- ED-516 Ethernet digital I/O (Modbus TCP)
Sensor / remote I/O module · Modbus register map
Brainboxes ED-516 Ethernet digital I/O (Modbus TCP) Modbus register map
Updated 17 November 2026
The ED-516 is a Brainboxes Ethernet I/O module with 16 digital inputs with pulse counters. It ships speaking the Brainboxes ASCII protocol; once its web page is switched to Modbus TCP, the I/O is exposed as coils, discrete inputs and registers. This map lists every object in the manufacturer's product table.
This page lists 81 Modbus registers for the Brainboxes ED-516 Ethernet digital I/O (Modbus TCP) — 16 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Brainboxes’s own free documentation (linked below) and checked against it.
- Manufacturer
- Brainboxes
- Model
- ED-516 Ethernet digital I/O (Modbus TCP)
- Equipment type
- Sensor / remote I/O module
- Registers
- 81 (16 writable)
- Transport
- Modbus TCP
- Default unit ID
- Not stated
- TCP port
- 502
- Documented addressing
- hexadecimal, 0-based
- Also known as
- ED-516, ED516
- Source document
- Using Modbus TCP with Brainboxes products
Integration notes: Brainboxes ED-516 Ethernet digital I/O (Modbus TCP)
Switch the module to Modbus TCP on its web page, then read the packed input or output register for a whole-module snapshot, or use the per-channel coils and discrete inputs. All values are single 16-bit registers or bits, so there is no word-order question.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 32 | Digital inputs (packed) | UINT16 | All digital input states in one read | Read |
| DI 0 | Digital input 0 | BIT | First digital input | Read |
| IR 0 | DI 0 counter | UINT16 | First input's pulse counter | Read |
| CO 512 | Clear DI 0 counter | BIT | Clear the first counter | Write |
Enable Modbus control & writes
Open the module's web page (http://<ip>/#/protocol) and change Current Protocol from ASCII to Modbus TCP. The factory IP is 192.168.127.254 unless DHCP assigned one.
Byte order & addressing
- Inputs appear three ways (coils from 0x0020, discrete inputs from 0x0000, packed input register 0x0020); they carry the same states.
- Counters can be read as input registers or holding registers at the same addresses.
Network setup
- TCP port defaults to 502, idle timeout 0 (never drop), up to 8 simultaneous connections; all set on the protocol web page.
Watch out for
- The module answers ASCII, not Modbus, until the protocol is changed on the web page.
- An idle timeout other than 0 closes quiet connections; poll faster than the timeout or leave it at 0.
Brainboxes ED-516 Ethernet digital I/O (Modbus TCP) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 32doc 00033 | Digital input 0 (coil view) | Input state, readable as a coil with FC1. | BIT | Read | ||||
| CO | 33doc 00034 | Digital input 1 (coil view) | Input state, readable as a coil with FC1. | BIT | Read | ||||
| CO | 34doc 00035 | Digital input 2 (coil view) | Input state, readable as a coil with FC1. | BIT | Read | ||||
| CO | 35doc 00036 | Digital input 3 (coil view) | Input state, readable as a coil with FC1. | BIT | Read | ||||
| CO | 36doc 00037 | Digital input 4 (coil view) | Input state, readable as a coil with FC1. | BIT | Read | ||||
| CO | 37doc 00038 | Digital input 5 (coil view) | Input state, readable as a coil with FC1. | BIT | Read | ||||
| CO | 38doc 00039 | Digital input 6 (coil view) | Input state, readable as a coil with FC1. | BIT | Read | ||||
| CO | 39doc 00040 | Digital input 7 (coil view) | Input state, readable as a coil with FC1. | BIT | Read | ||||
| CO | 40doc 00041 | Digital input 8 (coil view) | Input state, readable as a coil with FC1. | BIT | Read | ||||
| CO | 41doc 00042 | Digital input 9 (coil view) | Input state, readable as a coil with FC1. | BIT | Read | ||||
