Sensor (modular temperature controller) · Modbus register map
RKC Instrument SRX module type controller, TIO temperature control module (Modbus RTU) Modbus register map
Updated 19 November 2026
The SRX is a DIN-rail modular controller: each TIO module runs two PID loops, and extension, DI and DO modules share the bus of a basic TIO module. With DIP switch 6 set to Modbus, each TIO module answers Modbus RTU on RS-485 with channel 1 data at 0000H and channel 2 data at 1000H. This map covers measured values, events, setpoints, PID, manual output, program run control and the key input setup items.
This page lists 99 Modbus registers for the RKC Instrument SRX module type controller, TIO temperature control module (Modbus RTU) — 68 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from RKC Instrument’s own free documentation (linked below) and checked against it.
- Manufacturer
- RKC Instrument
- Model
- SRX module type controller, TIO temperature control module (Modbus RTU)
- Equipment type
- Sensor (modular temperature controller)
- Registers
- 99 (68 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8N1
- Documented addressing
- hexadecimal, 0-based
- Also known as
- SRX, X-TIO-A, X-TIO-B, SRX TIO module, RKC SRX
Integration notes: RKC Instrument SRX module type controller, TIO temperature control module (Modbus RTU)
Set DIP switch 6 ON (Modbus) and the rotary address, then read 0000H-0003H for CH1 PV, event state, output and SV monitor (1000H-1003H for CH2). Write the setpoint to 0010H/1010H and start control with 0030H = 1.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Measured value (PV) (CH1) | INT16 | CH1 measured value | Read |
| HR 1 | Comprehensive event state (CH1) | BITMAP16 | CH1 event state | Read |
| HR 2 | Manipulated output value (CH1) | INT16 | CH1 output | Read |
| HR 16 | Set value (SV) (CH1) | INT16 | CH1 set value | Read/write |
| HR 48 | Control RUN/STOP transfer (module) | UINT16 | Control RUN/STOP | Read/write |
| HR 4096 | Measured value (PV) (CH2) | INT16 | CH2 measured value | Read |
| HR 4112 | Set value (SV) (CH2) | INT16 | CH2 set value | Read/write |
Enable Modbus control & writes
Modbus is chosen with DIP switch 6 (ON = Modbus; factory setting is RKC protocol). Speed is set by DIP switches 1-2, data/parity by 3-5. Power off before changing switches.
Byte order & addressing
- The Modbus slave address is the rotary switch setting plus 1 (switch 00 = slave 1).
- Each module (slave address) carries at most two channels.
- Writes to undefined addresses are not allowed; with a data error part-way through a multi-write, the values before the error still take effect.
Network setup
- Factory DIP settings: 9600 bps, 8 data bits, no parity, 1 stop bit (fixed). Speeds 2400-38400 bps.
- Give the basic TIO module the lowest address when extension modules share its bus; terminate the internal data bus at both ends (DIP 8).
Watch out for
- Wait 30 bit times after a response before the next request; the response takes up to 5 ms (200 ms after initial-setting writes).
- Some items read 0 when the matching function is not fitted or not in use (no error is returned).
