- Unipi Extension xS54 universal analog input module
Sensor (remote I/O module) · Modbus register map
Unipi Technology Unipi Extension xS54 universal analog input module Modbus register map
Updated 19 November 2026
The Unipi Extension xS54 is an RS-485 Modbus RTU extension module with 4 digital inputs, 5 relay outputs and 8 universal analog inputs (voltage, current or resistance). The map covers I/O words, float input values, counters, watchdog and configuration.
This page lists 58 Modbus registers for the Unipi Technology Unipi Extension xS54 universal analog input module — 38 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Unipi Technology’s own free documentation (linked below) and checked against it.
- Manufacturer
- Unipi Technology
- Model
- Unipi Extension xS54 universal analog input module
- Equipment type
- Sensor (remote I/O module)
- Registers
- 58 (38 writable)
- Transport
- Modbus RTU
- Default unit ID
- 15
- Default serial
- 19200 baud, 8N1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- CDAB low word first (word-swapped)
- Also known as
- Unipi Extension xS54, xS54
- Source document
- Extension xS54 Modbus map · v2.0
Integration notes: Unipi Technology Unipi Extension xS54 universal analog input module
Read the 8 analog inputs as CDAB floats from register 2 onward; set the type of each at registers 1017-1024.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Digital Inputs | BITMAP16 | Digital input states | Read |
| HR 1 | Relay Outputs | BITMAP16 | Relay output states | Read/write |
| HR 2 | Analog Input 1 | FLOAT32 CDAB | Analog input 1 | Read |
| CO 0 | Relay Output 1 | BIT | Relay 1 | Read/write |
| HR 1017 | Configuration(U/I/R) of Analog Input 1 | UINT16 | AI 1 type | Read/write |
Enable Modbus control & writes
Modbus RTU is the native interface; nothing needs enabling. Factory settings are address 15, 19200 bps, 8N1.
Communication loss & watchdog
Master watchdog (MWD): enable it with the MWD Enable bit of the MWD status register and set the timeout in register 1008 (default 5000 ms). A watchdog reboot is flagged by the MWD Reboot Detected bit and coil 1000; the map does not describe the timeout behaviour further.
Byte order & addressing
- 32-bit values (floats, counters and the PCB serial number) are low word first (CDAB).
- Changes to RS-485 settings and other configuration need the Save configuration coil to survive a power cycle.
Network setup
- Set the address register (1026) and the packed RS-485 configuration register (1025), then write 1 to the save coil (1003) so the settings are used on startup.
Unipi Technology Unipi Extension xS54 universal analog input module Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 0x0000 | Relay Output 1 | Relay output state. | BIT | Read/write | ||||
| CO | 1doc 0x0001 | Relay Output 2 | Relay output state. | BIT | Read/write | ||||
| CO | 2doc 0x0002 | Relay Output 3 | Relay output state. | BIT | Read/write | ||||
| CO | 3doc 0x0003 | Relay Output 4 | Relay output state. | BIT | Read/write | ||||
| CO | 4doc 0x0004 | Relay Output 5 | Relay output state. | BIT | Read/write | ||||
| CO | 5doc 0x0005 | Digital Input 1 | Digital input state (read with FC01). | BIT | Read | ||||
| CO | 6doc 0x0006 | Digital Input 2 | Digital input state (read with FC01). | BIT | Read | ||||