| CO | 42doc 00043 | Digital input 10 (coil view) | Input state, readable as a coil with FC1. | BIT | Read | ||||
| CO | 43doc 00044 | Digital input 11 (coil view) | Input state, readable as a coil with FC1. | BIT | Read | ||||
| CO | 44doc 00045 | Digital input 12 (coil view) | Input state, readable as a coil with FC1. | BIT | Read | ||||
| CO | 45doc 00046 | Digital input 13 (coil view) | Input state, readable as a coil with FC1. | BIT | Read | ||||
| CO | 46doc 00047 | Digital input 14 (coil view) | Input state, readable as a coil with FC1. | BIT | Read | ||||
| CO | 47doc 00048 | Digital input 15 (coil view) | Input state, readable as a coil with FC1. | BIT | Read | ||||
| CO | 512doc 00513 | Clear DI 0 counter | Write to clear this input's counter. | BIT | Write | ||||
| CO | 513doc 00514 | Clear DI 1 counter | Write to clear this input's counter. | BIT | Write | ||||
| CO | 514doc 00515 | Clear DI 2 counter | Write to clear this input's counter. | BIT | Write | ||||
| CO | 515doc 00516 | Clear DI 3 counter | Write to clear this input's counter. | BIT | Write | ||||
| CO | 516doc 00517 | Clear DI 4 counter | Write to clear this input's counter. | BIT | Write | ||||
| CO | 517doc 00518 | Clear DI 5 counter | Write to clear this input's counter. | BIT | Write | ||||
| CO | 518doc 00519 | Clear DI 6 counter | Write to clear this input's counter. | BIT | Write | ||||
| CO | 519doc 00520 | Clear DI 7 counter | Write to clear this input's counter. | BIT | Write | ||||
| CO | 520doc 00521 | Clear DI 8 counter | Write to clear this input's counter. | BIT | Write | ||||
| CO | 521doc 00522 | Clear DI 9 counter | Write to clear this input's counter. | BIT | Write | ||||
| CO | 522doc 00523 | Clear DI 10 counter | Write to clear this input's counter. | BIT | Write | ||||
| CO | 523doc 00524 | Clear DI 11 counter | Write to clear this input's counter. | BIT | Write | ||||
| CO | 524doc 00525 | Clear DI 12 counter | Write to clear this input's counter. | BIT | Write | ||||
| CO | 525doc 00526 | Clear DI 13 counter | Write to clear this input's counter. | BIT | Write | ||||
| CO | 526doc 00527 | Clear DI 14 counter | Write to clear this input's counter. | BIT | Write | ||||
| CO | 527doc 00528 | Clear DI 15 counter | Write to clear this input's counter. | BIT | Write | ||||
| DI | 0doc 10001 | Digital input 0 | Input state via FC2. | BIT | Read | ||||
| DI | 1doc 10002 | Digital input 1 | Input state via FC2. | BIT | Read | ||||
| DI | 2doc 10003 | Digital input 2 | Input state via FC2. | BIT | Read | ||||
| DI | 3doc 10004 | Digital input 3 | Input state via FC2. | BIT | Read | ||||
| DI | 4doc 10005 | Digital input 4 | Input state via FC2. | BIT | Read | ||||
| DI | 5doc 10006 | Digital input 5 | Input state via FC2. | BIT | Read | ||||
| DI | 6doc 10007 | Digital input 6 | Input state via FC2. | BIT | Read | ||||
| DI | 7doc 10008 | Digital input 7 | Input state via FC2. | BIT | Read | ||||
| DI | 8doc 10009 | Digital input 8 | Input state via FC2. | BIT | Read | ||||
| DI | 9doc 10010 | Digital input 9 | Input state via FC2. | BIT | Read | ||||
| DI | 10doc 10011 | Digital input 10 | Input state via FC2. | BIT | Read | ||||
| DI | 11doc 10012 | Digital input 11 | Input state via FC2. | BIT | Read | ||||
| DI | 12doc 10013 | Digital input 12 | Input state via FC2. | BIT | Read | ||||
| DI | 13doc 10014 | Digital input 13 | Input state via FC2. | BIT | Read | ||||
| DI | 14doc 10015 | Digital input 14 | Input state via FC2. | BIT | Read | ||||
| DI | 15doc 10016 | Digital input 15 | Input state via FC2. | BIT | Read | ||||
| IR | 0doc 30001 | DI 0 counter | Pulse counter for input 0. | UINT16 | Read | ||||
| IR | 1doc 30002 | DI 1 counter | Pulse counter for input 1. | UINT16 | Read | ||||
| IR | 2doc 30003 | DI 2 counter | Pulse counter for input 2. | UINT16 | Read | ||||
