- Home
- Modbus register maps
- Moxa
- ioLogik R1240 RS-485 remote I/O
Sensor (remote I/O module) · Modbus register map
Moxa ioLogik R1240 RS-485 remote I/O Modbus register map
Updated 17 November 2026
The ioLogik R1240 is a Moxa RS-485 Modbus RTU remote I/O module with 8 analog inputs (0-10 V, 0-20 mA, 4-20 mA). It supports a repeater or dual RS-485 mode and a Modbus host-connection watchdog. This map covers the shared system registers (model, watchdog, serial settings) and the analog input raw values, min/max, status and range.
This page lists 72 Modbus registers for the Moxa ioLogik R1240 RS-485 remote I/O — 35 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Moxa’s own free documentation (linked below) and checked against it.
- Manufacturer
- Moxa
- Model
- ioLogik R1240 RS-485 remote I/O
- Equipment type
- Sensor (remote I/O module)
- Registers
- 72 (35 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 9600 baud, 8N1
- Documented addressing
- hexadecimal, 0-based
- Also known as
- ioLogik R1240, R1240, R1240-T
Integration notes: Moxa ioLogik R1240 RS-485 remote I/O
Read the raw analog values and channel status with function 04 and set each channel range with function 03/06. The host-connection watchdog (0x7564, timeout 0x7565) is shared by the whole series.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 30000 | SYS_modelID | UINT16 | Model ID check | Read |
| HR 30052 | SYS_modbusWatchdogFuntion | UINT16 | Enable communication watchdog | Read/write |
| HR 30053 | SYS_modbusWatchdogTimeout | UINT16 | Watchdog timeout | Read/write |
| IR 704 | AI-00_rawValue | UINT16 | First analog input raw value | Read |
| IR 992 | AI-00_status | UINT16 | First analog input status | Read |
Enable Modbus control & writes
Set the device ID (1-99) on the two rotary dials. Put the Initial/Run switch on Initial to configure the unit at 9600 baud, no parity, 8 data bits, 1 stop bit (with ioSearch or the SYS_port* registers), then switch back to Run.
Communication loss & watchdog
SYS_modbusWatchdogFuntion (0x7564) enables the host-connection watchdog, SYS_modbusWatchdogTimeout (0x7565) sets the timeout in seconds (factory default 10 s), SYS_modbusWatchdogStatus (0x7566) shows a timeout. It is disabled by default; safe-status settings only act when it is enabled.
Byte order & addressing
- System registers sit at 0x7530 and up (six-digit references 330001/430002).
- Write 404 to SYS_restartDevice or SYS_loadFactoryDefault to trigger them.
Network setup
- Device ID 1-99 on the rotary dials (x1 and x10).
- The Dual/Rep switch selects two separate RS-485 ports or repeater mode; SYS_rs485PortMode reports which is active.
- Baud rate codes: 1=1200 ... 4=9600, 5=19200 ... 9=921600.
Watch out for
- Factory defaults (reset button held 5 s, ioSearch, or SYS_loadFactoryDefault) return the serial settings to 9600 n 8 1 and disable the watchdog.
Moxa ioLogik R1240 RS-485 remote I/O Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 704doc 0x02C0 | AI-00_resetMinValue | BIT | Read/write | 1 = reset min. value | ||||
| CO | 705doc 0x02C1 | AI-01_resetMinValue | BIT | Read/write | 1 = reset min. value | ||||
| CO | 706doc 0x02C2 | AI-02_resetMinValue | BIT | Read/write | 1 = reset min. value | ||||
| CO | 707doc 0x02C3 | AI-03_resetMinValue | BIT | Read/write | 1 = reset min. value | ||||
| CO | 708doc 0x02C4 | AI-04_resetMinValue | BIT | Read/write | 1 = reset min. value | ||||
| CO | 709doc 0x02C5 | AI-05_resetMinValue | BIT | Read/write | 1 = reset min. value | ||||
| CO | 710doc 0x02C6 | AI-06_resetMinValue | BIT | Read/write | 1 = reset min. value | ||||