| CO | 7doc 0x0007 | Digital Input 3 | Digital input state (read with FC01). | BIT | Read | ||||
| CO | 8doc 0x0008 | Digital Input 4 | Digital input state (read with FC01). | BIT | Read | ||||
| CO | 9doc 0x0009 | User Programmable LED 1 | BIT | Read/write | |||||
| CO | 10doc 0x000A | User Programmable LED 2 | BIT | Read/write | |||||
| CO | 11doc 0x000B | User Programmable LED 3 | BIT | Read/write | |||||
| CO | 1000doc 0x03E8 | MWD reset indication | Set when the master watchdog has reset the module. | BIT | Read/write | ||||
| CO | 1002doc 0x03EA | Reset group MCU | Write 1 to reset the module processor. | BIT | Write | ||||
| CO | 1003doc 0x03EB | Save current configuration and use on startup | Write 1 to store the current settings as power-up defaults. | BIT | Write | ||||
| HR | 0doc 0x0000 | Digital Inputs | BITMAP16 | Read | bit 0 = Digital Input 1; bit 1 = Digital Input 2; bit 2 = Digital Input 3; bit 3 = Digital Input 4 | ||||
| HR | 1doc 0x0001 | Relay Outputs | BITMAP16 | Read/write | bit 0 = Relay Output 1; bit 1 = Relay Output 2; bit 2 = Relay Output 3; bit 3 = Relay Output 4; bit 4 = Relay Output 5 | ||||
| HR | 2doc 0x0002 | Analog Input 1 | Analog input reading (float); unit not stated in the map. | FLOAT32 | CDAB | Read | |||
| HR | 4doc 0x0004 | Analog Input 2 | Analog input reading (float); unit not stated in the map. | FLOAT32 | CDAB | Read | |||
| HR | 6doc 0x0006 | Analog Input 3 | Analog input reading (float); unit not stated in the map. | FLOAT32 | CDAB | Read | |||
| HR | 8doc 0x0008 | Analog Input 4 | Analog input reading (float); unit not stated in the map. | FLOAT32 | CDAB | Read | |||
| HR | 10doc 0x000A | Analog Input 5 | Analog input reading (float); unit not stated in the map. | FLOAT32 | CDAB | Read | |||
| HR | 12doc 0x000C | Analog Input 6 | Analog input reading (float); unit not stated in the map. | FLOAT32 | CDAB | Read | |||
| HR | 14doc 0x000E | Analog Input 7 | Analog input reading (float); unit not stated in the map. | FLOAT32 | CDAB | Read | |||
| HR | 16doc 0x0010 | Analog Input 8 | Analog input reading (float); unit not stated in the map. | FLOAT32 | CDAB | Read | |||
| HR | 18doc 0x0012 | Group MasterWatchDog (MWD) Status | BITMAP16 | Read/write | bit 0 = MWD Enable; bit 1 = MWD Reboot Detected | ||||
| HR | 19doc 0x0013 | Counter of Digital Input 1 | Pulse counter for this input; writable to preset. | UINT32 | CDAB | Read/write | |||
| HR | 21doc 0x0015 | Counter of Digital Input 2 | Pulse counter for this input; writable to preset. | UINT32 | CDAB | Read/write | |||
| HR | 23doc 0x0017 | Counter of Digital Input 3 | Pulse counter for this input; writable to preset. | UINT32 | CDAB | Read/write | |||
| HR | 25doc 0x0019 | Counter of Digital Input 4 | Pulse counter for this input; writable to preset. | UINT32 | CDAB | Read/write | |||
| HR | 27doc 0x001B | User-programmable LED states | BITMAP16 | Read/write | bit 0 = User LED 1; bit 1 = User LED 2; bit 2 = User LED 3 | ||||
| HR | 28doc 0x001C | Synchronised Relay Outputs | BITMAP16 | Read/write | bit 0 = Synchronised RO 1; bit 1 = Synchronised RO 2; bit 2 = Synchronised RO 3; bit 3 = Synchronised RO 4; bit 4 = Synchronised RO 5 | ||||
