Easy Modbus
  1. Home
  2. Modbus register maps
  3. RKC Instrument
  4. SRX module type controller, TIO temperature control module (Modbus RTU)

Sensor (modular temperature controller) · Modbus register map

RKC Instrument SRX module type controller, TIO temperature control module (Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

The SRX is a DIN-rail modular controller: each TIO module runs two PID loops, and extension, DI and DO modules share the bus of a basic TIO module. With DIP switch 6 set to Modbus, each TIO module answers Modbus RTU on RS-485 with channel 1 data at 0000H and channel 2 data at 1000H. This map covers measured values, events, setpoints, PID, manual output, program run control and the key input setup items.

This page lists 99 Modbus registers for the RKC Instrument SRX module type controller, TIO temperature control module (Modbus RTU) — 68 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from RKC Instrument’s own free documentation (linked below) and checked against it.

Manufacturer
RKC Instrument
Model
SRX module type controller, TIO temperature control module (Modbus RTU)
Equipment type
Sensor (modular temperature controller)
Registers
99 (68 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8N1
Documented addressing
hexadecimal, 0-based
Also known as
SRX, X-TIO-A, X-TIO-B, SRX TIO module, RKC SRX
Source document
SRX Communication Instruction Manual (Module Type Controller) · IMS01N01-E5 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: RKC Instrument SRX module type controller, TIO temperature control module (Modbus RTU)

Integration in brief

Set DIP switch 6 ON (Modbus) and the rotary address, then read 0000H-0003H for CH1 PV, event state, output and SV monitor (1000H-1003H for CH2). Write the setpoint to 0010H/1010H and start control with 0030H = 1.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0Measured value (PV) (CH1)INT16CH1 measured valueRead
HR 1Comprehensive event state (CH1)BITMAP16CH1 event stateRead
HR 2Manipulated output value (CH1)INT16CH1 outputRead
HR 16Set value (SV) (CH1)INT16CH1 set valueRead/write
HR 48Control RUN/STOP transfer (module)UINT16Control RUN/STOPRead/write
HR 4096Measured value (PV) (CH2)INT16CH2 measured valueRead
HR 4112Set value (SV) (CH2)INT16CH2 set valueRead/write

Enable Modbus control & writes

Modbus is chosen with DIP switch 6 (ON = Modbus; factory setting is RKC protocol). Speed is set by DIP switches 1-2, data/parity by 3-5. Power off before changing switches.

Byte order & addressing

Network setup

Watch out for

RKC Instrument SRX module type controller, TIO temperature control module (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