| CO | 711doc 0x02C7 | AI-07_resetMinValue | BIT | Read/write | 1 = reset min. value | ||||
| CO | 736doc 0x02E0 | AI-00_resetMaxValue | BIT | Read/write | 1 = reset max. value | ||||
| CO | 737doc 0x02E1 | AI-01_resetMaxValue | BIT | Read/write | 1 = reset max. value | ||||
| CO | 738doc 0x02E2 | AI-02_resetMaxValue | BIT | Read/write | 1 = reset max. value | ||||
| CO | 739doc 0x02E3 | AI-03_resetMaxValue | BIT | Read/write | 1 = reset max. value | ||||
| CO | 740doc 0x02E4 | AI-04_resetMaxValue | BIT | Read/write | 1 = reset max. value | ||||
| CO | 741doc 0x02E5 | AI-05_resetMaxValue | BIT | Read/write | 1 = reset max. value | ||||
| CO | 742doc 0x02E6 | AI-06_resetMaxValue | BIT | Read/write | 1 = reset max. value | ||||
| CO | 743doc 0x02E7 | AI-07_resetMaxValue | BIT | Read/write | 1 = reset max. value | ||||
| IR | 704doc 0x02C0 | AI-00_rawValue | UINT16 | Read | |||||
| IR | 705doc 0x02C1 | AI-01_rawValue | UINT16 | Read | |||||
| IR | 706doc 0x02C2 | AI-02_rawValue | UINT16 | Read | |||||
| IR | 707doc 0x02C3 | AI-03_rawValue | UINT16 | Read | |||||
| IR | 708doc 0x02C4 | AI-04_rawValue | UINT16 | Read | |||||
| IR | 709doc 0x02C5 | AI-05_rawValue | UINT16 | Read | |||||
| IR | 710doc 0x02C6 | AI-06_rawValue | UINT16 | Read | |||||
| IR | 711doc 0x02C7 | AI-07_rawValue | UINT16 | Read | |||||
| IR | 736doc 0x02E0 | AI-00_rawValueMin | UINT16 | Read | |||||
| IR | 737doc 0x02E1 | AI-01_rawValueMin | UINT16 | Read | |||||
| IR | 738doc 0x02E2 | AI-02_rawValueMin | UINT16 | Read | |||||
| IR | 739doc 0x02E3 | AI-03_rawValueMin | UINT16 | Read | |||||
| IR | 740doc 0x02E4 | AI-04_rawValueMin | UINT16 | Read | |||||
| IR | 741doc 0x02E5 | AI-05_rawValueMin | UINT16 | Read | |||||
| IR | 742doc 0x02E6 | AI-06_rawValueMin | UINT16 | Read | |||||
| IR | 743doc 0x02E7 | AI-07_rawValueMin | UINT16 | Read | |||||
| IR | 768doc 0x0300 | AI-00_rawValueMax | UINT16 | Read | |||||
| IR | 769doc 0x0301 | AI-01_rawValueMax | UINT16 | Read | |||||
| IR | 770doc 0x0302 | AI-02_rawValueMax | UINT16 | Read | |||||
| IR | 771doc 0x0303 | AI-03_rawValueMax | UINT16 | Read | |||||
| IR | 772doc 0x0304 | AI-04_rawValueMax | UINT16 | Read | |||||
| IR | 773doc 0x0305 | AI-05_rawValueMax | UINT16 | Read | |||||
| IR | 774doc 0x0306 | AI-06_rawValueMax | UINT16 | Read | |||||
| IR | 775doc 0x0307 | AI-07_rawValueMax | UINT16 | Read | |||||
| IR | 992doc 0x03E0 | AI-00_status | UINT16 | Read | 0 = normal; 1 = burnout; 2 = over range; 3 = under range | ||||
| IR | 993doc 0x03E1 | AI-01_status | UINT16 | Read | 0 = normal; 1 = burnout; 2 = over range; 3 = under range | ||||
| IR | 994doc 0x03E2 | AI-02_status | UINT16 | Read | 0 = normal; 1 = burnout; 2 = over range; 3 = under range | ||||
| IR | 995doc 0x03E3 | AI-03_status | UINT16 | Read | 0 = normal; 1 = burnout; 2 = over range; 3 = under range | ||||
| IR | 996doc 0x03E4 | AI-04_status | UINT16 | Read | 0 = normal; 1 = burnout; 2 = over range; 3 = under range | ||||
| IR | 997doc 0x03E5 | AI-05_status | UINT16 | Read | 0 = normal; 1 = burnout; 2 = over range; 3 = under range | ||||
| IR | 998doc 0x03E6 | AI-06_status | UINT16 | Read | 0 = normal; 1 = burnout; 2 = over range; 3 = under range | ||||
| IR | 999doc 0x03E7 | AI-07_status | UINT16 | Read | 0 = normal; 1 = burnout; 2 = over range; 3 = under range | ||||
| IR | 30000doc 0x7530 | SYS_modelID | UINT16 | Read | |||||
| IR | 30025doc 0x7549 | SYS_vendorID | UINT16 | Read | |||||
| IR | 30026doc 0x754A | SYS_unitID | UINT16 | Read | |||||
| IR | 30037doc 0x7555 | SYS_productName | STRING[20] | Read | |||||
| IR | 30058doc 0x756A | SYS_rs485PortMode | UINT16 | Read | 0 = initial-repeater; 1 = initial-dual RS- 485; 2 = run-repeater; 3 = run-dual RS-485 | ||||