| HR | 29doc 0x001D | Synchronised Relay Output Locks | BITMAP16 | Read/write | bit 0 = Synchronised RO Lock 1; bit 1 = Synchronised RO Lock 2; bit 2 = Synchronised RO Lock 3; bit 3 = Synchronised RO Lock 4; bit 4 = Synchronised RO Lock 5 | ||||
| HR | 1000doc 0x03E8 | Firmware Version | UINT16 | Read | |||||
| HR | 1001doc 0x03E9 | Number of I/Os | Packed counts: bits 0-7 DOs, bits 8-15 DIs. | UINT16 | Read | ||||
| HR | 1002doc 0x03EA | Number of peripherals | Packed counts: bits 0-3 RS485 lines, bits 4-7 AOs, bits 8-15 AIs. | UINT16 | Read | ||||
| HR | 1003doc 0x03EB | Firmware ID | UINT16 | Read | |||||
| HR | 1004doc 0x03EC | Hardware ID | UINT16 | Read | |||||
| HR | 1005doc 0x03ED | PCB Serial Number | UINT32 | CDAB | Read | ||||
| HR | 1008doc 0x03F0 | MasterWatchDog (MWD) Timeout (in 1ms) | Master watchdog timeout; default 5000 ms. | UINT16 | ms | Read/write | |||
| HR | 1009doc 0x03F1 | VRef of MCU | UINT16 | Read | |||||
| HR | 1010doc 0x03F2 | Debounce time (in 100us) for DI 1 | Input debounce time in 100 us steps. | UINT16 | × 0.1 | ms | Read/write | ||
| HR | 1011doc 0x03F3 | Debounce time (in 100us) for DI 2 | Input debounce time in 100 us steps. | UINT16 | × 0.1 | ms | Read/write | ||
| HR | 1012doc 0x03F4 | Debounce time (in 100us) for DI 3 | Input debounce time in 100 us steps. | UINT16 | × 0.1 | ms | Read/write | ||
| HR | 1013doc 0x03F5 | Debounce time (in 100us) for DI 4 | Input debounce time in 100 us steps. | UINT16 | × 0.1 | ms | Read/write | ||
| HR | 1014doc 0x03F6 | Enable DirectSwitch functionality | BITMAP16 | Read/write | bit 0 = Enable DirectSwitch on DI 1; bit 1 = Enable DirectSwitch on DI 2; bit 2 = Enable DirectSwitch on DI 3; bit 3 = Enable DirectSwitch on DI 4 | ||||
| HR | 1015doc 0x03F7 | Invert DirectSwitch Polarity | BITMAP16 | Read/write | bit 0 = Invert DirectSwitch Polarity on DI 1; bit 1 = Invert DirectSwitch Polarity on DI 2; bit 2 = Invert DirectSwitch Polarity on DI 3; bit 3 = Invert DirectSwitch Polarity on DI 4 | ||||
| HR | 1016doc 0x03F8 | Enabled DirectSwitch Toggle | BITMAP16 | Read/write | bit 0 = Enable DirectSwitch Toggle on DI 1; bit 1 = Enable DirectSwitch Toggle on DI 2; bit 2 = Enable DirectSwitch Toggle on DI 3; bit 3 = Enable DirectSwitch Toggle on DI 4 | ||||
| HR | 1017doc 0x03F9 | Configuration(U/I/R) of Analog Input 1 | Measurement type for this analog input. | UINT16 | Read/write | 0 = OFF; 1 = Voltage 0-10 V; 2 = Voltage 0-2 V; 3 = Current 0-20 mA; 4 = Resistance 75-2000 ohm; 5 = Resistance 1-20 kohm | |||
| HR | 1018doc 0x03FA | Configuration(U/I/R) of Analog Input 2 | Measurement type for this analog input. | UINT16 | Read/write | 0 = OFF; 1 = Voltage 0-10 V; 2 = Voltage 0-2 V; 3 = Current 0-20 mA; 4 = Resistance 75-2000 ohm; 5 = Resistance 1-20 kohm | |||
| HR | 1019doc 0x03FB | Configuration(U/I/R) of Analog Input 3 | Measurement type for this analog input. | UINT16 | Read/write | 0 = OFF; 1 = Voltage 0-10 V; 2 = Voltage 0-2 V; 3 = Current 0-20 mA; 4 = Resistance 75-2000 ohm; 5 = Resistance 1-20 kohm | |||
| HR | 1020doc 0x03FC | Configuration(U/I/R) of Analog Input 4 | Measurement type for this analog input. | UINT16 | Read/write | 0 = OFF; 1 = Voltage 0-10 V; 2 = Voltage 0-2 V; 3 = Current 0-20 mA; 4 = Resistance 75-2000 ohm; 5 = Resistance 1-20 kohm | |||