99 of 99 shown
RKC Instrument SRX module type controller, TIO temperature control module (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 0000Measured value (PV) (CH1)Raw integer; decimal places follow the input range decimal point setting (0873H).INT16Read
HR1doc 0001Comprehensive event state (CH1)BITMAP16Readbit 0 = Burnout; bit 1 = Event 1; bit 2 = Event 2; bit 3 = Heater break alarm; bit 4 = Control loop break alarm (LBA)
HR2doc 0002Manipulated output value (CH1)-5.0 to +105.0 %.INT16× 0.1%Read
HR3doc 0003Set value monitor (CH1)Raw integer; decimal places follow the input range decimal point setting (0873H).INT16Read
HR4doc 0004Error code (module)BITMAP16Readbit 0 = Memory backup error; bit 2 = Internal communication error; bit 3 = Adjustment data error; bit 4 = Input error; bit 5 = Current transformer input error; bit 6 = Temperature compensation error
HR6doc 0006Current transformer input measured value (CH1)0.0 to 30.0 A or 0.0 to 100.0 A depending on CT.INT16× 0.1ARead
HR8doc 0008Burnout state (CH1)UINT16Read0 = OFF; 1 = ON
HR9doc 0009Event 1 state (CH1)UINT16Read0 = OFF; 1 = ON
HR10doc 000AEvent 2 state (CH1)UINT16Read0 = OFF; 1 = ON
HR11doc 000BHeater break alarm (HBA) state (CH1)UINT16Read0 = OFF; 1 = Heater break; 2 = Relay welding
HR12doc 000CControl loop break alarm (LBA) state (CH1)UINT16Read0 = OFF; 1 = ON
HR15doc 000FOperation mode (CH1)UINT16Read/write0 = Unused; 1 = Monitor 1; 2 = Monitor 2; 3 = Control
HR16doc 0010Set value (SV) (CH1)Raw integer; decimal places follow the input range decimal point setting (0873H).INT16Read/write
HR17doc 0011Proportional band (CH1)0 = ON/OFF. Decimals follow the input range (0873H); V/I in % of span.INT16Read/write
HR18doc 0012Integral time (CH1)Raw integer; one or two decimal places in seconds per 085CH.UINT16Read/write
HR19doc 0013Derivative time (CH1)Raw integer; one or two decimal places in seconds per 085CH. 0 = off.UINT16Read/write
HR20doc 0014Control response parameters (CH1)UINT16Read/write0 = Slow; 1 = Medium; 2 = Fast
HR21doc 0015PV bias (CH1)Raw integer; decimal places follow the input range decimal point setting (0873H).INT16Read/write
HR22doc 0016Event 1 set value (CH1)Raw integer; decimal places follow the input range decimal point setting (0873H).INT16Read/write
HR23doc 0017Event 2 set value (CH1)Raw integer; decimal places follow the input range decimal point setting (0873H).INT16Read/write
HR32doc 0020PID/AT transfer (CH1)UINT16Read/write0 = PID control; 1 = Autotuning (AT)
HR33doc 0021Auto/Manual transfer (CH1)UINT16Read/write0 = Auto; 1 = Manual
HR34doc 0022Manual output value (CH1)-5.0 to +105.0 %.INT16× 0.1%Read/write
HR35doc 0023Output limiter (high) (CH1)Output limiter (low) to 105.0 %.INT16× 0.1%Read/write
HR36doc 0024Output limiter (low) (CH1)-5.0 % to output limiter (high).INT16× 0.1%Read/write
HR37doc 0025Proportional cycle time (CH1)0.2 to 50.0 s.UINT16× 0.1sRead/write
HR39doc 0027Digital filter (CH1)0.00 to 10.00 s.UINT16× 0.01sRead/write
HR40doc 0028Heater break alarm (HBA) set value (CH1)0.0 to 30.0 A or 0.0 to 100.0 A.UINT16× 0.1ARead/write
HR48doc 0030Control RUN/STOP transfer (module)UINT16Read/write0 = Control STOP; 1 = Control RUN
HR53doc 0035Manipulated output value at input error (CH1)-5.0 to +105.0 %.INT16× 0.1%Read/write
HR59doc 003BRemote/Local transfer (module)UINT16Read/write0 = Local; 1 = Remote
HR208doc 00D0Program operation mode selection (CH1)UINT16Read/write0 = RESET; 1 = RUN (program control); 2 = FIX (fixed set point control); 3 = MAN (manual control)
HR209doc 00D1Execution pattern (CH1)1 to 16.UINT16Read/write
HR210doc 00D2Execution segment (CH1)1 to 16.UINT16Read
HR212doc 00D4Number of program execution times (CH1)0 to 9999.UINT16Read
HR214doc 00D6Pattern end output state (CH1)UINT16Read0 = OFF; 1 = ON
HR215doc 00D7End state (CH1)UINT16Read0 = OFF; 1 = ON
HR216doc 00D8Wait state (CH1)UINT16Read0 = OFF; 1 = ON
HR217doc 00D9Hold state (CH1)UINT16Read/write0 = OFF; 1 = ON
HR218doc 00DAStep action (CH1)Write 1 to step to the next segment.UINT16Read/write0 = No step action; 1 = Step action execution
HR2137doc 0859Control loop break alarm (LBA) use selection (CH1)UINT16Read/write0 = Unused; 1 = Used
HR2138doc 085AControl loop break alarm (LBA) time (CH1)1 to 7200 s.UINT16sRead/write
HR2140doc 085CIntegral/derivative time decimal point position (CH1)UINT16Read/write0 = Two decimal places; 1 = One decimal place
HR2160doc 0870Input range number (CH1)Input type code 0-21, e.g. 0 = K thermocouple, 12 = Pt100, 15 = 4-20 mA.UINT16Read/write
HR2161doc 0871Input scale high limit (CH1)Raw integer; decimal places follow the input range decimal point setting (0873H).INT16Read/write
HR2162doc 0872Input scale low limit (CH1)Raw integer; decimal places follow the input range decimal point setting (0873H).INT16Read/write
HR2163doc 0873Input range decimal point position (CH1)UINT16Read/write0 = No decimal place; 1 = One decimal place; 2 = Two decimal places; 3 = Three decimal places; 4 = Four decimal places
HR2164doc 0874Temperature unit selection (CH1)UINT16Read/write0 = °C; 1 = °F
HR2165doc 0875Control type selection (CH1)UINT16Read/write0 = Direct action; 1 = Reverse action
HR2170doc 087AEvent 1 type selection (CH1)UINT16Read/write0 = Not provided; 1 = Process high; 2 = Process low; 3 = Deviation high; 4 = Deviation low; 5 = Deviation high/low; 6 = Band
