- MM-OT101 Modbus / OpenTherm gateway
Boiler gateway (OpenTherm to Modbus RTU) · Modbus register map
Unipi Technology MM-OT101 Modbus / OpenTherm gateway Modbus register map
Updated 17 November 2026
The MM-OT101 sits between an OpenTherm boiler and its thermostat (monitor mode) or replaces the thermostat (controller mode) and exposes the OpenTherm data on Modbus RTU. Each OpenTherm message ID maps straight to the register with the same number. This map covers the status flags, setpoints, temperatures, modulation, pressure, counters and remote parameters, the gateway's line settings and timing statistics, and the two mode coils.
This page lists 85 Modbus registers for the Unipi Technology MM-OT101 Modbus / OpenTherm gateway — 34 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Unipi Technology’s own free documentation (linked below) and checked against it.
- Manufacturer
- Unipi Technology
- Model
- MM-OT101 Modbus / OpenTherm gateway
- Equipment type
- Boiler gateway (OpenTherm to Modbus RTU)
- Registers
- 85 (34 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 19200 baud, 8E1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- MM-OT101, MM-OT1010, Unipi OpenTherm gateway
Integration notes: Unipi Technology MM-OT101 Modbus / OpenTherm gateway
In controller mode, clear coil 0, set the CH/DHW enable flags in the master status byte of register 0 and write the control setpoint to register 1 (f8.8), one register per write, repeated periodically. Read boiler status and temperatures from registers 0, 17, 25, 26 and 28.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Master / slave status flags | UINT16 | Status flags (CH/DHW enable, flame, fault) | Read/write |
| HR 1 | Control setpoint (CH water) | INT16 | Control setpoint | Write |
| HR 17 | Relative modulation level | INT16 | Relative modulation level | Read |
| HR 25 | Boiler flow water temperature | INT16 | Boiler flow temperature | Read |
| HR 28 | Return water temperature | INT16 | Return water temperature | Read |
| CO 0 | Monitor mode active | BIT | Monitor / controller mode | Read/write |
Enable Modbus control & writes
Set address (1-7), baud (9600/19200) and parity with the internal DIP switch: switch 1 = baud (ON 19200), switch 2 = parity (ON even), switches 3-5 = address weights 4/2/1. The gateway starts in monitor mode after power-up.
Byte order & addressing
- Registers 0-127 must be written one register at a time; multi-register writes work only for 1000 and up (memory only).
- f8.8 values: read as signed 16-bit and divide by 256.
- Direct reads to the boiler can take up to about 800 ms; set the master timeout accordingly.
Network setup
- Default: address 1, 19200 baud, even parity.
- On some versions parity is fixed to even regardless of the switch.
- 120-ohm termination is enabled with switch SW2.
Watch out for
- The gateway returns to monitor mode after power-up, so the controller must re-select controller mode.
- In controller mode the PLC must send commands to the boiler periodically.
Unipi Technology MM-OT101 Modbus / OpenTherm gateway Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0 | Monitor mode active | BIT | Read/write | 0 = Controller mode; 1 = Monitor mode | ||||
| CO | 1 | Active scan | BIT | Read/write | 0 = Send on each register write; 1 = Cycle all mapped messages to the boiler | ||||
| HR | 0 | Master / slave status flags | Master and slave status flag bytes; byte order unclear in the manual (see notes). | UINT16 | Read/write | ||||
| HR | 1 | Control setpoint (CH water) | f8.8: signed, divide by 256. Required in controller mode. | INT16 | × 0.00390625 | °C | Write | ||
| HR | 2 | Master configuration flags / member ID | High/low byte pair (flag8 / u8). | UINT16 | Write | ||||