RKC Instrument SRX module type controller, TIO temperature control module (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 0000 | Measured value (PV) (CH1) | Raw integer; decimal places follow the input range decimal point setting (0873H). | INT16 | Read | ||||
| HR | 1doc 0001 | Comprehensive event state (CH1) | BITMAP16 | Read | bit 0 = Burnout; bit 1 = Event 1; bit 2 = Event 2; bit 3 = Heater break alarm; bit 4 = Control loop break alarm (LBA) | ||||
| HR | 2doc 0002 | Manipulated output value (CH1) | -5.0 to +105.0 %. | INT16 | × 0.1 | % | Read | ||
| HR | 3doc 0003 | Set value monitor (CH1) | Raw integer; decimal places follow the input range decimal point setting (0873H). | INT16 | Read | ||||
| HR | 4doc 0004 | Error code (module) | BITMAP16 | Read | bit 0 = Memory backup error; bit 2 = Internal communication error; bit 3 = Adjustment data error; bit 4 = Input error; bit 5 = Current transformer input error; bit 6 = Temperature compensation error | ||||
| HR | 6doc 0006 | Current transformer input measured value (CH1) | 0.0 to 30.0 A or 0.0 to 100.0 A depending on CT. | INT16 | × 0.1 | A | Read | ||
| HR | 8doc 0008 | Burnout state (CH1) | UINT16 | Read | 0 = OFF; 1 = ON | ||||
| HR | 9doc 0009 | Event 1 state (CH1) | UINT16 | Read | 0 = OFF; 1 = ON | ||||
| HR | 10doc 000A | Event 2 state (CH1) | UINT16 | Read | 0 = OFF; 1 = ON | ||||
| HR | 11doc 000B | Heater break alarm (HBA) state (CH1) | UINT16 | Read | 0 = OFF; 1 = Heater break; 2 = Relay welding | ||||
| HR | 12doc 000C | Control loop break alarm (LBA) state (CH1) | UINT16 | Read | 0 = OFF; 1 = ON | ||||
| HR | 15doc 000F | Operation mode (CH1) | UINT16 | Read/write | 0 = Unused; 1 = Monitor 1; 2 = Monitor 2; 3 = Control | ||||
| HR | 16doc 0010 | Set value (SV) (CH1) | Raw integer; decimal places follow the input range decimal point setting (0873H). | INT16 | Read/write | ||||
| HR | 17doc 0011 | Proportional band (CH1) | 0 = ON/OFF. Decimals follow the input range (0873H); V/I in % of span. | INT16 | Read/write | ||||
| HR | 18doc 0012 | Integral time (CH1) | Raw integer; one or two decimal places in seconds per 085CH. | UINT16 | Read/write | ||||
| HR | 19doc 0013 | Derivative time (CH1) | Raw integer; one or two decimal places in seconds per 085CH. 0 = off. | UINT16 | Read/write | ||||
| HR | 20doc 0014 | Control response parameters (CH1) | UINT16 | Read/write | 0 = Slow; 1 = Medium; 2 = Fast | ||||
| HR | 21doc 0015 | PV bias (CH1) | Raw integer; decimal places follow the input range decimal point setting (0873H). | INT16 | Read/write | ||||
| HR | 22doc 0016 | Event 1 set value (CH1) | Raw integer; decimal places follow the input range decimal point setting (0873H). | INT16 | Read/write | ||||
| HR | 23doc 0017 | Event 2 set value (CH1) | Raw integer; decimal places follow the input range decimal point setting (0873H). | INT16 | Read/write | ||||
| HR | 32doc 0020 | PID/AT transfer (CH1) | UINT16 | Read/write | 0 = PID control; 1 = Autotuning (AT) | ||||
| HR | 33doc 0021 | Auto/Manual transfer (CH1) | UINT16 | Read/write | 0 = Auto; 1 = Manual | ||||
| HR | 34doc 0022 | Manual output value (CH1) | -5.0 to +105.0 %. | INT16 | × 0.1 | % | Read/write | ||
| HR | 35doc 0023 | Output limiter (high) (CH1) | Output limiter (low) to 105.0 %. | INT16 | × 0.1 | % | Read/write | ||
| HR | 36doc 0024 | Output limiter (low) (CH1) | -5.0 % to output limiter (high). | INT16 | × 0.1 | % | Read/write | ||