| IR | 3doc 30004 | DI 3 counter | Pulse counter for input 3. | UINT16 | Read | ||||
| IR | 4doc 30005 | DI 4 counter | Pulse counter for input 4. | UINT16 | Read | ||||
| IR | 5doc 30006 | DI 5 counter | Pulse counter for input 5. | UINT16 | Read | ||||
| IR | 6doc 30007 | DI 6 counter | Pulse counter for input 6. | UINT16 | Read | ||||
| IR | 7doc 30008 | DI 7 counter | Pulse counter for input 7. | UINT16 | Read | ||||
| IR | 8doc 30009 | DI 8 counter | Pulse counter for input 8. | UINT16 | Read | ||||
| IR | 9doc 30010 | DI 9 counter | Pulse counter for input 9. | UINT16 | Read | ||||
| IR | 10doc 30011 | DI 10 counter | Pulse counter for input 10. | UINT16 | Read | ||||
| IR | 11doc 30012 | DI 11 counter | Pulse counter for input 11. | UINT16 | Read | ||||
| IR | 12doc 30013 | DI 12 counter | Pulse counter for input 12. | UINT16 | Read | ||||
| IR | 13doc 30014 | DI 13 counter | Pulse counter for input 13. | UINT16 | Read | ||||
| IR | 14doc 30015 | DI 14 counter | Pulse counter for input 14. | UINT16 | Read | ||||
| IR | 15doc 30016 | DI 15 counter | Pulse counter for input 15. | UINT16 | Read | ||||
| IR | 32doc 30033 | Digital inputs (packed) | All inputs in one register; packed bits, layout not given in the manual. | UINT16 | Read | ||||
| HR | 0doc 40001 | DI 0 counter (holding view) | Same counter read with FC3. | UINT16 | Read | ||||
| HR | 1doc 40002 | DI 1 counter (holding view) | Same counter read with FC3. | UINT16 | Read | ||||
| HR | 2doc 40003 | DI 2 counter (holding view) | Same counter read with FC3. | UINT16 | Read | ||||
| HR | 3doc 40004 | DI 3 counter (holding view) | Same counter read with FC3. | UINT16 | Read | ||||
| HR | 4doc 40005 | DI 4 counter (holding view) | Same counter read with FC3. | UINT16 | Read | ||||
| HR | 5doc 40006 | DI 5 counter (holding view) | Same counter read with FC3. | UINT16 | Read | ||||
| HR | 6doc 40007 | DI 6 counter (holding view) | Same counter read with FC3. | UINT16 | Read | ||||
| HR | 7doc 40008 | DI 7 counter (holding view) | Same counter read with FC3. | UINT16 | Read | ||||
| HR | 8doc 40009 | DI 8 counter (holding view) | Same counter read with FC3. | UINT16 | Read | ||||
| HR | 9doc 40010 | DI 9 counter (holding view) | Same counter read with FC3. | UINT16 | Read | ||||
| HR | 10doc 40011 | DI 10 counter (holding view) | Same counter read with FC3. | UINT16 | Read | ||||
| HR | 11doc 40012 | DI 11 counter (holding view) | Same counter read with FC3. | UINT16 | Read | ||||
| HR | 12doc 40013 | DI 12 counter (holding view) | Same counter read with FC3. | UINT16 | Read | ||||
| HR | 13doc 40014 | DI 13 counter (holding view) | Same counter read with FC3. | UINT16 | Read | ||||
| HR | 14doc 40015 | DI 14 counter (holding view) | Same counter read with FC3. | UINT16 | Read | ||||
| HR | 15doc 40016 | DI 15 counter (holding view) | Same counter read with FC3. | UINT16 | Read |
Notes on this map
- The product table gives every object twice: as a logical (wire) address in hex and as a 984-style address (logical + 1 with a 0/1/3/4 prefix). The two columns agree, so the hex logical address is used here.
- Channel numbers in register names count from 0, matching the order of the logical addresses (channel 0 = first address of each block).
- The manual does not state the counter width; each counter occupies one 16-bit register in the table, so it is listed as UINT16.
- Brainboxes' own Node-RED guide (docs.brainboxes.com, 'Using Modbus TCP with Node-RED', ED-588) writes coil address 0 for output 0 and reads input registers from address 0 for inputs 0-7, which matches the product table. The manual's section 10 worked example (ED-527 only) instead puts the outputs at 0x0001-0x0010; that example also labels a 0xFF00 write as 'low', so it is treated as an error here.