| HR | 1021doc 0x03FD | Configuration(U/I/R) of Analog Input 5 | Measurement type for this analog input. | UINT16 | Read/write | 0 = OFF; 1 = Voltage 0-10 V; 2 = Voltage 0-2 V; 3 = Current 0-20 mA; 4 = Resistance 75-2000 ohm; 5 = Resistance 1-20 kohm | |||
| HR | 1022doc 0x03FE | Configuration(U/I/R) of Analog Input 6 | Measurement type for this analog input. | UINT16 | Read/write | 0 = OFF; 1 = Voltage 0-10 V; 2 = Voltage 0-2 V; 3 = Current 0-20 mA; 4 = Resistance 75-2000 ohm; 5 = Resistance 1-20 kohm | |||
| HR | 1023doc 0x03FF | Configuration(U/I/R) of Analog Input 7 | Measurement type for this analog input. | UINT16 | Read/write | 0 = OFF; 1 = Voltage 0-10 V; 2 = Voltage 0-2 V; 3 = Current 0-20 mA; 4 = Resistance 75-2000 ohm; 5 = Resistance 1-20 kohm | |||
| HR | 1024doc 0x0400 | Configuration(U/I/R) of Analog Input 8 | Measurement type for this analog input. | UINT16 | Read/write | 0 = OFF; 1 = Voltage 0-10 V; 2 = Voltage 0-2 V; 3 = Current 0-20 mA; 4 = Resistance 75-2000 ohm; 5 = Resistance 1-20 kohm | |||
| HR | 1025doc 0x0401 | RS485 Configuration - see Description sheet | Bits 0-12 baud code, bit 13 parity on, bit 14 odd parity; default 14 (19200 8N1). | UINT16 | Read/write | ||||
| HR | 1026doc 0x0402 | Modbus Address Configuration (1-254) | Modbus RTU slave address (default 15). | UINT16 | Read/write |
Notes on this map
- Word order: the description sheet states 16-bit values are big endian (AB) and 32-bit values are mid-little endian (CDAB, low word first).
- Registers marked Reserved - Do Not Use are left out.
- Baud codes for the RS-485 configuration register: 11 = 2400, 12 = 4800, 13 = 9600, 14 = 19200, 15 = 38400, 4097 = 57600, 4098 = 115200 bps.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Unipi Technology Unipi Extension xS54 universal analog input module
What Modbus registers does the Unipi Technology Unipi Extension xS54 universal analog input module have?
This map lists 58 registers: 15 coils, 43 holding registers. 38 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Unipi Technology Unipi Extension xS54 universal analog input module Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The map lists each register in decimal and hex starting at 0; the number is the wire address.
What byte order does the Unipi Technology Unipi Extension xS54 universal analog input module use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Unipi Technology Unipi Extension xS54 universal analog input module?
Start with HR 0 Digital Inputs (Digital input states); HR 1 Relay Outputs (Relay output states); HR 2 Analog Input 1 (Analog input 1); CO 0 Relay Output 1 (Relay 1); HR 1017 Configuration(U/I/R) of Analog Input 1 (AI 1 type).
How do I enable Modbus control of the Unipi Technology Unipi Extension xS54 universal analog input module?
Modbus RTU is the native interface; nothing needs enabling. Factory settings are address 15, 19200 bps, 8N1.
What happens when the Unipi Technology Unipi Extension xS54 universal analog input module loses Modbus communication?
Master watchdog (MWD): enable it with the MWD Enable bit of the MWD status register and set the timeout in register 1008 (default 5000 ms). A watchdog reboot is flagged by the MWD Reboot Detected bit and coil 1000; the map does not describe the timeout behaviour further.