HR2171doc 087BEvent 2 type selection (CH1)UINT16Read/write0 = Not provided; 1 = Process high; 2 = Process low; 3 = Deviation high; 4 = Deviation low; 5 = Deviation high/low; 6 = Band
HR4096doc 1000Measured value (PV) (CH2)Raw integer; decimal places follow the input range decimal point setting (0873H).INT16Read
HR4097doc 1001Comprehensive event state (CH2)BITMAP16Readbit 0 = Burnout; bit 1 = Event 1; bit 2 = Event 2; bit 3 = Heater break alarm; bit 4 = Control loop break alarm (LBA)
HR4098doc 1002Manipulated output value (CH2)-5.0 to +105.0 %.INT16× 0.1%Read
HR4099doc 1003Set value monitor (CH2)Raw integer; decimal places follow the input range decimal point setting (0873H).INT16Read
HR4102doc 1006Current transformer input measured value (CH2)0.0 to 30.0 A or 0.0 to 100.0 A depending on CT.INT16× 0.1ARead
HR4104doc 1008Burnout state (CH2)UINT16Read0 = OFF; 1 = ON
HR4105doc 1009Event 1 state (CH2)UINT16Read0 = OFF; 1 = ON
HR4106doc 100AEvent 2 state (CH2)UINT16Read0 = OFF; 1 = ON
HR4107doc 100BHeater break alarm (HBA) state (CH2)UINT16Read0 = OFF; 1 = Heater break; 2 = Relay welding
HR4108doc 100CControl loop break alarm (LBA) state (CH2)UINT16Read0 = OFF; 1 = ON
HR4111doc 100FOperation mode (CH2)UINT16Read/write0 = Unused; 1 = Monitor 1; 2 = Monitor 2; 3 = Control
HR4112doc 1010Set value (SV) (CH2)Raw integer; decimal places follow the input range decimal point setting (0873H).INT16Read/write
HR4113doc 1011Proportional band (CH2)0 = ON/OFF. Decimals follow the input range (0873H); V/I in % of span.INT16Read/write
HR4114doc 1012Integral time (CH2)Raw integer; one or two decimal places in seconds per 085CH.UINT16Read/write
HR4115doc 1013Derivative time (CH2)Raw integer; one or two decimal places in seconds per 085CH. 0 = off.UINT16Read/write
HR4116doc 1014Control response parameters (CH2)UINT16Read/write0 = Slow; 1 = Medium; 2 = Fast
HR4117doc 1015PV bias (CH2)Raw integer; decimal places follow the input range decimal point setting (0873H).INT16Read/write
HR4118doc 1016Event 1 set value (CH2)Raw integer; decimal places follow the input range decimal point setting (0873H).INT16Read/write
HR4119doc 1017Event 2 set value (CH2)Raw integer; decimal places follow the input range decimal point setting (0873H).INT16Read/write
HR4128doc 1020PID/AT transfer (CH2)UINT16Read/write0 = PID control; 1 = Autotuning (AT)
HR4129doc 1021Auto/Manual transfer (CH2)UINT16Read/write0 = Auto; 1 = Manual
HR4130doc 1022Manual output value (CH2)-5.0 to +105.0 %.INT16× 0.1%Read/write
HR4131doc 1023Output limiter (high) (CH2)Output limiter (low) to 105.0 %.INT16× 0.1%Read/write
HR4132doc 1024Output limiter (low) (CH2)-5.0 % to output limiter (high).INT16× 0.1%Read/write
HR4133doc 1025Proportional cycle time (CH2)0.2 to 50.0 s.UINT16× 0.1sRead/write
HR4135doc 1027Digital filter (CH2)0.00 to 10.00 s.UINT16× 0.01sRead/write
HR4136doc 1028Heater break alarm (HBA) set value (CH2)0.0 to 30.0 A or 0.0 to 100.0 A.UINT16× 0.1ARead/write
HR4149doc 1035Manipulated output value at input error (CH2)-5.0 to +105.0 %.INT16× 0.1%Read/write
HR4304doc 10D0Program operation mode selection (CH2)UINT16Read/write0 = RESET; 1 = RUN (program control); 2 = FIX (fixed set point control); 3 = MAN (manual control)
HR4305doc 10D1Execution pattern (CH2)1 to 16.UINT16Read/write
HR4306doc 10D2Execution segment (CH2)1 to 16.UINT16Read
HR4308doc 10D4Number of program execution times (CH2)0 to 9999.UINT16Read
HR4310doc 10D6Pattern end output state (CH2)UINT16Read0 = OFF; 1 = ON
HR4311doc 10D7End state (CH2)UINT16Read0 = OFF; 1 = ON
HR4312doc 10D8Wait state (CH2)UINT16Read0 = OFF; 1 = ON
HR4313doc 10D9Hold state (CH2)UINT16Read/write0 = OFF; 1 = ON
HR4314doc 10DAStep action (CH2)Write 1 to step to the next segment.UINT16Read/write0 = No step action; 1 = Step action execution
HR6233doc 1859Control loop break alarm (LBA) use selection (CH2)UINT16Read/write0 = Unused; 1 = Used
HR6234doc 185AControl loop break alarm (LBA) time (CH2)1 to 7200 s.UINT16sRead/write
HR6236doc 185CIntegral/derivative time decimal point position (CH2)UINT16Read/write0 = Two decimal places; 1 = One decimal place
HR6256doc 1870Input range number (CH2)Input type code 0-21, e.g. 0 = K thermocouple, 12 = Pt100, 15 = 4-20 mA.UINT16Read/write
HR6257doc 1871Input scale high limit (CH2)Raw integer; decimal places follow the input range decimal point setting (0873H).INT16Read/write
HR6258doc 1872Input scale low limit (CH2)Raw integer; decimal places follow the input range decimal point setting (0873H).INT16Read/write
HR6259doc 1873Input range decimal point position (CH2)UINT16Read/write0 = No decimal place; 1 = One decimal place; 2 = Two decimal places; 3 = Three decimal places; 4 = Four decimal places
HR6260doc 1874Temperature unit selection (CH2)UINT16Read/write0 = °C; 1 = °F
HR6261doc 1875Control type selection (CH2)UINT16Read/write0 = Direct action; 1 = Reverse action
HR6266doc 187AEvent 1 type selection (CH2)UINT16Read/write0 = Not provided; 1 = Process high; 2 = Process low; 3 = Deviation high; 4 = Deviation low; 5 = Deviation high/low; 6 = Band
HR6267doc 187BEvent 2 type selection (CH2)UINT16Read/write0 = Not provided; 1 = Process high; 2 = Process low; 3 = Deviation high; 4 = Deviation low; 5 = Deviation high/low; 6 = Band