- The same objects can also be reached with IEC 61131 %M/%MW addresses in some PLCs; those are listed in the manual and not repeated here.
- The manual does not say which bit of a packed register belongs to which channel, so no bit list is given; check against the per-channel objects on site.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Brainboxes ED-516 Ethernet digital I/O (Modbus TCP)
What Modbus registers does the Brainboxes ED-516 Ethernet digital I/O (Modbus TCP) have?
This map lists 81 registers: 32 coils, 16 discrete inputs, 17 input registers, 16 holding registers. 16 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Brainboxes ED-516 Ethernet digital I/O (Modbus TCP) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The table prints logical (on-the-wire) addresses in hex next to 984-style numbers. Use the hex value directly: input register 0x0020 is requested at address 32 and corresponds to 30033.
What are the minimum Modbus registers to integrate the Brainboxes ED-516 Ethernet digital I/O (Modbus TCP)?
Start with IR 32 Digital inputs (packed) (All digital input states in one read); DI 0 Digital input 0 (First digital input); IR 0 DI 0 counter (First input's pulse counter); CO 512 Clear DI 0 counter (Clear the first counter).
How do I enable Modbus control of the Brainboxes ED-516 Ethernet digital I/O (Modbus TCP)?
Open the module's web page (http://<ip>/#/protocol) and change Current Protocol from ASCII to Modbus TCP. The factory IP is 192.168.127.254 unless DHCP assigned one.
Where is the official Brainboxes ED-516 Ethernet digital I/O (Modbus TCP) Modbus documentation?
The source is Using Modbus TCP with Brainboxes products, published free by Brainboxes at https://www.brainboxes.com/files/catalog/product/ED/ED-516/documents/Brainboxes%20Modbus%20TCP%20Manual.pdf.
More Brainboxes Modbus register maps
- Sensor / remote I/O module
Brainboxes ED-538 Ethernet digital I/O (Modbus TCP)
Brainboxes ED-538 Ethernet I/O module with the protocol set to Modbus TCP.
Also known as: ED-538, ED538 - Sensor / remote I/O module
Brainboxes ED-588 Ethernet digital I/O (Modbus TCP)
Brainboxes ED-588 Ethernet I/O module with the protocol set to Modbus TCP.
Also known as: ED-588, ED588
Other remote i/o modules register maps
- Sensor (remote I/O module)
Moxa ioLogik R1210 RS-485 remote I/O
ioLogik R1210 per the ioLogik R1200 Series User's Manual, Edition 3.4 (April 2021).
Also known as: ioLogik R1210, R1210, R1210-T - Sensor (remote I/O module, analog outputs)
Seneca R-4AO-8DIDO Ethernet I/O (4 analog outputs, 8 digital I/O)
R-4AO-8DIDO in the Series R I/O manual MI-00604-29-EN.
Also known as: R4AO8DIDO, R-4AO-8DIDO, Seneca R series 4AO - Sensor (digital input / counter I/O module)
Seneca Z-D-IN 5-channel digital input / counter module (Modbus RTU)
Z-D-IN DIN-rail module, user manual MI00252-3-EN (revision 3, 13/01/2022).
Also known as: ZDIN, Z D IN, Seneca Z-D-IN - Sensor (remote I/O module)
Unipi Technology Unipi Extension xS53 analog input module
Unipi Extension xS53 RS-485 module per the Unipi Extension xS53 Modbus map v2.0.
Also known as: Unipi Extension xS53, xS53 - Sensor (thermistor input module)
ICP DAS M-7005 8-channel thermistor input module (Modbus RTU)
M-7005 in Modbus RTU mode, per I-7005/M-7005 User Manual Rev B2.4 (7MH-018-B24). The I-7005 uses the DCON protocol and is not covered.
Also known as: M-7005, M7005, I-7005/M-7005 - Sensor (remote I/O module)
Moxa ioLogik R1240 RS-485 remote I/O
ioLogik R1240 per the ioLogik R1200 Series User's Manual, Edition 3.4 (April 2021).
Also known as: ioLogik R1240, R1240, R1240-T
All remote i/o modules Modbus register maps →
Source: Using Modbus TCP with Brainboxes products. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.