Easy Modbus
  1. Home
  2. Modbus register maps
  3. Unipi Technology
  4. MM-OT101 Modbus / OpenTherm gateway

Boiler gateway (OpenTherm to Modbus RTU) · Modbus register map

Unipi Technology MM-OT101 Modbus / OpenTherm gateway Modbus register map

Updated 17 November 2026

Short answer

The MM-OT101 sits between an OpenTherm boiler and its thermostat (monitor mode) or replaces the thermostat (controller mode) and exposes the OpenTherm data on Modbus RTU. Each OpenTherm message ID maps straight to the register with the same number. This map covers the status flags, setpoints, temperatures, modulation, pressure, counters and remote parameters, the gateway's line settings and timing statistics, and the two mode coils.

This page lists 85 Modbus registers for the Unipi Technology MM-OT101 Modbus / OpenTherm gateway — 34 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Unipi Technology’s own free documentation (linked below) and checked against it.

Manufacturer
Unipi Technology
Model
MM-OT101 Modbus / OpenTherm gateway
Equipment type
Boiler gateway (OpenTherm to Modbus RTU)
Registers
85 (34 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
19200 baud, 8E1
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
MM-OT101, MM-OT1010, Unipi OpenTherm gateway
Source document
Technical documentation - Communication gateway with Modbus and Opentherm MM-OT101
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Unipi Technology MM-OT101 Modbus / OpenTherm gateway

Integration in brief

In controller mode, clear coil 0, set the CH/DHW enable flags in the master status byte of register 0 and write the control setpoint to register 1 (f8.8), one register per write, repeated periodically. Read boiler status and temperatures from registers 0, 17, 25, 26 and 28.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0Master / slave status flagsUINT16Status flags (CH/DHW enable, flame, fault)Read/write
HR 1Control setpoint (CH water)INT16Control setpointWrite
HR 17Relative modulation levelINT16Relative modulation levelRead
HR 25Boiler flow water temperatureINT16Boiler flow temperatureRead
HR 28Return water temperatureINT16Return water temperatureRead
CO 0Monitor mode activeBITMonitor / controller modeRead/write

Enable Modbus control & writes

Set address (1-7), baud (9600/19200) and parity with the internal DIP switch: switch 1 = baud (ON 19200), switch 2 = parity (ON even), switches 3-5 = address weights 4/2/1. The gateway starts in monitor mode after power-up.

Byte order & addressing

Network setup

Watch out for

Unipi Technology MM-OT101 Modbus / OpenTherm gateway Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