| HR | 37doc 0025 | Proportional cycle time (CH1) | 0.2 to 50.0 s. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 39doc 0027 | Digital filter (CH1) | 0.00 to 10.00 s. | UINT16 | × 0.01 | s | Read/write | ||
| HR | 40doc 0028 | Heater break alarm (HBA) set value (CH1) | 0.0 to 30.0 A or 0.0 to 100.0 A. | UINT16 | × 0.1 | A | Read/write | ||
| HR | 48doc 0030 | Control RUN/STOP transfer (module) | UINT16 | Read/write | 0 = Control STOP; 1 = Control RUN | ||||
| HR | 53doc 0035 | Manipulated output value at input error (CH1) | -5.0 to +105.0 %. | INT16 | × 0.1 | % | Read/write | ||
| HR | 59doc 003B | Remote/Local transfer (module) | UINT16 | Read/write | 0 = Local; 1 = Remote | ||||
| HR | 208doc 00D0 | Program operation mode selection (CH1) | UINT16 | Read/write | 0 = RESET; 1 = RUN (program control); 2 = FIX (fixed set point control); 3 = MAN (manual control) | ||||
| HR | 209doc 00D1 | Execution pattern (CH1) | 1 to 16. | UINT16 | Read/write | ||||
| HR | 210doc 00D2 | Execution segment (CH1) | 1 to 16. | UINT16 | Read | ||||
| HR | 212doc 00D4 | Number of program execution times (CH1) | 0 to 9999. | UINT16 | Read | ||||
| HR | 214doc 00D6 | Pattern end output state (CH1) | UINT16 | Read | 0 = OFF; 1 = ON | ||||
| HR | 215doc 00D7 | End state (CH1) | UINT16 | Read | 0 = OFF; 1 = ON | ||||
| HR | 216doc 00D8 | Wait state (CH1) | UINT16 | Read | 0 = OFF; 1 = ON | ||||
| HR | 217doc 00D9 | Hold state (CH1) | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 218doc 00DA | Step action (CH1) | Write 1 to step to the next segment. | UINT16 | Read/write | 0 = No step action; 1 = Step action execution | |||
| HR | 2137doc 0859 | Control loop break alarm (LBA) use selection (CH1) | UINT16 | Read/write | 0 = Unused; 1 = Used | ||||
| HR | 2138doc 085A | Control loop break alarm (LBA) time (CH1) | 1 to 7200 s. | UINT16 | s | Read/write | |||
| HR | 2140doc 085C | Integral/derivative time decimal point position (CH1) | UINT16 | Read/write | 0 = Two decimal places; 1 = One decimal place | ||||
| HR | 2160doc 0870 | Input range number (CH1) | Input type code 0-21, e.g. 0 = K thermocouple, 12 = Pt100, 15 = 4-20 mA. | UINT16 | Read/write | ||||
| HR | 2161doc 0871 | Input scale high limit (CH1) | Raw integer; decimal places follow the input range decimal point setting (0873H). | INT16 | Read/write | ||||
| HR | 2162doc 0872 | Input scale low limit (CH1) | Raw integer; decimal places follow the input range decimal point setting (0873H). | INT16 | Read/write | ||||
| HR | 2163doc 0873 | Input range decimal point position (CH1) | UINT16 | Read/write | 0 = No decimal place; 1 = One decimal place; 2 = Two decimal places; 3 = Three decimal places; 4 = Four decimal places | ||||
| HR | 2164doc 0874 | Temperature unit selection (CH1) | UINT16 | Read/write | 0 = °C; 1 = °F | ||||
| HR | 2165doc 0875 | Control type selection (CH1) | UINT16 | Read/write | 0 = Direct action; 1 = Reverse action | ||||
| HR | 2170doc 087A | Event 1 type selection (CH1) | UINT16 | Read/write | 0 = Not provided; 1 = Process high; 2 = Process low; 3 = Deviation high; 4 = Deviation low; 5 = Deviation high/low; 6 = Band | ||||
| HR | 2171doc 087B | Event 2 type selection (CH1) | UINT16 | Read/write | 0 = Not provided; 1 = Process high; 2 = Process low; 3 = Deviation high; 4 = Deviation low; 5 = Deviation high/low; 6 = Band | ||||
| HR | 4096doc 1000 | Measured value (PV) (CH2) | Raw integer; decimal places follow the input range decimal point setting (0873H). | INT16 | Read | ||||