Where is the official Unipi Technology Unipi Extension xS54 universal analog input module Modbus documentation?
The source is Extension xS54 Modbus map (v2.0), published free by Unipi Technology at https://kb.unipi.technology/_media/files:products:extensions:unipi-extension-xs54-modbus-map-v2.0.pdf.
More Unipi Technology Modbus register maps
- Boiler gateway (OpenTherm to Modbus RTU)
Unipi Technology MM-OT101 Modbus / OpenTherm gateway
Unipi MM-OT101 DIN-rail gateway between Modbus RTU (RS-485) and OpenTherm/Plus boilers and thermostats, per its technical documentation.
Also known as: MM-OT101, MM-OT1010, Unipi OpenTherm gateway - Sensor (1-Wire temperature gateway)
Unipi Technology Unipi Extension xG18 1-Wire temperature gateway
Unipi Extension xG18 RS-485 module per the Unipi Extension xG18 Modbus map v1.1.
Also known as: Unipi Extension xG18, xG18 - Sensor (remote I/O module)
Unipi Technology Unipi Extension xS11 I/O module
Unipi Extension xS11 RS-485 module per the Unipi Extension xS11 Modbus map v2.0.
Also known as: Unipi Extension xS11, xS11 - Sensor (remote I/O module)
Unipi Technology Unipi Extension xS51 I/O module
Unipi Extension xS51 RS-485 module per the Unipi Extension xS51 Modbus map v2.0.
Also known as: Unipi Extension xS51, xS51 - Sensor (remote I/O module)
Unipi Technology Unipi Extension xS52 resistance input module
Unipi Extension xS52 RS-485 module per the Unipi Extension xS52 Modbus map v2.0.
Also known as: Unipi Extension xS52, xS52 - Sensor (remote I/O module)
Unipi Technology Unipi Extension xS53 analog input module
Unipi Extension xS53 RS-485 module per the Unipi Extension xS53 Modbus map v2.0.
Also known as: Unipi Extension xS53, xS53
Other remote i/o modules register maps
- Sensor (counter/frequency input module)
ICP DAS M-7080 / M-7080B 2-channel counter/frequency module (Modbus RTU)
ICP DAS M-7080 and M-7080B two-channel 32-bit counter/frequency modules with two digital outputs, in Modbus RTU mode.
Also known as: M-7080, M-7080B, M7080, M7080B - Sensor (remote I/O module)
Moxa ioLogik R1241 RS-485 remote I/O
ioLogik R1241 per the ioLogik R1200 Series User's Manual, Edition 3.4 (April 2021).
Also known as: ioLogik R1241, R1241, R1241-T - Sensor (RTD temperature input module)
Seneca Z-4RTD2-SI 4-channel RTD input module (Modbus RTU)
Z-4RTD2-SI per user manual MI00584-4-EN.
Also known as: Z-4RTD2, Z4RTD2-SI, Seneca Z-4RTD2-SI - Sensor / remote I/O module
Brainboxes ED-516 Ethernet digital I/O (Modbus TCP)
Brainboxes ED-516 Ethernet I/O module with the protocol set to Modbus TCP.
Also known as: ED-516, ED516 - Sensor (remote I/O module)
Moxa ioLogik R1210 RS-485 remote I/O
ioLogik R1210 per the ioLogik R1200 Series User's Manual, Edition 3.4 (April 2021).
Also known as: ioLogik R1210, R1210, R1210-T - Sensor (remote I/O module, analog outputs)
Seneca R-4AO-8DIDO Ethernet I/O (4 analog outputs, 8 digital I/O)
R-4AO-8DIDO in the Series R I/O manual MI-00604-29-EN.
Also known as: R4AO8DIDO, R-4AO-8DIDO, Seneca R series 4AO
All remote i/o modules Modbus register maps →
Source: Extension xS54 Modbus map · v2.0. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.