Brainboxes ED-516 Ethernet digital I/O (Modbus TCP) Modbus register map

Updated 17 November 2026

Short answer

The ED-516 is a Brainboxes Ethernet I/O module with 16 digital inputs with pulse counters. It ships speaking the Brainboxes ASCII protocol; once its web page is switched to Modbus TCP, the I/O is exposed as coils, discrete inputs and registers. This map lists every object in the manufacturer's product table.

This page lists 81 Modbus registers for the Brainboxes ED-516 Ethernet digital I/O (Modbus TCP) — 16 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Brainboxes’s own free documentation (linked below) and checked against it.

Manufacturer
Brainboxes
Model
ED-516 Ethernet digital I/O (Modbus TCP)
Equipment type
Sensor / remote I/O module
Registers
81 (16 writable)
Transport
Modbus TCP
Default unit ID
Not stated
TCP port
502
Documented addressing
hexadecimal, 0-based
Also known as
ED-516, ED516
Source document
Using Modbus TCP with Brainboxes products
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Brainboxes ED-516 Ethernet digital I/O (Modbus TCP)

Integration in brief

Switch the module to Modbus TCP on its web page, then read the packed input or output register for a whole-module snapshot, or use the per-channel coils and discrete inputs. All values are single 16-bit registers or bits, so there is no word-order question.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 32Digital inputs (packed)UINT16All digital input states in one readRead
DI 0Digital input 0BITFirst digital inputRead
IR 0DI 0 counterUINT16First input's pulse counterRead
CO 512Clear DI 0 counterBITClear the first counterWrite

Enable Modbus control & writes

Open the module's web page (http://<ip>/#/protocol) and change Current Protocol from ASCII to Modbus TCP. The factory IP is 192.168.127.254 unless DHCP assigned one.

Byte order & addressing

Network setup

Watch out for

Brainboxes ED-516 Ethernet digital I/O (Modbus TCP) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