| HR | 4097doc 1001 | Comprehensive event state (CH2) | BITMAP16 | Read | bit 0 = Burnout; bit 1 = Event 1; bit 2 = Event 2; bit 3 = Heater break alarm; bit 4 = Control loop break alarm (LBA) | ||||
| HR | 4098doc 1002 | Manipulated output value (CH2) | -5.0 to +105.0 %. | INT16 | × 0.1 | % | Read | ||
| HR | 4099doc 1003 | Set value monitor (CH2) | Raw integer; decimal places follow the input range decimal point setting (0873H). | INT16 | Read | ||||
| HR | 4102doc 1006 | Current transformer input measured value (CH2) | 0.0 to 30.0 A or 0.0 to 100.0 A depending on CT. | INT16 | × 0.1 | A | Read | ||
| HR | 4104doc 1008 | Burnout state (CH2) | UINT16 | Read | 0 = OFF; 1 = ON | ||||
| HR | 4105doc 1009 | Event 1 state (CH2) | UINT16 | Read | 0 = OFF; 1 = ON | ||||
| HR | 4106doc 100A | Event 2 state (CH2) | UINT16 | Read | 0 = OFF; 1 = ON | ||||
| HR | 4107doc 100B | Heater break alarm (HBA) state (CH2) | UINT16 | Read | 0 = OFF; 1 = Heater break; 2 = Relay welding | ||||
| HR | 4108doc 100C | Control loop break alarm (LBA) state (CH2) | UINT16 | Read | 0 = OFF; 1 = ON | ||||
| HR | 4111doc 100F | Operation mode (CH2) | UINT16 | Read/write | 0 = Unused; 1 = Monitor 1; 2 = Monitor 2; 3 = Control | ||||
| HR | 4112doc 1010 | Set value (SV) (CH2) | Raw integer; decimal places follow the input range decimal point setting (0873H). | INT16 | Read/write | ||||
| HR | 4113doc 1011 | Proportional band (CH2) | 0 = ON/OFF. Decimals follow the input range (0873H); V/I in % of span. | INT16 | Read/write | ||||
| HR | 4114doc 1012 | Integral time (CH2) | Raw integer; one or two decimal places in seconds per 085CH. | UINT16 | Read/write | ||||
| HR | 4115doc 1013 | Derivative time (CH2) | Raw integer; one or two decimal places in seconds per 085CH. 0 = off. | UINT16 | Read/write | ||||
| HR | 4116doc 1014 | Control response parameters (CH2) | UINT16 | Read/write | 0 = Slow; 1 = Medium; 2 = Fast | ||||
| HR | 4117doc 1015 | PV bias (CH2) | Raw integer; decimal places follow the input range decimal point setting (0873H). | INT16 | Read/write | ||||
| HR | 4118doc 1016 | Event 1 set value (CH2) | Raw integer; decimal places follow the input range decimal point setting (0873H). | INT16 | Read/write | ||||
| HR | 4119doc 1017 | Event 2 set value (CH2) | Raw integer; decimal places follow the input range decimal point setting (0873H). | INT16 | Read/write | ||||
| HR | 4128doc 1020 | PID/AT transfer (CH2) | UINT16 | Read/write | 0 = PID control; 1 = Autotuning (AT) | ||||
| HR | 4129doc 1021 | Auto/Manual transfer (CH2) | UINT16 | Read/write | 0 = Auto; 1 = Manual | ||||
| HR | 4130doc 1022 | Manual output value (CH2) | -5.0 to +105.0 %. | INT16 | × 0.1 | % | Read/write | ||
| HR | 4131doc 1023 | Output limiter (high) (CH2) | Output limiter (low) to 105.0 %. | INT16 | × 0.1 | % | Read/write | ||
| HR | 4132doc 1024 | Output limiter (low) (CH2) | -5.0 % to output limiter (high). | INT16 | × 0.1 | % | Read/write | ||
| HR | 4133doc 1025 | Proportional cycle time (CH2) | 0.2 to 50.0 s. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 4135doc 1027 | Digital filter (CH2) | 0.00 to 10.00 s. | UINT16 | × 0.01 | s | Read/write | ||
| HR | 4136doc 1028 | Heater break alarm (HBA) set value (CH2) | 0.0 to 30.0 A or 0.0 to 100.0 A. | UINT16 | × 0.1 | A | Read/write | ||
| HR | 4149doc 1035 | Manipulated output value at input error (CH2) | -5.0 to +105.0 %. | INT16 | × 0.1 | % | Read/write | ||