| HR | 3 | Slave configuration flags / member ID | High/low byte pair (flag8 / u8). | UINT16 | Read | ||||
| HR | 4 | Remote command | Byte pair (u8 / u8). | UINT16 | Write | ||||
| HR | 5 | Application fault flags / OEM fault code | Fault flag byte plus OEM fault code. | UINT16 | Read | ||||
| HR | 6 | Remote parameter transfer-enable / read-write flags | Two flag bytes. | UINT16 | Read | ||||
| HR | 7 | Cooling control signal | f8.8: signed, divide by 256. | INT16 | × 0.00390625 | % | Write | ||
| HR | 8 | Control setpoint CH2 | f8.8: signed, divide by 256. | INT16 | × 0.00390625 | °C | Write | ||
| HR | 9 | Remote override room setpoint | f8.8: signed, divide by 256. | INT16 | × 0.00390625 | Read | |||
| HR | 10 | Number of transparent slave parameters | u8. | UINT16 | Read | ||||
| HR | 11 | Transparent slave parameter index / value | Index byte and value byte. | UINT16 | Read/write | ||||
| HR | 12 | Fault history buffer size | u8. | UINT16 | Read | ||||
| HR | 13 | Fault history entry index / value | Index byte and value byte. | UINT16 | Read | ||||
| HR | 14 | Max relative modulation setting | f8.8: signed, divide by 256. | INT16 | × 0.00390625 | % | Write | ||
| HR | 15 | Max boiler capacity (kW) / min modulation (%) | Two u8 bytes. | UINT16 | Read | ||||
| HR | 16 | Room setpoint | f8.8: signed, divide by 256. | INT16 | × 0.00390625 | °C | Write | ||
| HR | 17 | Relative modulation level | f8.8: signed, divide by 256. | INT16 | × 0.00390625 | % | Read | ||
| HR | 18 | CH water pressure | f8.8: signed, divide by 256. | INT16 | × 0.00390625 | bar | Read | ||
| HR | 19 | DHW flow rate | f8.8: signed, divide by 256. | INT16 | × 0.00390625 | l/min | Read | ||
| HR | 20 | Day of week and time of day | OpenTherm packed u8 bytes. | UINT16 | Read/write | ||||
| HR | 21 | Calendar date | Two u8 bytes. | UINT16 | Read/write | ||||
| HR | 22 | Calendar year | UINT16 | Read/write | |||||
| HR | 23 | Room setpoint CH2 | f8.8: signed, divide by 256. | INT16 | × 0.00390625 | °C | Write | ||
| HR | 24 | Room temperature | f8.8: signed, divide by 256. Sent by the thermostat/controller. | INT16 | × 0.00390625 | °C | Write | ||
| HR | 25 | Boiler flow water temperature | f8.8: signed, divide by 256. | INT16 | × 0.00390625 | °C | Read | ||
| HR | 26 | DHW temperature | f8.8: signed, divide by 256. | INT16 | × 0.00390625 | °C | Read | ||
| HR | 27 | Outside temperature | f8.8: signed, divide by 256. | INT16 | × 0.00390625 | °C | Read | ||
| HR | 28 | Return water temperature | f8.8: signed, divide by 256. | INT16 | × 0.00390625 | °C | Read | ||
| HR | 29 | Solar storage temperature | f8.8: signed, divide by 256. | INT16 | × 0.00390625 | °C | Read | ||
| HR | 30 | Solar collector temperature | f8.8: signed, divide by 256. | INT16 | × 0.00390625 | °C | Read | ||
| HR | 31 | CH2 flow water temperature | f8.8: signed, divide by 256. | INT16 | × 0.00390625 | °C | Read | ||
| HR | 32 | DHW temperature 2 | f8.8: signed, divide by 256. | INT16 | × 0.00390625 | °C | Read | ||
| HR | 33 | Boiler exhaust temperature | INT16 | °C | Read | ||||
| HR | 48 | DHW setpoint bounds | Upper / lower bound bytes, s8, °C. | UINT16 | Read | ||||
| HR | 49 | Max CH setpoint bounds | Upper / lower bound bytes, s8, °C. | UINT16 | Read | ||||
| HR | 50 | OTC heat curve ratio bounds | Upper / lower bound bytes, s8. | UINT16 | Read | ||||
| HR | 56 | DHW setpoint (remote parameter 1) | f8.8: signed, divide by 256. | INT16 | × 0.00390625 | °C | Read/write | ||
| HR | 57 | Max CH water setpoint (remote parameter 2) | f8.8: signed, divide by 256. | INT16 | × 0.00390625 | °C | Read/write | ||
| HR | 58 | OTC heat curve ratio (remote parameter 3) | f8.8: signed, divide by 256. | INT16 | × 0.00390625 | Read/write | |||
| HR | 100 | Remote override function flags | flag8: manual / program change handling. | UINT16 | Read | ||||