| HR | 704doc 0x02C0 | AI-00_mode | UINT16 | Read/write | 0 = 0-10 V; 1 = 0-20 mA; 2 = 4-20 mA burnout; 3 = 4-20 mA | ||||
| HR | 705doc 0x02C1 | AI-01_mode | UINT16 | Read/write | 0 = 0-10 V; 1 = 0-20 mA; 2 = 4-20 mA burnout; 3 = 4-20 mA | ||||
| HR | 706doc 0x02C2 | AI-02_mode | UINT16 | Read/write | 0 = 0-10 V; 1 = 0-20 mA; 2 = 4-20 mA burnout; 3 = 4-20 mA | ||||
| HR | 707doc 0x02C3 | AI-03_mode | UINT16 | Read/write | 0 = 0-10 V; 1 = 0-20 mA; 2 = 4-20 mA burnout; 3 = 4-20 mA | ||||
| HR | 708doc 0x02C4 | AI-04_mode | UINT16 | Read/write | 0 = 0-10 V; 1 = 0-20 mA; 2 = 4-20 mA burnout; 3 = 4-20 mA | ||||
| HR | 709doc 0x02C5 | AI-05_mode | UINT16 | Read/write | 0 = 0-10 V; 1 = 0-20 mA; 2 = 4-20 mA burnout; 3 = 4-20 mA | ||||
| HR | 710doc 0x02C6 | AI-06_mode | UINT16 | Read/write | 0 = 0-10 V; 1 = 0-20 mA; 2 = 4-20 mA burnout; 3 = 4-20 mA | ||||
| HR | 711doc 0x02C7 | AI-07_mode | UINT16 | Read/write | 0 = 0-10 V; 1 = 0-20 mA; 2 = 4-20 mA burnout; 3 = 4-20 mA | ||||
| HR | 30052doc 0x7564 | SYS_modbusWatchdogFuntion | UINT16 | Read/write | 0 = Disable; 1 = Enable | ||||
| HR | 30053doc 0x7565 | SYS_modbusWatchdogTimeout | UINT16 | s | Read/write | ||||
| HR | 30054doc 0x7566 | SYS_modbusWatchdogStatus | UINT16 | Read/write | 0 = Normal; 1 = Timeout | ||||
| HR | 30056doc 0x7568 | SYS_restartDevice | Write 404 to trigger. | UINT16 | Read/write | ||||
| HR | 30057doc 0x7569 | SYS_loadFactoryDefault | Write 404 to trigger. | UINT16 | Read/write | ||||
| HR | 30060doc 0x756C | SYS_port0Baudrate | UINT16 | Read/write | 1 = 1200; 2 = 2400; 3 = 4800; 4 = 9600; 5 = 19200; 6 = 38400; 7 = 57600; 8 = 115200; 9 = 921600 | ||||
| HR | 30061doc 0x756D | SYS_port1Baudrate | UINT16 | Read/write | 1 = 1200; 2 = 2400; 3 = 4800; 4 = 9600; 5 = 19200; 6 = 38400; 7 = 57600; 8 = 115200; 9 = 921600 | ||||
| HR | 30064doc 0x7570 | SYS_port0StopBit | UINT16 | Read/write | 0 = 1; 1 = 2 | ||||
| HR | 30065doc 0x7571 | SYS_port1StopBit | UINT16 | Read/write | 0 = 1; 1 = 2 | ||||
| HR | 30066doc 0x7572 | SYS_port0Parity | UINT16 | Read/write | 0 = None; 1 = Even; 2 = Odd | ||||
| HR | 30067doc 0x7573 | SYS_port1Parity | UINT16 | Read/write | 0 = None; 1 = Even; 2 = Odd |
Notes on this map
- Moxa does not appear to offer this manual on a public URL found in this pass; the link is an unaltered copy of the Moxa user's manual on a reseller's file host.
- Each table row gives the hex wire address, the 1-based decimal reference (e.g. 0x0000 = 40001; system registers use six digits, 0x7530 = 330001), access, size and function code.
- Left out: system strings and multi-word values whose format is not described (firmware version and release date, serial number, server name/location, password, vendor name).
- Left out: the 32-bit engineering values (current, min, max) and burnout values at 0x0320-0x03AF and 0x02E0-0x02EF (holding), because the table does not say whether they are integers or floats or how they are scaled. Raw values are listed with no scaling.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Moxa ioLogik R1240 RS-485 remote I/O
What Modbus registers does the Moxa ioLogik R1240 RS-485 remote I/O have?
This map lists 72 registers: 16 coils, 37 input registers, 19 holding registers. 35 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Moxa ioLogik R1240 RS-485 remote I/O Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each row prints the hex protocol address and a 1-based reference number (0x0000 = 00001/10001/30001/40001). The hex address is sent on the wire; the table (coil, discrete input, input or holding) is set by the function code column.