| HR | 4304doc 10D0 | Program operation mode selection (CH2) | UINT16 | Read/write | 0 = RESET; 1 = RUN (program control); 2 = FIX (fixed set point control); 3 = MAN (manual control) | ||||
| HR | 4305doc 10D1 | Execution pattern (CH2) | 1 to 16. | UINT16 | Read/write | ||||
| HR | 4306doc 10D2 | Execution segment (CH2) | 1 to 16. | UINT16 | Read | ||||
| HR | 4308doc 10D4 | Number of program execution times (CH2) | 0 to 9999. | UINT16 | Read | ||||
| HR | 4310doc 10D6 | Pattern end output state (CH2) | UINT16 | Read | 0 = OFF; 1 = ON | ||||
| HR | 4311doc 10D7 | End state (CH2) | UINT16 | Read | 0 = OFF; 1 = ON | ||||
| HR | 4312doc 10D8 | Wait state (CH2) | UINT16 | Read | 0 = OFF; 1 = ON | ||||
| HR | 4313doc 10D9 | Hold state (CH2) | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 4314doc 10DA | Step action (CH2) | Write 1 to step to the next segment. | UINT16 | Read/write | 0 = No step action; 1 = Step action execution | |||
| HR | 6233doc 1859 | Control loop break alarm (LBA) use selection (CH2) | UINT16 | Read/write | 0 = Unused; 1 = Used | ||||
| HR | 6234doc 185A | Control loop break alarm (LBA) time (CH2) | 1 to 7200 s. | UINT16 | s | Read/write | |||
| HR | 6236doc 185C | Integral/derivative time decimal point position (CH2) | UINT16 | Read/write | 0 = Two decimal places; 1 = One decimal place | ||||
| HR | 6256doc 1870 | Input range number (CH2) | Input type code 0-21, e.g. 0 = K thermocouple, 12 = Pt100, 15 = 4-20 mA. | UINT16 | Read/write | ||||
| HR | 6257doc 1871 | Input scale high limit (CH2) | Raw integer; decimal places follow the input range decimal point setting (0873H). | INT16 | Read/write | ||||
| HR | 6258doc 1872 | Input scale low limit (CH2) | Raw integer; decimal places follow the input range decimal point setting (0873H). | INT16 | Read/write | ||||
| HR | 6259doc 1873 | Input range decimal point position (CH2) | UINT16 | Read/write | 0 = No decimal place; 1 = One decimal place; 2 = Two decimal places; 3 = Three decimal places; 4 = Four decimal places | ||||
| HR | 6260doc 1874 | Temperature unit selection (CH2) | UINT16 | Read/write | 0 = °C; 1 = °F | ||||
| HR | 6261doc 1875 | Control type selection (CH2) | UINT16 | Read/write | 0 = Direct action; 1 = Reverse action | ||||
| HR | 6266doc 187A | Event 1 type selection (CH2) | UINT16 | Read/write | 0 = Not provided; 1 = Process high; 2 = Process low; 3 = Deviation high; 4 = Deviation low; 5 = Deviation high/low; 6 = Band | ||||
| HR | 6267doc 187B | Event 2 type selection (CH2) | UINT16 | Read/write | 0 = Not provided; 1 = Process high; 2 = Process low; 3 = Deviation high; 4 = Deviation low; 5 = Deviation high/low; 6 = Band |
Notes on this map
- RKC's own download center does not offer this manual publicly; the linked copy is the unaltered RKC manual hosted by a US distributor (a distributor stamp on the cover only).
- All registers are 16-bit; FFFFH is -1. Values are sent without a decimal point: PV/SV-type items follow the input range decimal point (0873H), integral/derivative time follows 085CH, others have the fixed decimals shown (scale).
- Items marked (module) exist once per module (channel 1 address only); all others repeat for channel 2 at +1000H.
- The decimal-handling list prints Manual output value twice and does not name the manipulated output (0002H); its scale 0.1 rests on its printed -5.0 to +105.0 % range.
- Level PID tables, program pattern/segment tables, digital input assignments and the DI/DO module maps are left out.