| HR | 115 | OEM diagnostic / service code | UINT16 | Read | |||||
| HR | 116 | Burner starts | UINT16 | Read/write | |||||
| HR | 117 | CH pump starts | UINT16 | Read/write | |||||
| HR | 118 | DHW pump/valve starts | UINT16 | Read/write | |||||
| HR | 119 | Burner starts in DHW mode | UINT16 | Read/write | |||||
| HR | 120 | Burner operating hours | UINT16 | h | Read/write | ||||
| HR | 121 | CH pump running hours | UINT16 | h | Read/write | ||||
| HR | 122 | DHW pump/valve running hours | UINT16 | h | Read/write | ||||
| HR | 123 | Burner hours in DHW mode | UINT16 | h | Read/write | ||||
| HR | 124 | OpenTherm version, master | f8.8: signed, divide by 256. | INT16 | × 0.00390625 | Write | |||
| HR | 125 | OpenTherm version, slave | f8.8: signed, divide by 256. | INT16 | × 0.00390625 | Read | |||
| HR | 126 | Master product version and type | Two u8 bytes. | UINT16 | Write | ||||
| HR | 127 | Slave product version and type | Two u8 bytes. | UINT16 | Read | ||||
| HR | 1000 | OT line logical 0 current | Gateway setting (memory only). | UINT16 | mA | Read/write | |||
| HR | 1001 | OT line logical 1 current | Gateway setting (memory only). | UINT16 | mA | Read/write | |||
| HR | 1002 | Gap before reply to thermostat | Gateway setting (memory only). | UINT16 | µs | Read/write | |||
| HR | 1003 | Boiler transaction timeout | Gateway setting (memory only). | UINT16 | ms | Read/write | |||
| HR | 1004 | Sanity gap before reply | Gateway setting (memory only). | UINT16 | ms | Read/write | |||
| HR | 2000 | Max time of 1 bit (boiler line) | OpenTherm line timing statistic; unit not stated. | UINT16 | Read | ||||
| HR | 2001 | Min time of 1 bit (boiler line) | OpenTherm line timing statistic; unit not stated. | UINT16 | Read | ||||
| HR | 2002 | Pulse time min (boiler line) | OpenTherm line timing statistic; unit not stated. | UINT16 | Read | ||||
| HR | 2003 | Pulse time threshold (boiler line) | OpenTherm line timing statistic; unit not stated. | UINT16 | Read | ||||
| HR | 2020 | Average long bit time (boiler line) | OpenTherm line timing statistic; unit not stated. | UINT16 | Read | ||||
| HR | 2021 | Min long bit time (boiler line) | OpenTherm line timing statistic; unit not stated. | UINT16 | Read | ||||
| HR | 2022 | Max long bit time (boiler line) | OpenTherm line timing statistic; unit not stated. | UINT16 | Read | ||||
| HR | 2023 | Average short bit time (boiler line) | OpenTherm line timing statistic; unit not stated. | UINT16 | Read | ||||
| HR | 2024 | Min short bit time (boiler line) | OpenTherm line timing statistic; unit not stated. | UINT16 | Read | ||||
| HR | 2025 | Max short bit time (boiler line) | OpenTherm line timing statistic; unit not stated. | UINT16 | Read | ||||
| HR | 2026 | Start bit min time (boiler line) | OpenTherm line timing statistic; unit not stated. | UINT16 | Read | ||||
| HR | 2027 | Start bit max time (boiler line) | OpenTherm line timing statistic; unit not stated. | UINT16 | Read | ||||
| HR | 2100 | Max time of 1 bit (boiler line, set 2) | OpenTherm line timing statistic; unit not stated. | UINT16 | Read | ||||
| HR | 2101 | Min time of 1 bit (boiler line, set 2) | OpenTherm line timing statistic; unit not stated. | UINT16 | Read | ||||
| HR | 2102 | Pulse time min (boiler line, set 2) | OpenTherm line timing statistic; unit not stated. | UINT16 | Read | ||||
| HR | 2103 | Pulse time threshold (boiler line, set 2) | OpenTherm line timing statistic; unit not stated. | UINT16 | Read | ||||
| HR | 2120 | Average long bit time (boiler line, set 2) | OpenTherm line timing statistic; unit not stated. | UINT16 | Read | ||||
| HR | 2121 | Min long bit time (boiler line, set 2) | OpenTherm line timing statistic; unit not stated. | UINT16 | Read | ||||