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the RKC Instrument SRX module type controller, TIO temperature control module (Modbus RTU)

What Modbus registers does the RKC Instrument SRX module type controller, TIO temperature control module (Modbus RTU) have?

This map lists 99 registers: 99 holding registers. 68 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the RKC Instrument SRX module type controller, TIO temperature control module (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The data map prints each register in hex and decimal; the value is the address sent on the wire. The manual's read example asks for 0000H-0002H and gets back PV, event state and output, so 0000H is a real register (CH1 measured value).

What are the minimum Modbus registers to integrate the RKC Instrument SRX module type controller, TIO temperature control module (Modbus RTU)?

Start with HR 0 Measured value (PV) (CH1) (CH1 measured value); HR 1 Comprehensive event state (CH1) (CH1 event state); HR 2 Manipulated output value (CH1) (CH1 output); HR 16 Set value (SV) (CH1) (CH1 set value); HR 48 Control RUN/STOP transfer (module) (Control RUN/STOP); HR 4096 Measured value (PV) (CH2) (CH2 measured value); HR 4112 Set value (SV) (CH2) (CH2 set value).

How do I enable Modbus control of the RKC Instrument SRX module type controller, TIO temperature control module (Modbus RTU)?

Modbus is chosen with DIP switch 6 (ON = Modbus; factory setting is RKC protocol). Speed is set by DIP switches 1-2, data/parity by 3-5. Power off before changing switches.

Where is the official RKC Instrument SRX module type controller, TIO temperature control module (Modbus RTU) Modbus documentation?

The source is SRX Communication Instruction Manual (Module Type Controller) (IMS01N01-E5). RKC Instrument doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.flw.com/rkc/pdf/ims01n01e5.pdf. It may be an older revision, so check it against the live unit.

More RKC Instrument Modbus register maps

Other temperature & process controllers register maps

All temperature & process controllers Modbus register maps →

Source: SRX Communication Instruction Manual (Module Type Controller) · IMS01N01-E5 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.