85 of 85 shown
Unipi Technology MM-OT101 Modbus / OpenTherm gateway Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0Monitor mode activeBITRead/write0 = Controller mode; 1 = Monitor mode
CO1Active scanBITRead/write0 = Send on each register write; 1 = Cycle all mapped messages to the boiler
HR0Master / slave status flagsMaster and slave status flag bytes; byte order unclear in the manual (see notes).UINT16Read/write
HR1Control setpoint (CH water)f8.8: signed, divide by 256. Required in controller mode.INT16× 0.00390625°CWrite
HR2Master configuration flags / member IDHigh/low byte pair (flag8 / u8).UINT16Write
HR3Slave configuration flags / member IDHigh/low byte pair (flag8 / u8).UINT16Read
HR4Remote commandByte pair (u8 / u8).UINT16Write
HR5Application fault flags / OEM fault codeFault flag byte plus OEM fault code.UINT16Read
HR6Remote parameter transfer-enable / read-write flagsTwo flag bytes.UINT16Read
HR7Cooling control signalf8.8: signed, divide by 256.INT16× 0.00390625%Write
HR8Control setpoint CH2f8.8: signed, divide by 256.INT16× 0.00390625°CWrite
HR9Remote override room setpointf8.8: signed, divide by 256.INT16× 0.00390625Read
HR10Number of transparent slave parametersu8.UINT16Read
HR11Transparent slave parameter index / valueIndex byte and value byte.UINT16Read/write
HR12Fault history buffer sizeu8.UINT16Read
HR13Fault history entry index / valueIndex byte and value byte.UINT16Read
HR14Max relative modulation settingf8.8: signed, divide by 256.INT16× 0.00390625%Write
HR15Max boiler capacity (kW) / min modulation (%)Two u8 bytes.UINT16Read
HR16Room setpointf8.8: signed, divide by 256.INT16× 0.00390625°CWrite
HR17Relative modulation levelf8.8: signed, divide by 256.INT16× 0.00390625%Read
HR18CH water pressuref8.8: signed, divide by 256.INT16× 0.00390625barRead
HR19DHW flow ratef8.8: signed, divide by 256.INT16× 0.00390625l/minRead
HR20Day of week and time of dayOpenTherm packed u8 bytes.UINT16Read/write
HR21Calendar dateTwo u8 bytes.UINT16Read/write
HR22Calendar yearUINT16Read/write
HR23Room setpoint CH2f8.8: signed, divide by 256.INT16× 0.00390625°CWrite
HR24Room temperaturef8.8: signed, divide by 256. Sent by the thermostat/controller.INT16× 0.00390625°CWrite
HR25Boiler flow water temperaturef8.8: signed, divide by 256.INT16× 0.00390625°CRead
HR26DHW temperaturef8.8: signed, divide by 256.INT16× 0.00390625°CRead
HR27Outside temperaturef8.8: signed, divide by 256.INT16× 0.00390625°CRead
HR28Return water temperaturef8.8: signed, divide by 256.INT16× 0.00390625°CRead
HR29Solar storage temperaturef8.8: signed, divide by 256.INT16× 0.00390625°CRead
HR30Solar collector temperaturef8.8: signed, divide by 256.INT16× 0.00390625°CRead
HR31CH2 flow water temperaturef8.8: signed, divide by 256.INT16× 0.00390625°CRead
HR32DHW temperature 2f8.8: signed, divide by 256.INT16× 0.00390625°CRead
HR33Boiler exhaust temperatureINT16°CRead
HR48DHW setpoint boundsUpper / lower bound bytes, s8, °C.UINT16Read
HR49Max CH setpoint boundsUpper / lower bound bytes, s8, °C.UINT16Read
HR50OTC heat curve ratio boundsUpper / lower bound bytes, s8.UINT16Read
HR56DHW setpoint (remote parameter 1)f8.8: signed, divide by 256.INT16× 0.00390625°CRead/write
HR57Max CH water setpoint (remote parameter 2)f8.8: signed, divide by 256.INT16× 0.00390625°CRead/write
HR58OTC heat curve ratio (remote parameter 3)f8.8: signed, divide by 256.INT16× 0.00390625Read/write
HR100Remote override function flagsflag8: manual / program change handling.UINT16Read
HR115OEM diagnostic / service codeUINT16Read
HR116Burner startsUINT16Read/write
HR117CH pump startsUINT16Read/write
HR118DHW pump/valve startsUINT16Read/write
HR119Burner starts in DHW modeUINT16Read/write
HR120Burner operating hoursUINT16hRead/write
HR121CH pump running hoursUINT16hRead/write
HR122DHW pump/valve running hoursUINT16hRead/write
HR123Burner hours in DHW modeUINT16hRead/write
HR124OpenTherm version, masterf8.8: signed, divide by 256.INT16× 0.00390625Write
HR125OpenTherm version, slavef8.8: signed, divide by 256.INT16× 0.00390625Read
HR126Master product version and typeTwo u8 bytes.UINT16Write
HR127Slave product version and typeTwo u8 bytes.UINT16Read
HR1000OT line logical 0 currentGateway setting (memory only).UINT16mARead/write
HR1001OT line logical 1 currentGateway setting (memory only).UINT16mARead/write
HR1002Gap before reply to thermostatGateway setting (memory only).UINT16µsRead/write
HR1003Boiler transaction timeoutGateway setting (memory only).UINT16msRead/write
HR1004Sanity gap before replyGateway setting (memory only).UINT16msRead/write
HR2000Max time of 1 bit (boiler line)OpenTherm line timing statistic; unit not stated.UINT16Read
HR2001Min time of 1 bit (boiler line)OpenTherm line timing statistic; unit not stated.UINT16Read
HR2002Pulse time min (boiler line)OpenTherm line timing statistic; unit not stated.UINT16Read
HR2003Pulse time threshold (boiler line)OpenTherm line timing statistic; unit not stated.UINT16Read
HR2020Average long bit time (boiler line)OpenTherm line timing statistic; unit not stated.UINT16Read
HR2021Min long bit time (boiler line)OpenTherm line timing statistic; unit not stated.UINT16Read
HR2022Max long bit time (boiler line)OpenTherm line timing statistic; unit not stated.UINT16Read
HR2023Average short bit time (boiler line)OpenTherm line timing statistic; unit not stated.UINT16Read
HR2024Min short bit time (boiler line)OpenTherm line timing statistic; unit not stated.UINT16Read
HR2025Max short bit time (boiler line)OpenTherm line timing statistic; unit not stated.UINT16Read
HR2026Start bit min time (boiler line)OpenTherm line timing statistic; unit not stated.UINT16Read
HR2027Start bit max time (boiler line)OpenTherm line timing statistic; unit not stated.UINT16Read
HR2100Max time of 1 bit (boiler line, set 2)OpenTherm line timing statistic; unit not stated.UINT16Read
HR2101Min time of 1 bit (boiler line, set 2)OpenTherm line timing statistic; unit not stated.UINT16Read
HR2102Pulse time min (boiler line, set 2)OpenTherm line timing statistic; unit not stated.UINT16Read
HR2103Pulse time threshold (boiler line, set 2)OpenTherm line timing statistic; unit not stated.UINT16Read
HR2120Average long bit time (boiler line, set 2)OpenTherm line timing statistic; unit not stated.UINT16Read
HR2121Min long bit time (boiler line, set 2)OpenTherm line timing statistic; unit not stated.UINT16Read
HR2122Max long bit time (boiler line, set 2)OpenTherm line timing statistic; unit not stated.UINT16Read
HR2123Average short bit time (boiler line, set 2)OpenTherm line timing statistic; unit not stated.UINT16Read
HR2124Min short bit time (boiler line, set 2)OpenTherm line timing statistic; unit not stated.UINT16Read
HR2125Max short bit time (boiler line, set 2)OpenTherm line timing statistic; unit not stated.UINT16Read
HR2126Start bit min time (boiler line, set 2)OpenTherm line timing statistic; unit not stated.UINT16Read
HR2127Start bit max time (boiler line, set 2)OpenTherm line timing statistic; unit not stated.UINT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Unipi Technology MM-OT101 Modbus / OpenTherm gateway