| HR | 2122 | Max long bit time (boiler line, set 2) | OpenTherm line timing statistic; unit not stated. | UINT16 | Read | ||||
| HR | 2123 | Average short bit time (boiler line, set 2) | OpenTherm line timing statistic; unit not stated. | UINT16 | Read | ||||
| HR | 2124 | Min short bit time (boiler line, set 2) | OpenTherm line timing statistic; unit not stated. | UINT16 | Read | ||||
| HR | 2125 | Max short bit time (boiler line, set 2) | OpenTherm line timing statistic; unit not stated. | UINT16 | Read | ||||
| HR | 2126 | Start bit min time (boiler line, set 2) | OpenTherm line timing statistic; unit not stated. | UINT16 | Read | ||||
| HR | 2127 | Start bit max time (boiler line, set 2) | OpenTherm line timing statistic; unit not stated. | UINT16 | Read |
Notes on this map
- OpenTherm f8.8 values are signed 16-bit numbers divided by 256 (the manual's example: 1.3 is stored as 333).
- Registers that hold two 8-bit OpenTherm fields (flag8/u8, u8/u8, s8 pairs) are listed as one UINT16; split them into high and low byte yourself. The manual does not say which byte holds which field for every pair, so check against the OpenTherm specification.
- Left out: the 32-bit statistics counters (2004-2018 and 2104-2118), because the manual does not state their word order.
- In monitor mode, registers 0-127 hold the last value seen passing between boiler and thermostat; messages that never passed read 0. Unmapped registers and coils also read 0.
- The manual names separate read functions (a single-register read goes straight to the boiler in controller mode, a multi-register read returns the memory map) but gives no function-code numbers; registers are listed here as holding registers.
- Statistics units (bit times) are not stated.
- Register 0: the minimum-configuration table puts the master status flags (bit 0 CH enable, bit 1 DHW enable, bit 2 cooling enable, bit 3 OTC active, bit 4 CH2) in the high byte and the slave flags (bit 0 fault, 1 CH mode, 2 DHW mode, 3 flame, 4 cooling, 5 CH2 mode, 6 diagnostic) in the low byte, but the register map table prints the register as LB(flag8)/HB(flag8) for master and slave. Because the byte order is not settled, the bits are not mapped here; confirm on site.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Unipi Technology MM-OT101 Modbus / OpenTherm gateway
What Modbus registers does the Unipi Technology MM-OT101 Modbus / OpenTherm gateway have?
This map lists 85 registers: 2 coils, 83 holding registers. 34 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Unipi Technology MM-OT101 Modbus / OpenTherm gateway Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register numbers equal OpenTherm message IDs (0-127) and are sent unchanged; register 0 (status flags) exists, so the numbering is 0-based. Gateway registers 1000+ and coils 0/1 follow the same rule.
What are the minimum Modbus registers to integrate the Unipi Technology MM-OT101 Modbus / OpenTherm gateway?
Start with HR 0 Master / slave status flags (Status flags (CH/DHW enable, flame, fault)); HR 1 Control setpoint (CH water) (Control setpoint); HR 17 Relative modulation level (Relative modulation level); HR 25 Boiler flow water temperature (Boiler flow temperature); HR 28 Return water temperature (Return water temperature); CO 0 Monitor mode active (Monitor / controller mode).
How do I enable Modbus control of the Unipi Technology MM-OT101 Modbus / OpenTherm gateway?
Set address (1-7), baud (9600/19200) and parity with the internal DIP switch: switch 1 = baud (ON 19200), switch 2 = parity (ON even), switches 3-5 = address weights 4/2/1. The gateway starts in monitor mode after power-up.
Where is the official Unipi Technology MM-OT101 Modbus / OpenTherm gateway Modbus documentation?