81 of 81 shown
Brainboxes ED-516 Ethernet digital I/O (Modbus TCP) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO32doc 00033Digital input 0 (coil view)Input state, readable as a coil with FC1.BITRead
CO33doc 00034Digital input 1 (coil view)Input state, readable as a coil with FC1.BITRead
CO34doc 00035Digital input 2 (coil view)Input state, readable as a coil with FC1.BITRead
CO35doc 00036Digital input 3 (coil view)Input state, readable as a coil with FC1.BITRead
CO36doc 00037Digital input 4 (coil view)Input state, readable as a coil with FC1.BITRead
CO37doc 00038Digital input 5 (coil view)Input state, readable as a coil with FC1.BITRead
CO38doc 00039Digital input 6 (coil view)Input state, readable as a coil with FC1.BITRead
CO39doc 00040Digital input 7 (coil view)Input state, readable as a coil with FC1.BITRead
CO40doc 00041Digital input 8 (coil view)Input state, readable as a coil with FC1.BITRead
CO41doc 00042Digital input 9 (coil view)Input state, readable as a coil with FC1.BITRead
CO42doc 00043Digital input 10 (coil view)Input state, readable as a coil with FC1.BITRead
CO43doc 00044Digital input 11 (coil view)Input state, readable as a coil with FC1.BITRead
CO44doc 00045Digital input 12 (coil view)Input state, readable as a coil with FC1.BITRead
CO45doc 00046Digital input 13 (coil view)Input state, readable as a coil with FC1.BITRead
CO46doc 00047Digital input 14 (coil view)Input state, readable as a coil with FC1.BITRead
CO47doc 00048Digital input 15 (coil view)Input state, readable as a coil with FC1.BITRead
CO512doc 00513Clear DI 0 counterWrite to clear this input's counter.BITWrite
CO513doc 00514Clear DI 1 counterWrite to clear this input's counter.BITWrite
CO514doc 00515Clear DI 2 counterWrite to clear this input's counter.BITWrite
CO515doc 00516Clear DI 3 counterWrite to clear this input's counter.BITWrite
CO516doc 00517Clear DI 4 counterWrite to clear this input's counter.BITWrite
CO517doc 00518Clear DI 5 counterWrite to clear this input's counter.BITWrite
CO518doc 00519Clear DI 6 counterWrite to clear this input's counter.BITWrite
CO519doc 00520Clear DI 7 counterWrite to clear this input's counter.BITWrite
CO520doc 00521Clear DI 8 counterWrite to clear this input's counter.BITWrite
CO521doc 00522Clear DI 9 counterWrite to clear this input's counter.BITWrite
CO522doc 00523Clear DI 10 counterWrite to clear this input's counter.BITWrite
CO523doc 00524Clear DI 11 counterWrite to clear this input's counter.BITWrite
CO524doc 00525Clear DI 12 counterWrite to clear this input's counter.BITWrite
CO525doc 00526Clear DI 13 counterWrite to clear this input's counter.BITWrite
CO526doc 00527Clear DI 14 counterWrite to clear this input's counter.BITWrite
CO527doc 00528Clear DI 15 counterWrite to clear this input's counter.BITWrite
DI0doc 10001Digital input 0Input state via FC2.BITRead
DI1doc 10002Digital input 1Input state via FC2.BITRead
DI2doc 10003Digital input 2Input state via FC2.BITRead
DI3doc 10004Digital input 3Input state via FC2.BITRead
DI4doc 10005Digital input 4Input state via FC2.BITRead
DI5doc 10006Digital input 5Input state via FC2.BITRead
DI6doc 10007Digital input 6Input state via FC2.BITRead
DI7doc 10008Digital input 7Input state via FC2.BITRead
DI8doc 10009Digital input 8Input state via FC2.BITRead
DI9doc 10010Digital input 9Input state via FC2.BITRead
DI10doc 10011Digital input 10Input state via FC2.BITRead
DI11doc 10012Digital input 11Input state via FC2.BITRead
DI12doc 10013Digital input 12Input state via FC2.BITRead
DI13doc 10014Digital input 13Input state via FC2.BITRead
DI14doc 10015Digital input 14Input state via FC2.BITRead
DI15doc 10016Digital input 15Input state via FC2.BITRead
IR0doc 30001DI 0 counterPulse counter for input 0.UINT16Read
IR1doc 30002DI 1 counterPulse counter for input 1.UINT16Read
IR2doc 30003DI 2 counterPulse counter for input 2.UINT16Read
IR3doc 30004DI 3 counterPulse counter for input 3.UINT16Read
IR4doc 30005DI 4 counterPulse counter for input 4.UINT16Read
IR5doc 30006DI 5 counterPulse counter for input 5.UINT16Read
IR6doc 30007DI 6 counterPulse counter for input 6.UINT16Read
IR7doc 30008DI 7 counterPulse counter for input 7.UINT16Read
IR8doc 30009DI 8 counterPulse counter for input 8.UINT16Read
IR9doc 30010DI 9 counterPulse counter for input 9.UINT16Read
IR10doc 30011DI 10 counterPulse counter for input 10.UINT16Read
IR11doc 30012DI 11 counterPulse counter for input 11.UINT16Read
IR12doc 30013DI 12 counterPulse counter for input 12.UINT16Read
IR13doc 30014DI 13 counterPulse counter for input 13.UINT16Read
IR14doc 30015DI 14 counterPulse counter for input 14.UINT16Read
IR15doc 30016DI 15 counterPulse counter for input 15.UINT16Read
IR32doc 30033Digital inputs (packed)All inputs in one register; packed bits, layout not given in the manual.UINT16Read
HR0doc 40001DI 0 counter (holding view)Same counter read with FC3.UINT16Read
HR1doc 40002DI 1 counter (holding view)Same counter read with FC3.UINT16Read
HR2doc 40003DI 2 counter (holding view)Same counter read with FC3.UINT16Read
HR3doc 40004DI 3 counter (holding view)Same counter read with FC3.UINT16Read
HR4doc 40005DI 4 counter (holding view)Same counter read with FC3.UINT16Read
HR5doc 40006DI 5 counter (holding view)Same counter read with FC3.UINT16Read
HR6doc 40007DI 6 counter (holding view)Same counter read with FC3.UINT16Read
HR7doc 40008DI 7 counter (holding view)Same counter read with FC3.UINT16Read
HR8doc 40009DI 8 counter (holding view)Same counter read with FC3.UINT16Read
HR9doc 40010DI 9 counter (holding view)Same counter read with FC3.UINT16Read
HR10doc 40011DI 10 counter (holding view)Same counter read with FC3.UINT16Read
HR11doc 40012DI 11 counter (holding view)Same counter read with FC3.UINT16Read
HR12doc 40013DI 12 counter (holding view)Same counter read with FC3.UINT16Read
HR13doc 40014DI 13 counter (holding view)Same counter read with FC3.UINT16Read
HR14doc 40015DI 14 counter (holding view)Same counter read with FC3.UINT16Read
HR15doc 40016DI 15 counter (holding view)Same counter read with FC3.UINT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Brainboxes ED-516 Ethernet digital I/O (Modbus TCP)

What Modbus registers does the Brainboxes ED-516 Ethernet digital I/O (Modbus TCP) have?

This map lists 81 registers: 32 coils, 16 discrete inputs, 17 input registers, 16 holding registers. 16 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Brainboxes ED-516 Ethernet digital I/O (Modbus TCP) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The table prints logical (on-the-wire) addresses in hex next to 984-style numbers. Use the hex value directly: input register 0x0020 is requested at address 32 and corresponds to 30033.

What are the minimum Modbus registers to integrate the Brainboxes ED-516 Ethernet digital I/O (Modbus TCP)?

Start with IR 32 Digital inputs (packed) (All digital input states in one read); DI 0 Digital input 0 (First digital input); IR 0 DI 0 counter (First input's pulse counter); CO 512 Clear DI 0 counter (Clear the first counter).

How do I enable Modbus control of the Brainboxes ED-516 Ethernet digital I/O (Modbus TCP)?

Open the module's web page (http://<ip>/#/protocol) and change Current Protocol from ASCII to Modbus TCP. The factory IP is 192.168.127.254 unless DHCP assigned one.

Where is the official Brainboxes ED-516 Ethernet digital I/O (Modbus TCP) Modbus documentation?

The source is Using Modbus TCP with Brainboxes products, published free by Brainboxes at https://www.brainboxes.com/files/catalog/product/ED/ED-516/documents/Brainboxes%20Modbus%20TCP%20Manual.pdf.

More Brainboxes Modbus register maps