- Writing input range, scale, decimal point, unit or event type can take up to 200 ms to answer; stop control (0030H) before changing initial-setting items.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the RKC Instrument SRX module type controller, TIO temperature control module (Modbus RTU)
What Modbus registers does the RKC Instrument SRX module type controller, TIO temperature control module (Modbus RTU) have?
This map lists 99 registers: 99 holding registers. 68 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the RKC Instrument SRX module type controller, TIO temperature control module (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The data map prints each register in hex and decimal; the value is the address sent on the wire. The manual's read example asks for 0000H-0002H and gets back PV, event state and output, so 0000H is a real register (CH1 measured value).
What are the minimum Modbus registers to integrate the RKC Instrument SRX module type controller, TIO temperature control module (Modbus RTU)?
Start with HR 0 Measured value (PV) (CH1) (CH1 measured value); HR 1 Comprehensive event state (CH1) (CH1 event state); HR 2 Manipulated output value (CH1) (CH1 output); HR 16 Set value (SV) (CH1) (CH1 set value); HR 48 Control RUN/STOP transfer (module) (Control RUN/STOP); HR 4096 Measured value (PV) (CH2) (CH2 measured value); HR 4112 Set value (SV) (CH2) (CH2 set value).
How do I enable Modbus control of the RKC Instrument SRX module type controller, TIO temperature control module (Modbus RTU)?
Modbus is chosen with DIP switch 6 (ON = Modbus; factory setting is RKC protocol). Speed is set by DIP switches 1-2, data/parity by 3-5. Power off before changing switches.
Where is the official RKC Instrument SRX module type controller, TIO temperature control module (Modbus RTU) Modbus documentation?
The source is SRX Communication Instruction Manual (Module Type Controller) (IMS01N01-E5). RKC Instrument doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.flw.com/rkc/pdf/ims01n01e5.pdf. It may be an older revision, so check it against the live unit.
More RKC Instrument Modbus register maps
Other temperature & process controllers register maps
- Sensor (digital temperature controller)
Shinko Technos FC series digital indicating controller (C/C5 option, Modbus ASCII)
Shinko FCS-23A, FCR-13A, FCR-23A and FCD-13A with the C or C5 serial option; FCR-15A and FCD-15A have no Modbus (Shinko protocol only). Manual No.FC1CE11.
Also known as: FCS-23A, FCR-13A, FCR-23A, FCD-13A - Sensor (digital temperature controller)
Shinko Technos WCL-13A 2-channel digital indicating controller (C5 option)
Shinko WCL-13A two-loop controller with the C5 option; communication manual No.WCL1CE3.
Also known as: WCL-13A-C5, WCL-13A C5 - Sensor / counter-timer (programmable counter and timer)
Autonics CT series programmable counter / timer (Modbus RTU)
Autonics CT series counters/timers with RS-485 communication, communication manual MCC-CTC1-V1.3-EN.
Also known as: CT4S, CT6, CT6S, CT6M, CT6Y, CT6M-2P, CT6S-1P4 - Sensor (digital temperature controller)
Shinko Technos DCL-33A digital indicating controller (C5 option)
Shinko DCL-33A with the C5 serial option, plain (non-block) Modbus protocol setting; manual No.DCL32CE3.
Also known as: DCL-33A-C5, DCL-33A C5 - Sensor (digital temperature controller)
Shinko Technos PCD-33A programmable controller (C5 option)
Shinko PCD-33A program controller with the C5 RS-485 option; manual printed No.PCD3CE1 2003.02 (file PCD3CE2).
Also known as: PCD-33A-R/M, PCD-33A-S/M - Process controller (sensor / PID controller)
ABB Protronic 100/500/550 and Digitric 500 process controllers (Modbus RTU)
ABB Protronic 100/500/550 and Digitric 500 universal process controllers with the RS-485/RS-232 Modbus interface module, interface description 42/62-50040 EN Rev. 04.
Also known as: Protronic 100, Protronic 500, Protronic 550, Digitric 500
All temperature & process controllers Modbus register maps →
Source: SRX Communication Instruction Manual (Module Type Controller) · IMS01N01-E5 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.