The source is Technical documentation - Communication gateway with Modbus and Opentherm MM-OT101, published free by Unipi Technology at https://kb.unipi.technology/_media/files:products:extensions_gateyways:mm-ot101:mm-ot101-technical_manual_en.pdf.
More Unipi Technology Modbus register maps
- Sensor (1-Wire temperature gateway)
Unipi Technology Unipi Extension xG18 1-Wire temperature gateway
Unipi Extension xG18 RS-485 module per the Unipi Extension xG18 Modbus map v1.1.
Also known as: Unipi Extension xG18, xG18 - Sensor (remote I/O module)
Unipi Technology Unipi Extension xS11 I/O module
Unipi Extension xS11 RS-485 module per the Unipi Extension xS11 Modbus map v2.0.
Also known as: Unipi Extension xS11, xS11 - Sensor (remote I/O module)
Unipi Technology Unipi Extension xS51 I/O module
Unipi Extension xS51 RS-485 module per the Unipi Extension xS51 Modbus map v2.0.
Also known as: Unipi Extension xS51, xS51 - Sensor (remote I/O module)
Unipi Technology Unipi Extension xS52 resistance input module
Unipi Extension xS52 RS-485 module per the Unipi Extension xS52 Modbus map v2.0.
Also known as: Unipi Extension xS52, xS52 - Sensor (remote I/O module)
Unipi Technology Unipi Extension xS53 analog input module
Unipi Extension xS53 RS-485 module per the Unipi Extension xS53 Modbus map v2.0.
Also known as: Unipi Extension xS53, xS53 - Sensor (remote I/O module)
Unipi Technology Unipi Extension xS54 universal analog input module
Unipi Extension xS54 RS-485 module per the Unipi Extension xS54 Modbus map v2.0.
Also known as: Unipi Extension xS54, xS54
Other ac & vrf gateways register maps
- VRF / split AC gateway
Daikin DTA116A51 D-NET / Modbus communication adaptor (VRV)
DTA116A51 adaptor with up to 16 VRV indoor units (D-NET 1-00 to 1-15), per functional specification CB13A033 first edition.
Also known as: DTA116A51, DIII-NET Modbus adaptor, D3NET Modbus adapter - Split AC unit (VRF / split AC gateway built in)
Gree U-Match all-DC-inverter duct / cassette / floor-ceiling units (built-in Modbus)
Gree U-Match fourth-generation all-DC-inverter light-commercial units whose controller has the integrated Modbus RTU interface; Chinese-English protocol dated 2018-03-07.
Also known as: U-Match, Gree U-Match 4th generation DC inverter, U-Match BMS Modbus - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Panasonic application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Panasonic application (U1U2 P-Link / S-Link), Modbus RTU / TCP server, user manual version 1.1.7 (2025-12-09).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSFGL001R000 Fujitsu AC to Modbus RTU gateway
One Fujitsu indoor unit, or a group of up to 16 controlled together as one, on the 3-wire BWR remote-controller bus via INMBSFGL001R000, user manual v2.4 (02/2025).
Also known as: INMBSFGL001R000, Intesis Fujitsu Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSLGE016O000 LG VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)
Intesis Modbus - LG VRF, order codes INMBSLGE016O000 / INMBSLGE064O000 (legacy LG-AC-MBS-16 / -64), user manual r1.0 (04/2020); LG PI485 bus.
Also known as: INMBSLGE016O000, INMBSLGE064O000, LG-AC-MBS-16, LG-AC-MBS-64, Intesis Modbus LG VRF - Heat pump gateway (VRF / split AC gateway)
Intesis (HMS Networks) INMBSPAN001A100 Panasonic Aquarea H/J/K/L/M air-to-water to Modbus RTU gateway
Intesis (HMS Networks) INMBSPAN001A100 gateway connected to Panasonic Aquarea H, J, K, L and M series air-to-water heat pumps, per user manual version 1.0.2 (2026-02-04).
Also known as: INMBSPAN001A100, Aquarea Modbus, Panasonic Aquarea Modbus RTU, Intesis Aquarea, INMBSPAN001A000 (legacy order code)
All ac & vrf gateways Modbus register maps →
Source: Technical documentation - Communication gateway with Modbus and Opentherm MM-OT101. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.