What are the minimum Modbus registers to integrate the Moxa ioLogik R1240 RS-485 remote I/O?
Start with IR 30000 SYS_modelID (Model ID check); HR 30052 SYS_modbusWatchdogFuntion (Enable communication watchdog); HR 30053 SYS_modbusWatchdogTimeout (Watchdog timeout); IR 704 AI-00_rawValue (First analog input raw value); IR 992 AI-00_status (First analog input status).
How do I enable Modbus control of the Moxa ioLogik R1240 RS-485 remote I/O?
Set the device ID (1-99) on the two rotary dials. Put the Initial/Run switch on Initial to configure the unit at 9600 baud, no parity, 8 data bits, 1 stop bit (with ioSearch or the SYS_port* registers), then switch back to Run.
What happens when the Moxa ioLogik R1240 RS-485 remote I/O loses Modbus communication?
SYS_modbusWatchdogFuntion (0x7564) enables the host-connection watchdog, SYS_modbusWatchdogTimeout (0x7565) sets the timeout in seconds (factory default 10 s), SYS_modbusWatchdogStatus (0x7566) shows a timeout. It is disabled by default; safe-status settings only act when it is enabled.
Where is the official Moxa ioLogik R1240 RS-485 remote I/O Modbus documentation?
The source is ioLogik R1200 Series User's Manual (Edition 3.4), revision 2021-04. Moxa doesn't publish it on its own website, so this map was re-typed from a free copy at https://cdn11.bigcommerce.com/s-hltjsp5jm3/content/pdfs/moxa-iologik-r1200-series-manual.pdf. It may be an older revision, so check it against the live unit.
More Moxa Modbus register maps
- Sensor (remote I/O module)
Moxa ioLogik R1210 RS-485 remote I/O
ioLogik R1210 per the ioLogik R1200 Series User's Manual, Edition 3.4 (April 2021).
Also known as: ioLogik R1210, R1210, R1210-T - Sensor (remote I/O module)
Moxa ioLogik R1212 RS-485 remote I/O
ioLogik R1212 per the ioLogik R1200 Series User's Manual, Edition 3.4 (April 2021).
Also known as: ioLogik R1212, R1212, R1212-T - Sensor (remote I/O module)
Moxa ioLogik R1214 RS-485 remote I/O
ioLogik R1214 per the ioLogik R1200 Series User's Manual, Edition 3.4 (April 2021).
Also known as: ioLogik R1214, R1214, R1214-T - Sensor (remote I/O module)
Moxa ioLogik R1241 RS-485 remote I/O
ioLogik R1241 per the ioLogik R1200 Series User's Manual, Edition 3.4 (April 2021).
Also known as: ioLogik R1241, R1241, R1241-T
Other remote i/o modules register maps
- Sensor (I/O module, 4 analog inputs)
Seneca Z-4AI 4-channel analog input module
Seneca Z-4AI DIN-rail module with 4 voltage/current inputs and RS-485 Modbus RTU, per user manual MI002572-E.
Also known as: Z-4AI - Sensor (thermocouple input module)
Teracom TST320 2-channel thermocouple module with Modbus RTU
TST320 per the Teracom TST320 user manual Revision R1.6.
Also known as: TST320 - Sensor (Ethernet analog input module)
Acromag BusWorks XT1211-000 / XT1221-000 8-channel differential analog input (Modbus TCP)
BusWorks XT1211-000 (current) and XT1221-000 (voltage) per user's manual 8500951K.
Also known as: XT1211-000, XT1221-000, XT1211, XT1221, BusWorks XT1211, BusWorks XT1221 - Sensor / remote digital I/O module
ICP DAS tM series digital I/O modules tM-P4C4, tM-C8, tM-P8 (Modbus RTU)
tM-P4C4 (4 DI + 4 DO), tM-C8 (8 DO) and tM-P8 (8 DI) with the Modbus RTU protocol selected, per the tM Series DIO User Manual Rev A1.4.
Also known as: tM-P4C4, tM-C8, tM-P8 - Sensor (remote I/O module, digital inputs/outputs)
Seneca R-32DIDO Ethernet I/O (32 digital inputs/outputs)
R-32DIDO (R-32DIDO-1 / R-32DIDO-2) in the Series R I/O manual MI-00604-29-EN.
Also known as: R32DIDO, R-32DIDO-1, R-32DIDO-2, Seneca R series 32DIDO - Sensor (I/O module, 8 analog inputs)
Seneca Z-8AI 8-channel analog input module
Seneca Z-8AI DIN-rail module with 8 voltage/current inputs and RS-485 Modbus RTU, per user manual MI00259-3-EN.
Also known as: Z-8AI
All remote i/o modules Modbus register maps →
Source: ioLogik R1200 Series User's Manual · Edition 3.4 · rev. 2021-04 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.