000, user manual v2.4 (02/2025).
Also known as: INMBSFGL001R000, Intesis Fujitsu Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSLGE016O000 LG VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)
Intesis Modbus - LG VRF, order codes INMBSLGE016O000 / INMBSLGE064O000 (legacy LG-AC-MBS-16 / -64), user manual r1.0 (04/2020); LG PI485 bus.
Also known as: INMBSLGE016O000, INMBSLGE064O000, LG-AC-MBS-16, LG-AC-MBS-64, Intesis Modbus LG VRF
All ac & vrf gateways Modbus register maps →
Source: CL-MC03*** Series Modbus Interface Module Instruction Manual · Document Rev. 2 · rev. 2017-10 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.