What Modbus registers does the Unipi Technology MM-OT101 Modbus / OpenTherm gateway have?

This map lists 85 registers: 2 coils, 83 holding registers. 34 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Unipi Technology MM-OT101 Modbus / OpenTherm gateway Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register numbers equal OpenTherm message IDs (0-127) and are sent unchanged; register 0 (status flags) exists, so the numbering is 0-based. Gateway registers 1000+ and coils 0/1 follow the same rule.

What are the minimum Modbus registers to integrate the Unipi Technology MM-OT101 Modbus / OpenTherm gateway?

Start with HR 0 Master / slave status flags (Status flags (CH/DHW enable, flame, fault)); HR 1 Control setpoint (CH water) (Control setpoint); HR 17 Relative modulation level (Relative modulation level); HR 25 Boiler flow water temperature (Boiler flow temperature); HR 28 Return water temperature (Return water temperature); CO 0 Monitor mode active (Monitor / controller mode).

How do I enable Modbus control of the Unipi Technology MM-OT101 Modbus / OpenTherm gateway?

Set address (1-7), baud (9600/19200) and parity with the internal DIP switch: switch 1 = baud (ON 19200), switch 2 = parity (ON even), switches 3-5 = address weights 4/2/1. The gateway starts in monitor mode after power-up.

Where is the official Unipi Technology MM-OT101 Modbus / OpenTherm gateway Modbus documentation?

The source is Technical documentation - Communication gateway with Modbus and Opentherm MM-OT101, published free by Unipi Technology at https://kb.unipi.technology/_media/files:products:extensions_gateyways:mm-ot101:mm-ot101-technical_manual_en.pdf.

More Unipi Technology Modbus register maps

Other ac & vrf gateways register maps

All ac & vrf gateways Modbus register maps →

Source: Technical documentation - Communication gateway with Modbus and Opentherm MM-OT101. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.